High starting Torque,
Powerful Drive and easy setting
High starting Torque
Improved Sensorless Vector Control and Auto Tuning
produce high starting torque of 200% or more at 0.3Hz.*
Easy setup of motor constants
Ideal for applications which need high torque, such as
cranes, extruders and lifts.
Motor Torque vs. Speed
200
0.3Hz
100
0
-100
Torque [%]
-200
*1Starting torque
SeriesApplicable motor
SJ700
SJ700B
30060090012001500 1800
Speed (min-1)
0.4 to 55kW
75 to 132kW
185 to 400kW
11 to 75kW
90 to 160kW
Starting torque
0.3Hz/200%
0.3Hz/180%
0.3Hz/150%
0.5Hz/150%
0.5Hz/120%
1
Trip avoidance function
Over current &
voltage suppress function
Higher internal calculation speed improves current control
performance.
Over-current suppress and Over-voltage suppress functions
avoid inverter trip during acceleration and deceleration.
Frequency
OC-Trip
Motor current
Over-current suppress OFF
Possible with SJ700 Series
Hitachi exclusive
0Hz Domain sensorless
)
vector control
Develops 150%(SJ700B:120%)
0Hz speed reference
Ideal for cranes and other applications
that require high torque at starting.
*2 when inverter is one frame size larger than motor.
Position Control Function
The SJ700, with optional feedback board installed, together
with an encoder-equipped motor can perform position control.
For many applications, suitable performance can be
achieved at a lower cost than servo systems.
Based on your four motion parameters (position command,
speed command, acceleration time and deceleration time),
the SJ700 will move an object from original position A to
target position B.
After the movement,
the inverter keeps servo
lock status.
*
2
torque at
*
Starting point A
Target point B
)
*
Impact load
Suppresses over current and continues running
Over-current suppress ON
DC Bus AVR Function
During Deceleration
The SJ700 controls deceleration time so that the DC bus
voltage does not exceed the over-voltage trip level, providing
trip-less operation during deceleration.
Motor current
Voltage of the
main circuit DC
Output frequency
) Derating is applied for SJ700B. Please consult technician at Hitachi or its distributor before use.
*
12
High performance, powerful functions,
yet user friendly.
Programming [EzSQ: Easy Sequence] function
Inverter control by Built-in
Programming function
Sequence operation is realized by downloading to an inverter a
program created with Hitachi's EzSQ software.
Tailor inverter operation to meet changing process
requirements, and replace separate PLCs in some cases.
By simplifying or eliminating external hardware, signficant cost
savings can be achieved.
Password function is incorporated to provide security for
proprietary program data against loss or unauthorized
modification.
Typical Example - Replacing External Relay Circuit
Standard InverterSJ700 Using EzSQ
PB2
PB1
RY1
PB2
RY2
Operation
circuit
RYA
RYB
CM1
RY1
T2
RYA
T1
PB1
RY2
T1
RYB
T2
EzSQ
Programming
Programming Window
Download
PB1
FW
8
1
PB2
2
CM1
ItemDescription
Language type BASIC Like
Supported Device
Memory area
Programming
environment
Language SpecI/O functionReserved word
Executable format
External input
External output
Command
Variable
Windows® is a registered trademark of Microsoft Corporation.U.S.A and other countries.
*
Windows(DOS/V)OS:Windows2000, WindowsXP)
1,024 steps or 6k byte
(Smaller of these)Program is stored in internal of inverter.
Editor(Windows), Display(Windows)
Grammar check(Windows)
Program download/upload, All clear
Interpreter 2.0ms/command (Sub routine supported. 8 nested)
External digital
contact input
External analog
input
General-purpose
output terminal
External analog
output
Programmable flow control <Loop, Unconditional jump, conditional jump,
Time control, Sub routine, Others>
Operation command <+,-,,*, /, substitution, mod, abs>
I/O control(Bit input, Word input, Bit output, Word output)
Timer control <on delay, off delay>
Inverter parameter setting
UserU(00)-U(31)/32 point
TimerUL(00)-UL(07)/8 point
Set frequencySET-Freq
Acceleration time
Deceleration time
Monitor
General-purpose
input contact
General-purpose
output contact
Internal timer
contact
Inverter input
and output
Contact signal/Open collector signal input
(Internal DC24V power supply available)
YA(0) : Setup for FM terminal is possible.
YA(1) : Setup for AM terminal is possible.
YA(2) : Setup for AMI terminal is possible.
ACCEL
DECEL
Output frequency, Output current, Rotative direction,
PID feedback, Converted frequency, Output torque,
Output voltage, Power, Cumulative RUN time,
Cumulative power-on time, trip
X(00)-X(07)/8 point
Y(00)-Y(05)/6 point(1 point is relay output)
UB(00)-UB(07)/8 pointInternal user
TD(0)-TD(7)/8 point
In a remote operator display code.
FW terminal is reserved
Maximum of 8 point(X(00)-X(07))
EMC Filter & Brake circuit integrated as Standard
Example (SJ700-110HFEF2)
Built-in EMC Filter up to 150kW
Cost and space reduction compared with external EMC Filter.
Reduces electromagnetic noise.
Meets EN61800-3 2nd-Environment
SJ700: European Version and Japanese Version does not have 150 kW
*
SJ700B: All models
Brake circuit up to 22kW
Cost and Space reduction compared with external Braking
Controller.
SJ700B: Up to 30kW
*
*
*
130
120
110
100
90
80
70
60
50
Level [db]
40
30
20
10
0
150k 200k 500k 1M 2M 5M 7M 10M 20M 30M
EN61800-3 2nd Envinment
[C3]QP Limit Level
Frequency [Hz]
QP: Quasi Peak
Ease of MaintenanceEasy Operation
Easy-removable construction
for maintenance
Field replacement of cooling fan(s) and DC bus capacitors
can be accomplished in a fraction of the time.
Using Logic terminal move to SJ700 without wiring change.
Read SJ300 Parameter by SRW remote operator and write
them in to SJ700
Easy-removable
Cooling Fan
SJ300seriesSJ700series
Removable Control circuit terminals
(Move to SJ700 without rewiring)
Easy-removable
DC bus Capacitors
(SJ700: above 15kW
SJ700B: above 18.5kW)
Parameter
read write
User selection of Displayed
Parameters
Data comparison function
Allows display of only parameters changed from default.
User selected function
Display of up to 12 User Defined Parameters U001 to U012.
Basic mode (default)
Basic display mode for commonly used parameters.
Basic
mode
Indication only
Chose Basic
Parameter
Other Functions
-The direct input of function code selection is possible rather
than scrolling through the list.
-Holding down the function key for 3 seconds, causes the
display to jump to output frequency monitor (d001) mode
from any menu location.
Basic Parameter
*1 Control circuit terminals comparison table
SeriesInput terminals
SJ700
SJ700B
SJ300
L300P
9terminals
(Intelligent 8terminals,FW)
6terminals
(Intelligent 5terminals,FW)
Output terminals
5terminals
(Open collector outputs)
2terminals
(Relay outputs)
Long life time components &
Life time warning function
Long life time components
Design lifetime 10 Years or more for DC bus capacitors &
Cooling Fan.
Cooling Fan ON/OFF control function for longer fan life.
*Ambient temperature: Average 40 deg C (SJ700B: 30 deg C)
(no corrosive gases, oil mist or dust)
Design lifetime is calculated, and not guaranteed.
Life time warning function
Perform preventive maintenance before a failure occurs
using the Lifetime Warning function.
DC bus capacitor, cooling fan, heat sink temperature and
motor temperature can be monitored in order to replace
components prior to failure.
Network compatibility
A serial RS-485 Modbus-RTU port is standard.
The SJ700 can communicate with DeviceNet,
PROFIBUS-DP, and other networks with communication
options.
-DeviceNet is a trade mark of Open DeviceNet Vender Association, Inc.
-PROFIBUS-DP is a registered trade mark of PROFIBUS Nutzer
Organization
Simple & Low cost wiring, Ease of installation and replacement
Input voltage 240V for 200V class and 480V
for 400V class as standard.
Environmental Friendliness
Micro Surge Voltage
suppress function
Hitachi original PWM control method limits motor terminal
voltage to less than two of inverter DC bus voltage.
Lower than Hitachi motor Max. insulation voltage (1,250V)
(During regeneration, the motor terminal voltage may exceed the motor
maximum insulation voltage(1,250V))
Motor terminal voltage
Instantaneous Power Failure
Disregard Function
The SJ700 ignores instantaneous power failure when power
fluctuation happens frequently, as long as DC bus voltage
remains higher than under-voltage trip level.
Emergency stop
Shuts down the inverter by hardware, bypassing
the CPU, to achieve a reliable, emergency stop function.
Intelligent input terminal and output
terminal ON/OFF delay function
Helps simplify external circuits.
Active frequency matching function
Motor frequency match restart function operates
effectively even without motor residual voltage.
Controlled deceleration and stop
on power loss
Analog Input Disconnection
Detection Function
The SJ700 (SJ700B) outputs a disconnection signal when
frequency command through analog input is lost.
Acceleration/ Deceleration curve
functions
The curve shape (five kinds, such as S-curve, etc.) can be
chosen according to the application requirements.
Analog Command Holding
Function (AHD)
Output frequency can be changed with UP/DOWN Function,
or with an analog signal as reference value. The set
frequency at power shutdown can be saved, too.
1,250V
E=650V, cable=100m
EU RoHS compliant
EU RoHS compliant (except solder in power module)
Improvement of environment
Varnish coating of internal PC board & plating of main circuit
copper bus bar are standard.
Pulse train input function
Pulse train input for Frequency reference or PID
feed back signal, with SJ-FB (speed feed back card option).
Integrated Input Electric Power
monitor
Input electric power (kW) and Integrated input electric
power for monitoring energy saving.
Automatic Carrier Frequency
Adjustment Function
The SJ700 detects motor current and automatically reduces
carrier frequency according to the current.
The resolution of analog outputs
(voltage, current) is improved to 10 bits.
4
STANDARD SPECIFICATIONS
SJ700 Series
3-phase 200V class
110LFF2
075LFF2
004LFF2
007LFF2
015LFF2
015LFUF2
1.5(2)
2.6
3.1
7.5
8.3
35
3.5(7.7)
022LFF2
022LFUF2
2.2(3)
3.6
4.3
10.5
3-phase (3-wire) 200 to 240V (corresponding to input voltage)
12
Built-in BRD circuit (optional resistor)
35
3.5(7.7)
Model SJ700-
Enclosure (*1)IP20
Applicable motor (4-pole, kW(HP)) (*2)
Rated capacity
(kVA)
Output Ratings
Input Rating
Braking
Vibration (*5)
EMC filter
Zero-phase Reactor
Weight [kg] (lbs.)
Rated output current (A)
Overload capacity(output current)
Rated output voltage (*3)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
Minimum value of resistor (Ω)
JP Version
US Version
200V
240V
004LFUF2
0.4(1/2)
1.0
1.2
3
3.3
50
3.5(7.7)
007LFUF2
0.75(1)
1.7
2.0
5
5.5
50
3.5(7.7)
3-phase 400V class
037HFF2
022HFF2
015HFF2
JP Version
Model SJ700-
Enclosure (*1)IP20
Applicable motor (4-pole, kW(HP)) (*2)
Rated capacity
(kVA)
Output Ratings Rated output current (A)
Overload capacity(output current)
Rated output voltage (*3)
Input Rating
Braking
Vibration (*5)
EMC filter
Zero-phase Reactor
Weight [kg] (lbs.)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
Minimum value of resistor (Ω)
European Version
US Version
400V
480V
007HFF2
007HFEF2
007HFUF2
0.75(1)
1.7
2.0
2.5
2.8
100
3.5(7.7)
015HFEF2
015HFUF2
1.5(2)
2.6
3.1
3.8
4.2
100
3.5(7.7)
040HFEF2
022HFEF2
040HFUF2
022HFUF2
3.7(5)
2.2(3)
4.0(5)
6.2
3.6
7.4
4.4
9.0
5.3
3-phase (3-wire) 380 to 480V (corresponding to input voltage)
9.9
5.8
Built-in BRD circuit (optional resistor)
70
100
3.5(7.7)
3.5(7.7)
055LFF2
037LFF2
110LFUF2
075LFUF2
055LFUF2
037LFUF2
11(15)
7.5(10)
5.5(7.5)
3.7(5)
15.9
11.0
8.3
5.7
19.1
13.3
9.9
6.8
46
32
24
16.5
150%,60sec., 200%,3sec.
