After reading this manual, keep it at handy for future reference.
SJ300/L300P SERIES
(DeviceNet Option)
INSTRUCTION MANUAL
Thank you for purchase of “HITACHI INVERTER”. This manual
explains about treatment of “SJ-DN (DeviceNet Option)”
manual and an instruction manual of inverter use practically for
installation, maintenance, and inspection. After reading this manual,
keep it handy for future reference.
Make sure to reach this manual to the end user.
Table of Contents
Chapter1 Introduction
Chapter6 DeviceNet Communication Function 11
Appendix Parameter Object Lists 23
NB618X
- Request Thank you for purchase of “SJ-DN (DeviceNet Option)”.
This instruction manual explains about treatment and maintenance of “SJ-DN”. Before using the product,
carefully read this manual with the instruction manual of inverter, and keeps it handy for quick reference of
operator and maintenance inspector. Before installing, operating, maintenance and inspection read this
manual carefully and follow the instructions exactly.
Always keep various kinds of specification mentioned in this manual and use exactly. And make sure to
prevent trouble by correct inspection and maintenance. Make sure to reach this manual to the end user.
- About treatment of this manual (1)Please consent that mentioned items of this manual may be change without permission.
(2)Keep this manual carefully not to lose because it can not be reissued
(3)All right reserved.
(4)Contents in this manual is written to make assurance doubly sure but, but please contact if you have
some doubts about spelling mistakes, omitted word etc.
(5)Please agree that there is no responsibility for effects resulted, in spite of contents above mentioned.
- About trademark (1)DeviceNet is trademark of Open DeviceNet Vendor Association, Inc.
Revision History Table
No.Revision contentsThe date of issuedManual No.
1.Initial release of Manual NB618XJan. 2001NB618X
Except this table, revised only spelling mistakes omitted words, and error writings without notice.
SAFETY PRECAUTIONS
CAUTION
SAFTY PRECAUTIONS
Carefully read this manual and all of the warning labels attached to the inverter before installing, operating,
maintaining, inspecting, it. Safety precautions are classified into “Warning” and “Caution ” in this manual.
:Indicates a potentially hazardous situation which, if not avoided, can result in serious
WARNING
!
injury or death.
:Indicates a potentially hazardous situation which, if not avoided, can result in minor to
CAUTION
!
moderate injury, or serous damage to the product
The situation described in may, if not avoided, lead to serious results. Important safety
measures are described in CAUTION (as well as WARNING) so be sure observe them.
Notes are described in this manual in “(Note)”. Carefully read the contents and follow them exactly.
In all the illustrations in this manual, covers and safely device are occasionally removed to describe the
details. When the product is operated, make sure that the covers and safety devices are placed as they
were specified originally and operate it according to the instruction manual.
!
CAUTION
!
SAFETY PRECAUTIONS
WARNING
!
Wiring:
Wiring work shall be carried out by electrical experts.
Otherwise, there is a danger of electric shock, fire and/or damage of product.
Implement wiring after checking that the power supply is off.
Otherwise, there is a danger of electric shock and/or fire.
Operating:
Be sure not to touch the surface or the terminal of option board while energizing.
Otherwise, there is a danger of electric shock and/or fire.
Be sure not to remove the DeviceNet option printed board while operating.
Otherwise, there is a danger of electric shock and/or fire.
Maintenance, Inspection and Part Replacement:
Wait at least 10 minutes after turning off the input power supply before performing maintenance and
inspection.
(Confirm the charge lamp on the inverter is off, checks direct current voltage between P-N terminals and
confirm it is less than 45V)
Otherwise, there is a danger of electric shock.
Make sure that only qualified persons will perform maintenance, inspection, and part replacement
(Before starting the work, remove metallic objects from your person (wristwatch, bracelet, etc.).
Be sure to use tools protected with insulation.)
Otherwise, there is a danger of electric shock and/or injury.
Note:
Never modify the unit.
Otherwise, there is a danger of electric shock and/or injury.
CAUTION
!
Installation:
Be sure not to let the foreign matter enter such as wire clippings, spatter from welding, metal shaving,
dust etc.
Otherwise, there is a danger of fire.
Be sure to fix inverter to option printed board with an attached fixed screw.
Otherwise, there is a danger of connecting error.
Be sure to fasten the screws connecting signal wire in side of option printed board. Check for any
loosening of screw.
Otherwise, there is a danger of connecting error.
Wiring:
Be sure to fasten the screws not to loose.
Otherwise, there is a danger of connecting error.
Operation:
Check rotary direction, abnormal motor noise and vibrations during operating.
Otherwise, there is a danger of injury to personnel and/or machine breakage
CHAPTER 1 INTRODUCTION
1.1 INSPECTION UPON UNPACKING
Make sure to treat the product carefully not to give shock and vibration while unpacking. Check that the
product is the one you ordered, no defect, and that there is no damage during transportation.
(Contents of packing)
If you discover any problems, contact your sales agent immediately.
1.2 INQUIRY OF THE PRODUCT AND WARRANTY FOR THE PRODUCT
1.2.1 REQUIRE WHILE INQUIRING
If inquiry of breakage, question, damage etc. is needed, please tell the following information to the supplier
you ordered or the nearest Hitachi Distributor.
(1) Type(SJ-DN)
(2) Manufacturing number (Item of label, that labeled surface of printed board. SJ-DN XXX )
(3) Date of purchasing
(4) Contents of inquiry
・Damage parts and its condition etc.
・Question parts and their contents etc.
In order to shorten impossible working time, standing spare unit is recommended.
1.2.2 WARRANTY OF THE PRODUCT
This product is guaranteed to last for one year after purchase. But, the next case is toll repair, even if within
warranty period.
(1) In case caused by operating mistake, and incorrect repair and modification.
(2) Trouble caused by reasons except the shipped product.
(3) In case of using in range over the value of specification.
(4) In case caused by natural calamity, disaster, and secondary disaster.
Warranty mentioned here means warranty for shipped product itself. Damage caused by trouble of shipped
product is not guaranteed.
[Toll repair]
Any explanation and repair after the warranty period (one-year) shall be charged to the purchaser. And also
any explanation and repair out of warranty mentioned above, even within warranty period, shall be charged
to the purchaser. If you require the toll repair, please contact your Hitachi distributor.
1
CHAPTER 1 INTRODUCTION
Connector for connecting to SJ300/L300P (Rear of unit)
SJ-DN is DeviceNet communication board for SJ300/L300P series inverter.
SJ-DN conforms to open field Network DeviceNet and it activates as slave function (Group 2 only server).
SJ-DN is also conforms ODVA’s certification.
(SJ-DN has been tested by ODVA's authorized Independent Test Lab and found to comply with ODVA
Conformance Test Software Version A-13.)
The following functions are available via DeviceNet communication function by installing SJ-DN to
SJ300/L300P series.
Polled Input/Output message connection
This command can exchange the master’s I/O data for the slave (Inverter) ’s I/O data.
Output data (from master to SJ-DN):
Run/Stop, reference frequency, Acceleration time, Deceleration time, Fault reset etc.
Input data (from SJ-DN to master):
Inverter status, output frequency, output current, trip history etc.
Explicit message connection
This function can reads and writes (configuration) the inverter’s parameter data, when it is necessary.
