Thank you for purchase of “HITACHI INVERTER”. This manual
explains about treatment of “SJ-LW (LonWorks Option)”. By reading this
manual and an instruction manual of inverter use practically for
installation, maintenance, and inspection. After reading this manual,
keep it handy for future reference.
Make sure to reach this manual to the end user.
(LonWorks Option)
Table of Contents
Chapter1 Introduction 1
Chapter2 Installation method of printed board 5
Chapter3 Wiring, Connecting 6
Chapter4 Setting 7
Chapter5 LonWorks Communication Function 8
Chapter6 Control from LonWorks 17
Chapter7 Countermeasure for abnormality 21
Appendix1 Parameter Object Lists
Appendix2 Trip monitor data address
After reading this manual, keep it at handy for future reference.
23
32
NB623X
Page 2
SAFTY PRECAUTIONS
- Request Thank you for purchase of “SJ-LW (LonWorks Option)”.
This instruction manual explains about treatment and maintenance of “SJ-LW ”. Before using the product,
carefully read this manual with the instruction manual of inverter, and keeps it handy for quick reference of
operator and maintenance inspector. Before installing, operating, maintenance and inspection read this
manual carefully and follow the instructions exactly.
Always keep various kinds of specification mentioned in this manual and use exactly. And make sure to
prevent trouble by correct inspection and maintenance. Make sure to reach this manual to the end user.
- About treatment of this manual (1)Please consent that mentioned items of this manual may be change without permission.
(2)Keep this manual carefully not to lose because it can not be reissued
(3)All right reserved.
(4)Contents in this manual is written to make assurance doubly sure but, but please contact if you have
some doubts about spelling mistakes, omitted word etc.
(5)Please agree that there is no responsibility for effects resulted, in spite of contents above mentioned.
- About trademark (1) Echelon, Neuron, LON, LonTalk, LonWorks, 3120 are registered trademark of Echelon Corporation.
(LON: Local Operating Network)
(2) LonMaker, LonMark are trademark of Echelon Corporation.
- Reference
W hen Co nne ct ing S J- LW to LON netwo rk ,XI F f ile is n eces s ar y as ex ter na l in ter fac e file .
XIF file is possible to download from the web site below.
http://www.hitachi-ds.com
General information regarding LonWorks and how to get LonW orks specificatio ns , re fer to the web site belo w.
http://www.lonmark.org
Revision His tor y Table
No.
1.Initial release of Manual NB623XSep. 2001NB623X
Revision contentsThe date of issuedManual No.
Except this table, revised only spelling mistakes omitted words, and error writings without notice.
Page 3
SAFTY PRECAUTIONS
!
!
!
!
SAFTY PRECAUTIONS
Carefully read this manual and all of the warning labels attached to the inverter before installing, operating,
maintaining, inspecting, it. Safety precautions are classified into “Warning” and “Caution” in this manual.
:Indicates a potentially hazardous situation which, if not avoided, can result in serious
WARNING
injury or death.
CAUTION
:Indicates a potentially hazardous situation which, if not avoided, can result in minor to
moderate injury, or serous damage to the product
The situation described in may, if not avoided, lead to serious results. Important safety
measures are described in CAUTION (as well as WARNING) so be sure observe them.
Notes are described in this manual in “(Note)”. Carefully read the contents and follow them exactly.
CAUTION
CAUTION
In all the illustrations in this manual, covers and safely device are occasionally removed to describe the
details. When the product is operated, make sure that the covers and safety devices are placed as they
were specified originally and operate it according to the instruction manual.
Page 4
SAFTY PRECAUTIONS
!
!
WARNING
Wiring:
W iring work shall be carried out by electrical experts.
Otherwise, there is a danger of electric shock, fire and/or damage of product.
Implement wiring after checking that the power supply is off.
Otherwise, there is a danger of electric shock and/or fire.
Operating:
Be sure not to touch the surface or the terminal of option board while energizing.
Otherwise, there is a danger of electric shock and/or fire.
Be sure not to remove the LonWorks option printed board while operating.
Otherwise, there is a danger of electric shock and/or fire.
Maintenance, Inspection and Part Replacement:
Wait at least 10 minutes after turning off the input power supply before performing maintenance and
inspection.
(Confirm the charge lamp on the inverter is off, checks direct current voltage between P-N terminals and
confirm it is less than 45V)
Otherwise, there is a danger of electric shock.
Make sure that only qualified persons will perform maintenance, inspection, and part replacement
(Before st ar tin g th e work , rem ov e me tall ic o bje cts fr om your per son (wr is twa tch , br ac ele t, etc .) .
Be sure to use tools protected with insulation.)
Otherwise, there is a danger of electric shock and/or injury.
Note:
Never modify the unit.
Otherwise, there is a da nger o f e lec tric sh ock and /o r inju r y.
CAUTION
Installation:
Be sure not to let the foreign matter enter such as wire clippings, spatter from welding, metal shaving,
dust etc.
Otherwise, there is a danger of fire.
Be sure to fix inverter to option printed board with an attached fixed screw.
Otherwise, there is a danger of connecting error.
Be sure to fasten the screws connecting signal wire in side of option printed board. Check for any
loosening of screw.
Otherwise, there is a danger of connecting error.
Wiring:
Be sure to fasten the screws not to loose.
Otherwise, there is a danger of connecting error.
Operation:
Check rotary direction, abnormal motor noise and vibrations during operating.
Otherwise, there is a da nger o f inju r y to pe rso nnel and/o r ma chi ne brea kage
Page 5
CHAPTER 1 INTRODUCTION
1.1 INSPECTION UPON UNPACKING
Make sure to treat the product carefully not to give shock and vibration while unpacking. Check that the
product is the one you ordered, no defect, and that there is no damage during transportation.
(Content s of pack i ng)
If you discover any problems, contact your sales agent immediately.
1.2 INQUIRY OF THE PRODUCT AND WARRANTY FOR THE PRODUCT
1.2.1 REQUIRE WHILE INQUIRING
If inquiry of breakage, question, damage etc. is needed, please tell the following information to the supplier
you ordered or the nearest Hitachi Distributor.
(1) Type(SJ-LW )
(2) Manuf ac tu rin g num b er (It em of lab e l, th at labe le d s urfac e of pr i nte d bo ard . SJ -LW XXX
(3) Date of purchasing
(4) Contents of inquiry
Damage parts and its condition etc.
・
Question parts and their contents etc.
・
In order to shorten impossible working time, standing spare unit is recommended.
)
1.2.2 WARRANTY OF THE PRODUCT
This product is guaranteed to last for one year after purchase. But, the next case is toll repair, even if within
warranty period.
(1) In case caused by operating mistake, and incorrect repair and modification.
(2) Trouble caused by reasons except the shipped product.
(3) In case of using in range over the value of specification.
(4) In case caused by natural calamity, disaster, and secondary disaster.
Warranty mentioned here means warranty for shipped product itself. Damage caused by trouble of shipped
product is not guaranteed.
[Replacement]
Any inspection and replacement after the expiration of warranty period (one-year) shall be charged to the
purchaser. And also any inspection and repair which are not covered in warranty mentioned above, even if it
is within warranty period, it shall be charged to the purchaser. If you require the replacement, please contact
your Hitachi distributor.
1
Page 6
CHAPTER 1 INTRODUCTION
1.3 Outline of product
SJ-LW is LonWorks communication board for SJ300/L300P series inverter.
SJ300/L300P series inverter can get to connect another devices via LonWorks when install SJ-LW.
SJ-LW is possible to connect for all models of SJ300/L300P series.
The SJ-LW option card communi cate s a ccording to t he L on Works P roto col Stan dard ANS I/EIA 709. 1- A -1999.
This means that it can communicate with all LonWorks nodes that comply with this standard, but it does not
necessarily mean that all services available in the LonWorks standard are supported. The “LonMark
Functional Profile: Variable Speed motor Drive” (doc no. 6010_11) is supported.
In a control system the option board will act as a node that can be read and written to, from any other
LonWorks node that has SNVT’s that corresponds to the one on SJ-LW.