3-phase 200 to 240V+10%, -15%, 50/60Hz±5%
51
35
26
18
10
10
16
35
2
(0.6G), 10-55Hz
5.9m/s
Built-in (EN61800-3 category C3)
Built-in
6(13.2)
6(13.2)
6(13.2)
3.5(7.7)
110HFF2
075HFF2
055HFF2
110HFEF2
075HFEF2
055HFEF2
110HFUF2
075HFUF2
055HFUF2
11(15)
7.5(10)
5.5(7.5)
17.3
13.1
9.7
20.7
15.8
11.6
25
19
14
150%,60sec., 200%,3sec.
3-phase 380 to 480V +10%, -15%, 50/60Hz±5%
30
23
17
35
35
70
2
(0.6G), 10-55Hz2.9m/s2(0.3G), 10-55Hz
5.9m/s
Built-in (EN61800-3 category C3)
Built-in
6(13.2)
6(13.2)
6(13.2)
150LFF2
150LFUF2
15(20)
22.1
26.6
64
70
7.5
14(30.8)
150HFF2
150HFEF2
150HFUF2
15(20)
22.1
26.6
32
35
24
14(30.8)
185LFF2
185LFUF2
18.5(25)
26.3
31.5
76
84
7.5
14(30.8)
185HFF2
185HFEF2
185HFUF2
18.5(25)
26.3
31.5
38
42
24
14(30.8)
220LFF2
220LFUF2
22(30)
32.9
39.4
95
105
5
14(30.8)
220HFF2
220HFEF2
220HFUF2
22(30)
33.2
39.9
48
53
20
14(30.8)
550LFF2
450LFF2
370LFF2
300LFF2
550LFUF2
450LFUF2
370LFUF2
300LFUF2
55(75)
45(60)
37(50)
30(40)
76.2
63.0
50.2
41.9
91.4
75.6
60.2
50.3
220
182
145
121
242
200
160
133
External dynamic braking unit (option)
2.9m/s2(0.3G), 10-55Hz
22(48.4)
300HFF2
300HFEF2
300HFUF2
30(40)
40.1
48.2
58
64
External dynamic braking unit (option)
22(48.4)
30(66)
370HFF2
370HFEF2
370HFUF2
37(50)
51.9
62.3
75
83
30(66)
-
30(66)
450HFF2
450HFEF2
450HFUF2
45(60)
63.0
75.6
91
100
-
30(66)
43(94.6)
550HFF2
550HFEF2
550HFUF2
55(75)
77.6
93.1
112
123
30(66)
Model SJ700-
Enclosure (*1)
Applicable motor (4-pole, kW(HP)) (*2)
Rated capacity
(kVA)
Output Ratings Rated output current (A)
Overload capacity(output current)
Rated output voltage (*3)
Input Rating
Braking
Vibration (*5)
EMC filter
Zero-phase Reactor
Weight [kg] (lbs.)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
Minimum value of resistor (Ω)
5
European Version
US Version
JP Version
400V
480V
2200HFE2
1850HFE2
1320HFEF2
1100HFEF2
900HFEF2
750HFEF2
2200HFU2
1850HFU2
1500HFUF2
1100HFUF2
900HFUF2
750HFUF2
2200HF2
1850HF2
1320HFF2
1100HFF2
900HFF2
750HFF2
IP00
220(300)
185(250)
132(175)
110(150)
90(125)
75(100)
305
256
180.1
150.3
121.9
103.2
366
308
216.1
180.4
146.3
123.8
440
370
260
217
176
149
150%,60sec., 200%,0.5sec.
3-phase (3-wire) 380 to 480V (corresponding to input voltage)
3-phase 380 to 480V +10%, -15%, 50/60Hz±5%
286
239
194
164
External dynamic braking unit (option)
2.9m/s2(0.3G), 10-55Hz
Built-in (EN61800-3 category C3)
80(176)
80(176)
60(132)
60(132)
150%,60sec., 180%,0.5sec.
455
389
-
140(308)
2
(0.2G), 10-55Hz
1.96m/s
External Option
External OptionBuilt-in
145(319)
3150HFE2
3150HFU2
3150HF2
315(400)
416
499
600
630
210(462)
4
000HFE2
4000HFU2
4000HF2
400(550)
554
665
800
840
360(792)
STANDARD SPECIFICATIONS
SJ700B Series
3-phase 400V class
Model SJ700B-
110HFF
150HFF
185HFF
Enclosure (*1)IP20IP00
Applicable motor (4-pole, kW(HP)) (*2)
Rated capacity
(kVA)
Output Ratings
Rated output current (A)
400V
480V
11(15)
15.2
18.2
22
15(20)
20.0
24.1
29
18.5(25)
25.6
30.7
37
Overload capacity(output current)
Rated output voltage (*3)
Input Rating
Braking
Vibration (*5)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
Minimum value of resistor (Ω)
24
32
Built-in BRD circuit (optional resistor)
35
35
2
5.9m/s
41
24
(0.6G), 10-55Hz
EMC filter
Zero-phase Reactor
6(13.2)
6(13.2)
Weight (lbs.)
*1: The protection method conforms to JEM 1030.
*2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole).To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3: The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4: Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5: Conforms to the test method specified in JIS C 60068-2-6:2010 (IEC 60068-2-6 :2007).
*6: To operate the motor beyond 50/60Hz, please consult with the motor manufacturer about the maximum allowable rotation speed.
*7: Storage temperature refers to the temperature in transportation.
*8: The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10VDC, or at 19.6mA for input current 4 to 20mA.
If this characteristic is not satisfactory for your application,contact your Hitachi representative.
14(30.8)
300HFF
30(40)
39.4
47.3
57
370HFF
37(50)
48.4
58.1
70
450HFF
45(60)
58.8
70.6
85
550HFF
55(75)
72.7
87.2
105
750HFF
75(100)
220HFF
22(30)
29.7
35.7
43
120%,60sec
3-phase (3-wire) 380 to 480V (corresponding to input voltage)
3-phase 380 to 480V +10%, -15%, 50/60Hz±5%
63
47
77
94
116
External dynamic braking unit (option)
20
24
2.9m/s2(0.3G), 10-55Hz
Built-in (EN61800-3 category C3)
Built-in
14(30.8)
14(30.8)
22(48.4)
30(66)
30(66)
93.5
112.2
135
149
30(66)
900HFF
90(125)
110.8
-
55(121)
133
160
176
1100HFF
110(150)
135.1
162.1
195
199
55(121)
1320HFF
132(150)
159.3
191.2
230
253
70(154)
1600HFF
160(220)
200.9
241.1
290
300
70(154)
Model Name Indication
Model Configuration
Applicable Motor kW (HP)
SJ700
3-phase 200V
3-phase 400V
SJ700B
3-phase 400V
LFUF2
LFF2
HFEF2
HFUF2
HFF2
HFF
SJ700 series
Series NameSeries Name
Applicable Motor Capacity 004: 0.4kW(1/2HP)
Power Source
SJ700 - 055HFEF2
|
4000:400kW(500HP)
L: 3-phase 200V class
H: 3-phase 400V class
F: With keypad
U : US version
E : European version
Note: Japanese version
F: Integrated EMC filter
Version
Control method
Output frequency range (*6)
Frequency accuracy
Frequency resolution
V/f characteristics
Control
Input signal
Output signal
Monitoring on display
Other functions
Protective functions
Environmental
conditions
Options
*1: The protection method conforms to JEM 1030.
*2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole).
To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3: The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4: Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5: Conforms to the test method specified in JIS C 60068-2-6:2010 (IEC 60068-2-6:2007).
*6: To operate the motor beyond 50/60Hz, please consult with the motor manufacturer about the maximum allowable rotation speed.
*7: Storage temperature refers to the temperature in transportation.
*8:
The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10VDC,or at 19.6mA for input current 4 to 20mA.If this characteristic is not satisfactory for your application,contact your Hitachi representative.
*9: SJ700B series is -10 to 45℃.
*10: Please be sure to connect DC reactor attached to 1850HF,2200HF,3150HF and 4000HF.
*11: 1850HF,2200HF,3150HF and 4000HF:The function is not provided.
SJ700 (Sensorless vector control): 200% at 0.3Hz/ 75kW to 150kW:180% at 0.3Hz,185kW and over:150% at 0.3Hz.
SJ700B (Sensorless vector control): 150% at 0.5Hz/ 90kW and over:120% at 0.5Hz,
SJ700 (0Hz domain with motor one frame size down):150% at around 0Hz/ 75kW and over: 130% at around 0Hz.
SJ700: 0.5-15.0kHz(185kW and over:0.5-3.0kHz)/SJ700B: 0.5-12.0kHz(90kW and over:0.5-8.0kHz)
Performs at start: under set frequency at deceleration, via an external input (braking force, time, and operating frequency).
Up and Down keys
DC 0-10V, -10-+10V (input impedance 10kΩ), 4-20mA (input impedance 100Ω)
Setting via RS485 communication
Start/stop commands (forward/reverse switching by parameter setting)
Forward-operation start/stop commands (reverse-operation start/stop possible when relevant commands are assigned to intelligent input terminals)3-wire
input possible (when relevant commands are assigned to control circuit terminals)
Running (RUN), constant-speed reached (FA1), set frequency overreached (FA2), overload notice advance signal (1) (OL), output deviation for PID control
(OD), alarm signal (AL), set frequency reached (FA3), over-torque (OTQ), instantaneous power failure (IP), undervoltage (UV), torque limited (TRQ),
operation time over (RNT), plug-in time over (ONT), thermal alarm signal (THM), brake release (BRK), braking error (BER), 0Hz detection signal (ZS),
speed deviation maximum (DSE), positioning completed (POK), set frequency overreached 2 (FA4), set frequency reached 2 (FA5), overload notice
advance signal (2) (OL2), PID feedback comparison (FBV), communication line disconnection (NDc), logical operation result 1 (LOG1), logical operation
result 2 (LOG2), logical operation result 3 (LOG3), logical operation result 4 (LOG4), logical operation result 5 (LOG5), logical operation result 6 (LOG6),
capacitor life warning (WAC)(*11), cooling-fan speed drop (WAF), starting contact signal (FR), heat sink overheat warning (OHF), low-current indication
signal (LOC), general-purpose output 1 (M01), general-purpose output 2 (M02), general-purpose output 3 (M03), general-purpose output 4 (M04),
general-purpose output 5 (M05), general-purpose output 6 (M06), inverter ready (IRDY), forward rotation (FWR), reverse rotation (RVR), major failure
(MJA), window comparator O (WCO), window comparator OI (WCOI), window comparator O2 (WCO2), alarm code 0 to 3 (AC0 to AC3)
Analog voltage output, analog current output, pulse-string output (e.g., A-F, D-F [n-fold, pulse output only], A, T, V, P)
Output frequency, output current, output torque, frequency conversion data, trip history, input/output terminal status, electric power, and others
Free V/f setting (7 breakpoints), frequency upper/lower limit, jump (center) frequency, acceleration/deceleration according to characteristic curve, manual
torque boost level/breakpoint, energy-saving operation, analog meter adjustment, start frequency setting, carrier frequency adjustment, electronic thermal
function (available also for free setting), external start/end frequency/frequency rate, analog input selection, retry after trip, restart after instantaneous power
failure, output of various signals, starting with reduced voltage, overload restriction, initial-value setting, automatic deceleration at power failure, AVR
function, fuzzy acceleration/deceleration, online/offline auto-tuning, high-torque multi-motor operation(*11) (sensorless vector control of two motors by one
inverter)
Overcurrent protection, overvoltage protection, undervoltage protection, electronic thermal protection, temperature error protection, instantaneous power
failure protection, phase loss input protection, braking-resistor overload protection, ground-fault current detection at power-on, USP error, external trip,
emergency stop trip, CT error, communication error, option board error, and others
-10-50˚C(*9) / -20-65˚C / 20-90%RH (No condensation)
*1 Vent-Holes A are formed on both right and left side portions.Vent-Holes B are just on right side.
450(17.71)
Air Intake
4-M12 Screw Holes For Eyebolts
SJ700-4000HFE2Attachment DC reactor(DCL-H-400-H-R)
2-M16 Screw Holes
15(0.59)
1700(66.92)
1670(65.74)
15
(0.59)
75(2.95)
Exhaust
Wall
450(17.71)
Air Intake
4-M16 Screw Holes For Eyebolts
365365
180
460285
285
15x25
335
2-φ14
50
100
Downward details drawing
25
Digital Oprator
75(2.95)
φ15(0.59)
4-
2-M16 Eyebolts
15(0.59)
300(11.81) 300(11.81) 300(11.81)
1050(41.33)
5
[Unit : mm(inch)]
Inches for reference only.
* 1850H,2200H,3150H and 4000H of US/JP Version:Please contact Hitachi sales office.