SJ-DN can use inverter below:
SJ300-004LF to 550LF, 007HF to 550HF, L300P-110LFR to 750LFR, 110HFR to 750HFR
(Note) RS485 communication function is disabled by installing SJ-DN to the inverter.
1.4 Appearance and Names of Parts
Figure 1-1 indicates the appearance of SJ-DN.
DeviceNet connector (open type)
Figure 1-1 Appearance of SJ-DN
Network status LED (NET)
2
CHAPTER 1 INTRODUCTION
Specifications label
Inverter model
1.5 DeviceNet Support Version
SJ-DN can use following Production number(MFG No) of SJ300/L300P series.
After MFG No. : XX8KXXXXXXXXXXXX
(Note) Production number (MFG No) is written in specifications label on main body of
SJ300/L300Pseries. Refer to figure 1-2, figure 1-3.
(Figure1-2,1-3 are the example of SJ300 series. L300P series are the same manner as
SJ300 series.)
Figure 1-2 Position of specifi cations label
Maximum applicable
Output ratings
Production number
motor
Input ratings
Figure 1-3 Contents of specifications label
3
CHAPTER 2 INSTALLATION METHOD OF PRINTED BOARD
2.1 Mounting method of option board
Figure 2-1 describes how to mount the option board to the option port 1 or 2.
There are four holes on the option board, match the two of them with the screw holes on the option port 1 or 2.
and mount the other two holes with the guide posts which are located on the option port 1 and 2. To avoid
connection failure, secure the option board with screws after connection.
Option board
Guide posts for mounting the
option board.
Option port 1
Screw holes for secure option board.
(M3 Screws)
Figure 2-1 Installation of option board
Option port 2
4
CHAPTER 3 WIRING, CONNECTING
Wiring of DeviceNet
No.
CAN_H
3.1 Connection for DeviceNet connector
SJ-DN has a Pluggable open connector (Male contacts), and a Network connector (Female contacts)
attached. The inverter and attach connector have a seal which is color coordinated to correspond to the
DeviceNet cable. Ensure the cable and contact are wired in the same color cable.
Cable side connector (attached connector)
Maker
Phoenix contact co, Ltd.MSTB 2.5/5ST-5.08 AU
Type
Dimension
15
18.2
Communication connector
Figure 3-1 Connector specification
Blue
Black
8.3
1V-- (Minus) side of power supplyBlack
2CAN_LCommunication data (Low)Blue
3ShieldShieldBare
4
5V++ (Plus) side of power supplyRed
2.54
Signal
mark
5.0
20.32
25.4
Type of signal
Communication data (High)White
White
Red
Color label
Dimension in mm
Cable
color
3.2 Communication cable for DeviceNet
Use the connector which conforms to DeviceNet specification or five conductor cable and also make sure
that cable, connector and Network distance conform to DeviceNet specification.
Baud rate(kbps)
Maximum Trunk line length(m)
(Or Maximum system length(m))Maximum length(m)Maximum total length(m)
Drop line
125500156
25025078
6
500100
5
39
CHAPTER 3 WIRING, CONNECTING
HITACHI
Terminating
Terminating
Power
Drop
HITACHI
3.3 Wiring note
1.Installing / removing the cable or connector must be done after checking the power supply off.
2.Wiring should not have bare cables exposed between connector contacts.
3.Network cables should be fixed without tension. Cables fixed under tension have potential of causing a
communication fault by to be removed a connector.
4.Provide a communication power source (DC24V).
5.A terminating resistor is not built-in the unit. Please provide it.
6.Ensure external emergency stop measures are taken to stop the inverter, in the event of a network fault.
(a) Remove the Power supply of the Inverter when the network master detects a communication fault.
(b) When the master detects a communication fault, turn on the intelligent input terminal which would be
allocated (FRS), (RS) and/or (EXT) function.
(c) Setting command P045 to except “02”.
In this setting, the inverter is tripped, deceleration or free run stop when it detects a communication
fault itself. (Factory initialization of command P045 is trip after deceleration stop (code: 01).)
See “4.2 Setting of the Inverter” and “4.3 Explanation of additional parameters” about explanation of
P045 (Inverter action when communication error).
7.Basic components for construction of DeviceNet application are shown bellow.
Refer to the master ’s description manuals when DeviceNet Network system comes into operation.
DeviceNet Master UNIT
resistor(121Ω)
(PLC)
Trunk line
SJ300/L300P
Configurater (PC)
line
Multi port Tap
SJ300/L300P
Multiple Node branching drop line.
DC24V
Supply
Other slave units
Trunk line
resistor
(121Ω)
Figure 3-2 Example of components for construction of DeviceNet application
6
CHAPTER 4 SETTING
Inverter action When
Polled I/O OUTPUT
except 0:setting and monitoring by [min-1]
↓
DR1
DR
↑
DR1
DR
↓
DR1
DRO
DR
0
MAC ID
4.1 Setting methods of Baud rate and MAC ID
Follow the procedure below to set Baud rate in DeviceNet and MAC ID, reset the power supply after
changing the setting (setting will be reflected after resetting power supply.). Initial Baud rate: 125kbps, Initial
MAC ID: 0.
4.1.1 Setting method of Baud rate
The table below is the setting method of Baud rate (Front view of the option board.).
(↑,↓ indicate direction for switch of Dip switch )
Baud rate125kbps250kbps500kbps
Dip switch
Setting
↓
DRO
ON
↓
OFF
DRO
ON
OFF
ON
↑
OFF
(Note) Do not switch on DR1 and DR0 at the same time.
4.1.2 Setting method of MAC ID
The table below is the setting method of MAC ID (Front view of the option board).
MAC IDDip switch setting
Figure left describes the direction of Dip switches. See below.
1
NA32 NA16 NA8 NA4 NA2 NA1
Bottom: 0 Upper: 1
Bit increases from right to left switches.
Therefore, figure left becomes formula below.
1・2 +0・2 +1・2 +0・2 +0・2 +1・2 =29(Hex)=41(dec)
NA32NA16NA8NA4NA2NA1
4
5
32
1
0
4.2 Setting of the Inverter
Following table describes setting items which relate SJ300 / L300P series Inverters with SJ-DN.
To set appropriate settings refer to inverter instruction manual “chapter 3 Operation”, “chapter 4 Explanation
of function” and this manual.
CodeFunctionRange of data
P044
P045
P046
P047
P048
P049
Timer setting of
communication
timeout Whilst
running
communication
error.
Instance number
Polled I/O INPUT
Instance number
Inverter action when
Idle mode detected.
Motor poles setting
for revolutions per
minute
0.00 to 99.99(sec)
setting resolution 10nsec
Case of set to 0.00, this func. Is disable.
00(trip)/01(trip after deceleration stop)
/02(ignore)/03(free run)
/04(deceleration stop)
20,21,10021impossibleimpossible
70,71,10171
00(trip)/01(trip after deceleration stop)
/02(ignore)/03(free run)
/04(deceleration stop)
0 to 38
Only even number is possible to set.
set to 0:setting and monitoring by [Hz ]
Initial
data
1.00impossibleimpossible
Setting on
run
01impossibleimpossible
impossibleimpossible
01impossibleimpossible
0impossibleimpossible
Change
mode on
run
Setting
Set data
when it
is need.
7
CHAPTER 4 SETTING
4.3 Explanation of additional parameters
Following information provide explanation of additional parameters which are necessary to use SJ-DN.