(Note) RS485 communication function is disabled by installing SJ-LW to the inverter.
1.4 Appearance and Names of Parts
Figure 1-1 indicates the appearance of SJ-LW.
Connector for connection to SJ 300 /L300 P(Rea r o f unit)
Terminal S witch(S2 )
BUS
NO
FT
Service Pin (S1)
LonWorks contact (open type)
PhoenixContactCo.Ltd.(MC1.5/3‑ST‑3.81)etc
Serial Channel Status LE D (S ER IAL )
LonWorks Service LED (SERV)
Power/Status LED ( POWER)
Figure 1-1 Appearance of SJ-LW
2
Page 7
CHAPTER 1 INTRODUCTION
118KT1234510001
118KT1234510001118KT1234510001
118KT1234510001
0101
1.5 LonWorks Supported Version
SJ-LW can use following Manufacturing number (MFG No) of SJ300/L300P series.
After Manufacturing number : XX8KXXXXXXXXXXXX(SJ300-0.4-55kW / L300P-11-75kW supported
XXEMXXXXXXXXXXXX(SJ300-75-132kW / L300P-90-132kW supported
)
)
(Note) Manufacturing number is written in specifications label on main body of SJ300/L300Pseries. Refer to
figure 1- 2, f igur e 1- 3.
(Figure 1-2 , 1- 3 ar e t he example of SJ 3 00 se r ies . L3 00P ser i es ar e th e s am e manne r as SJ 300 ser ies .)
Specifications label
Figure 1-2 Position of specifications label
Inverter model
Maximum applicable motor
Input ratings
Output ratings
Manufacturing numbe r
Figure 1- 3 Co nt ent s of spe cif i cat ion s l abe l
1.6 Technical features of Lonworks
Transmission Technique:
- Free topology (FTT-10A) twisted pair cable
- Transmission rate 78kbits/s
Max Bus length: Bus up to 2000 m
Max. node-to-node distance: 500m
Max amount of nodes: 32.385 nodes divided as 127 nodes/subnet, 255 subnets/domain.
Medium Ac c ess : Pr edi ct ive CS MA
Data types: Peer-to-peer communication
LonWorks communication ASIC: TMPN3120FE5 chip from Toshiba.
LonWorks transceiver: FTT10A from Echelon.
3
Page 8
CHAPTER 1 INTRODUCTION
1.7 Production specification
Bacicaly, the environmental specification of the SJ-LW is in accordance with SJ300/L300P series inverter.
Please refer the instruction manual of SJ300/L300P series.
But only application temperature of SJ-LW is different. Please note.
applicat i on temperature : 0 t o 50 deg re e
4
Page 9
CHAPTER 2 INSTALLATION METHOD OF PRINTED BOARD
p
g
p
(
)
2.1 Mounting method of option board
Figure 2-1 describes how to mount the option board to the option port 1 or 2.
There are four holes on th e optio n boa rd, mat ch the t wo o f th em with t he screw holes on t he o ption po rt 1 or 2 .
and mount the other two holes with the guide posts which are located on the option port 1 and 2. To avoid
connection failure, secure the option board with screws after connection.
Option board
Guide posts for mountin
the option board.
Option port 1
Screw holes for secure o
M3 Screws
O
tion port 2
tion board.
Figure 2-1 In st al l ation o f opt io n bo a rd
5
Page 10
CHAPTER 3 WIREING,CONNECTING
3.1 Connection for LonWorks connector
The SJ-LW connects t o the LonWorks net work wit h a 3- pin c onn ec tor. For the p in l a yout , ref er to Fi gu r e 3-1.
NOTE : NET A and NET B connection is not polarity sensitive.
Pin No. 1 2 3
2.3
No.Signal markFunction
1ShieldShield connection
2NET ALonWorks NET A connection
3NET BLonWorks NET B connection
3.2 Network cabling
3.8
7.62
12.22
Dimensio n i n mm
For detailed information about recommended cables for a LonWorks network, please see the FTT-10A Free
Topology Transceiver User’s Guide (doc.id.078-0156-01F) available at http://www.echelon.com
Below are some recommended cables :
-Belden 85102, unshielded
-Belden 8471, unshielded
-Level IV 22AWG, unshielded
-JY (St) Y 2x2x0.8, shielded
-TIA568A Cat.5 24AW G
Note) To be able to communicate in a noisy environment, and to fulfil all EMC-requirements, it’s
important that a shielded cable is used, and that proper grounding is provided.
3.3 Wiring note
1.Installing the cable to Network connector must be done after checking the power supply off.
2.Wiring should not have bare cables exposed between connector contacts.
3.Network cables should be fixed without tension. Cables fixed under tension have potential of causing a
communication fault by to be removed a connector.
4.Ensure external emergency stop measures are taken to stop the inverter, in the event of a network fault.
(a) Remove the Power supply of the Inverter when the network master detects a communication fault.
(b) When the m aster d etects a com m unicat ion f ault, turn on the intellig ent input terminal which would be
allocated (FRS), (RS) and/or (EXT) function.
6
Page 11
CHAPTER 4 SETTING
4.1 Setting of controlling frequency and start/stop commands
The Hitachi SJ300/L300P inverters can be configured to take reference set-points and commands from
several different locations. Re fer to the ta ble below for info rmation of how t o configu re the inve rter so that the
Lonworks controls frequency and the commands.
CommandFunctionSetting rangeSetting data
A001
A002
Frequency
setting selection
Operating mode
selection
The SJ-LW option board provides internal termination of the LonWorks network. To enable/disable the
termination a switch (S2) is used. See Figure 1-1 for location of the switch. The following table explains the
possible switch-settings :
For more information about termination, see the FTT-10A Free Topology Transceiver User’s Guide
(doc.id.078-0156-01F) available at http://www.echelon.com
Note) Risk of equipment damage exists. The SJ-LW contains ESD (Electrostatic Discharge) sensitive
parts that can be damaged if you do not follow ESD control procedures. Static control precautions
are required when handling the adapter.
4.3 Service pin (S1)
The SJ-LW option board provides one Service pushbutto n (S1 ), which i s used d uring the i nstalla tion pha se to
identify the node. See Figure 1-1 for location of the pushbutton.
The SJ-LW is installed in a LonWorks network using any standard LonWorks installation tool.
(i.e. “LonMaker for Windows” from Echelon).
4.4 Baudrate
The SJ-LW has a fixe d bau dr at e of 78k bps (F TT -10 A).
7
Page 12
CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
5.1 Operating the drive via Lon Mark profile
A LonMark profile defines a functional profile for a node communicating with others. A LonMark profile
specifies which SNVT’s and SCPT’s to be used and also a semantic meaning about the information being
communicated.
When a prof ile is imp lemen ted in a nod e, it is call ed a Lo nMa rk Objec t. O ne node can have s evera l obj ects
implemented. The SJ300 LonWorks adapter has two objects, a node-object and a drive-object. The nodeobject is used to control the other objects in a node.
This input is used to enable control commands and updates from network.
The valid iden tif ic at io n num b ers mus t be us ed. The v al id num bers ar e 0 and 1.
The status of the node is reported in nvoObjStatus, see chapter 5.3.1.
ValueIdentifierFunction
0RQ_NORMALenable settings of nviDrvSpeedStpt and nviDrvSpeedScale
again, if they were disabled by RQ_DISABLED. Speed
settings need to be updated to start the inverter again if
disabled.
1RQ_DISABLEDdisables settings of nviDrvSpeedStpt and
nviDrvSpeedScale. It also stops the inverter.
2RQ_UPDATE_STATU Supdates nvoObjStatus
5RQ_REPORT_MASKreports supported requests in nvoObjStatus
7RQ_ENABLEenable settings of nviDrvSpeedStpt and nviDrvSpeedScale
again, if they were disabled by RQ_DISABLED. Speed
settings need to be updated to start the inverter again if
disabled.