10
OPERATION and PROGRAMMING
SJ700 and SJ700B Series can be easily operated with the digital operator provided as standard. The digital operator can also be
detached and can be used for remote-control. Operator with copy function (WOP) and digital operator with potentiometer are also
available as options.
Parameter DisplayPower LED
Displays frequency, motor current,
rotational speed of the motor, and
an alarm code.
Lights when the power input
to the drive is ON.
Monitor LEDs
Shows drive status.
RUN key enable LED
Lights up when the inverter
is ready to respond to the
RUN key.
RUN Key
Press to run the motor.
STOP/RESET Key
Press to stop the drive or
reset an alarm.
Function Key
Press to set or monitor a
parameter value.
Setting the output frequency
Power on
(1) or the value previously monitored is displayed.
POWER
ALARM
FUNCFUNC
FUNC
Hz
V
kW
A
%
記憶
STR
POWER
ALARM
Hz
V
kW
A
%
記憶
STR
POWER
ALARM
Hz
V
kW
A
%
記憶
STR
RUN
PRG
機能
FUNC
Press key.
(2)Function code appears.
RUN
PRG
機能
FUNC
Press
until appears.
(3)appears.
RUN
PRG
機能
FUNC
Press key.
(4)Preset value is displayed.
POWER
ALARM
RUN
PRG
機能
FUNC
Hz
V
kW
A
%
記憶
STR
Press
to set desired value.
(5)Newly set value is displayed.
POWER
ALARM
STR
Hz
V
kW
A
%
記憶
STR
RUN
PRG
機能
FUNC
Press key
to store the value.
(6)Returns to and the setting is complete.
POWER
ALARM
RUN
PRG
機能
FUNC
Hz
V
kW
A
%
記憶
STR
*To run the motor, go back to
monitor mode or basic setting mode.
ALARM LED
Lights to indicate that the
inverter has tripped.
Display Unit LEDs
Indicates the unit associated
with the parameter display.
Store Key
Press to write the new value
to the EEPROM.
Up/Down Keys
Press up or down to sequence
through parameters and functions
shown on the display, and
increment/decrement values.
The contents of a basic mode display.(default)
If a desired parameter is not displayed, check the
setting of function "b037" (function code display
restriction). To display all parameters, specify "00" for
"b037".
Item
Monitor display
Output frequency setting
Acceleration (1) time setting
Deceleration (1) time setting
Operation direction setting
Frequency source setting
Run command source setting
Base frequency setting
Maximum frequency setting
[AT] selection
Multi-speed frequency setting
Multi-speed 1 setting
Multi-speed 2 setting
Multi-speed 3 setting
1st control method
V/f gain setting
Operation mode selection
Selection of restart mode
Allowable under-voltage power failure time
Retry-after-trip selection
Retry wait time after trip
Function code display restriction
Carrier frequency setting
Initialization mode selection
Selection of overvoltage suppression function
Setting of overvoltage suppression level
Setting of intelligent output terminal 11
Setting of intelligent output terminal 12
Alarm relay active state
11
FUNCTION LIST
●MONITORING FUNCTIONS and MAIN PROFILE PARAMETERS
Code
Output frequency monitor
d001
Output current monitor
d002
Rotation direction minitoring
d003
Process variable (PV), PID feedback monitor
d004
Intelligent input terminal status
d005
Intelligent output terminal status
d006
Scaled output frequency monitoring
d007
Actual-frequency monitoring
d008
Torque command monitoring
d009
Torque bias monitoring
d010
Torque monitoring
d012
Output voltage monitoring
d013
Power monitoring
d014
Cumulative power monitoring
d015
Cumulative operation RUN time monitoring
d016
Cumulative power-on time monitoring
d017
Heat sink temperature monitoring
d018
Motor temperature monitoring
d019
Monitor Mode
Life-check monitoring
d022
Program counter
d023
Program number monitoring
d024
User monitor 0
d025
User monitor 1
d026
User monitor 2
d027
Pulse counter
d028
Position setting monitor
d029
Position feedback monitor
d030
Trip Counter
d080
-
d081
Trip monitoring 1-6
d086
Programming error monitoring
d090
DC voltage monitoring
d102
BRD load factor monitoring
d103
Electronic thermal overload monitoring
d104
Output frequency setting
F001
Acceleration (1) time setting
F002
Acceleration (1) time setting, 2nd motor
F202
Acceleration (1) time setting, 3rd motor
F302
Deceleration (1) time setting
F003
Setting Mode
Deceleration time setting, 2nd motor
F203
Deceleration time setting, 3rd motor
F303
Keypad Run key routing
F004
A Group: Standard functions
A---
b Group: Fine tuning functions
b---
C Group: Intelligent terminal functions
C---
H Group: Motor constants functions
H---
P Group: Expansion card functions
P---
Expanded Function
U Group: User-selectable menu functions
U---
(*1) 4000HF:0.00 to 99.99,100.0 to 120.0(Hz) (*2)4000HF: -120. to -100., -99.9 to 0.00 to 99.99,100.0 to 120.0(Hz)
Function Name
Monitored data or setting
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.0 to 999.9, 1000 to 9999 (A)
F (forward rotation), o (stopped), r (reverse rotation)
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999. 1000 to 9999 (10000 to 99990), 「100 to 「999 (10000 to 999000)
FW
5 48 72361
AL
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0. to +200. (%)
-200. to +200. (%)
-200. to +200. (%)
0.0 to 600.0 (V)
0.0 to 999.9 (kW)
0.0 to 999.9, 1000. to 9999.,1000 to 9999 (10000 to 99990), 「100 to 「999 (100000 to 999000)
0. to 9999., 1000 to 9999 (10000 to 99990), 「100 to 「999 (10000 to 999000) (hr)
0. to 9999., 1000 to 9999 (10000 to 99990),
-020. to 200.0 (℃)
-020. to 200.0 (℃)
0 to 1024
0000 to 9999
-2147483647 to 2147483647 (upper 4 digits including “-“)
-2147483647 to 2147483647 (upper 4 digits including “-“)
-2147483647 to 2147483647 (upper 4 digits including “-“)
0 to 2147483647 (upper 4 digits)
-1073741823 to 1073741823 (upper 4 digits including “-“)
-1073741823 to 1073741823 (upper 4 digits including “-“)
0. to 9999., 1000 to 6553 (10000 to 65530) (times)
Factor, frequency (Hz), current (A), voltage across P-N (V),
running time (hours), power-on time (hours)
Warning code
0.0 to 999.9 (V)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
0.0, "start frequency" to "maximum frequency" (or maximum frequency, 2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s)
00 (forward rotation), 01 (reverse rotation)
ON
(Example) FW, 7, 2, 1 : ON
OFF
8, 6, 5, 4, 3 : OFF
ON
(Example) 12, 11 : ON
OFF
12131115 14
2 1
AL, 15, 14, 13 :OFF
「
ON
1: Capacitor on main circuit board
OFF
2: Cooling-fan speed drop
100 to 「999 (10000 to 999000) (hr)
●A GROUP: STANDARD FUNCTIONS
Code
Frequency source setting
A001
Run command source setting
A002
Base frequency setting
A003
Base frequency setting, 2nd motor
A203
Base frequency setting, 3rd motor
A303
Basic settings
Maximum frequency setting
A004
Maximum frequency setting, 2nd motor
A204
Maximum frequency setting, 3rd motor
A304
[AT] selection
A005
and others
[O2] selection
A006
Analog input
(*1) This setting is valid only when the OPE-SR is connected. (*2) 4000HF:30. to 120. (Hz)
00 (switching between O and OI terminals), 01 (switching between O and O2 terminals),
02 (switching between O terminal and keypad potentiometer) (*1), 03 (switching between OI terminal
and keypad potentiometer) (*1), 04 (switching between O2 and keypad potentiometer) (*1)
00 (single), 01 (auxiliary frequency input via O and OI terminals) (nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible), 03 (disabling O2 terminal)
Default Setting
SJ700
-FE(CE) -FU(UL)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.00
0.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
30.00
00
00
Default Setting
SJ700
-FE(CE) -FU(UL)
01
01
01
01
60.
50.
60.
50.
60.
50.
60.
50.
60.
50.
60.
50.
00
00
03
03
[◯= Allowed ×= Not permitted]
Setting
during operation
SJ700B
-F(JP)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.00
30.00
30.00
30.00
30.00
30.00
30.00
00
-F(JP)
02
02
60.
60.
60.
60.
60.
60.
00
03
(allowed or not)
-
◯
-
-
-
-
-
-
-
-
-
-
-
◯
)
-
-
*
)
-
-
*
)
-
-
*
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
)
-
-
*
)
-
-
*
-
-
-
-
-
-
-
-
-
-
-
-
0.00
◯
30.00
30.00
30.00
30.00
30.00
30.00
[◯= Allowed ×= Not permitted]
SJ700B
00
01
01
50.
50.
50.
50.
50.
50.
00
03
◯
◯
◯
◯
◯
◯
×
)
Not available
*
Setting
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
×
Change
during operation
(allowed or not)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
◯
◯
◯
◯
◯
◯
◯
×
Change
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
×
12
Code
O-L input active range start frequency
A011
O-L input active range end frequency
A012
O-L input active range start voltabe
A013
O-L input active range end voltabe
A014
O-L input active range start frequency selection
A015
External frequency filter time constant
A016
Analog input and others
Easy sequence function selection
A017
Multispeed operation selection
A019
Multispeed frequency setting
A020
Multispeed frequency setting, 2nd motor
A220
Multispeed frequency setting, 3rd motor
A320
A021
Multispeed 1-15 setting
I
A035
Jog frequency setting
A038
Jog stop mode
A039
Multispeed operation and Jogging
Torque boost method selection
A041
Torque boost method selection, 2nd motor
A241
Manual torque boost value
A042
Manual torque boost value, 2nd motor
A242
Manual torque boost value, 3rd motor
A342
Manual torque boost frequency adjustment
A043
Manual torque boost frequency adjustment, 2nd motor
A243
Manual torque boost frequency adjustment, 3rd motor
A343
V/F characteristic curve selection, 1st motor
A044
V/F characteristic curve selection, 2nd motor
A244
V/F characteristic curve selection, 3rd motor
A344
V/f gain setting
A045
V/f CharacteristicDC BrakingPID ControlAVR
Frequency Upper/Lower Limit and Jump Frequency
Operation Mode and acceleration/
Voltage compensation gain setting
A046
for automatic torque boost. 1st motor
Voltage compensation gain setting
A246
for automatic torque boost, 2nd motor
Slippage compensation gain setting
A047
for automatic torque boost, 1st motor
Slippage compensation gain setting
A247
for automatic torque boost, 2nd motor
DC braking enable
A051
DC braking frequency setting
A052
DC braking wait time
A053
DC braking force during deceleration
A054
DC braking time for deceleration
A055
DC braking/edge or level detection for [DB] input
A056
DC braking force for starting
A057
DC braking time for starting
A058
DC braking carrier frequency setting
A059
Frequency upper limit setting
A061
Frequency upper limit setting, 2nd motor
A261
Frequency lower limit setting
A062
Frequency lower limit setting, 2nd motor
A262
Jump (center) frequency setting 1
A063
Jump (hysteresis) frequency width setting 1
A064
Jump (center) frequency setting 2
A065
Jump (hysteresis) frequency width setting 2
A066
Jump (center) frequency setting 3
A067
Jump (hysteresis) frequency width setting 3
A068
Acceleration stop time frequency setting
A069
Acceleration stop time frequency setting
A070
PID function enable
A071
PID proportional gain
A072
PID integral time constant
A073
PID derivative gain
A074
PV scale conversion
A075
PV source setting
A076
Output of inverted PID deviation
A077
PID variation range
A078
AVR function select
A081
AVR voltage select
A082
Operation mode selection
A085
Energy saving mode tuning
A086
Acceleration (2) time setting
A092
Acceleration (2) time setting, 2nd motor
A292
Acceleration (2) time setting, 3rd motor
A392
Deceleration (2) time setting
A093
deceleration function
Deceleration (2) time setting, 2nd motor
A293
Deceleration (2) time setting, 3rd motor
A393
(*1)
Derating is applied for SJ700B. Please consult technician at Hitachi or its distributor before use. (*2) 4000HF:0.00 to 99.99,100.0 to 120.0(Hz)
13
Function Name
Monitored data or setting
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
00 (disabling), 01 (enabling)
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable with 7 terminals)
0.0 or “start frequency” to “maximum frequency” (Hz)
0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
"Start frequency" to 9.99 (Hz)
00 (free-running after jogging stops [disabled during operation]), 01 (deceleration and stop
after jogging stops [disabled during operation]), 02 (DC braking after jogging stops
[disabled during operation]), 03 (free-running after jogging stops [enabled during
operation]), 04 (deceleration and stop after jogging stops [enabled during operation]),
05 (DC braking after jogging stops [enabled during operation])
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
00 (frequency command + A145), 01 (frequency command - A145)
0. to 50. (%)
0. to 50. (%)
0. to 50. (%)
0. to 50. (%)
●B GROUP: FINE TUNING FUNCTIONS
Code
Selection of restart mode
b001
Allowable under-voltage power failure time
b002
Retry wait time before motor restart
b003
Instantaneous power failure/under-voltage
b004
trip alarm enable
Number of restarts on power
b005
failure/under-voltage trip events
Phase loss detection enable
b006
Restart frequency threshold
b007
Selection of retry after tripping
b008
Selection of retry after undervoltage
b009
Selection of retry count after overvoltage
b010
or overcurrent
Restart after instantaneous power failure or tripping
Retry wait time after tripping
b011
Electronic thermal setting (calculated within
b012
the inverter from current output)
Electronic thermal setting (calculated within
b212
the inverter from current output), 2nd motor
Electronic thermal setting (calculated within
b312
the inverter from current output), 3rd motor
Electronic thermal characteristic
b013
Electronic thermal characteristic, 2nd motor
b213
Electronic thermal characteristic, 3rd motor
b313
Free-setting electronic thermal frequency (1)
b015
Free-setting electronic thermal current (1)
b016
Free-setting electronic thermal frequency (2)
b017
Electronic thermal function
Free-setting electronic thermal current (2)
b018
Free-setting electronic thermal frequency (3)
b019
Free-setting electronic thermal current (3)
b020
Overload restriction operation mode
b021
Overload restriction setting
b022
Deceleration rate at overload restriction
b023
Overload restriction operation mode (2)
b024
Overload restriction setting (2)
b025
Deceleration rate at overload restriction (2)
b026
Overload restriction and overcurrent restraint
Overcurrent suppression enable
b027
(*1)
4000HF:5.0 (*2) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz) (*3) 4000HF:0. to 120.(Hz)
Function Name
Monitored data or setting
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03 (tripping after
deceleration and stopping with matching frequency), 04 (restarting with active matching frequency)
0.3 to 25.0 (s)
0.3 to 100.0 (s)
00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating to stop)
00 (16 times), 01 (unlimited)
00 (disabling), 01 (enabling)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03 (tripping after
deceleration and stopping with matching frequency), 04 (restarting with active matching frequency)
00 (16 times), 01 (unlimited)
1 to 3 (times)
0.3 to 100.0 (s)
0.20 x "rated current" to 1.00 x "rated current" (A)
0.20 x "rated current" to 1.00 x "rated current" (A)
0.20 x "rated current" to 1.00 x "rated current" (A)
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling during
constant speed), 03 (enabling during acceleration and deceleration (increasing the speed
during regeneration))
SJ700: 0.20 x "rated current" to 2.00 x "rated current" (A) < 75kW and over:0.20 x 1.80 >
SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling during
constant speed), 03 (enabling during acceleration and deceleration (increasing the speed
during regeneration))
SJ700: 0.20 x "rated current" to 2.00 x "rated current" (A) < 75kW and over:0.20 x 1.80 >
SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (disabling), 01 (enabling)
Default Setting
SJ700
-FE(CE) -FU(UL)
00
00
00
00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
00
00
00
00
0.00
0.00
0.00
0.00
20.