4.3.1 P044 (Timer setting of communication timeout whilst running)
Set the allowable time that is an interval of polled I/O from DeviceNet master when the inverter is running.
When the timeout occurs, the inverter ’s behavior is as set in command P045.
4.3.2 P045 (Inverter action when communication error)
This command decides what action occurs when a communication fault is detected on the network or P044
timeout occurs at the inverter while controlled from DeviceNet.
When set to 0.00, this function is disable.
4.3.3 P046 (Polled I/O OUTPUT Instance number)
This command is instance number of assembly object Polled I/O output. Set the parameter to comply with
table below. (Combination table for P046, P047).
4.3.4 P047 (Polled I/O INPUT Instance number)
This command is instance number of assembly object Polled I/O input. Set the parameter to comply with
table below. (Combination table for P046, P047).
4.3.5 P048 (Inverter action when Idle mode detected)
This command decides what action occurs when on Idle mode is detected on the network. Inverter can start
to operate after behavior below.
At the time of set to 00, 01:After Idle mode released and fault reset, inputs stop command and run command.
At the time of set to 02 :After Idle mode released.
At the time of set to 03, 04:After Idle mode released, inputs stop command and run command.
4.3.6 P049 (Motor poles setting for revolutions per minute)
Set the Motor poles for AC Drive device profile.
0 to 38 (even number value only)
Set to 0 when frequency setting (Hz).
Set to 2 to 38 when revolution speed setting (min-1).
(Combination table for P046 and P047)
P047
7071101
20○−−
21−○−P046
100−−○
○:combine.
−:Do not combine.
(Note) Do not combine P046 with P047 except for combination table above, otherwise data may not be set
correctly or may not be displayed correctly.
8
CHAPTER 5 OPERATION
OUT
Reverse
Forward
5.1 Operate with Frequency command〔Hz〕
Following information indicate the explanation of the inverter control data at P046: 100 and P047: 101.
See Chapter 6 about explanation of Polled I/O message.
Explanation on each data frame
[Output data frame]
(1) Stop command. Set frequency: 50Hz (1388hex), Acceleration: 10sec.(0064hex) and Deceleration: 10sec.
(0064hex). Both Frequency source and Run command source set from DeviceNet.
(2) Forward running command.
(3) Change frequency setting: 10Hz(03E8hex).
(4) Stop command
(5) Reverse running command. Set Frequency: 50Hz(1388hex), Acceleration: 20sec.(00C8hex) and
Deceleration: 20sec.(00C8hex).
(6) Stop command
[Input data frame]
(7) Stop condition
(8) While the inverter is in the forward run condition and accelerating, “XX” represents frequency and current.
(9) Constant speed condition. Frequency arrives at 50Hz.
(10) Deceleration condition.
(11) Constant speed condition. Frequency arrives at 10Hz.
(12) Deceleration condition.
(13) Stop condition.
(14) The inverter is in the reverse run condition and accelerating.
(15) Constant speed condition. Frequency arrives at 50Hz.
(16) Deceleration condition.
(17) Stop condition.
ACC,DEC=10sec.
50Hz
running
running
0Byte
7Byte
IN
0Byte
7Byte
60
00
88
13
64
00
64
00
00
00
00
00
00
00
00
C0
10Hz
61
00
88
13
64
00
64
00
(8)(7)
11
01
01
01
88
xx
13
xx
xx
xx
xx
xx
00
00
C0
C0
61
00
E8
03
64
00
64
00
01
01
xx
xx
xx
xx
00
C0
11
01
E8
03
xx
xx
00
C0
60
00
E8
03
64
00
64
00
01
01
xx
xx
xx
xx
00
C0
ACC,DEC=20sec.
62
00
88
13
C8
00
C8
00
02
00
01
00
xx
00
xx
00
xx
00
xx
00
00
00
C0
C0
12
01
88
13
xx
xx
00
C0
50Hz
(6)(5)(4)(3)(2)(1)
60
00
88
13
C8
00
C8
00
02
01
xx
xx
xx
xx
00
C0
(17)(16)(15)(14)(13)(12)(11)(10)(9)
00
00
00
00
00
00
00
C0
9
CHAPTER 5 OPERATION
min
Reverse
Forward
5.2 Operate with Rotational speed command〔min-1〕
Following information indicate the example of the inverter control data at P046: 21, P047: 71 and P049: 4.
See Chapter 6 about explanation of Polled I/O message.
Explanation on each data frame.
[Output frame]
(1) Stop command. Set rotational speed:1800min-1(0708hex). Acceleration / Deceleration command are
dependant on the inverter setting. Both rotational speed and run command set from DeviceNet.
(2) Forward running command.
(3) Change rotational speed command: 600min-1 (0258hex).
(4) Stop command.
(5) Reverse running command. Set rotational speed:1800min-1 (0708hex).
(6) Stop command.
[Input frame]
(7) Stop condition
(8) While the inverter is forward run condition and accelerating, “XX” represents rotational speed.
(9) Constant speed condition. Revolutions arrive at 1800min-1.
(10) Deceleration condition.
(11) Constant speed run condition. Revolutions arrive at 600min-1.
(12) Deceleration condition.
(13) Stop condition.
(14) The inverter is in the reverse run condition and accelerating.
(15) Constant speed condition. Revolutions arrive at 1800min-1.
(16) Deceleration condition.
(17) Stop condition.
1800
-1
running
running
0Byte
3Byte
0Byte
3Byte
OUT
IN
60
00
08
07
70
03
00
00
61
00
08
07
(8)(7)(17)(16)(15)(14)(13)(12)(11)(10)(9)
F4
74
04
04
08
xx
07
xx
61
00
58
02
74
05
xx
xx
600min
F4
04
58
02
60
00
58
02
74
05
xx
xx
10
-1
-1
(6)(5)(4)(3)(2)(1)
60
00
08
07
78
05
xx
xx
70
03
00
00
70
03
00
00
62
00
08
07
78
04
xx
xx
1800min
F8
04
08
07
CHAPTER 6 DEVICENET COMMUNICATION FUNCTION
6.1 Feature of DeviceNet communication function
SJ-DN conforms to open field Network DeviceNet and it activates as slave function (Group 2 only server).
There are two ways to communicate with the master, one is polled I/O message communication and the other
one is explicit message communication. Also SJ-DN corresponds to the AC Drive profile.
6.2 Basic DeviceNet specification
The table below describes basic DeviceNet specification of this product.
DeviceNet Volume I -Release2.0
DeviceNet Volume II-Release2.0
64 Nodes (Maximum number of Node for slaves are 63 Nodes)
Explicit Message
Polled Input/Output Message
Explicit Message (Each of Data has different length which are
dependant on data.)
Polled Input/Output Message 4Bytes / 8 Bytes
Group2 Only Server
(Predefined Master/Slave Connection Set)
List of object for mounting is shown below.
Name of objectsClass IDInstance IDContents
Identity01
Message Router02
DeviceNet03
Connection05
Motor Data40
Control Supervisor41
AC/DC Drive42
Inverter parameter
100〜1091,2,3
1
1
1
20,21,100
70,71,101
1,2
1
1
1
Information for distinguishing Device type, Serial
number and Vender ID etc.
This Router gives Explicit message to appropriate
object.