9RQ_CLE AR _STATUSclears n voO bj Sta tus
10RQ_CLEAR_ALARMresets a fault (trip) in the drive
13RQ_MANUAL_CTRLcan be used when the inverter only want to be monitored
from Lon Network, not controled. No message containing a
WRITE_DEMAND_CODE (0x02) in the FrameType f ield of
the Hitachi high-speed serial protocol will be communicated
to the inverter from the option card. All messages with other
FrameType codes will be sent to the inverter.
14RQ_REMORT_CTRLallow WRITE_DEMAND_CODE(0x02)
messages to be communicated to the inverter.
If RQ_SELF_TEST, RQ_OVERRIDE, RQ_RMV_OVERRIDE, RQ_ALARM_NOTIFY_ENABLED,
RQ_ALARM_NOTIFY_DISABLED, RQ_PROGRAM or RQ_NUL is requested, the invalid_request bit will be
set in nvoObjStatus.
Which request of RQ_DISABLED, RQ_NORMAL or RQ_ENABLE is set last is remembered. This means that
nviObjRequest can first be set RQ_DISABLED and then e.g RQ_REPORT_MASK. Then it is still disabled
but reported masks will be shown in nvoObjStatus.
Which requ est of RQ_M ANUAL_CT RL or RQ_RE MOTE_CTRL is set last is remember ed. This m eans that
nviObjRequest can first be set RQ_MANUAL_CTRL and then e.g RQ_REPORT_MASK. Then it is still in
manual control but reported masks will be shown in nvoObjStatus.
With regard to RQ_MANUAL_CTRL and RQ_REMOTE_CTRL, please refer chapter 6.8.
5.2.3 Inverter frequency sett in g (SNVT_f req_hz nviIn vSetFre q)
This input network variable provides a low-resolution speed setpoint.
When nv iD r v S p e ed S t pt.State i s set to ze ro the dr i v e is stopped using ramp 1 (Normal Stop).
Following two methods are used for setting frequency.
(1) nviInvSetFreq = 0x7FFF (D efault)
It is possible to set the request speed by using ratio of Nominal Frequency (Refer to chapter 5.4.6) or
Nominal Speed (Refer to chapter 5.4.5).
(2) nviInvSetFreq = 0 to 400,
I
t is possible to set 0 to 400Hz to nviInvSetFreq directly.
9
Page 14
CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
NviInvSetFreq
0x7FFF
(Initial value)
0〜400Hz
Note: Requested speed will not be greate r then th e valu e de fined by n ciMaxSpeed (Refer to chapte r 5.4. 8) o r
less then t he v al ue d ef ined b y nci Min Sp eed ( R efer to c h apt er 5. 4. 7).
*1:nviDrvSpeedScale = 100, Direction: Forward
= -100, Direction: Reverse = When a value in nviDrvSpeedScale is set any value except for 100 and –100, i t
Default value:
Default value is AUTO (state = 0xFF). T his value will be adapted at power-up. This network variable input
may use the Receive Heartbeat function depending on if Receive Heartbeat function is setup for use. The
actual value of drive speed does also depend on nviDrvSpeedScale.
NviDrvSpeedStpt
StateValue
0xFFN/AN/AAUTO(Invalid)
0N/AN/A
100%0%
1
1201 〜255100.0%100.0%
0xFFN/AN/AAUTO(Invalid)
0N/AN/A
1N/AN/AnviInvSetFreq *1
1〜2000.5〜100.0 %nciNmlFreq*nviDrvSpeedSpt
becomes the stop command (Run: Deceleration stop, Stop: Maintain to stop).
This input network variable provides scaling for nviDrvSpdStpt. For example if nviDrvSpeedStpt value is
100% and nviDrvSpeedScale value is -150%, then actual speed setpoint value is -15 0% meaning reverse 1,5
times nominal speed. The requested speed will not be greater than the value defi ned by nciMaxSpeed or
less than t he v al ue d ef ined b y nci Min Sp eed.
Depending on Drive Speed Setpoint, behavior of Speed Setpoint Scaling will be changed. Followings are
explanation of behavior.
(1) nviInvSetFreq = 0x7FFF(Initial value)
It prescribes the scaling for Drive Speed Setpoint (Refer to chapter 5.2.2).
(2) nviInvSetFreq = 0 to 400
It sets direction of rotation.
nviDrvSpeedScale = 100, Direction: Forward
= -100, Direction: Reverse = When a value in nviDrvSpeedScale is set any value except for 100 and –100, i t
becomes the stop command (Run: Deceleration stop, Stop: Maintain to stop).
Example (1): nviInvSetFreq = 0x7FFF
For example if nviDrvSpeedStpt value is 100% and nviDrvSpeedScale value is -150%, then actual speed
setpoint value is -150% meaning reverse 1,5 times nominal speed (Refer to chapter 5.3.6).
Also refer to 6.1.4.
10
Page 15
CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
Example (2) : nviInvSetFreq = 0 to 400
When nviI n vSet Fr eq is at 60H z and nviDrvSpeedScale is 100%, the inverter is in forward run at 60Hz.
Valid Range: -163.84 to163.83%
Default Value: Is defined by nciDrvSpeedScale (Refer to 5.4.14).
Scaling: See chapter 6.1.4
When EMER G_S HUTD OW N c omm and is inputted, the inverter executes the deceleration stop and also the
value in EMERG_SHUTDOWN is supported but the other values are not supported.
(Deceleration time is dependant on Ramp Down Time (Refer to chapter 5.4.10))
5.3.1 Node Object Status (SNVT_obj_status nvoObjStatus)
This nvo reports node object status. It will be updated every time status change. See chap. 5.1.1 for different
requests.
IdentifierStatus
Invalid_requestThe node has been asked for an unsupported request.
Report_maskReport supported fields.
Comm_failureNo contact with SJ300/L300P.
In_alarmThe SJ300/L300P inverter is tripped.
DisabledNviObjRequest have received a RQ_DISABLED request. Settings of
nviSpeedScale and nviSpeedStpt is disabled.
Manual_controlSJ300/L300P is not controlled from the option card.
See digital operator value at A001 (should be 02 to avoid manual control to be
set) and A002 (should be 01 to avoid manual control to be set). Manual_control
will be set if option-board isn’t in control over one parameter. O ption card can
still give or der wh er e it h as com m and .
It will be set if NviObjRequest have received a RQ_MANUAL_CTRL request.
Invalid IDIf another identification number then 0 and 1 have been set in request by SNVT
nviObjRequest. The request will not be carried out.
5.3.2 Drive Status (UNVT_sj300 nvoDrvStatus)
This output network variable provides the status of the drive.
The first three bytes will be mapped directly from the information received at address 0xFFFF8E10 in the
SJ300/L300P. If tripped, the last byte will contain an error code read from where pointer of last trip
(0x08000363) points too.
data format :
Status AStatus BStatus CStatus D
Status C : Lad mode
Status A: Inverter status 1
ValueState
00initial status
01---02On stopping
03On running
04On FRS
05On JG
06On DB
07On reading frequency
08On retrying
09On UV
10On TRIP
11On waiting reset
ValueState
00--01Stop
02Deceleration speed
03Constant speed
04Acceleration speed
05Forward
06Reverse
07Reverse from forward
08Forward from reverse
09Forward start
10Revers e start
This output network variable provides the speed of the drive as a percentage of the nominal speed. Since
nominal speed and nominal frequncy are tightly connected to eachother, the out value is calculated on the
nominal (base) frequency and the running (out) frequency. This output network variable is used as a
heartbeat to monitor the health of the LonWorks communication interface. See chapter 5.3.1 about
heartbeats.
Scaling:
If value of present running is forward then run_dir will be1.
If value of present running is reverse then run_dir will be -1.
BASE_FREQ / ((raw data format)OUT_FREQ / 1000) * (run_dir) = nvoDrvSpeed
5.3.5 Drive Power (SNVT_power_kilo nvoDrvPwr)
This output network variable provides the drive power in kilowatts.
5.3.6 Drive voltage (SNVT_volt nvoDrvVolt)
This output network variable provides the drive voltage in volts.