20.
100.
100.
00
00
0.00
0.00
0.00
0.00
-100.
-100.
100.
100.
02
02
02
02
02
02
03
03
00
00
0.00
0.00
00
00
25.
25.
25.
25.
25.
25.
25.
25.
Default Setting
SJ700
-FE(CE) -FU(UL)
00
00
1.0
1.0
1.0
1.0
(*1)
(*1)
00
00
00
00
00
00
0.00
0.00
00
00
00
00
3
3
(*1)
(*1)
1.0
1.0
Rated current of
inverterx 1..0
01
01
01
01
01
01
0.
0.
0.0
0.0
0.
0.
0.0
0.0
0.
0.
0.0
0.0
01
01
Rated current x 1.50
1.00
1.00
01
01
Rated current x 1.50
1.00
1.00
01
01
[◯= Allowed ×= Not permitted]
Setting
during operation
SJ700B
-F(JP)
0.00
0.00
0.00
0.00
0.00
0.00
20.
100.
0.00
0.00
-100.
100.
0.00
25.
25.
25.
25.
-F(JP)
1.0
1.0
0.00
1.0
00
00
00
00
00
02
02
02
03
00
00
00
(*1)
00
00
00
00
00
3
(*1)
(allowed or not)
00
×
00
×
0.00
×
0.00
×
0.00
×
0.00
×
00
×
00
×
0.00
×
0.00
×
20.
×
100.
×
00
×
0.00
×
0.00
100.
02
02
02
03
00
0.00
00
25.
25.
25.
25.
00
1.0
1.0
00
00
00
0.00
00
00
1.0
3
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Setting
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
×
×
-100.
[◯= Allowed ×= Not permitted]
SJ700B
×
×
×
×
01
00
00
00
0.
0.0
0.
0.0
0.
0.0
01
1.00
01
1.00
01
Rated
current
x 1.20
Rated
current
x 1.20
01
01
0.
0.0
0.
0.0
0.
0.0
01
1.00
01
1.00
01
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Change
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
×
×
×
Change
during operation
(allowed or not)
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
14
15
Code
overcurrent restraint
Overload restriction and
lock
software
Others
Torque limitation
Non-stop operation at
momentary power failure
Window comparatorOthersFree setting of V/f characteristic
[◯= Allowed ×= Not permitted]
Function Name
Active frequency matching, scan start frequency
b028
Active frequency matching, scan-time constant
b029
Active frequency matching, restart frequency select
b030
Software lock mode selection
b031
RUN/ power-on warning time
b034
Rotational direction restriction
b035
Reduced voltage start selection
b036
Function code display restriction
b037
Initial-screen selection
b038
Automatic user-parameter setting function enable
b039
Torque limit selection
b040
Torque limit(1)
b041
(Forward-driving in 4-quadrant mode)
Torque limit(2)
b042
(Reverse-regenerating in 4-quadrant mode)
Torque limit(3)
b043
(Reverse-driving in 4-quadrant mode)
Torque limit(4)
b044
(Forward-regenerating in 4-quadrant mode)
Torque limit LADSTOP enable
b045
Reverse RUN protection enable
b046
Controlled deceleration and stop on power loss
b050
DC bus voltage trigger level during power loss
b051
Over-voltage threshold during power loss
b052
Deceleration time setting during power loss
b053
Initial output frequency decrease during power loss
b054
Proportional gain setting for nonstop operation at power loss
b055
Integral time setting for nonstop operation at power loss
b056
Maximum-limit level of window comparators O
b060
Minimum-limit level of window comparators O
b061
Hysteresis width of window comparators O
b062
Maximum-limit level of window comparators OI
b063
Minimum-limit level of window comparators OI
b064
Hysteresis width of window comparators OI
b065
Maximum-limit level of window comparators OI
b066
Minimum-limit level of window comparators O/OI/O2
b067
Hysteresis width of window comparators O/OI/O2
b068
Operation level at O disconnection
b070
Operation level at OI disconnection
b071
Operation level at O2 disconnection
b072
Cumulative input power data clearance
b078
Cumulative input power display gain setting
b079
Start frequency adjustment
b082
Carrier frequency setting
b083
Initialization mode (parameters or trip history)
b084
Country code for initialization
b085
Frequency scaling conversion factor
b086
STOP key enable
b087
Restart mode after FRS
b088
Automatic carrier frequency reduction
b089
Dynamic braking usage ratio
b090
Stop mode selection
b091
Cooling fan control
b092
Dynamic braking control
b095
Dynamic braking activation level
b096
Thermistor for thermal protection control
b098
Thermal protection level setting
b099
Free-setting V/f frequency (1)
b100
Free-setting V/f voltage (1)
b101
Free-setting V/f frequency (2)
b102
Free-setting V/f voltage (2)
b103
Free-setting V/f frequency (3)
b104
Free-setting V/f voltage (3)
b105
Free-setting V/f frequency (4)
b106
Free-setting V/f voltage (4)
b107
Free-setting V/f frequency (5)
b108
Free-setting V/f voltage (5)
b109
Free-setting V/f frequency (6)
b110
Free-setting V/f voltage (6)
b111
Monitored data or setting
SJ700: 0.20 x "rated current" to 2.00 x "rated current" (A) < 75kW and over:0.20 x 1.50 >
SJ700B: 0.20 x "rated current" to 1.50 x "rated current" (A)
0.10 to 30.00 (s)
00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set frequency)
00 (disabling change of data other than "b031" when SFT is on), 01 (disabling change
of data other than "b031" and frequency settings when SFT is on), 02 (disabling change
of data other than "b031"), 03 (disabling change of data other than "b031" and
frequency settings), 10 (enabling data changes during operation)
0. to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hr)
00 (enabling both forward and reverse rotations), 01 (enabling only forward rotation),
02 (enabling only reverse rotation)
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start time)
00 (full display), 01 (function-specific display), 02 (user setting), 03 (data comparison
display), 04 (basic display)
00 (screen displayed when the STR key was pressed last), 01 (d001), 02 (d002),
03 (d003), 04 (d007), 05 (F001)
0. to 10. (lower limit : b066 - b067 / 2) (%)
0 to 100 (%) or "no" (ignore)
0 to 100 (%) or "no" (ignore)
0 to 100 (%) or "no" (ignore)
Clearance by setting "01" and pressing the STR key
1. to 1000.
0.10 to 9.99 (Hz)
SJ700: 0.5 to 15.0(kHz) <75 to 132kW:0.5 to 10.0/185kW and over:0.5 to 3.0>
SJ700B: 0.5 to 12.0 (kHz) <90kW and over:0.5 to 8.0.>
00 (clearing the trip history), 01 (initializing the data), 02 (clearing the trip history and
initializing the data)
00 (Japan), 01 (EU), 02 (U.S.A.)
0.1 to 99.0
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting with active
matching frequency)
00: invalid, 01: valid
0.0 to 100.0 (%)
00 (deceleration until stop), 01 (free-run stop)
00 (always operating the fan), 01 (operating the fan only during inverter operation
[including 5 minutes after power-on and power-off])
00 (disabling), 01 (enabling [disabling while the motor is topped]), 02 (enabling [enabling
also while the motor is topped])
330 to 380, 660 to 760(V)
00 (disabling the thermistor), 01 (enabling the thermistor with PTC),
02 (enabling the thermistor with NTC)
0. to 9999. (Ω)
0. to "free-setting V/f frequency (2)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (3)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (4)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (5)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (6)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (7)" (Hz)
0.0 to 800.0 (V)
Default Setting
SJ700
-FE(CE) -FU(UL)
-F(JP)
Rated current of inverterx 1..0
0.50
00
01
0.
00
06
04
01
00
00
150.
150.
150.
150.
00
00
00
220.0/440.0
360.0/720.0
1.00
0.00
0.20
0.100
100
0
0
100
0
0
100
-100
0
255(no)
255(no)
127(no)
00
1.
0.50
5.0(*2)
00
02
1.0
00
00
00
0.0
00
00
00
360/720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.50
00
01
0.
00
06
04
01
00
00
150.
150.
150.
150.
00
00
00
220.0/440.0
360.0/720.0
1.00
0.00
0.20
0.100
100
0
0
100
0
0
100
-100
0
255(no)
255(no)
127(no)
00
1.
0.50
5.0(*2)
00
00
1.0
00
00
00
0.0
00
00
00
360/720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.50
00
01
0.
00
06
04
01
00
00
150.
150.
150.
150.
00
00
00
220.0/440.0
360.0/720.0
1.00
0.00
0.20
0.100
100
0
0
100
0
0
100
-100
0
255(no)
255(no)
127(no)
00
1.
0.50
5.0(*2)
00
01
1.0
00
00
00
0.0
00
00
00
360/720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
SJ700B
0.50
00
01
0.
00
06
04
01
00
00
120.
120.
120.
120.
00
00
00
220.0/440.0
360.0/720.0
1.00
0.00
0.20
0.100
100
0
0
100
0
0
100
-100
0
255(no)
255(no)
127(no)
00
1.