It controls Physical connection for DeviceNet
It controls Pol led I/O Output Message.Assembly04
It controls Pol led I/O Input Message.
It controls Connection.
It controls the motor connected to the inverter.
It controls control information of the inverter.
It controls operational information of the inverter.
It controls inverter parameter.
See Appendix about details of Inverter parameter.
11
CHAPTER6 DEVICENET COMMUNICATION FUNCTION
6.3 Details of Polled I/O communication
6.3.1 Basic I/O instance
This I/O instance is standard I/O instance, which is defined by AC drive profile in DeviceNet.
Run FwdThe inverter is running forward. 0:Stop 1:Run
Fault Reset
Speed Reference
When the bit is set to “1”, the trip states can be cancelled
0:- 1:Fault reset
It indicates speed command of the inverter.
[P049:Except for 0]
Rotational speed setting: Speed Reference(min-1) / 2 SS: Speed scale
Range of setting:0〜24000(min-1) (Resolution: 1min-1) Magnification: 1 time
e.g.) When the order of speed setting is 1800 min-1, (Speed scale:0)
Speed Reference=1800/2 =1800=0708(Hex)
[P049:0]
Operational frequency setting (Resolution: 0.01Hz ).
Range of setting:0.00 to 400.00(Hz) Magnification: 100 time
O
Fault
Reset
-Run Fwd
SS
SJ-DN to Master: Instance70 (P047 : 70)
ByteBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
0----1-
2Speed Actual (Low Byte)
3Speed Actual (High Byte)
DataContents
Faulted
Running 1
Speed Actual
It indicates the inverter is in a fault detecting state.
0:Normal 1:During detecting fault state
It indicates inverter’s running state.
0:Stop/During Reverse run 1:During Forward Run
It indicates inverter speed.
[P049:Except for 0]
Rotational speed monitor: Speed Actual(min-1) / 2 SS: Speed scale
Range of monitor:0〜24000(min-1) (Resolution: 1min-1) Magnification: 1 time
e.g.) When Speed Actual is 03E8(Hex) (Speed scale:0)
Speed Actual=03E8(Hex)/2 =1000/2 =1000(min-1)
[P049:0]
Current frequency display (Resolution: 0.01Hz ).
Range of monitor:0.00 to 400.00(Hz) Magnification: 100 time
O
Running
1
O
-Faulted
SS
12
CHAPTER 6 DEVICENET COMMUNICATION FUNCTION
6.3.2 Expansive I/O Instance
This I/O instance is standard I/O instance, which is defined by AC drive profile in DeviceNet.
Run FwdThe inverter is running forward. 0:Stop 1:Run forward
Run RevThe inverter is running reverse. 0:Stop 1:Run reverse
Fault Reset
NetCtrl
NetRef
Speed Reference
When the Bit is set to “1”, the trip states can be cancelled.
0:- 1:Fault reset
It indicates method of operation command.
0:Method of operation command, which is selected at operation command
selection(A002).
1:Method of Operation command from DeviceNet is valid.
It indicates method of frequency command.
0:Method of frequency command, which is selected at frequency command
selection(A001).
1:Method of frequency command from DeviceNet is valid.
It indicates speed command of the inverter.
[P049:Except for 0]
Rotational speed setting: Speed Reference(min-1) / 2 SS: Speed scale
Range of setting:0〜24000(min-1) (Resolution: 1 min-1) Magnification: 1 time
e.g.) When the order of speed setting is 1800 min-1, (Speed scale:0)
Speed Reference=1800/2 =1800=0708(Hex)
[P049:0]
Operational frequency setting (Resolution: 0.01Hz).
Range of setting:0.00 to 400.00(Hz) Magnification: 100 time
O
Fault
Reset
Run RevRun Fwd
SS
(Note) When set both Run Fwd and Run Rev to 1, the inverter executes the command, which is inputted first.
13
CHAPTER6 DEVICENET COMMUNICATION FUNCTION
SJ-DN to Master: Instance71 (P047 : 71)
ByteBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
0
1Drive Status
2Speed Actual (Low Byte)
3Speed Actual (High Byte)
Faulted
Warning
Running1(Fwd)
Running2(Rev)
Ready
Ctrl From Net
Ref From Net
At Reference
Drive Status
Speed Actual
At
Reference
DataContents
Ref From
Net
It indicates the inverter is in a fault detecting state.
0:Normal 1:During detecting fault state
It indicates the inverter is in a warning detecting state.
0:Normal
1:During detecting warning (When there is contradiction on the inverter setting.).
It indicates inverter’s running condition.
0:Stop / During reverse run 1:During forward run
It indicates inverter’s running condition.
0:Stop / During forward run 1:During reverse run
It indicates the inverter ready for drive.
0:Except Drive status: 3,4,5.
1:Complete ready to drive (Drive Status: 3,4,5).
It indicates selection state for inputting the inverter operational command
0:Operation command selection(A002) is valid to set.
1:Operation command from DeviceNet is valid.
It indicates selection state for inputting the inverter frequency command.
0:Frequency command selection(A001) is valid to set.
1:Frequency command from DeviceNet is valid.
It indicates arrival frequency detecting state for the inverter.
0:During stop / During accelerate or decelerate
1:Arrival frequency
It indicates inverter status.
1:Startup (Only R0-T0 power supply is ON)
2:Not Ready (Just after turn on power supply)
3:Ready (Able to activate the inverter )
4:Enabled (Inverter is running by run command)
5:Stopping (Inverter is decelerating by stop command)
6:Fault Stop (Inverter is decelerating because trip is detected)
7:Faulted (Trip condition)
It shows inverter speed.
[P49:Except for 0]
Rotational speed monitor: Speed Actual(min-1) / 2 SS: Speed scale
Range of monitor:0〜24000(min-1) (Resolution: 1min-1) Magnification: 1 time
e.g.) When Speed Actual is 03E8(Hex) (Speed scale:0)
Speed Actual=03E8(Hex)/2 =1000/2 =1000(min-1)
[P049:0]
Current frequency display (Resolution: 0.01Hz ).
Range of monitor:0.00 to 400.00(Hz) Magnification: 100 time
Ctrl From
Net
Ready
Running2
(Rev)
OO
Running1
(Fwd)
SS
WarningFaulted
14
CHAPTER 6 DEVICENET COMMUNICATION FUNCTION
6.3.3 Hitachi inverter I/O Instance
This I/O instance is able to control the operation control, which is necessary to Hitachi inverters.
Master to SJ-DN: Instance100 (P046: 100
ByteBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
0−NetRefNetCtrl−
1−
2Speed Reference (Low Byte)
3Speed Reference (High Byte)
4Acceleration time (Low Byte)
5Acceleration time (High Byte)
6Deceleration time (Low Byte)
7Deceleration time (High Byte)
DataContents
Run FwdThe inverter is running forward run. 0:Stop 1:Run forward
Run RevThe inverter is running reverse run. 0:Stop 1:Run reverse
When the Bit is set to “1”, the trip states can be cancelled.
Fault Reset
Free run stop
NetCtrl
NetRef
Speed Reference
Acceleration time /
Deceleration time
(Note) When set both Run Fwd and Run Rev to 1, the inverter executes as stop command.
0:- 1:Fault reset
Case of the inverter is not in trip condition, when the Bit is set to “1”, the inverter
will stop the motor.