5.3.7 Output Frequency (SNVT_fre q_hz n voFreqA ct)
Output frequency in Hz. Always positive, i.e. no information about direction of revolution (forward/reverse).
5.3.9 Parameter value out (SNVT_count_inc nvoParam)
Used as feedback variable for generic parameter requests. See nciRdAdr (chapter 5.3.13), nciWriAdr
(chapter 5.3.11) and nciWriValue (chapter 5.3.12).
5.3.10 Emergency Status (SNVT_hvac_emerg nvoEmergStatus)
It indicates emergency stop status. Emergency stop state (nvoEmergStatus) is indicated as
EMERG_ SHUT DOWN while em er g ency stop com m and (nvi Em er gO ver ri de) is EME R G_S HUT DOWN.
ValueDefinitionContentsSupport
0EMERG_NORM ALNo emer ge nc y mo deYe s
1EMERG_PRESSURIZEEmergency pressurizeNo
2EMERG_DEPRESSURIZEEmergency depressurizeNo
3EMERG_PURGEEmergency purge modeNo
4EMERG_SHUTDOWNEmergency shutdownYes
5EMERG_FIRE
0xFFEMERG_NULValue not availableNo
−
No
5.3.11 Drive Alarm (SNVT_switch nvoDrvAlarm)
5.3.12 Drive Warning (SNVT_switch nvoDrvWarning)
It is defined as Drive Alarm: when an inverter trip occurs, Drive Warning: when an inverter warning occurs,
and then output the warning state.
TripWarning
YesNo1100(%)00(%)Drive Alarm
NoYes00(%)1100(%)Drive Warning
YesYes1100(%)1100(%)Drive Alarm and Warning
NoNo00(%)00(%)No warning
NvoDrvAlarmnvoDrvWarning
Statevaluestatevalue
13
Contents
Page 18
CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
5.4 Configuration Properties - nc i’s
If an nci has a corresponding parameter in the inverter it will be written to with the value of the nci at some
occations, apart from when nci is update from network. These occations are when:
-Node is brought online
-Inverter is power-cycled
-Inverter is tripped and error is reset from LonWorks option card
-If there is a communication error between neuron chip and option board host processor
This means that if setting e.g. F002 (Ra mp up ti me) fro m the D.O. to e.g . 3 sec will be set to 3 sec until an y of
these things happen. To ensure that these parameters have the values intended, set them from the option
board.
5.4.1 Send Heartbeat (SNVT_time_sec nciSndHrtBt)
This input configuration network variable provides the maximum send time for the variable nvoDrvSpeed.
Default value = 0 (disabled).
This configuration property is used to control the maximum time that elapses between updates of the input
network variable nviDrvSpe edStpt. If timeout occurs, the module will trip the inverter by setting
OPT1(2)_TRIP_N low.
The valid range is any value between 0.0 sec and 6,553.4 sec. Setting nciRcvHrtBt=0 disables the Receive
Heartbeat mechanism. Default value is 0.
5.4.3 Minimum Send Time (SNVT_time_sec nciMinOutTm)
This input configuration network variable control the minimum period of time that expires before the networkoutput variables can be resent. This is good for limiting use of bandwidth on the LonWorks channel.
The valid range is any value between 0.0 to 6,553.4 secs. Setting nciMinOutTm = 0 disables transmission
limiting.
Default va lu e = 0.
5.4.4 Location Label (SNVT_str_asc n ciLo cation)
This configuration property can optionally be used to provide more descriptive physical location information
than can be provided by the Neuron Chip’s 6-by te location string. The loca tion relates to the ob ject and not t o
the node.
Default va lu e = em pt y sp ac es.
5.4.5 Motor Nominal Speed (SNVT_rpm nciNmlSpeed)
This configuration property can be used for setting the base frequency (Range of setting: 30 to 400Hz or
equivalent frequency).
Base frequency(Hz)=the number of rotation(min
-1
)*the number of motor poles/120
Initial value is the value which is set at first base frequency: A003. If data is changed, it will be reflected to
A003.
Inverter parameter P049 is used for setting the number of motor poles.
14
Page 19
CHAPTER 5 LONWORKS COMMUNICATION FUNCTION
5.4.6 Nominal Frequency (SNVT_freq_hz nciNmlFreq)
This configuration property is used to provide the nominal frequency of the motor. This value is necessary to
determine the minimum and maximum frequency.
This configuration property is used to define the minimum speed of a motor. It’s value is entered as a
percent of nominal frequency, as defined by the Nominal frequency (nciNmlFreq) configuration value. Set
this parameter when drive is stopped for be st resul t, sin ce thi s i s a w rite pr ote cted p ara meter in SJ300/L300P
when drive is running. If parameter is set when running it will only be saved in optionboard and not in drive.
If the running ordered frequency is lower then nciMinSpeed, ordered frequency will not be highered.
NciMinSpeed will be in effect on the next frequency setting.
If nciNmlFreq = 50Hz and nciMinSpeed = 10%, the minimum frequency is 5Hz.
5.4.8 Maximum Speed (SNVT_lev_percent nciMaxSpeed)
This configuration property is used to define the maximum speed of a motor. It’s value is entered as a
percent of nominal speed, as defined by the Nominal Speed (nciNomSpeed) configuration value. Set this
parameter when drive is stopped for best result, since this is a write protected parameter in SJ300/L300P
when drive is running. If parameter is set when running it will only be saved in optionboard and not in drive.
If the running ordered frequency is higher then nciMaxSpeed, ordered frequency will not be lowered.
NciMaxSpeed will be in effect on the next frequency setting.
If nciNmlFreq = 50Hz and nciMaxSpeed = 125%, the maximum frequency is 65.5Hz.
The value of the maximum speed must be validated against the value of the minimum speed as follows:
This nci is used as a value input for the user selected parameter nciWriAdr. The SCPT uses the following
format:
struct{
unsigned long int lowWord; //Used for byte and word data
unsigned long int highWord; //Used for highWord when
transmitting 4 byte data
}UNVT_sj300
Scaling is defined in SJ300/L300P user’s manual.
5.4.13 Generic Parameter address setting, Read (SNVT_coun t nc iRdAdr)
Chooses the parameter address (16 bits) to be read from the drive. Addresses in the 0xFFFF**** area can
not be reached.
Default value: 0x0070
Valid range: See SJ300/L300P manual.
5.4.14 Speed setpoint scaling default value (SNVT_ lev_percent)
This parameter is used for setting its value to nviDrvSpeedScale (see chapter5.1.3) on every startup.
Default value : 0
Valid range : -163-163%
5.4.15 Power Up Out Time (SNVT_time_sec nciPwUpOutTm)
When the p ower is ON, the inv er te r a nd P C do not com m unic a te e ac h ot her d ur ing se tt ing tim e.
This setting is used for avoiding data collision, when the power is ON.
16
Page 21
CHAPTER 6 CONTROL FROM LONWORKS
6.1 Conditions for operating
This section will decsribe what conditions there are for performing some common actions and how the
combination of SNVTs and SCPTs will affect the operation of the SJ300/L300P inverter.
6.1.1 General
Communication and configuation of LonWorks optionboard and SJ300/L300P must be set up and function
properly. See manuals on both subjects.
Note: The SJ300/L300P parameter A001 must be set to 02 and A002 must be set to 01 if drive is to accept
frequency settings or/and start/stop commands from LonWorks optionboard.
6.1.2 Start
The inverter will output a frequency if nviDrvSpeedStpt.value is greater than zero, nviDrvSpeedStpt.state
isn’t zero and nviDrvSpeedScale isn’t zero. RQ_NORMAL or RQ_ENABLE has to be requested more
recently then RQ_DISABLED. RQ_REMOTE_CTRL has to be requested more recently then
RQ_MANUAL_CTRL. Node has to be online.
6.1.3 Stop
The inverter will stop and use the normal stop ramp if NviSpeedStpt.state is set to any value different from 1
or if node is brought offline. The inverter will aslo stop if RQ_DISABLED or RQ_MANUAL_CTRL is requested
in nviObjRequest or if saving to inverter EEPROM, using using 0xFFFF in nviWriteAdr.