0.50
3.0(*1)
00
01
1.0
00
00
00
0.0
00
00
00
360/720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
Setting
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
○
○
○
○
○
○
○
○
○
○
○
×
×
×
○
×
×
×
×
×
○
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
(*1) “Over current protection” , ” Overload restriction” , “Over current limiting” and “Electronic thermal protection” might operate from the set value when “Carrier frequency setting” is used
with less than 2kHz by a low value. Please set to 2kHz or more and use the setting of “Carrier frequency setting” for such a situation. (*2) 1850HF, 2200HF and 3150HF:2.1, 4000HF:1.9
Change
during operation
(allowed or not)
○
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
×
×
×
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
○
×
×
×
○
○
○
×
○
○
○
○
○
○
○
×
×
×
×
×
×
×
×
×
×
×
×
Default Setting
Code
of V/f
Free setting
characteristic
Others
Function Name
Free-setting V/f frequency (7)
b112
Free-setting V/f voltage (7)
b113
Brake control enable
b120
Brake wait time for release
b121
Brake wait time for acceleration
b122
Brake wait time for stopping
b123
Brake wait time for confirmation
b124
Brake release frequency setting
b125
Brake release current setting
b126
Braking frequency
b127
Overvoltage suppression enable
b130
Overvoltage suppression level
b131
Acceleration and deceleration rate
b132
at overvoltage suppression
Overvoltage suppression propotional gain
b133
Overvoltage suppression Integral time
b134
Monitored data or setting
0.0 to 400.0 (Hz) (*1)
0.0 to 800.0 (V)
00 (disabling), 01 (enabling)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.0 to 2.00 x "rated current"
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
00 (disabling the restraint), 01 (decelerating and stagnating), 02 (enabling acceleration)
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
0.10 to 30.00 (s)
0.00 to 2.55
0.000 to 9.999 / 10.00 to 63.53 (s)
SJ700
-FE(CE) -FU(UL)
0.
0.
0.0
0.0
00
00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Rated current x 1.00
0.00
0.00
00
00
380/760
380/760
1.00
1.00
0.50
0.50
0.060
0.060
-F(JP)
0.
0.0
00
0.00
0.00
0.00
0.00
0.00
0.00
00
380/760
1.00
0.50
0.060
(*1) 4000HF: 0.0 to 120.0(Hz) (*2)4000HF: 0.00 to 99.99, 100.0 to 120.0(Hz)
●C GROUP: INTELLIGENT TERMINAL FUNCTIONS
Default Setting
Code
C001
C002
C003
C004
C005
Intelligent input terminals
C006
C007
C008
C011
C012
C013
C014
C015
C016
C017
C018
Intelligent input terminals
C019
C021
C022
C023
C024
Intelligent output terminalsAnalog monitoring
C025
C026
C027
C028
C029
Terminal [1] function (*1)
Terminal [2] function
Terminal [3] function (*1)
Terminal [4] function
Terminal [5] function
Terminal [6] function
Terminal [7] function
Terminal [8] function
Terminal (1) active state
Terminal (2) active state
Terminal (3) active state
Terminal (4) active state
Terminal (5) active state
Terminal (6) active state
Terminal (7) active state
Terminal (8) active state
Terminal FW active state
Terminal (11) function
Terminal (12) function
Terminal (13) function
Terminal (14) function
Terminal (15) function
Alarm relay terminal function
FM signal selection
AM signal selection
AMI signal selection
Function Name
Monitored data or setting
01 (RV: Reverse RUN), 02 (CF1: Multispeed 1 setting), 03 (CF2: Multispeed 2 setting),
04 (CF3: Multispeed 3 setting), 05 (CF4: Multispeed 4 setting), 06 (JG: Jogging), 07 (DB:
external DC braking), 08 (SET: Set 2nd motor data), 09 (2CH: 2-stage
acceleration/deceleration), 11 (FRS: free-run stop), 12 (EXT: external trip), 13 (USP:
unattended start protection), 14: (CS: commercial power source enable), 15 (SFT: software
lock), 16 (AT: analog input voltage/current select), 17 (SET3: 3rd motor control), 18 (RS:
reset), 20 (STA: starting by 3-wire input), 21 (STP: stopping by 3-wire input), 22 (F/R:
forward/reverse switching by 3-wire input), 23 (PID: PID disable), 24 (PIDC: PID reset),
26 (CAS: control gain setting), 27 (UP: remote control UP function), 28 (DWN: remote
control DOWN function), 29 (DWN: remote control data clearing), 31 (OPE: forcible
operation), 32 (SF1: multispeed bit 1), 33 (SF2: multispeed bit 2), 34 (SF3: multispeed bit
3), 35 (SF4: multispeed bit 4), 36 (SF5: multispeed bit 5), 37 (SF6: multispeed bit 6),
38 (SF7: multispeed bit 7), 39 (OLR: overload restriction selection), 40 (TL: torque limit
enable), 41 (TRQ1: torque limit selection bit 1), 42 (TRQ2: torque limit selection bit 2),
43 (PPI: P/PI mode selection), 44 (BOK: braking confirmation), 45 (ORT: orientation), 46
(LAC: LAD cancellation), 47 (PCLR: clearance of position deviation), 48 (STAT: pulse train
position command input enable), 50 (ADD: trigger for frequency addition [A145]), 51 (F-TM:
forcible-terminal operation), 52 (ATR: permission of torque command input), 53 (KHC:
cumulative power clearance), 54 (SON: servo-on),
55 (FOC: pre-excitation), 56 (MI1: general-purpose input 1), 57 (MI2: general-purpose input
(*1) When the emergency stop function is enabled (SW1 = ON), "18" (RS) and "64" (EMR) are forcibly written to parameters "C001" and "C003",
respectively. (You cannot arbitrarily write "64" to "C001".) If the SW1 signal is turned off and then turned on, "no" (no assignment) is set in parameter "C003".
(*2) 1850HF,2200HF,3150HF and 4000HF:The function is not provided.
SJ700
-FE(CE) -FU(UL)
18(RS)
18(RS)
16(AT)
16(AT)
06(JG)
06(JG)
11(FRS)
11(FRS)
09(2CH)
09(2CH)
03(CF2)
13(USP)
02(CF1)
02(CF1)
01(RV)
01(RV)
00
00
00
00
00
00
00
00
00
00
01
00
00
00
00
00
00
00
01(FA1)
01(FA1)
00(RUN)
00(RUN)
03(OL)
03(OL)
07(OTO)
07(OTO)
40(WAF)
40(WAF)
05(AL)
05(AL)
00
00
00
00
00
00
-F(JP)
18(RS)
16(AT)
06(JG)
11(FRS)
09(2CH)
03(CF2)
02(CF1)
01(RV)
00
00
00
00
00
00
00
00
00
01(FA1)
00(RUN)
03(OL)
07(OTO)
40(WAF)
05(AL)
00
00
00
[◯= Allowed ×= Not permitted]
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
×
×
×
×
○
○
)
Not available
*
during operation
(allowed or not)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Change
×
×
○
○
○
○
○
○
○
○
○
○
○
○
○
Change
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Setting
during operation
SJ700B
(allowed or not)
0.
)
0.0
*
)
0.0
*
)
0.00
*
)
0.00
*
)
0.00
*
)
0.00
*
)
0.00
*
)
0.00
*
00
380/760
1.00
0.50
0.060
[◯= Allowed ×= Not permitted]
Setting
during operation
SJ700B
(allowed or not)
18(RS)
16(AT)
06(JG)
11(FRS)
09(2CH)
03(CF2)
02(CF1)
01(RV)
00
00
00
00
00
00
00
00
00
01(FA1)
00(RUN)
03(OL)
07(OTO)
40(WAF)
05(AL)
00
00
00
16
●C GROUP: INTELLIGENT TERMINAL FUNCTIONS
Code
Analog
monitoring
Intelligent
output terminals
Levels and output terminal statusCommunication functionAdjustmentOthers
Meter adjustment
Terminal
Adjustment
Output terminal operation function
Digital current monitor reference value
C030
Terminal (11) active state
C031
Terminal (12) active state
C032
Terminal (13) active state
C033
Terminal (14) active state
C034
Terminal (15) active state
C035
Alarm relay terminal active state
C036
Low-current indication signal output mode selection
C038
Low-current indication signal detection level
C039
Overload signal output mode
C040
Overload level setting
C041
Frequency arrival setting for accel.
C042
Frequency arrival setting for decel.
C043
PID deviation level setting
C044
Frequency arrival setting for acceleration (2)
C045
Frequency arrival setting for deceleration (2)
C046
Maximum PID feedback data
C052
Minimum PID feedback data
C053
Over-torque(Forward-driving) level setting
C055
Over-torque(Reverse-regenerating) level setting
C056
Over-torque(Reverse-driving) level setting
C057
Over-torque(Forward-regenerating) level setting
C058
Electronic thermal warning level setting
C061
Alarm code input
C062
Zero speed detection level
C063
Heat sink overheat warning level
C064
Communication speed selection
C071
Node allocation
C072
Communication data length selection
C073
Communication parity selection
C074
Communication stop bit selection
C075
Selection of the operation after communication error
C076
Communication timeout limit before tripping
C077
Communication wait time
C078
Communication mode selection
C079
O input span calibration
C081
OI input span calibration
C082
O2 input span calibration
C083
Thermistor input tuning
C085
Debug mode enable
C091
UP/DOWN memory mode selection
C101
Reset mode selection
C102
Restart mode after reset
C103
FM gain adjustment
C105
AM gain adjustment
C106
AMI gain adjustment
C107
AM bias adjustment
C109
AMI bias adjustment
C110
Overload setting (2)
C111
O input zero calibration
C121
OI input zero calibration
C122
O2 input zero calibration
C123
Output 11 on-delay time
C130
Output 11 off-delay time
C131
Output 12 on-delay time
C132
Output 12 off-delay time
C133
Output 13 on-delay time
C134
Output 13 off-delay time
C135
Output 14 on-delay time
C136
Output 14 off-delay time
C137
Output 15 on-delay time
C138
Output 15 off-delay time
C139
Output RY on-delay time
C140
Output RY off-delay time
C141
Logical output signal 1 selection 1
C142
Logical output signal 1 selection 2
C143
Logical output signal 1 operator selection
C144
Logical output signal 2 selection 1
C145
Logical output signal 2 selection 2
C146
Logical output signal 2 operator selection
C147
Logical output signal 3 selection 1
C148
(*1) 4000HF:0.00 to 99.99, 100.0 to 120.0(Hz)
Function Name
SJ700:0.20 x "rated current" to 2.00 x "rated current" (A) / SJ700B:0.20 x "rated current" to 1.50 x "rated current" (A)
(Current with digital current monitor output at 1,440 Hz)
SJ700:0.0 to 2.00 x "rated current" (A) / SJ700B:0.0 to 1.50 x "rated current" (A)
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
SJ700:0.0 to 2.00 x "rated current" (A) / SJ700B:0.0 to 1.50 x "rated current" (A)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.0 to 100.0 (%)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.0 to 100.0 (%)
0.0 to 100.0 (%)
SJ700: 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700B: 0. to 150. (%)
SJ700: 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700B: 0. to 150. (%)
SJ700: 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700B: 0. to 150. (%)
SJ700: 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700B: 0. to 150. (%)
0. to 100. (%)
00(Disabled) / 01(3-bit) / 02(4-bit)
1. to 32.
7 (7 bits), 8 (8 bits)
00 (no parity), 01 (even parity), 02 (odd parity)
1 (1 bit), 2 (2 bits)
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors),
03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
0.00 to 99.99 (s)
0. to 1000. (ms)
00(ASCII), 01(Modbus-RTU)
0. to 9999., 1000 to 6553(10000 to 65530)
0. to 9999., 1000 to 6553(10000〜65530)
0. to 9999., 1000 to 6553(10000〜65530)
0.0 to 999.9, 1000.
(Do not change this parameter, which is intended for factory adjustment.)
00 (not storing the frequency data), 01 (storing the frequency data)
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off),
02 (enabling resetting only upon tripping [resetting when RS is on])
00 (starting with 0 Hz), 01 (starting with matching frequency),
02 (restarting with active matching frequency)
50. to 200. (%)
50. to 200. (%)
50. to 200. (%)
0. to 100. (%)
0. to 100. (%)
SJ700:0.0 to 2.00 x "rated current" (A) <75kW and over:0.0 to 1.80 x "rated current">
SJ700B:0.0 to 1.50 x "rated current" (A)
0. to 9999., 1000 to 6553 (10000 to 65530)
0. to 9999., 1000 to 6553 (10000 to 65530)
0. to 9999., 1000 to 6553 (10000 to 65530)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
0.0 to 100.0 (s)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
17
Monitored data or setting
[◯= Allowed ×= Not permitted]
Default Setting
SJ700
-FE(CE) -FU(UL)
00
00
00
00
00
01
01
Rated current of inverterx 1..0
01
Rated current of inverterx 1..0
0.00
0.00
3.0
0.00
0.00
100.0
0.0
100.
100.
100.
100.
80.
00
0.00
120.
04
1.
7
00
1
02
0.00
0.