When the Bit is set to “1”, the inverter stops output and the motor enters the free
run mode.
0:- 1:Free run stop
It indicates setting for method of operational command.
0:Method of operation command, which is selected at operation command
selection (A002).
1:Method of Operation command from DeviceNet is valid.
It indicates setting for method of frequency command.
0:Method of Frequency command, which is selected at frequency command
selection(A001) and setting at Acc / Dec time(F002, F003).
1:Method of frequency and Acc / Dec time command from DeviceNet is valid.
It indicates setting for output frequency of the inverter.
Range of setting:0.00 to 400.00(Hz), Resolution: 0.01(Hz), Magnification:100
times, Transmit data:0 to 9C4O(Hex)
It indicates setting for Acc/Dec time of the inverter.
Range of setting:0.1 to 3600.0(sec), Resolution:0.1(sec), Magnification:10 times
Transmit data:1 to 8CA0(Hex)
If Acceleration / Deceleration time has not been set by DeviceNet, the inverter will
use the settings in command F002 / F003.
)
Free run
stop
Fault
Reset
Run RevRun Fwd
15
CHAPTER6 DEVICENET COMMUNICATION FUNCTION
SJ-DN to Master: Instance101 (P047: 101)
ByteBit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
Input
Terminal
0
3 State
1Drive Status
2Speed Actual (Low Byte)
3Speed Actual (High Byte)
4Output current (Low Byte)
5Output current (High Byte)
6Trip cause
Ref From
7
Running1(Fwd)
Running2(Rev)
Faulted
At Reference
Input Terminal 1 State0: (opened) 1: Input terminal 1 and common are closed.
Input Terminal 2 State0: (opened) 1: Input terminal 2 and common are closed.
Input Terminal 3 State0: (opened) 1: Input terminal 3 and common are closed.
Input Terminal 4 State0: (opened) 1: Input terminal 4 and common are closed.
Input Terminal 5 State0: (opened) 1: Input terminal 5 and common are closed.
Input Terminal 6 State0: (opened) 1: Input terminal 6 and common are closed.
Input Terminal 7 State0: (opened) 1: Input terminal 7 and common are closed.
Input Terminal 8 State0: (opened) 1: Input terminal 8 and common are closed.
Forward Terminal State0: (opened) 1: Forward terminal (FW) and common are closed.
Drive Status
Speed Actual
Net
DataContents
Input
Terminal
2 State
Ctrl From
Net
It indicates inverter’s running condition.
0:Stop / During reverse run 1:During forward run
It indicates inverter’s running condition.
0:Stop / During forward run 1:During reverse run
It indicates the inverter is in a fault detecting state.
0:Normal 1:During detecting fault state
It indicates arrival frequency detecting state for the inverter.
0:During stop / During accelerate or decelerate
1:Arrival frequency
It indicates the inverter condition.
00:The inverter is stopping.
01:The inverter is running.
02:The inverter is in jogging mode.
03:The inverter’s output is stopped and the motor is free running (coasting).
04:The inverter is executing DC braking.
This includes the DC braking wait time.
05:The inverter is trying to restart with frequency matching.
Command b001 is set to ”3”.
06:Stop output at instantaneous power failure.
07:The inverter is trying to restart with frequency matching.
Command b001 is set to “2”.
08:The inverter is waiting before it runs on motor again to restart with
frequency matching (by setting b001, b088, C103).
This waiting time is as setting value command b003.
10:The inverter is in a trip condition.
11:The inverter is in under-voltage condition.
It indicates the inverter’s output frequency monitor.
Monitor range:0.00 to 400.00(Hz), Resolution: 0.01(Hz), Magnification:100
times, Receiving data:0 to 9C4O(Hex)
Input
Terminal
1 State
Forward
Terminal
state
At
Reference
Input
Terminal
8 State
−Faulted
Input
Terminal
7 State
Terminal
Input
6 State
Running2
(Rev)
Input
Terminal
5 State
Running1
(Fwd)
Input
Terminal
4 State
16
DataContents
Output current
Trip cause
Ctrl From Net
Ref From Net
CHAPTER 6 DEVICENET COMMUNICATION FUNCTION
It indicates the inverter’s output current monitor.
Monitor range:0 to 6553.5A, Magnification:10 times, Receiving data:0 to
FFFF(Hex)
Following codes are latest trip history.
00:No trip
01:Over current protection (at constant speed)
02:Over current protection (at deceleration)
03:Over current protection (at acceleration)
04:Over current protection (at the other)
05:Over load protection
06:Dynamic break resistor protection
07:Over voltage protection
08:EEPROM error
09:Under voltage
10:CT error
11:CPU error
12:External trip
13:USP error
14:Ground fault protection
15:Input over voltage protection
16:Instantaneous power failure protection
21:Abnormal temperature
23:Gate array error
24:Phase-failure
30:IGBT error
35:Thermistor error
36:Abnormal break
60 to 69:Option error 1
70 to 79:Option error 2
It indicates selection state for inputting the inverter operational command
0:Operation command selection(A002) is valid to set.
1:Operation command from DeviceNet is valid.
It indicates selection state for inputting the inverter frequency command.
0:Frequency command selection(A001), Aceeleration time setting (F002) and
Deceration time setting (F003) are valid to set.
1:Frequency command from DeviceNet is valid.
17
CHAPTER6 DEVICENET COMMUNICATION FUNCTION
Communication
ID
Type of data
ID
Type of data
6.4 Detail of DeviceNet profile
6.4.1 Overall Specification
General
Device data
PhysicalNetwork power consumption50mA
ConformanceType of connectorOpen connector
DataIsolated physical layerYes
Data
6.4.2 Identity Object (ID=1 Hex)
Instance0Not supported――――
Instance1Vender ID1GetUINT74 AC Drive
Support service (Common service)
Get_Attribute_SingleH’0E
ResetH’0500:Reset
NOPH’17
DeviceNet specificationVolume I -Release2.0
Vender nameHitachi, Ltd.Vender ID=74
DeviceNet profile nameSlave AC DriveProfile No=2
Product Catalog NO.
Product revision1.1
Operation power sourceDC11V to 24V
Support LEDModule status, Network status
Setting of MAC IDSet at Dip SW.
Default MAC ID0
Communication Baud rate settingSet at Dip SW.
Communication Baud rate supported125kbps/250kbps/500kbps
Device Network behaviorGroup 2 only server
When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history
monitor (d081 to d086) also displays the same error code as the inverter.
Inverter’s running condition of trip detected
7.2 Protection function list
The table below describes an error code for protecting the inverter and the motor.
Error Display in the table below, X is 6 (Error for option slot 1) or 7 (Error for option slot 2).
No.FunctionError
Display
1DeviceNet
EX0This error is displayed, disconnection occurs when BusOff or
communication error
2Duplicate MACIDEX1This error indicates that component have the same MADID,
3External tripEX2This error is displayed, when Fault / Trip is set to 1 toward
4Inverter communication
EX9This error is displayed, when communication timeout occurs
error
With regard to the other errors except table above, refer to Inverter instruction manual chapter 4 Explanation
of function.
Action
timeout is occurred, while the inverter is operating with
DeviceNet. (Trip is caused by P045 and P048 setting)
which exist on the same network.
control supervisor object data: Instance 1, Attribute 17.
between the inverter and the option board.