6.1.4 Frequency setting
Followings describe two methods for setting frequency.
(1) nviInvSetFreq = 0x7FFF(Initial value)
It is possible to set request speed by using ratio of Nominal Frequency (Refer to chapter 5.4.6) or
Nominal Speed (Refer to chapter 5.4.5).
The formula below is calculation of frequency.
Frequency setting(Hz)=nviDrvSpeedStpt.value(%)×nviDrvSpeedScale(%)×nciNml Freq(Hz)
(2) nviInvSetFreq = 0 to 400,
It is possible to set 0 to 400Hz to nviInvSetFreq directly.
Example below indicates frequency setting.
(1) nviInvSetFreq = 0x7FFF(Initial value)
NviSpeedScale
0%0%10HzForwar d comman d
100%0%10HzForward command
0%100%10HzForward command
150%100%01.5*1.0* nciNmlFreqStop command
150%100%11.5*1.0* nciNmlFreqForward command
N/A1nviInvSetFreqReverse comm and
N/A1nviInvSetFreqReverse comm and
N/A1nviInvSetFreqStop comm and
Frequency settingOperation command
6.1.5 Write value to an address
1. Change address in nciWriAdr.
2. Change value in nciWriValue.
It is the changing of value in nciWriValue that triggers writing to an address in SJ300/L300P. This means that
just changing address alone will not perform a writing sequence.
To be sure that SJ300/L300P has accepted the value written to it, read it back with setting nciRdAdr to the
same address as nciWriAdr. See SJ300/L300P manual or chapter 4 for a description of available adresses.
Only addresses in the 0x0800**** area can be reached.
This parameter is also used for saving values set from option board in SJ300/L300P EEPROM. See chapter
6.2 for more details.
Address wantedNciWriAdrNciWriValueResult
0x080000000x00000“1st setting multispeed frequency 0” set
to zero
Other val id ad dr es sLast two b ytes of
valid address
Other val id ad dr es sLast two b ytes of
valid address
Access inhibited
area
Save to
SJ300/L300P
EEPROM
Last two bytes of
access inhibited
area
0xFFFFAny (but writing
Valid valueAddress written to with value
Unvalid value
Value
needed to
compleat
sequence).
Address written to with unvalid value.
SJ300/L300P take cares of unvalid
values.
Address written to with value.
SJ300/L300P take cares of access
inhibited addresses.
Saving values set from option board in
SJ300/L300P EEPROM.
18
Page 23
CHAPTER 6 CONTROL FROM LONWORKS
6.1.6 Read value from an address
The address set in nciRdAdr will be polled and result will be written to nvoParam as often as value on
address changes or the workload on the host application and nciMinOutTime allows.
If nciRdAdr is set to 0 x007 0 it will not load the ne twork wi th i n formati on not wan ted or need ed for th e momen t.
This is recommended to minimalize network load. Addresses in the 0xFFFF**** area can not be read.
0x08000070 is an area in SJ300/L300P where access is inhibited. There are other areas in SJ300/L300P
were access is inhibited but if such address is set it to nciRdAdr the option board will try to read it anyway.
See appendix 1 for a list of valid addresses.
Default value: 0x08000070 (Access Inhibited in SJ300/L300P)
Address wantedNc i RdAdrNvoParam
0x080000700x0070Zero or latest polled value , not updated
Other access inhibited area
Valid addressValid addressPolled from SJ300, continuously updated
Other access inhibited
area
Polled from SJ300, continuously updated
6.1.7 Reset fault
If an error has occured SJ300/L300P will trip. By removing the reason for tripping and setting nviObjRequest
to RQ_CLEAR_ALARM it can be reset.
6.1.8 Prioritation between nciMinOutTm and nciSendHrtBt
The nciMinOutTm will have prioritation over nciSendHrtBt. This will mean that heartbeats will not be sent as
often as specified in nciSendHrtBt if nciMinOutTm has a longer time set.
6.2 Save data in SJ300/L300P EEPRO M
To store parameter values set from option board in SJ300/L300 between power-cycles they have to be saved
in SJ300/L300P EEPROM.
Setting nciWriAdr to 0xFFFF (65535 decimal) and writing any value to nciWriValue will save parameters to
SJ300/L300P EEPROM.
NOTE : The inverter will be stopped using the normal stop ramp before saving, so it’s recommended to send
the save command only when inverter already is stopped.
The values set from option board will now remain the same after a boot sequence of the inverter.
There is no need to use the saving to EEPROM function when parameters are set from the digital operator
since they always are saved between power-cycles.
6.3 Optionboard Error han dling
If there is no response from SJ300/L300P on the serial channel in three messages in a row communication is
believed to be down.
Communication with LON is considered down if heartbeats aren’t received within nciRcvHrtBt time.
This will make SJ300/L300P trip.
19
Page 24
CHAPTER 6 CONTROL FROM LONWORKS
6.4 How to switch to operation command and f req uenc y co mmand
Table below indicates how to switch to operation command and frequency command by using the commands
in nviObjRequest. (Refer to chapter 4.1, 5.2.1 and 5.3.1)
nviObjRequestCommand setting dataControl and frequency setting
RQ_REMOTE_
CTRL
RQ_MANUAL_
CTRL
A001 = 02(Operator)
A002 = 01(Terminal)
Any data for A001 and A002
except above.
A001 = 02(Operator)
A002 = 01(Terminal)
Any data for A001 and A002
except above.
Comply with LonWork s.
Comply with A001 and A002.
Command setting mentioned as left.
Comply with A001 and A002.
6.5 Internal SJ300/L300P error codes
The malfunction codes are coded as follows. See chapter 5.3.2. Those error codes will be found in
the fourth byte of nvoDrvStatus.
Fault code SJ300/L300PFault description
0No fault
1Overcur re nt dri ve.
2Overcurrent deceleration.
3Overcurrent acceleration.
4Overcurrent.
5Overload protection.
6Braking resistor overload protection.
7Over-voltage protection.
8EEPROM error.
9Under-voltage.
10Current detector error.
11CPU error.
12External trip.
13USP error.
14Ground fault protection.
15Incoming over-voltage protection.
16Temporary power loss protection.
21Abnormal temperature.
23Gate allay error.
24Open-phase error.
30IGBT error.
35Therm is tor error.
36Abnorm al br ake.
60-69Option 1 error 0-9.
70-79Option 2 error 0-9.
20
Page 25
CHAPTER 7 COUNTERMEASURE FOR ABNORMALITY
7.1 Trip display
When the in vert er is in a tripped state, the inverter displays an error code (See table below). The trip history
monitor (d081 to d086) also displays the same error code as the inverter.
Trip code
Inverter’s running condition of trip d etect ed
7.2 Protection function list
The table below describes an error code for protecting the inverter and the motor.
Error Display in the table below, X is 6 (Error for option slot 1) or 7 (Error for option slot 2).
No.Function
1Lonworks
communic a ti on err or
2Inverter communication
error
With regard to the other errors except table above, refer to Inverter instruction manual chapter 4 Explanation
of funct i o n.
Error
Display
EX0This error is displayed, when disconnection occured, while
the inverter is operating with Lonworks.
EX9This error is displayed, when communication timeout occurs
between the inverter and the option board.
Action
7.3 Countermeasure for a trip state
The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to
Inverter instruction manual chapter 4 Explanation of function.
Trip codeName of tri pCauseConformationCountermeasure
EX0L on w o r ks
Communication
error
EX9Inverter
communication
error
Defective connector
for signal cable
causes connection
fail.
Terminating resistor
is not connected.
Wiring distance does
not much with
baudrate.
Option board is
removed.
Check the ar ea of
Connection.
Check the
Connection
Check the wir in g
Distance
Check as
Mentioned left
Improve the connection and then
reset the power supply.
Connect the terminating Resistor
and then reset the power supply
Adjust the setting to the matching
Baudrate
Adjust wiring distance
Mount the option board again
and then secure it with screws.