00
-F(JP)
Rated current of
inverterx 1..0
00
00
00
00
00
00
00
00
00
00
01
01
01
01
01
01
0.00
0.00
0.00
0.00
3.0
3.0
0.00
0.00
0.00
0.00
100.0
100.0
0.0
0.0
100.
100.
100.
100.
100.
100.
100.
100.
80.
80.
00
00
0.00
0.00
120.
120.
04
04
1.
1.
7
7
00
00
1
1
02
02
0.00
0.00
0.
0.
00
00
Factory set
00
00
00
00
00
100.
100.
100.
0.
20.
00
00
00
00
00
00
00
100.
100.
100.
100.
100.
100.
0.
0.
20.
20.
Rated current of
inverterx 1..0
Factory set
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
00
00
00
00
00
00
00
00
00
00
00
00
00
00
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
00
00
00
00
00
00
00
SJ700B
00
00
00
00
00
01
01
01
0.00
0.00
3.0
0.00
0.00
100.0
0.0
100.
100.
100.
100.
80.
00
0.00
120.
04
1.
7
00
1
02
0.00
0.
00
00
00
00
00
100.
100.
100.
0.
20.
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
00
00
00
00
00
00
00
Setting
during operation
(allowed or not)
○
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
○
×
○
○
○
○
○
×
○
○
○
○
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Change
during operation
(allowed or not)
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
×
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Code
C149
C150
C151
C152
C153
C154
C155
C156
C157
C158
Output terminal operation function
C159
C160
C161
C162
C163
C164
C165
C166
C167
Input terminal response
C168
C169
other
Function Name
Logical output signal 3 selection 2
Logical output signal 3 operator selection
Logical output signal 4 selection 1
Logical output signal 4 selection 2
Logical output signal 4 operator selection
Logical output signal 5 selection 1
Logical output signal 5 selection 2
Logical output signal 5 operator selection
Logical output signal 6 selection 1
Logical output signal 6 selection 2
Logical output signal 6 operator selection
Input terminal response time setting 1
Input terminal response time setting 2
Input terminal response time setting 3
Input terminal response time setting 4
Input terminal response time setting 5
Input terminal response time setting 6
Input terminal response time setting 7
Input terminal response time setting 8
Input terminal response time setting FW
Multistage speed/position determination time
Monitored data or setting
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
Same as the settings of C021 to C026 (except those of LOG1 to LOG6)
00 (AND), 01 (OR), 02 (XOR)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×2ms)
0. to 200. (×10ms)
Default Setting
SJ700
-FE(CE) -FU(UL)
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
[◯= Allowed ×= Not permitted]
Setting
during operation
SJ700B
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
1
1
1
1
0
(allowed or not)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
-F(JP)
00
00
00
00
00
00
00
00
00
00
00
1
1
1
1
1
1
1
1
1
0
Change
during operation
(allowed or not)
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
●H GROUP: MOTOR CONSTANTS FUNCTIONS
Code
H001
Auto-tuning Setting
H002
Motor data selection, 1st motor
H202
Motor data selection, 2nd motor
H003
Motor capacity, 1st motor
H203
Motor capacity, 2nd motor
H004
Motor poles setting, 1st motor
H204
Motor poles setting, 2nd motor
H005
Motor speed constant, 1st motor
H205
Motor speed constant, 2nd motor
H006
Motor stabilization constant, 1st motor
H206
Motor stabilization constant, 2nd motor
H306
Motor stabilization constant, 3rd motor
H020
Motor constant R1, 1st motor
H220
Motor constant R1, 2nd motor
H021
Motor constant R2, 1st motor
H221
Motor constant R2, 2nd motor
H022
Motor constant L, 1st motor
Control constants
H222
Motor constant L, 2nd motor
H023
Motor constant Io
H223
Motor constant Io, 2nd motor
H024
Motor constant J
H224
Motor constant J, 2nd motor
H030
Auto constant R1, 1st motor
H230
Auto constant R1, 2nd motor
H031
Auto constant R2, 1st motor
H231
Auto constant R2, 2nd motor
H032
Auto constant L, 1st motor
H232
Auto constant L, 2nd motor
H033
Auto constant Io, 1st motor
H233
Auto constant Io, 2nd motor
H034
Auto constant J, 1st motor
H234
Auto constant J, 2nd motor
H050
PI proportional gain for 1st motor
H250
PI proportional gain for 2nd motor
H051
PI integral gain for 1st motor
H251
PI integral gain for 2nd motor
H052
P proportional gain setting for 1st motor
H252
P proportional gain setting for 2nd motor
H060
Zero LV lmit for 1st motor
H260
Zero LV lmit for 2nd motor
H061
Zero LV starting boost current for 1st motor
H261
Zero LV starting boost current for 2nd motor
Control constants
H070
Terminal selection PI proportional gain setting
H071
Terminal selection PI integral gain setting
H072
Terminal selection P proportional gain setting
H073
Gain switching time
(*1) 1850HF,2200HF,3150HF and 4000HF:0.1 to 999.9,1000. to 6553.(mΩ).
(*2) 1850HF,2200HF,3150HF and 4000HF:0.001 to 9.999,10.00. to 65.53(mH).
(*3) 1850HF,2200HF,3150HF and 4000HF:0.01 to 0.35 “ rated current ”(A).
Function Name
Monitored data or setting
00 (disabling auto-tuning), 01 (auto-tuning without rotation),
02 (auto-tuning with rotation)
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
SJ700:0.20 to 400.0 (kW)/SJ700B:0.20 to 160(kW)
SJ700:0.20 to 400.0 (kW)/SJ700B:0.20 to 160(kW)
2, 4, 6, 8, 10 (poles)
2, 4, 6, 8, 10 (poles)
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000)
0. to 255.
0. to 255.
0. to 255.
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.001 to 9.999, 10.00 to 65.53 (Ω) (*1)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (mH) (*2)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.01 to 99.99, 100.0 to 655.3 (A) (*3)
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
Operation mode on expansion card 1 error
Operation mode on expansion card 2 error
Encoder pulse-per-revolution (PPR) setting
Control pulse setting
Pulse input mode setting
Home search stop position setting
Home search speed setting
Home search direction setting
Home search completion range setting
Home search completion delay time setting
Electronic gear set position selection
Electronic gear ratio numerator setting
Electronic gear ratio denominator setting
Feed-forward gain setting
Position loop gain setting
Position bias setting
Temperature compensation thermistor enable
Over-speed error detection level setting
Speed deviation error detection level setting
Numerator of motor gear ratio
Denominator of motor gear ratio
Accel./decel. time input selection
Positioning command input selection
Torque command input selection
Torque command setting
Polarity selection at the torque command
input via O2 terminal
Torque bias mode
Torque bias value
Torque bias polarity selection
Speed limit for torque-controlled operation
(forward rotation)
Speed limit for torque-controlled operation
(reverse rotation)
DeviceNet comm watchdog timer
Inverter action on DeviceNet comm error
DeviceNet polled I/O : Output instance number
DeviceNet polled I/O : input instance number
Inverter action on DeviceNet idle mode
DeviceNet motor poles setting for RPM
Pulse-string frequency scale
Time constant of pulse-string frequency filter
Pulse-string frequency bias
Pulse-string frequency limit
I
Multistage position setting 0-7
Zero-return mode selection
Zero-return direction selection
Low-speed zero-return frequency
High-speed zero-return frequency
Position range specification (forward)
Position range specification (reverse)
Teaching selection
00 (as indicated by the sign), 01 (depending on the operation direction)
00 (disabling the mode), 01 (digital operator), 02 (input via O2 terminal)
-200. to +200. (%)
00 (as indicated by the sign), 01 (depending on the operation direction)
0.00 to "maximum frequency" (Hz)
0.00 to "maximum frequency" (Hz)
0.00 to 99.99 (s)
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors),
03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
20, 21, 100
70, 71, 101
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors),
03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
You can mount the keypad
with the potentiometer for a
NEMA1 rated installation.
The kit also provides for
removing the potentiometer
knob to meet NEMA 4X
requirements,as shown
(part no.4X-KITmini).
For Furthermore Operation
......
Use option as WOP
Main Features for WOP :
-Large LCD screen
-Real time clock
-Copy function: Storing parameter settings of a total 4 units of inverters
-Multi-language (Japanese, English and Chinese) [ Planning to expand to 10 languages ] SJ700 and SJ700B is English only.
-Selectable display contents
●
Dimentions (Unit:mm(inch) Inches for reference only)
Common Terminal for
Intelligent Input Terminals,
Common Terminal for
External Power Supply for
PLCs, etc.
Intelligent Output Terminals
Common Terminal for
Intelligent Output Terminals
Thermistor Input Terminals
Alarm Output Terminals
Common terminal for H, O, O2, OI, AM, and AMI. Do not ground.
Power supply for frequency command input
Maximum frequency is attained at DC 10V in DC 0-10V range. Set the voltage at
A014 to command maximum frequency below DC 10V.
O2 signal is added to the frequency command of O or OI in DC 0-±10V range. By
changing configuration, frequency command can be input also at O2 terminal.
Maximum frequency is attained at DC 20mA in DC 4-20mA range.
When the intelligent terminal configured as AT is on, OI signal is enabled.
Selection of one function from:
Output frequency, output current, torque, output voltage, input power, electronic
thermal load ratio, and LAD frequency.
[DC0-10V o utput (PWM output)] Selection of one fun ction from: Output
frequency, output current, torque, output voltage, input power, electronic thermal
load ratio, and LAD frequency.
[Digital pulse output (Pulse voltage DC 0/10V)] Outputs the value of output
frequency as digital pulse (duty 50%)
Internal power supply for input terminals. In the case of source type logic,
common terminal for contact input terminals.
Common terminal for P24, TH, and FM. In the case of sink type logic, common
terminal for contact input terminals. Do not ground.
The motor runs forward when FW terminal is ON,
and stops when FW is OFF.
Assign 8 functions to terminals.
(Refer to the standard specifications for the functions.)
Select sink or source logic with the short-circuit bar on the control terminals.
Sink logic: Short P24 to PLC / Source logic: Short CM1 to PLC.
When applying external power source, remove the short-circuit bar and connect
PLC terminal to the external device.
Assign 5 functions to open collector outputs.
When the alarm code is selected at C062, terminal 11-13 or 11-14 are reserved
for error codes of inverter trip.
(Refer to the standard specifications for the functions.)
Both sink and source logic are always applicable between each terminal and CM1.
Common terminal for intelligent output terminal 11-15.
The inverter trips when the external thermistor detects abnormal temperature.
Common terminal is CM1.
[Recommended thermistor characteristics]
Allowable rated power: 100mW or over.
Impedance in the case of abnormal temperature: 3kΩ
Note: Thermal protection level can be set between 0 and 9999Ω.
In default setting, an alarm is activated when inverter output is turned off by a
protective function.
[Input ON condition]
Voltage between each terminal
and PLC: DC 18V min.
[Input OFF condition]
Voltage between each terminal
and PLC: DC 3V max.
Input impedance between each
terminal and PLC: 4.7Ω
Allowable maximum voltage
between each terminal and
PLC: DC 27V
Decrease in voltage between
each terminal and CM2:
4V max. during ON
Allowable maximum voltage: DC 27V
Allowable maximum current: 50mA
Maximum capacity of relays
AL1-AL0: AC 250V, 2A(R load)/0.2A(L load)
AL2-AL0:AC 250V, 1A(R load)/0.2A(L load)
Minimum capacity of relays
AL1-AL0, AL2-AL0:
AC100V, 10mA DC5V, 100mA
-
DC 10V, 20mA max.
Input impedance: 10kΩ, Allowable
input voltage range: DC -0.3-+12V
Input impedance:10kΩ, Allowable
input voltage range: DC 0-±12V
Input impedance: 100Ω, Allowable
input voltage range: DC 0-24mA
DC 0-10V, 2mA max.
DC 4-20mA, 250Ω max.
Digital output frequency
range: 0-3.6kHz, 1.2mA max.
DC 24V, 100mA max.
-
Allowable input voltage range
DC0-8V
[
]
Input Circuit
TH
Thermistor
CM1
DC 30V, 8A(R load)/0.6A(L load)
DC 30V, 1A(R load)/0.2A(L load)
DC8V
10kΩ
1kΩ
Terminal Arrangement
HLO2OAMOIFM
AM1THP24FWPLC8CM1
Screw diameter:M3Terminal Width:6.4mm
CM17563
412141513CM21112
Relay Output PCB(L300PTM)
L300PTM is available in case a relay output function is nessessary.