7.3 Countermeasure for a trip state
The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to
Inverter instruction manual chapter 4 Explanation of function.
Trip
code
EX0DeviceNet
EX1Duplicate
EX2External
EX9Inverter
Name of tripCauseConformationCountermeasure
Communication
error
MACID
Trip
communication
error
Baud rate is different.Check Baud
rate
Wiring distance does not
match with Baud rate
Defective connector for
signal cable causes
connection fail.
Terminating resistor is
not connected.
Network power supply is
not connected. Network
power supply is out of
regulation.
Exceeding maximum
Node.
Components have the
same MACID, which are
connected on the same
network.
Class : 29Hex
Instance: 1
Attribute: 17
Option board is
removed.
Check the wiring
distance
Check the area of
connection.
Check the
Connection
Check the
Network power
Supply voltage
(DC11 to 24V)
Check the Node.Remove unnecessary components
Check the all MACID
and also check the
component which has
the same MACID
Check as mentioned left. Set Fault/ trip to 0 toward class:
Check as mentioned leftMount the option board again and
Install correct Baud rate and then
reset the power supply.
Adjust the setting to the matching
Baud rate.
Adjust Wiring distance.
Improve the connection and then
reset the power supply.
Connect the terminating
Resistor and then reset the power
supply
Connect Network power supply and
then reset the power supply.
and adjust Node to 64 (Maximum)
or under, then reset the power
supply.
Set MACID and then reset the
power supply.
17.
then secure it with screws.
21
CHAPTER 7 COUNTERMEASURE FOR ABNORMALITY
possible to restore. Mostly this state
7.4 LED display and Countermeasure
Following states are indicated by module LED and Network LED.
MOD (Module status) LED: It indicates Inverter condition.
NET (Network status) LED: It indicates Network condition.
LEDColorExplanationCountermeasure
MODGreen lamp
is ON
Green lamp
goes ON
and OFF
Red lamp
is ON
Red lamp
goes ON
and OFF.
OFFPower off
NETGreen lamp
is ON
Green lamp
goes ON
and OFF
Red lamp
is ON
Red lamp
goes ON
and OFF.
OFFPower off / DeviceNet offline
The inverter is in normal condition
The inverter is in standby condition.
An abnormality occurred which is
impossible to restore.
But except status below.
User initializing with b084 set to 01, 02.
An abnormality occurred which is
occurs, when the inverter is in trip
conditi on.
But except status below.
User initializing with b084 set to 01, 02.
Online state and Connection are
established.
Online state and Connection are not
established.
Check the followings
Duplicate MACID.
Communication speed.
Cable disconnection.
Connection’s fail for connector.
Connection for terminating resistor.
Length of cable
Communication speed.
Cable disconnection.
Connection’s fail for connector.
Connection for terminating resistor.
Length of cable.
−
−
−
−
−
−
7.5 Other notes
When SJ-DN is installed and the Inverter ’s setting is below, the inverter will be reset to fault status when it
occur trip while driving from DeviceNet command.
Case of the inverter drive again, set run command again after release run command.
Operating mode select(A002) setting: 02(Remort)
22
APPENDIX PARAMETER OBJECT LISTS
mand
Bit6 : Dig input 7 Bit5 : Dig input 6
Bit4 : Dig input 5 Bit3 : Dig input 4
Bit2 : Dig input 3 Bit1 : Dig input 2
110
d007
111
d012
112
d013
121
d080
123
d081
124
d081
125
d081
126
d081
127
d081
130
d082
131
d082
132
d082
133
d082
135
d083
136
d083
141
d084
142
d084
(1) Inverter Data monitor/Basic Data Setting object. Class ID=100
Multi-Speed 9 (Param84)112940.00 to 400.00(Hz)100Get/SetA029
Multi-Speed 10 (Param85)113040.00 to 400.00(Hz)100Get/SetA030
Multi-Speed 11 (Param86)113140.00 to 400.00(Hz)100Get/SetA031
Multi-Speed 12 (Param87)113240.00 to 400.00(Hz)100Get/SetA032
Multi-Speed 13 (Param88)1
Multi-Speed 14 (Param89)1
Multi-Speed 15 (Param90)1
JoggingFrequency (Param91)1
Jog StopMode Sel (Param92)11391
Torque Boost Sel (Param93)1
2ndTrq-Boost Sel (Param340)2
TorqueBoostValue (Param94)1
2ndTrqBoostValue (Param341)214210.0 to 20.0(%)10Get/SetA242
3rdTrqBoostValue (Param375)314210.0 to 20.0(%)10Get/SetA342
TorqueBoostPoint (Param95)114320.0 to 50.0(%)10Get/SetA043
2ndTrqBoostPoint (Param342)214320.0 to 50.0(%)10Get/SetA243
3rdTrqBoostPoint (Param376)3
Control Select (Param96)11441
2ndControlSelect (Param343)21441
3rdControlSelect (Param377)31441
Out-Voltage Gain (Param97)1
DC Brake Enable (Param98)1
DC Br Start Freq (Param99)1
DC Br Wait Time (Param100)1
DC Brake Power (Param101)1
DC Brake Time (Param102)115520.0 to 60.0(s)10Get/SetA055
DC Brake ModeSel (Param103)1156100(Edge)/01(Level)1Get/SetA056
DCBrPowerAtStart (Param104)115710 to 70(%)1Get/SetA057
DCBrTime AtStart (Param105)115820.0 to 60.0(s)10Get/SetA058
DCBr CarrierFreq (Param106)1
Upper Freq Limit (Param59)1
2
Lower Freq Limit (Param58)1
2
Jump Frequency 1 (Param107)1
Jump Freq Width 1 (Param108)1
00(Invalid)/01(O/OI-no reverse)/
02(O/OI-reverse)
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
10 to 100(%)1
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
20.00 to 9.99(Hz)100
00(Free run)/01(Deceleration)/
02(DC Braking)/03(R-Free run)/
04(R-Deceleration)/
05(R-DC Braking)
100(Manual)/01(Automatic)1
100(Manual)/01(Automatic)1
10.0 to 20.0(%)10