21
Page 26
CHAPTER 7 COUNTERMEASURE FOR ABNORMALITY
7.4 LED display and Counter measur e
Following states are indicated by three LED's.
LEDColorFunctionCountermeasure
GreenPower on and CPU running
Red flashingFlash or RAM error
Power/
Status
LonWorks
Service
Serial
channel
status
RedHardware error(if flashing red
together with Serial Status
LED, Wink command has been
received) or during initializing
inverter data.
UnlitNeuron Chip is
Configured/Normal Run mode
Flash Green
1Hz
GreenNeuron Chip is Applicationless,
GreenSerial channel status OK.
Flash Red
1Hz
RedNo serial communication. (If
Neuron Chip is Unconfigured
(No Netwo rk co nfi gur a tio n)
Unrecoverable fault
Serial communication error.Confirm cable length and connection fails
flashing red together with
Power/Status LED, Wink
command has been received)
Need to change the SJ-LW.
(Back to green after initializing data)
Confirm system setting and adjust
adequate.
Need to change the SJ-LW.
of connector. And then adjust adequate.
Confirm cable length and connection fails
of connector. And then adjust adequate.
−
−
−
−
22
Page 27
APPENDIX PARAMETER OBJECT LISTS
APPENDIX1 Parameter cross-reference list
AddressSize
H'080000004 0〜400.00Hz*1001st setting Multispeed frequency 0A020
H'080000044
H'080000084
H'0800000C4
H'080000104 0〜400.00Hz*100Multispeed frequency 2A022
H'080000144
H'080000184
H'0800001C4
H'080000204 0〜400.00Hz*100Multispeed frequency 6A026
H'080000244
H'080000284
H'0800002C4
H'080000304 0〜400.00Hz*100Multispeed frequency 10A030
H'080000344
H'080000384
H'0800003C4
H'080000404 0〜400.00Hz*100Multispeed frequency 14A034
H'080000444
H'080000484
*100Arrival frequency at acceleration2NoC045
*100Arrival frequency at deceleration2NoC046
*11st Base frequencyA003
*12nd Base frequencyA203
*13rd Base frequencyNoA303
*11st Maximum frequencyA004
*12nd Maximum frequencyA204
*13rd Maximum frequencyNoA304
*10001st Primary resistor R1 of motorNoH020
*10002nd Primary resistor R1 of motorNoH220
*10001st Secondary resistor R2 of motorNoH021
*10002nd Secondary resistor R2 of motorNoH221
*1001st Inductance L of motorNoH022
*1002nd Inductance L of motorNoH222
*1002nd No load current Io of motorNoH223
*1001st Inertia J of motorNoH024
*1002nd Inertia J of motorNoH224
*10001st Primary resistor R1 of motor (Auto)NoH030
*10002nd Primary resistor R1 of motor (Auto)NoH230
*10001st Secondary resistor R2 of motor (Auto)NoH031
*10002nd Secondary resistor R2 of motor (Auto)NoH231
*1001st Inductance L of motor (Auto)NoH032
*1002nd Inductance L of motor (Auto)NoH232
*1001st No load current Io of motor (Auto)NoH033
*1002nd No load current Io of motor (Auto)NoH233
*1001st Inertia J of motor (Auto)NoH034
*1002nd Inertia J of motor (Auto)NoH234
*101st Break point of manual torque boostA043
*103rd Break point of manual torque boostNoA343
*100Frequency of DC braking startA052
*10Time of DC braking workingA055
*10
*100Width of jumping frequency 1A064
*100Width of jumping frequency 2A066
*100Width of jumping frequency 3A068
*10Integrate (I) gain of PID controlA073
*100Differential (D) gain of PID controlA074
*100Scale of PID controlA075
*10Waiting time of retryb003
Time of DC braking working for beginning of
inverter running
operator
code
A058
24
Page 29
APPENDIX PARAMETER OBJECT LISTS
AddressSize
H'080001702
H'080001722
H'080001742 20.0〜120.0*10Level of 3rd Electronic thermal protectionNob312
H'080001762
H'080001782
H'0800017A2
H'0800017C2 0〜1000.0A*10Free electronic thermal current 2b018
H'0800017E2
H'080001802
H'080001822
H'080001842 0.0〜800.0V*10Free V/F control voltage 1b101
H'080001862
H'080001882
H'0800018A2
H'0800018C2 0.0〜800.0V*10Free V/F control voltage 3b105
H'0800018E2
H'080001902
H'080001922
H'080001942 0.0〜800.0V*10Free V/F control voltage 5b109
H'080001962
H'080001982
H'0800019A2
H'0800019C2 0.0〜800.0V*10Free V/F control voltage 7b113
*10Level of 1st Electronic thermal protect ionb012
*10Level of 2nd Electronic thermal protect ionb212
*1Free electronic thermal frequency 1b015
*10Free electronic thermal current 1b016
*1Free electronic thermal frequency 2b017
*1Free electronic thermal frequency 3b019
*10Free electronic thermal current 3b020
*1Free V/F control frequency 1b100
*1Free V/F control frequency 2b102
*10Free V/F control voltage 2b103
*1Free V/F control frequency 3b104
*1Free V/F control frequency 4b106
*10Free V/F control voltage 4b107
*1Free V/F control frequency 5b108
*1Free V/F control frequency 6b1 10
*10Free V/F control voltage 6b111
*1Free V/F control frequency 7b1 12
*10Level of Overload restriction 1
*100Constant value of Overload restriction 1b023
*10Level of Overload restriction 2
*100Constant value of Overload restriction 2b026
*1/10Display time of warningb034
*10
*100Minimum frequencyb082
*10Usage rate of BRDb090
*1On level of BRDb096
*1Level of Thermister errorb099
*100
*100Waiting time for acceleration at external brakingNob122
*100Waiting time for stop at external brakingNob123
Starting voltage of Nonstop operation
for Instantaneous power failure
Starting voltage of OV-LAD stop at Nonstop
operation for Instantaneous power failure
Frequency width of starting deceleration at
Nonstop operation for Instantaneous power failure
Waiting time for establishing external braking
condition
Waiting time for confirmation signal at external
braking
50.0
150.0
50.0
150.0
Nob051
Nob052
Nob054
Nob121
Nob124
〜
〜
operator
code
b022
b025
25
Page 30
APPENDIX PARAMETER OBJECT LISTS
AddressSize
H'080001DE2
H'080001E02 0〜1000.0(%)*101st Integral gain of speed control (PI control)NoH051
H'080001E22
H'080001E42
H'080001E62
H'080001E82 0〜100.0*101st Limiter of 0Hz controlNoH060
H'080001EA2
H'080001EC2
H'080001EE2
H'080001F02 0.01〜10.00*100P Proportion gain ChangeNoH072
H'080001F22 --Access InhibitedNo-
H'080001F41
H'080001F54 --Acces s I nhibi tedNo-
H'080001F91 00〜07codeSelection of AMI functionC029
H'080001FA1
H'080001FB1
H'080001FC1 --Access InhibitedNoH'080001FD1 00,01codeSelection of Debug mode methodC091
H'080001FE4 --Access InhibitedNo-
H'080002022
H'080002042
H'080002062
H'080002082 0〜100.00Hz*100Level f detecting Zero speedNoC063
H'0800020A2 --Access InhibitedNoH'0800020C2
H'0800020E2 0〜1000ms*1Waiting time of communication startC078
H'0800021018 --Access InhibitedNo-
H'080002222 128〜65000pls*1Pulse number of the encoderNoP011
H'080002242
H'080002262
H'080002282
H'0800022A2 0〜9.99s*100Delay time of completion Orientation modeNoP018
H'0800022C2
H'0800022E2
H'080002302
H'080002322 0〜100.00*100Loop gain of position controlNoP023
H'080002342
H'080002362
H'080002386 -- Access InhibitedNoH'0800023E1 00,01codeSelection of running direction for DIG-OPEF004
H'0800023F1
H'080002401 01〜05codeSelection of running command destinationA002
H'080002411 00,01codeSelection of AT functionA005
H'080002421
H'080002431 0〜100%*1Starting rate of O terminalA013
*102nd Proportional gain of speed control (PI control) NoH250
*102nd Integral gain of speed control (PI control)NoH251