Terminal SymbolSpecifications
11A
11C
12A
12C
Contacting Maximum Rate
Contacting Minimum Rate
AL0 AL2
AC250V
DC30A
DC1V
AL1
5A
1A
5A
1A
1mA
22
PROTECTIVE FUNCTIONS
Name
Over-current protection
Overload protection(*1)
Braking resistor
overload protection
Over-voltage protection
EEPROM error(*2)
Under-voltage error
CT(Current transformer) error
CPU error
External trip
USP error
Ground fault
Input over-voltage protection
Instantaneous power failure
Temperature error due to low
cooling-fan speed
Inverter thermal trip
Gate array error
Phase loss detection
Main circuit error (*3)
Cooling-fan speed drop signal
IGBT error
Thermistor error
Braking error
Emergency stop (*4)
Low-speed overload protection
Modbus communication error
Out of operation due
to under-voltage
Cause(s)
The inverter output was short-circuited, or the motor shaft is locked or has a
heavy load. These conditions cause excessive current for the inverter, so the
inverter output is turned off.
When a motor overload is detected by the electronic thermal function, the inverter trips and turns off its
output.
When the regenerative braking resistor exceeds the usage time allowance or an over-voltage caused by the
stop of the BRD function is detected, the inverter trips and turns off its output.
When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor, the inverter trips
and turns off its output.
When the built-in EEPROM memory has problems due to noise or excessive temperature, the inverter trips
and turns off its output.
A decrease of internal DC bus voltage below a threshold results in a control circuit fault. This condition can
also generate excessive motor heat or cause low torque. The inverter trips and turns off its output.
If a strong source of electrical interference is close to the inverter or abnormal operations occur in the
built-in CT, the inverter trips and turns off its output.
When a malfunction in the built-in CPU has occurred, the inverter trips and turns off its output.
When a signal to an intelligent input terminal configured as EXT has occurred, the inverter trips and turns
off its output.
An error occurs when power is cycled while the inverter is in RUN mode if the Unattended Start Protection
(USP) is enabled. The inverter trips and does not go into RUN mode until the error is cleared.
The inverter is protected by the detection of ground faults between the inverter output and the motor during
power-up tests. This feature protects the inverter only.
When the input voltage is higher than the specified value, it is detected 60 seconds after power-up and the
inverter trips and turns of its output.
When power is cut for more than 15ms, the inverter trips and turns off its output. If power failure continues,
the error will be cleared. The inverter restarts if it is in RUN mode when power is cycled.
The inverter will display the error code shown on the right if the lowering of cooling-fan speed is detected at
the occurrence of the temperature error described below.
When the inverter internal temperature is higher than the specified value, the thermal sensor in the inverter
module detects the higher temperature of the power devices and trips, turning off the inverter output.
Communication error has occurred between CPU and gate array.
One of three lines of 3-phase power supply is missing.
The inverter will trip if the gate array cannot confirm the on/off state of IGBT because of a malfunction due
to noise or damage to the main circuit element.
If the rotation speed of the internal cooling fan decreases so that the cooling effect decreases,inverter
output turns OFF for protection.(available only for SJ700 1850-4000)
When an instantaneous over-current has occurred, the inverter trips and turns off its output to protect main
circuit element.
When the thermistor inside the motor detects temperature higher than the specified value, the inverter trips
and turns off its output.
The inverter turns off its output when it can not detect whether the braking is ON or OFF within waiting time
set at b024 after it has released the brake. (When braking is enabled at b120)
If the EMR signal (on three terminals) is turned on when the slide switch (SW1) on the logic board is set to
ON, the inverter hardware will shut off the inverter output and display the error code shown on the right.
If overload occurs during the motor operation at a very low speed at 0.2 Hz or less, the electronic thermal protection
circuit in the inverter will detect the overload and shut off the inverter output. (2nd electronic thermal control)
(Note that a high frequency may be recorded as the error history data.)
If timeout occurs because of line disconnection during the communication in Modbus-RTU mode, the inverter
will display the error code shown on the right. (The inverter will trip according to the setting of "C076".)
Due to insufficient voltage, the inverter has turned off its output and been trying to
restart. If it fails to restart, it goes into the under-voltage error.
While at constant speed
During deceleration
During acceleration
Others
Display
on digital
operator
Display on remote
operator/copy unit
ERR1****
OC.Drive
OC.Decel
OC.Accel
Over.C
Over.L
OL.BRD
Over.V
EEPROM
Under.V
CT
CPU
EXTERNAL
USP
GND.Flt.
OV.SRC
Inst.P-F
OH.stFAN
OH FIN
GA.COM
PH.Fail
Main.Cir
Fan. Slow
IGBT
TH
BRAKE
EMR
OL-LowSP
NET.ERR
UV.WAIT
PRG.CMD
Easy sequence function Error
Error indications by protective functions with the easy sequence function used.
PRG.NST
PRG.ERR1
DB
〜
〜
CodeDescription
8
9
Expansion card 1 connection error
Expansion card 2 connection error
(*1): Reset operation is acceptable 10 seconds after the trip.(185kW and over :90 seconds)(*2): Check the parameters when EEPROM error occurs.(*3): The inverter will not accept reset commands input via the RS terminal
or entered by the STOP/RESET key. Therefore, turn off the inverter power. (*4): The inverter will not accept the reset command entered from the digital operator. Therefore, reset the inverter by turning on the RS terminal.
〈Status Display〉
An error has been detected in an expansion card or at its connecting terminals.
CodeDescription
0
1
Reset
Stop
CodeDescription
2
3
Deceleration
Constant Speed
CodeDescription
4
5
Acceleration
f0 Stop
CodeDescription
6
7
Starting
〜
OP1-0OP1-9
〜
OP2-0OP2-9
Overload Restriction
Forcible or servo-on
〈How to access the details about the present fault〉
Status at trip pointError code
Output frequency
at trip point
Motor current
at trip point
23
Voltage between
P(+) and N(−) at trip point
Cumulative inverter
RUN time at trip point
Cumulative power-on
time at trip point
CONNECTING DIAGRAM
Source type logic
200V class 200V-240V+10%, -15%
50/60Hz±5%
400V class 380V
50/60Hz±5%
-
480V+10%, -15%
(*2)Remove connection with J51
when RoTo power is supplied
externally
Control power source
Forward command
Intelligent input
terminals (8 terminals)
FM monitor output
AM monitor output
(Analog output)
AM monitor output
(Analog output)
Terminal Name
(PWM)
Thermistor
Frequency
setting device
500-2kΩ
DC0-10V
DC4
DC0
DC4
FW, 1, 2, 3, 4, 5, 6, 7, 8 FM, TH H, O, O2, OI, AM, AMI
Common terminal
R
Short-circuit
DC-10-+10V
-
DC0-10V
(12bit)
(12bit)
-
20mA(12bit)
-
10V(10bit)
-
20mA(10bit)
bar
+
P24CM1
R(L1)
S(L2)
T(L3)
T(J51)
R0
T0
P24
PLC
CM1
FW
8
7
6
1
FM
CM1
TH
H
O
O2
OI
L
AM
AMI
SJ700/SJ700B
(*2)
10kΩ
10kΩ
100Ω
DC10V
DC24V
(G)
L
(T1)U
(T2)V
(T3)W
(+1)PD
(+)
RB
-
(
AL0
AL1
AL2
SP
SN
RP
SN
IM
DC link choke(Note1)
Dynamic braking unit (BRD)
P
P
)
N
SJ700: For 30kW(40HP) and over
SJ700B: For 37kW(50HP) and over
SJ700: For up to 22kW(30HP)
SJ700B: For up to 30kW(40HP)
P
P
RB
RB
(Inverter)
N
Braking resistor(RB
Option
Customer wiring
(Outside the inverter)
AL
AL2
)
(To operating circuit)
Note1:Please be sure to connect DC reactor attached to 1850HF,2200HF,3150HF and 4000HF.
25
CONNECTING TO PLC
Connection with Input Terminals
1.Using Internal Power Supply of The Inverter
(1)
Sink type logic
S
P24
PLC
FW
(2)
Source type logic
+
--
DC24V
COM
P24
PLC
FW
+
DC24V
Hitachi EH-150 series PLC
Output Module
EH-YT16
2.Using External Power Supply
(1)
Sink type logic
COMCM1
DC24V
S
FW
8
1
SCM1
Inverter
+
-
P24
PLC
+
-
DC24V
8
1
(2)
Source type logic
Hitachi EH-150 series PLC
Output Module
EH-YTP16
8
1
(Note: Place short-circuit bar
between PLC and CM1 instead
of P24 and PLC)
COM
DC24V
+
-
FW
P24
PLC
8
1
Inverter
+
DC24V
COMCM1
Hitachi EH-150 series PLC
Output Module
EH-YT16
(Note: Be sure to turn on the inverter after turning on the PLC and its external power source to prevent the parameters in the inverter from being modified.)
Connection with Output Terminals
(1)
Sink type logic
11
12
CM2
Inverter
Inverter
(Note: Remove short-circuit bar
between P24 and PLC)
COM
DC24V
Hitachi EH-150 series PLC
Input Module
EH-XD16
(2)
Source type logic
SCM1
Hitachi EH-150 series PLC
Output Module
EH-YTP16
CM2
DC24V
11
12
Inverter
Inverter
(Note: Remove short-circuit
bar between P24 and PLC)
COM
Hitachi EH-150 series PLC
Input Module
EH-XD16
26
WIRING and ACCESSORIES
Power Supply
R
ST
(L1) (L2) (L3)
Inverter
R0
T0
(T1) (T2) (T3)
UVW
IM
Fuse
PD
(+1)
P
(+)
RB
-
)
(
N
Motor
Motor Output
Input
Voltage
Note1:
Connector must be fixed using the crimping tool specified by the connector manufacture.
Note2: Be sure to use large wire gauges for power wiring if the distance exceeds 20m (66ft).
This is useful in suppressing harmonics induced on the power supply
Input side AC reactor
EMI filter
Radio noise filter
Radio noise filter
(Capacitor filter)
DC link choke
Braking resistor
Braking unit
Output side noise filter
Radio noise filter
AC reactor
LCR filter
lines, or when the main power voltage imbalance exceeds 3% (and
power source capacity is more than 500kVA), or to smooth out line
fluctuations. It also improves the power factor.
Reduces the conducted noise on the power supply wiring generated by
the inverter. Connect to the inverter input side.
Electrical noise interference may occur on nearby equipment such as a
radio receiver. This magnetic choke filter helps reduce radiated noise
(can also be used on output).
This capacitor filter reduces radiated noise from the main power wires in
the inverter input side.
Suppresses harmonics generated by the inverter.
This is useful for increasing the inverter's control torque for high
duty-cycle (on-off) applications, and improving the decelerating capability.
Reduces radiated noise from wiring in the inverter output side.
Electrical noise interference may occur on nearby equipment such as a
radio receiver. This magnetic choke filter helps reduce radiated noise
(can also be used on input).
This reactor reduces the vibration in the motor caused by the inver-ter's
switching waveforms, by smoothing the waveforms to approxi-mate
commercial power quality. It is also useful when wiring from the inverter
to the motor is more than 10m in length, to reduce harmonics.
Sine wave shaping filter for the output side.
Note: An EMI filter is required for European EMC directive and C-Tick, but the others are not for this purpose.
SJ700SJ700SJ700
2
2
1000
Fuse
(Class J)
SJ700B
5
10
15
20
30
30
40
60
80
100
125
150
175
225
250
-
5
10
10
15
15
15
20
30
40
50
50
60
70
90
225
225
300
300
300
700
700
700
30
40
50
60
70
90
125
125
225
225
300
300
300
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
27
TORQUE CHARACTORISTIC
SJ700 Series / Maximum Torque with Short - Time Rating
Sensorless vector controlV/f control (maximum torque boosting)
200
180
150
130
Output torque (%)
60
55
45
0.4〜55kW
75〜132kW
30〜45kW
55〜132kW
(65Hz max.)
0.4〜3.7kW
5.5〜22kW
150
130
100
60
Output torque (%)
55
45
55〜132kW
30〜45kW
0.4〜3.7kW
5.5〜22kW
Base frequency = 60Hz
Output frequency (Hz)
1001206560460.3
Sensorless vector control
200
180
150
109
Output torque (%)
60
45
35
Base frequency = 50Hz
0.4〜55kW
75〜132kW
55〜132kW
30〜45kW
Output frequency (Hz)
0.4〜3.7kW
5.5〜22kW
1001205065380.3
SJ700B Series / Maximum Torque with Short - Time Rating
Sensorless vector control
150
120
110
100
Output torque (%)
50
45
40
11〜75kW
90〜160kW
30〜45kW
55〜160kW
(65Hz max.)