02(Free setting V/f)
120 to 1001
100(invalid)/01(Valid)1
20.00 to 60.00(Hz)100
10.0 to 5.0(s)10
10 to 100(%)1
10.5 to 15.0(kHz)10
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
20.00 to 10.00(Hz)100
cation
1Get/SetA006
1Get/SetA039
1Get/SetA044
1Get/SetA244
1Get/SetA344
rule
mand
25
APPENDIX PARAMETER OBJECT LISTS
Magnifi-
Access
Com-
mand
168
Get/Set
A068
169
Get/Set
A069
170
Get/Set
A070
171
Get/Set
A071
172
Get/Set
A072
173
Get/Set
A073
174
Get/Set
A074
175
Get/Set
A075
176
Get/Set
A076
EnergySavingResp (Param124)
186
Get/Set
A086
192
Get/Set
A092
192
Get/Set
A292
194
Get/Set
A094
194
Get/Set
A294
195
Get/Set
A095
195
Get/Set
A295
196
Get/Set
A096
196
Get/Set
A296
02(U Curve)/03(Reverse U Curve)
102
Get/Set
A102
103
Get/Set
A103
104
Get/Set
A104
105
Get/Set
A105
113
Get/Set
A113
114
Get/Set
A114
FunctionInstAttrSizeMonitoring/Setting Range
Jump Frequency 2 (Param109)116540.00 to 400.00(Hz)100Get/SetA065
Jump Freq Width 2 (Param110)116620.00 to 10.00(Hz)100Get/SetA066
Jump Frequency 3 (Param111)116740.00 to 400.00(Hz)100Get/SetA067
Jump Freq Width 3 (Param112)1
Accel Stop Freq (Param113)1
Accel Stop Time (Param114)1
PID Enable (Param115)1
PID-P Gain (Param116)1
PID-I Gain (Param117)1
PID-D Gain (Param118)1
PID Scale (Param119)1
PID Feedback Sel (Param120)1
AVR Selection (Param121)11811
MotorVoltage Sel (Param122)11821
OperationModeSel (Param123)11851
1
Accel Time 2 (Param125)1
2nd Accel Time 2 (Param344)2
3rd Accel Time 2 (Param378)319240.01 to 3600.00(s)100Get/SetA392
Decel Time 2 (Param126)119340.01 to 3600.00(s)100Get/SetA093
2nd Decel Time 2 (Param345)219340.01 to 3600.00(s)100Get/SetA293
3rd Decel Time 2 (Param379)319340.01 to 3600.00(s)100Get/SetA393
Accel/Decel2 Sel (Param127)1
2nd Acc/Dec2 Sel (Param346)2
Accel2 StartFreq (Param128)1
2ndAcc2StartFreq (Param347)2
Decel2 StartFreq (Param129)1
2ndDec2StartFreq (Param348)2
AccelPattern Sel (Param130)11971
DecelPattern Sel (Param131)11981
20.00 to 10.00(Hz)100
40.00 to 400.00(Hz)100
20.0 to 60.0(s)10
100(Invalid)/01(Valid)1
10.2 to 51
20.0 to 3600.0(s)10
20.00 to 100.00(s)100
20.01 to 99.99(%)100
100(OI)/01(O)1
00(ON)/01(OFF)/
02(OFF on decel)
00(200)/01(215)/02(220)/03(230)/
04(240)/05(380)/06(400)/07(415)/
08(440)/09(460)/10(480)/11(575)/
12(600)
00(Normal)/01(Energy saving)/
02(Fuzzy)
20.0 to 100.0(s)10
40.01 to 3600.00(s)100
40.01 to 3600.00(s)100
100(Terminal)/01(Frequency)1
100(Terminal)/01(Frequency)1
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
40.00 to 400.00(Hz)100
10 to 100(%)1
10 to 100(%)1
100(Set Frequency)/01(0Hz)1
1-100 to 100(%)1
1-100 to 100(%)1
01(small swelling) to
10(large swelling)
01(small swelling) to
10(large swelling)
Magnifi-
cation
1Get/SetA131
1Get/SetA132
Access
rule
Support service
Service nameCode
Get_Attribute_SingleH’0E
Set_Attribute_SingleH’10
Com-
mand
26
(3) Extend Group B object Class ID=103
Magnifi-
Access
mand
102
Get/Set
b002
103
Get/Set
b003
105
Get/Set
b005
106
Get/Set
b006
107
Get/Set
b007
112
Get/Set
b012
112
Get/Set
b212
112
Get/Set
b312
115
Get/Set
b015
116
Get/Set
b016
117
Get/Set
b017
118
Get/Set
b018
119
Get/Set
b019
120
Get/Set
b020
122
Get/Set
b022
123
Get/Set
b023
00(Inactive)/01(Inactive at dec 1)/
126
Get/Set
b026
134
Get/Set
b034
01(Forward only)/02(Reverse only)
ReducedV TimeSel (Param166)
136
Get/Set
b036
141
Get/Set
b041
142
Get/Set
b042
143
Get/Set
b043
144
Get/Set
b044
Torq LADSTOP Sel (Param173)
145
Get/Set
b045
IPNonStopDecTime (Param178)
153
Get/Set
b053
154
Get/Set
b054
180
Get/Set
b080
181
Get/Set
b081
182
Get/Set
b082
183
Get/Set
b083
185
Get/Set
b085
FunctionInstAttrSizeMonitoring/Setting Range
Restart Mode Sel (Param143)11011
Allowable UVTime (Param144)1
Restart WaitTime (Param145)1
IP/UVTrip AtStop (Param146)11041
IP/UVRestartTime(Param147)1
Open-phaseSelect (Param148)1
FreqSet To Match (Param149)1
E-Thermal Level (Param150)1
2nd E- ThermalLvl (Param349)2
3rd E-ThermalLvl (Param380)3
E- ThermalCharSel (Param151)11131
2ndEThermCharSel (Param350)21131
3rdEThermCharSel (Param381)31131
E-Thermal Freq 1 (Param152)1
E-Thermal Cur 1 (Param153)1
E-Thermal Freq 2 (Param154)1
E-Thermal Cur 2 (Param155)1
E-Thermal Freq 3 (Param156)1
E-Thermal Cur 3 (Param157)1
OL Limit Enable (Param158)11211
OL Limit Level (Param159)1
OL Limit Const (Param160)1
APPENDIX PARAMETER OBJECT LISTS
cation
00(Trip)/01(0Hz Start)/
02(Synchronize)/
03(Sync& Stop& Trip)
10.3 to 1.0(s)10
20.3 to 100.0(s)10
00(Invalid)/01(Valid)/
02(Invalid on stop)
100(16 times)/01(Free)1
100(Invalid)/01(Valid)1
40.00 to 400.00(Hz)100
220 to 120(%)(constant current)1
220 to 120(%)(constant current)1
220 to 120(%)(constant current)1
FRS Cancel Sel (Param187)1188100(0Hz start)/01(Synchronize start)1Get/Setb088
BRD Using Rate (Param188)1
Stop Mode Select (Param189)1
CoolingFunContrl (Param190)1192100(Always ON)/01(ON During Run)1Get/Setb092
BRD Mode Select (Param191)11951
BRD ON Level (Param192)1
Thermistor Sel (Param193)11981
ThermistorErrLvl (Param194)119920 to 9999(Ω)1Get/Setb099
20.0 to 100.0(%)10
100(Deceleration)/01(Free run)1
02(Valid)
2330 to 380(V)/660 to 760(V)1
00(Invalid)/01(PTC Enable)/
02(NTC Enable)
cation
1Get/Setb095
1Get/Setb098
rule
Support service
Service nameCode
Get_Attribute_SingleH’0E
Set_Attribute_SingleH’10
(4) Extend Group B object Class ID=104
FunctionInstAttrSizeMonitoring/Setting Range