*1001st Proportional gain of speed control (P control)NoH052
*1002nd Proportional gain of speed control (P control) NoH252
*102nd Limiter of 0Hz controlNoH260
*10PI Proportion gain ChangeNoH070
*10PI Integral gain ChangeNoH071
codeRpm change Pole selectP049
*1Adjustment of AMI outputC087
*10Adjustment of Offset of AMI outputC088
*10Level1 of overload restriction warningC041
*10Level2 of overload restriction warningNoC111
*10Level over acceptable deviation of PID controlC044
*1Warning Level of electronic thermal protectionC061
*1Stop position at Orientation modeNoP014
*100Speed at Orientation modeNoP015
*1Defining Area of completion of Orientation modeNoP017
*1The numerator of electric gearNoP020
*1The denominator of electric gearNoP021
*100Feed forward gain of position controlNoP022
*10Level of detecting over speedNoP026
*100Value of detecting over deviationNoP027
codeSelection of frequency command destinationA001
codeSelection of O2 terminal functionA006
operator
code
26
Page 31
APPENDIX PARAMETER OBJECT LISTS
AddressSize
H'080002441
H'080002451 00,01codeSelection of starting function of O terminalA015
H'080002461
H'080002471
H'080002481
H'080002491 0〜100%*1Starting rate of OI terminalA103
H'0800024A1
H'0800024B1 00,01codeSelection of starting function of OI terminalA105
H'0800024C3 --Access InhibitedNoH'0800024F1 00,01codeSelection of Multispeed methodA019
H'080002501 00〜05codeSelection of Jogging methodA039
H'080002511 00,01codeSelection of 1st Torque boost MethodA041
H'080002521 00,01codeSelection of 2nd Torque boost MethodA241
H'080002531
H'080002541
H'080002551
H'080002561 00〜05codeSelection of 1st Control method00〜02A044
H'080002571
H'080002581 00,01codeSelection of 3rd Control methodNoA344
H'080002591 20〜100%*1Gain of output voltageA045
H'0800025A1 00,01codeSelection of DC braking methodA051
H'0800025B1
H'0800025C1 0〜100*1Power of DC braking(end of running)A054
H'0800025D1 00,01code
H'0800025E1
H'0800025F1
H'080002601 00,01codeSelection of PID control presenceA071
H'080002611
H'080002621 00,01code
H'080002631
H'080002641
H'080002651
H'080002661 00,01codeSelection of 1st 2-stage accel/decel MethodA094
H'080002671 00,01codeSelection of 2nd 2-stage accel/decel MethodA294
H'080002681 00〜03codeSelection of acceleration patternA097
H'080002741 00,01codeSelection of fail phase functionb006
H'080002751
H'080002761 00〜02code
H'080002771 00〜02code
H'080002781 --Access InhibitedNo-
H'080002791
Setting
range
0〜100%
1〜30times
-100〜100%
-100〜100%
0〜100%
0〜20.0%
0〜20.0%
0〜20.0%
00〜04
0〜5.0s
0〜100
0.5〜15.0kHz
0.2〜5.0
00〜02
200〜240/
380〜480
00〜02
00〜03
01〜10
01〜10
00〜03
0.3〜1.0s
00〜02
00〜02
00〜03
magn.ContentsL300P
*1End rate of O terminalA014
*1Sampling number of fetching data from “O”naA016
*1Starting rate of O2 terminalA113
*1End rate of O2 terminalA114
*1End rate of OI terminalA104
*10Value of 1st Manual torque boostA042
*10Value of 2nd Manual torque boostA242
*10Value of 3rd Manual torque boostNoA342
codeSelection of 2nd Control method
*10Delay time of DC braking startA053
Selection of edge/level action of
DC braking trigger
*1Power of DC braking(start of running)A057
*10Carrier frequency of DC braking
*10Proportional(P) gain of PID controlA072
Selection of feedback destination
for PID control
codeSelection of AVR functionA081
codeSelection of Motor voltageA082
codeSelection of operation mode00,01A085
codeSelection of deceleration patternA098
codeCurve constant of accelerationA131
codeCurve constant of decelerationA132
codeSelection of retry methodb001
*10Acceptable time for Instantaneous power failureb002
code
code
codeSelection of method of overload restriction1b021
Selection of method(action)
at instantaneous power and under voltage
Retry number of instantaneous power and
under voltage
Selection of characteristic of
1st electronic thermal protection
Selection of characteristic of
2nd electronic thermal protection
Selection of characteristic of
3rd electronic thermal protection
H'080002851 00,01codeSelection of LAD stop by torqueNob045
H'080002861
H'080002871 00,01codeSelection of preventive of reverse runningNob046
H'080002881 00〜06*1Selection of method of reducing voltage startb036
H'080002891 --Access InhibitedNoH'0800028A1 00,01code
H'0800028B1 0〜255*1Adjustment of AM(analog monitor)b080
H'0800028C1
H'0800028D1
H'0800028E1
H'0800028F1
H'080002901 00,01codeSelection of “STOP” key functionb087
H'080002911 00,01codeSelection free run functionb088
H'080002921 00,01codeSelection of action at stopb091
H'080002931 -- Access InhibitedNo-
H'080002941 00,01codeSelection of action of cooling fanb092
H'080002951
H'080002961
H'080002971 00,01codeSelection of external braking functionNob120
H'080002981 -- Access InhibitedNo-
H'080002991
H'0800029A1
H'0800029B1
H'0800029C1
H'0800029D1
H'0800029E1
H'0800029F1
H'080002A01
H'080002A11 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A21 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A31 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A41 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A51 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A61 00,01codeSelection of a(NO) or b(NC) contact in Intelligent NoC016
Setting
range
00〜03
00〜03,10
00〜02
00〜04
0〜200%
00〜02
0〜255
0.5〜15.0kHz
00〜02
00〜02
00〜02
00〜02
01〜48,255
01〜48,255
01〜48,255
01〜48,255
01〜48,255
01〜48,255
01〜48,255
01〜48,255
magn.ContentsL300P
codeSelection of method of overload restriction2b024
codeSelection of method of Software lockb031
codeSelection of Displayb037
codeSelection of method of Torque limiterNob040
Level of torque limiter in forward and drive
(1st quadrant)
*1
codeSelection of running direction limitationb035
*1Adjustment of FM(digital monitor)b081
*10Carrier frequency(PWM frequency
codeSelection of Initializationb084
codeSelection of initialized datab085
codeSelection of BRD functionb095
codeSelection of Thermister functionb098
codeSelection of function in Intelligent input 1
codeSelection of function in Intelligent input 2
codeSelection of function in Intelligent input 3
codeSelection of function in Intelligent input 4
codeSelection of function in Intelligent input 5
codeSelection of function in Intelligent input 6NoC006
codeSelection of function in Intelligent input 7NoC007
codeSelection of function in Intelligent input 8NoC008
Level of torque limiter in reverse and regenerative
(2nd quadrant)
Level of torque limiter in reverse and drive
(3rd quadrant)
Level of torque limiter in forward and regenerative
(4th quadrant)
Selection of Non stop operation at instantaneous
power failure
H'080002A71 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A81 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002A91 00,01codeSelection of a(NO) or b(NC) contact in FW inputC019
H'080002AA1 00,01codeSelection of UP/DOWN functionC101
H'080002AB1 00,02codeSelection of RESET functionC102
H'080002AC1 00,01codeSelection of frequency matching function at
H'080002AD1
