Low noise, low vibration & high reliability.
Great energy savings with Multi-Drive Control.
SRL-5.5MB5A
Scroll Compression Principle
High Reliability Space Saving
Multi-Drive Control
Energy Saving
1. Compressor sucks air through an air inlet located at outer scroll.
2. Compression chamber becomes smaller with the rotary movement
and trapped air is compressed.
3. Compression chamber achieves minimum volume at the centre of the
scroll and air is pumped out through the air outlet located at the centre
of scroll.
4. The suction, compression & discharging process is repeated continuously.
Compression
chamber
Suction process
Discharging process
Compression process
Intake
Air
Fixed scroll
Orbiting scroll
Outlet
SRL - 5.5MB 5 A
for ASIA/Australia
Frequency(5:50Hz)
MB type
Motor Nominal Output(kW)
Oil-free SCROLL
Model Nomenclature:
HITACHI BEBICON COMPRESSORS
Oil-free Scroll Air Compressor (2.2-22kW)
Innovation, Performance and Reliability

Control Mode setting can be changed between Multi-Drive Control and Pressure Switch Control.
Under Multi-Drive Control mode, the operation of SRL heads is modified automatically, responding to the need of air.
The necessary pressure is maintained producing an optimized, energy-saving performance.
P-Mode:
Similar to conventional Pressure Switch Control, if
maximum pressure is reached, the compressor will
stop operating. When the pressure decreases to the
cut-in pressure, the compressor will restart.
Multi-Drive Mode:
The compressor is automatically controlled to maintain
the necessary operating pressure(control pressure).
Unnecessary power consumption is prevented by
avoiding reaching maximum pressure - and energy
savings are achieved.
Max. Pressure
Control Pressure
Cut-in Pressure
Time
Pressure
P-mode
Operation
Multi-Drive mode
Operation
Energy-Saving
Eect
P-mode Operation
Multi-Drive mode Operation
Space saving
Energy saving with Multi-Drive Control
Control Mode setting can be changed between Multi-Drive Control and Pressure Switch Control. Under Multi-Drive Control mode,
the operation of SRL heads is modied automatically, responding to the need of air. The necessary pressure is maintained producing
an optimized, energy-saving performance.
P-Mode:
Similar to conventional Pressure Switch Control, if
maximum pressure is reached, the compressor will
stop operating. When the pressure decreases to the
cut-in pressure, the compressor will restart.
Multi-Drive Mode:
The compressor is automatically controlled to maintain
the necessary operating pressure (control pressure).
Unnecessary power consumption is prevented by
avoiding reaching maximum pressure - and energy
savings are achieved.
Because the back and right sides are at and the exhaust extraction is from the top, it’s possible to install the compressor with
two sides close to walls. Installation space is greatly saved.
*
It is still necessary to secure space for maintenance.
Low noise, low vibration
◦
Noise level is a low 47dB[A]-as quiet as a library !(3.7kW)◦Low vibration:pencils remain standing on the top during operation.
1. Compressor sucks air through an air inlet located at
outer scroll.
2. Compression chamber becomes smaller with the
rotary movement and trapped air is compressed.
3. Compression chamber achieves minimum volume at
the center of the scroll and air is pumped out through
the air outlet located at the center of scroll.
4. The suction, compression & discharging process is
repeated continuously.
SRL - 5.5MB 5 A
for ASIA/Australia
Frequency(5:50Hz)
M type, MB type
Motor Output(kW)
Oil-free SCROLL
Model Nomenclature
Compression
chamber
Suction process
Discharging process
Compression process
Intake
Air
Fixed scroll
Orbiting scroll
Outlet
Because the back and right sides are flat and the exhaust extraction is from the top, it’s possible to install the compressor
with two sides close to walls. Installation space is greatly saved.
*
It is still necessary to secure space for maintenance.
Control Mode setting can be changed between Multi-Drive Control and Pressure Switch Control.
Under Multi-Drive Control mode, the operation of SRL heads is modified automatically, responding to the need of air.
The necessary pressure is maintained producing an optimized, energy-saving performance.
Pressure
Easy to use
1. No need to change oil and separate the oil from drain. No need to install oil mist lter as well.*
2. Well-designed structure means easy maintenance - for the draining and cleaning of suction lters.
*
If the suction air is thought to contain oil, it is necessary to install an oil mist lter.
Hitachi Australia Pty Ltd
Level 8, 123 Epping Road, Macquarie Park NSW 2113
Locked Bag 2052, North Ryde NSW 2113
TEL: +61 (2) 9888-4100 FAX: +61 (2) 9888-4188
Email: compressors@hitachi.com.au
Website: www.hitachi.com.au/products/business/power/atg.dhtml
For further information please contact your nearest sales representative.
Specications
Note:
1. Air capacity is converted value at its inlet condition. For guaranteed values, contact your nearest dealer or
HIT
ACHI local representative ofce.
2. Noise level is measured at 1.5m front, under full-load operation in an anechoic room. It may vary in different
operation conditions or envir
onments.
3. It is necessary to install an air receiver tank for 5.5kW and above models to reduce ON-OFF frequency.
For 2.2/3.7kW models, it is also r
ecommended to install an additional air receiver tank.
4. External dimensions indicate the package panel ONLY, NOT including protruding objects such as
discharge outlet.
5. Ambient temperatur
e must be between 0 (at which there is no freeze of drain water) and 40°C.
6. 1.0MPa model is optional for all models except for 3.7kW. Refer ( ) for corresponding data.
7. Hitachi air compressors are not designed, intended or approved for breathing air applications.
8. Motors start with full voltage and on 3 phase source.
Control
Method
Motor
Nominal
Output
Model
Compressor
Air Outlet
Air Tank Volume
External Dimensions
(WxDxH)
Weight
Noise
Level
Max Pressure
ON-OFF Control Pressure
0.8 MPa 0.85 MPa 1.0 MPa
Capacity at Maximum Pressure
kW - MPa MPa PSIG MPa PSIG MPa PSIG L/min CFM L/min CFM L/min CFM - L mm Kg dB(A)
P-Mode
2.2
3.7
SRL-2.2MB5A
SRL-3.7MB5A
0.85 (1.0)
0.85
0.85 (1.0)
0.8 (1.0)
-
-
-
-
-
-
0.65-0.85
94 -123
0.8 - 1.0
-
0.8 - 1.0
116 -145
-
116 -145
-- -
-
240
400
8.5 200
7
-
Rc 3/8 Stop
Value x 1
18
24
680 x 640 x 1,030
750 x 715 x 1,070
129
1754647
5.5
SRL-5.5MB5A
-
- 600 21 500 18
24
(Necessary for additional
air receiver talk)
184 50
MultiDrive/
P-Mode
7.7
SRL-7.5MB5A
0.65 - 0.8 94 - 116
-
- 0.8 - 1.0
116 -145
880 31 - - 700 25
Rc3/4 x 1
-
960 x 660 x 1,190
315 (312) 57
11
SRL-11MB5A
1,260 45 - - 1,000 35
350 (344) 59
16.5
22
SRL-15MB5A
SRL-22MB5A
1,890
2520
67
89
- - 1,500
2000
53
R1 x 1
1,280 x 770 x 1,450
1,330 x 880 x 1,900
515 (506)
720 (708)6161
0.8 MPa 0.85 MPa 1.0 MPa
14
- -
70.6