Free V/f Freq 1(Param195)110020 to 400(Hz)1Get/Setb100
Free V/f Volt 1(Param196)110120.0 to 800.0(V)10Get/Setb101
Free V/f Freq 2 (Param197)110220 to 400(Hz)1Get/Setb102
Free V/f Volt 2 (Param198)110320.0 to 800.0(V)10Get/Setb103
Free V/f Freq 3(Param199)1
Free V/f Volt 3 (Param200)1
Free V/f Freq 4(Param201)1
Free V/f Volt 4 (Param202)1
Free V/f Freq 5 (Param203)1
Free V/f Volt 5 (Param204)1
Free V/f Freq 6(Param205)1
Free V/f Volt 6 (Param206)1
Free V/f Freq 7 (Param207)1
Free V/f Volt 7 (Param208)1
BrakeControlMode (Param209)1
Brake Start Wait (Param210)112120.00 to 5.00(s)100Get/Setb121
Brake Accel Wait (Param211)112220.00 to 5.00(s)100Get/Setb122
Brake Stop Wait (Param212)112320.00 to 5.00(s)100Get/Setb123
BrakeConformWait (Param213)112420.00 to 5.00(s)100Get/Setb124
Releasing Freq (Param214)1
ReleasingCurrent (Param215)1
20 to 400(Hz)1
20.0 to 800.0(V)10
20 to 400(Hz)1
20.0 to 800.0(V)10
20 to 400(Hz)1
20.0 to 800.0(V)10
20 to 400(Hz)1
20.0 to 800.0(V)10
20 to 400(Hz)1
20.0 to 800.0(V)10
100(Invalid)/01(Valid)1
20.00 to 400.00(Hz)100
20 to 200(%) (constant current)1
Magnifi-
cation
Access
rule
Com
Command
b104
b105
b106
b107
b108
b109
b110
b111
b112
b113
b120
b125
b126
Support service
Service nameCode
Get_Attribute_SingleH’0E
Set_Attribute_SingleH’10
(5) Extend Group C object Class ID=105
FunctionInstAttrSizeMonitoring/Setting Range
Digital Input 1 (Param216)11011
Digital Input 2 (Param217)1
Digital Input 3 (Param218)1
cation
01(RV)/02(CF1)/03(CF2)/04(CF3)/
05(CF4)/06(JG)/07(DB)/08(SET)/
09(2CH)/11(FRS)/12(EXT)/
13(USP)/14(CS)/15(SFT)/16(AT)/
17(SET3)/18(RS)/20(STA)/
21(STP)/22(F/R)/23(PID)/
24(PIDC)/26(CAS)/27(UP)/
28(DWN)/29(UDC)/31(OPE)/
32(SF1)/33(SF2)/34(SF3)/35(SF4)/
36(SF5)/37(SF6)/38(SF7)/
39(OLR)/40(TL)/41(TRQ1)/
42(TRQ2)/43(PPI)/44(BOK)/
45(ORT)/46(LAC)/47(PCLR)/
48(STAT)/255(NO)
1Same above1
1Same above1
28
rule
1Get/SetC001
Com
mand
APPENDIX PARAMETER OBJECT LISTS
Magnifi-
Access
111
Get/Set
C011
112
Get/Set
C012
113
Get/Set
C013
114
Get/Set
C014
115
Get/Set
C015
116
Get/Set
C016
117
Get/Set
C017
118
Get/Set
C018
119
Get/Set
C019
00(RUN)/01(FA1)/02(FA2)/03(OL)/
04(OD)/05(AL)/06(FA3)/07(OTQ)/
126
Get/Set
C026
131
Get/Set
C031
132
Get/Set
C032
133
Get/Set
C033
134
Get/Set
C034
135
Get/Set
C035
AlarmReray NO/NC (Param247)
136
Get/Set
C036
140
Get/Set
C040
145
Get/Set
C045
146
Get/Set
C046
155
Get/Set
C055
156
Get/Set
C056
157
Get/Set
C057
158
Get/Set
C058
161
Get/Set
C061
162
Get/Set
C062
FunctionInstAttrSizeMonitoring/Setting Range
Digital Input 4 (Param219)11041Same above1Get/SetC004
Digital Input 5 (Param220)11051Same above1Get/SetC005
Digital Input 6 (Param221)11061Same above1Get/SetC006
Digital Input 7 (Param222)11071Same above1Get/SetC007
Reset f MacthSel (Param278)1103100(0Hz start)/01(Synchronize)1Get/SetC103
OL Alarm Level 2 (Param279)111120 to 200(%) (constant current)1Get/SetC111
O ZeroAdjustment (Param280)112120 to 655301Get/SetC121
OIZeroAdjustment (Param281)112220 to 655301Get/SetC122
2nd 0Hz-SLV Limit (Param369)216020.0 to 100(%)10Get/SetH260
PIProport-Gain2 (Param303)117020.0 to 1000(%)10Get/SetH070
PIIntegrat-Gain2 (Param304)117120.0 to 1000(%)10Get/SetH071
P Proport-Gain2 (Param305)117220.00 to 10.00100Get/SetH072
40.00 to 655.3( mH)100
40.00 to 655.3( mH)100
40.00 to 655.3( mH)100
40.00 to 655.3( mH)100
40.001 to 9999(kgm2)1000
40.001 to 9999(kgm2)1000
20.0 to 1000(%)10
20.0 to 1000(%)10
20.0 to 1000(%)10
20.0 to 1000(%)10
20.01 to 10.00100
20.01 to 10.00100
20.0 to 100(%)10
Control Mode Sel (Param310)1
Pulse Train Mode (Param311)11131
Orient-Stop Pos (Param312)1
Orient-Speed Set (Param313)1
Orient-Direction (Param314)1
Orient-CompDelay (Param316)1
Elect-GearPosSel (Param317)1
Elect-Gear Num (Param318)1
Elect-Gear Dnom (Param319)1
Feed-ForwardGain (Param320)1
Pos-CtrlLoopGain (Param321)112320.00 to 100100Get/SetP023
Compensation R2 (Param322)1125100(Invalid)/01(Valid)1Get/SetP025
Over Speed Level (Param323)112620.0 to 150(%)10Get/SetP026
SpeedErDetectLvl (Param324)112720.00 to 120(Hz)100Get/SetP027
DGInp-SelAcc/Dec (Param325)11311
OrientPosInp-Sel (Param326)11321
CommErrTime (Param327)1
1
1
1
100(Trip)/01(Run)1
100(Invalid)/01(Valid)1
2128 to 650001
100(ASR mode)/01(APR mode)1
00(Mode 0)/01(Mode 1)/
02(Mode 2)
20 to 40951
20.00 to 120(Hz)100
100(Forward)/01(Reverse)1
20 to 100001
20.00 to 9.99(s)100
100(Feedback)/01(Reference)1
21 to 99991
21 to 99991
20.00 to 655.35100
00(Operator)/01(Option 1)/
02(Option 2)
00(Operator)/01(Option 1)/
02(Option 2)
20.00 to 99.99(s)100
cation
1Get/SetP013
1Get/SetP031
1Get/SetP032
rule
Com
31
APPENDIX PARAMETER OBJECT LISTS
Magnifi-
Access
mand
146
Get/Set
P046
147
Get/Set
P047
0,2,4,6,8,10,12,14,16,18,20,22,24,
FunctionInstAttrSizeMonitoring/Setting Range
CommTimOutAction (Param328)11451
Output Assembly (Param329)1
Input Assembly(Param330)1
Idle Mode Action (Param331)11481
Rpm chg Pole sel (Param332)11491
Support service
Service nameCode
Get_Attribute_SingleH’0E
Set_Attribute_SingleH’10
cation
00(Trip)/01(Dec and trip)/
02(Hold last)/03(Free run stop)/
04(Deceleration stop)
120,21,1001
170,71,1011
00(Trip)/01(Dec and trip)/
02(Hold last)/03(Free run stop)/
04(Deceleration stop)
26,28,30,32,34,36,38
rule
Com
1Get/SetP045
1Get/SetP048
1Get/SetP049
32
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.