H'080002AE1
H'080002AF1
H'080002B01
H'080002B11
H'080002B21
H'080002B31
H'080002B41
H'080002B51
H'080002B61 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002B71 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002B81 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002B91 00,01codeSelection of a(NO) or b(NC) contact in Intelligent
H'080002C31 02〜05codeSelection of Data commandC070
H'080002C41
H'080002C51
H'080002C61 7,8bits*1Selection of bit length of data for RS485C073
H'080002C71
H'080002C81 1,2bits*1Selection of stop bit for RS485C075
H'080002C92 -- Access InhibitedNoH'080002CB1
H'080002CC1
H'080002CD1 00〜02codeSelection of Motor constant for 2nd motorNoH202
H'080002CE1
H'080002CF1
H'080002D01
H'080002D11 00〜03codeSelection of Motor poles for 2nd motorH204
H'080002D21 00,01codeSelection of Control ModeNoP012
Setting
00〜26
00〜26
00〜26
00〜26
00〜26
00〜26
00〜07
00〜07
0〜10.0V
0〜200%
00〜02
02〜06
1〜32
00〜02
00〜02
00〜02
00〜21
00〜21
00〜03
range
magn.ContentsL300P
input 6
NoC017
input 7
NoC018
input 8
RESET
codeSelection of function
in Intelligent output 11
codeSelection of function in Intelligent output 12
codeSelection of function in Intelligent output 13NoC023
codeSelection of function in Intelligent output 14NoC024
codeSelection of function in Intelligent output 15NoC025
codeSelection of function in Alarm relay output
codeSelection of FM functionC027
codeSelection of AM functionC028
*10Adjustment of offset of AMC086
output 11
output 12
output 13
output 14
Selection of a(NO) or b(NC) contact in Intelligent
output 15
Selection of a(NO) or b(NC) contact in Alarm relay
output
Selection of output mode of overload warning
signal
Level of over torque in forward and drive
(1st quadrant)
Level of over torque in reverse and regenerative
(2nd quadrant)
Level of over torque in reverse and drive
(3rd quadrant)
*1
codeSelection of Alarm codeNoC062
codeSelection of communication speed for RS485C071
*1Selection of Inverter address for RS 485C072
codeSelection of parity (odd or even) for RS485C074
codeSelection of Auto-tuning presenceNoH001
codeSelection of Motor constant for 1st motorNoH002
codeSelection of Motor capacity for 1st motorH003
codeSelection of Motor capacity for 2nd motorH203
codeSelection of Motor poles for 1st motorH004
Level of over torque in forward and regenerative
(4th quadrant)
00〜13
00〜13
00〜13
NoC033
NoC034
NoC035
NoC055
NoC056
NoC057
NoC058
operator
code
C103
C021
C022
C026
C031
C032
C036
C040
29
Page 34
APPENDIX PARAMETER OBJECT LISTS
AddressSize
H'080002D31
H'080002D41 00,01codeSet of Orientation directionNoP016
H'080002D51 00,01codeSelection of location of electric gearNoP019
H'080002D61 00,01codeSelection of action at option1 errorP001
H'080002D71 00,01codeSelection of action at option2 errorP002
H'080002D81 00,01codeSelection of feedback optionNoP010
Note 14
Note 14
Note 12 0〜1000.0A*10Output current of Trip1
Note 12
Note 14
Note 14 0〜4294836225s*1Accumulated time during power ON of Trip1
Note 14
Note 14
Note 12
Note 12 0〜1000.0V*10PN voltage (DC voltage) of Trip2
Note 14
Note 14
Note 14
Note 14 0〜400.00Hz*100Frequency of Trip3
Note 12
Note 12
Note 14
Note 14 0〜4294836225s*1Accumulated time during power ON of Trip3
Note 14
Note 14
Note 12
Note 12 0〜1000.0V*10PN voltage (DC voltage) of Trip4
Note 14
Note 14
Note 14
Note 14 0〜400.00Hz*100Frequency of Trip5
Note 12
Note 12
Setting
range
00〜03
00〜02
0〜4294836225s
0〜1000.0
0〜65535
0〜65535
0〜65535
0〜65535
0〜65535
0〜65535
00〜05
00〜H'FF
0〜400.00Hz
0〜1000.0V
0〜4294836225s
00〜H'FF
0〜400.00Hz
0〜1000.0A
0〜4294836225s
0〜4294836225s
00〜H'FF
0〜1000.0A
0〜1000.0V
0〜4294836225s
00〜H'FF
0〜400.00Hz
0〜1000.0A
0〜4294836225s
0〜4294836225s
00〜H'FF
0〜1000.0A
0〜1000.0V
magn.ContentsL300P
codeSelection of method of Pulse lines inputNoP013
Selection of Available of compen sat ion of
secondary resistor
codeAcc/Dec input mode selectionP031
*1Set of Accumulated time during runningd016
*10Adjusting value of ThermisterC085
*1Adjustment of “O2” terminalerC083
*1Adjustment of “OI” terminalerC082
*1Adjustment of Zero of “O” terminalerC121
*1Adjustment of Zero of “O2” terminalrC123
*1Adjustment of Zero of “OI” terminalrC122
*1Accumulated number of Trip(error)d080
*1Pointer of history of last trip(error)
*1Factor and Status of Trip1
*100Frequency of Trip1
*10PN voltage (DC voltage) of Trip1
*1Accumulated time during running of Trip1
*1Factor and Status of Trip2
*100Frequency of Trip2
*10Output current of Trip2
*1Accumulated time during running of Trip2
*1Accumulated time during power ON of Trip2
*1Factor and Status of Trip3
*10Output current of Trip3
*10PN voltage (DC voltage) of Trip3
*1Accumulated time during running of Trip3
*1Factor and Status of Trip4
*100Frequency of Trip4
*10Output current of Trip4
*1Accumulated time during running of Trip4
*1Accumulated time during power ON of Trip4
*1Factor and Status of Trip5
*10Output current of Trip5
*10PN voltage (DC voltage) of Trip5
NoP025
operator
code
30
Page 35
APPENDIX PARAMETER OBJECT LISTS
AddressSize
Note 14
Note 14
Note 14 00〜H'FF*1Factor and Status of Trip6
Note 14
Note 12
Note 12
Note 14 0〜4294836225s*1Accumulated time during running of Trip6
Note 14
H'080003DC21 -- Access InhibitedNo-
H'080003F11 00〜02codeSelection of Area code of inverterC195
H'080003F21
H'080003F31 00,01codeSelection of Voltage of inverterC197
H'080003F41 00,01codeSelection of Changeover of inverter modeC198
H'080003F511 -- Access InhibitedNo-
H'080004482
H'0800044A1 00〜02codeDirection of present runningd003
Setting
range
0〜4294836225s
0〜4294836225s
0〜400.00Hz
0〜1000.0A
0〜1000.0V
0〜4294836225s
01〜15
0〜400.000Hz
0〜39960.000
0〜400.000Hz
0〜4294836225s
0〜400.000Hz
0〜400.000Hz
0〜1000.0A
-300〜+300%
0〜1000.0kW
0〜1000.0V
0〜100.0s
0〜100.0%
0〜H'FFFF
0〜1000.0V
magn.ContentsL300P
*1Accumulated time during running of Trip5
*1Accumulated time during power ON of Trip5
*100Frequency of Trip6
*10Output current of Trip6
*10PN voltage (DC voltage) of Trip6
*1Accumulated time during power ON of Trip6
codeSelection of Capacity code of inverterC196
*1000Feedback data of PID controld004
*1000Value of conversion of frequencyd007
*1000Output frequency after Vector controld101
*1Accumulated time during Power ON(d017)
*1000Setting frequency from terminal*1000Setting frequency from attached potentiometer-
*10Output currentd002
*1Output TorqueNod012
*10Input electric powerd014
*10DC voltaged102
*10On time of BRD runningd103
*10Used rate of electronics thermal protectiond104
bitStatus of output terminald006
*10Output voltaged013
operator
code
Note1: show APPENDIX 2 Tr ip monitor data address
31
Page 36
APPENDIX PARAMETER OBJECT LISTS
APPENDIX 2 Trip monitor data address
Trip monitor data address is decided Trip monitor No. and Trip pointer(H'08000363).
Following table is Trip monitor data address.
ex.:Choiceing Last occurred trip cause(d081) .
if trip pointer equal 1,data address equal H'08000378.
if trip pointer equal 4,data address equal H'080003B4.