11〜22kW
6
200.3
6560
Output frequency (Hz)
V/f control (maximum torque boosting)
150
130
109
100
60
Output torque (%)
45
35
5
55〜132kW
30〜45kW
Output frequency (Hz)
V/f control (maximum torque boosting)
130
110
85
50
Output torque (%)
45
40
55〜160kW
30〜45kW
100120
0.4〜3.7kW
5.5〜22kW
100120506516.70.3
11〜22kW
Base frequency = 60HzBase frequency = 50Hz
Output frequency (Hz)
1001206560460.5
Sensorless vector control
150
120
109
Output torque (%)
50
45
40
11〜75kW
90〜160kW
55〜132kW
30〜45kW
Output frequency (Hz)
11〜22kW
1001205065380.5
130
110
92
85
50
Output torque (%)
40
30
200.5
6
Output frequency (Hz)
V/f control (maximum torque boosting)
55〜132kW
5
Output frequency (Hz)
6560
30〜45kW
100120
11〜22kW
100120506516.70.5
28
TORQUE CHARACTORISTIC
SJ700/SJ700B Series / Torque Under Continous Operation
Sensorless vector control
V/f control
30〜45kW
0.4〜3.7kW
5.5〜22kW
100
Output torque (%)
95
92
80
70
55
45
35
30
0.4〜3.7kW
0.4〜11kW
15〜22kW
30〜55kW
55〜132kW
100
Output torque (%)
95
90
85
75
70
65
55
45
36
30
0.4〜3.7kW
30〜55kW
5.5〜22kW
0.4〜3.7kW
55〜132kW
Sensorless vector control
V/f control
30〜45kW
0.4〜3.7kW
5.5〜22kW
Base frequency = 60Hz
6
Output frequency (Hz)
1001206560200.3
DERATING DATA
SJ700
100
95
90
85
80
75
70
65
60
Output current(Ratio to the rating:%)
55
200V class
45, 5 5 k W
0.5 2 4 6 8 10 12 14 15
Carrierfrequency(kHz)
11 k W0.4〜7 . 5 k W
15k W
18. 5 k W
30k W
37k W
22k W
Base frequency = 50Hz
100120655016.70.3
11 0 k W
SJ700
5
400V class
Output frequency (Hz)
90k W
100
95
90
85
80
75
70
65
60
Output current(Ratio to the rating:%)
55
75k W
132 k W
0.5 2 4 6 8 10 12 14 15
Carrierfrequency(kHz)
30k W45k W37k W
0.75〜11kW
15k W
18. 5 k W
22k W
55k W
29
SJ700B
400V class
90k W30 k W
100
95
90
85
80
75
70
65
60
Output current(Ratio to the rating:%)
55
0.5 2 4 6 8 10 12
132 k W
11 0 k W
Carrierfrequency(kHz)
55k W
160 k W
45k W
11 〜 1 8 . 5kW
22k W
37k W
75k W
DIFFERENCE and COMPATIBILITY
of SJ300 series and SJ700 series
Items
You can copy the parameter settings from the SJ300 series into the SJ700 series.
Copying the parameter settings
Parameter display mode.
Retry or trip parameter
d001:
Output frequency monitoring
d007:
Scaled output frequency monitoring
Change function
Control
Circuit
Terminal
Main
Circuit
Easy-removable Dc bus Capacitor
Dynamic Brake circuit
Minimum value of
resistor(Ω)
Dimensions
Digital operator position
Option boards
Note1:Since a response falls the V/F characteristic curve selection SLV should make this setup small.
Note2:370, 450L/H and 550H:Metal fittings differ.
A016:External frequency filter
time const.
A038:Jog frequency setting
A105:[OI]-[L] input start
frequency enable
b012, b212, b312:
Electronic thermal function
C025:Terminal [15] function
Removable
Position
110L/H
Screw diameter
Position
Arrangement
Others
055L
075L
110L
055H
075H
Installation
External radiating fin
SJ-DG
SJ-FB
SJ-DN / SJ-DN2
SJ-LW
SJ-PBT
Option position
300L
450L
370H
(You cannot copy the parameter settings from the SJ700 series to the SJ300 series because the SJ700
series has many new functions and additional parameters.)
No display mode selection.
(full display)
Instantaneous power failure/under-voltage/
overvoltage/overcurrent:It sets up by b001.
You can not change the output frequency
setting by using the △ and/or ▽ key.
Default:08(instantaneous power failure)Default:40(cooling-fan speed drop)
Removable
Other model:same position. 055L/H:5mm upper part from SJ300. 300L/H:97mm upper part from SJ300.
M6(Ground Screw)M5(Ground Screw)
M8(Ground Screw)
M10M8
M6M8
055 to 110L/H:10mm upper part from SJ300.
150 to 300L/H:20mm upper part from SJ300.550L:30mm upper part from SJ300.
Other model:same position.
055 to 110L/H:Two steps, 150 to 550L/H:One step
150 to 220L/H:RB there is not a terminal.
All the models are possible.
up to 11kW
055L/H: SJ700 is in next larger enclosure vs. SJ300. All other models are the same enclosure size.
055L/H:Those with no compatibility.075 to 550L/H:Those with compatibility. Note 2
055L/H:5mm upper part from SJ300. 300L/H:97mm upper part from SJ300.
Other model:same position.
Those with compatibility.
Those with compatibility.
Note:Since the SJ700 series has many new functions and additional parameters,
some functions of the SJ-DN, SJ-LW, and SJ-PBT (option boards conforming to the open network
specifications) cannot be implemented on the SJ700 series. SJ-DN2 has compatibility to SJ700.
Other model:same position. 055L/H:5mm upper part from SJ300. 300L/H:97mm upper part from SJ300.
SJ300seriesSJ700series
17
17
17
50
50
Basic display mode/Data comparison function addition.
Note:basic display mode [factory setting])
To display all parameters, specify "00" for "b037".
Instantaneous power failure/under-voltage:It sets
up by b001.
overvoltage/overcurrent:It sets up by b008.
You can not change the output frequency
setting by using the △ and/or ▽ key.
Setting range:
0.01 to 999Hz(0Hz setup is impossible)
Removable
(You can mount the SJ300 series into the SJ700 series.)
M6(Ground Screw)
055 to 550L/H:One step
150 to 220L/H:RB there is a terminal.
15kW or more is possible.
up to 22kW
16
10
10
35
35
30
DIFFERENCE and COMPATIBILITY
of L300P series and SJ700B series
Items
You can copy the parameter settings from the L300P series into the SJ700B series.
Copying the parameter settings
Parameter display mode.
Retry or trip parameter
d001:Output frequency monitoring
d007:Scaled output frequency monitoring
A001:
Frequency source setting
A016:
External frequency filter time const.
Change function
Control
circuit
Terminal
Main
circuit
Easy-removable Dc bus Capacitor
Dynamic Brake circuit
Minimum value of
resistor(Ω)
Dimensions
Digital operator position
Keypad potentiometer on digital operator
Option boards
Note1:Since a response falls the V/F characteristic curve selection SLV should make this setup small.
Note2:450, 550L/H and 750H:Metal fittings differ.
(You cannot copy the parameter settings from the SJ700B series to the L300P series because the SJ700B
series has many new functions and additional parameters.)
No display mode selection.
(full display)
Instantaneous power failure/under-voltage/
overvoltage/overcurrent:It sets up by b001.
You can not change the output frequency setting
by using the up and or down key.
Default:00
(Keypad potentiometer on digital operator)
370L/H:97mm upper part from L300P.
Other model:same position.
M6(Ground Screw)M5(Ground Screw)
M8(Ground Screw)M6(Ground Screw)
M10M8
M6M8
110,150LF/HF:10mm upper part from L300P.
185 to 370L/H:20mm upper part from L300P.
750L:30mm upper part from L300P.
Other model:same position.
185 to 300L/H:RB there is not a terminal.
All the models are possible.
Up to 15kW
All models are the same enclosure size.
Those with compatibility. Note 2
300L/H:97mm upper part from L300P.
Other model:same position.
Those with compatibility.
Those with compatibility.
Note:Since the SJ700B series has many new functions and additional parameters,some functions of the
SJ-DN, SJ-LW, and SJ-PBT(option boards conforming to the open network specifications)cannot be
implemented on the SJ700B series. SJ-DN2 has compatibility to SJ700.
370L/H:97mm upper part from L300P.
Other model:same position.
L300PseriesSJ700B series
Basic display mode/Data comparison function addition.
Note:basic display mode [factory setting])To display all
parameters,
specify "00" for "b037".
Instantaneous power failure/under-voltage:It sets
up by b001.
overvoltage/overcurrent:It sets up by b008.
You can not change the output frequency setting
by using the up and or down key.
Default:02
(Digital operator)
Setting range:
0.01 to 999Hz(0Hz setup is impossible)
Default:01 (operating the fan only during inverter
operation
[including 5 minutes after power-on and power-off])
Default:01 (enabling [disabling while the motor is
topped])
Removable
(You can mount the L300P into the SJ700B .)
8 terminals
185 to 300H:RB there is a terminal.
18.5kW or more is possible.
Up to 30kW
17
1710
5035
5035
Yes.No.(Option)
10
31
MEMO
32
FOR CORRECT OPERATION
Application to Motors
Application to general-purpose motors
The overspeed endurance of a general-purpose motor is 120% of the rated speed for 2 minutes (JIS C4,004). For operation at higher
Operating frequency
Torque characteristics
Motor loss and
temperature increase
Noise
Vibration
Power transmission
mechanism
Application to special motors
Gear motor
Brake-equipped motor
Pole-change motor
Submersible motor
Explosion-proof motor
Synchronous (MS) motor
High-speed (HFM) motor
Single-phase motor
Application to the 400V-class motor
A system applying a voltage-type PWM inverter with IGBT may have surge voltage at the motor terminals resulting from the cable constants including
the cable length and the cable laying method. Depending on the surge current magnification, the motor coil insulation may be degraded. In particular,
when a 400V-class motor is used, a longer cable is used, and critical loss can occur, take the following countermeasures:
(1) install the LCR filter between the inverter and the motor,
(2) install the AC reactor between the inverter and the motor, or
(3) enhance the insulation of the motor coil.
than 60Hz, it is required to examine the allowable torque of the motor, useful life of bearings, noise, vibration, etc. In this case,
be sure to consult the motor manufacturer as the maximum allowable rpm differs depending on the motor capacity, etc.
The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power
(starting torque decreases in particular). Carefully check the load torque characteristic of a connected machine and the driving torque
characteristic of the motor.
The torque characteristics of driving a general-purpose motor with an inverter differ from those of driving it using commercial power
When run by an inverter, a general-purpose motor generates noise slightly greater than with commercial power.
When run by an inverter at variable speeds, the motor may generate vibration, especially because of (a) unbalance of the rotor
including a connected machine, or (b) resonance caused by the natural vibration frequency of a mechanical system. Particularly, be
careful of (b) when operating at variable speeds a machine previously fitted with a constant speed motor. Vibration can be minimized
by (1) avoiding resonance points using the frequency jump function of the inverter, (2) using a tire-shaped coupling, or (3) placing a
rubber shock absorber beneath the motor base.
Under continued, low-speed operation, oil lubrication can deteriorate in a power transmission mechanism with an oil-type gear box
(gear motor) or reducer. Check with the motor manufacturer for the permissible range of continuous speed. To operate at more than
60Hz, confirm the machine , s ability to withstand the centrifugal force generated.
The allowable rotation range of continuous drive varies depending on the lubrication method or motor manufacturer.
(Particularly in case of oil lubrication, pay attention to the low frequency range.)
For use of a brake-equipped motor, be sure to connect the braking power supply from the primary side of the inverter.
There are different kinds of pole-change motors (constant output characteristic type, constant torque characteristic type, etc.), with
different rated current values. In motor selection, check the maximum allowable current for each motor of a different pole count. At
the time of pole changing, be sure to stop the motor. Also see: Application to the 400V-class motor.
The rated current of a submersible motor is significantly larger than that of the general-purpose motor. In inverter selection, be sure
to check the rated current of the motor.
Inverter drive is not suitable for a safety-enhanced explosion-proof type motor. The inverter should be used in combination with a
pressure-proof explosion-proof type of motor.
*Explosion-proof verification is not available for SJ700 / SJ700B Series.
In most cases, the synchronous (MS) motor and the high-speed (HFM) motor are designed and manufactured to meet the
specifications suitable for a connected machine. As to proper inverter selection, consult the manufacturer.
A single-phase motor is not suitable for variable-speed operation by an inverter drive. Therefore, use a three-phase motor.
Notes on Use
Drive
Run/Stop
Emergency motor stop
High-frequency run
Run or stop of the inverter must be done with the keys on the operator panel or through the control circuit terminal. Do not operate
by installing a electromagnetic contactor (MC) in the main circuit.
When the protective function is operating or the power supply stops, the motor enters the free run stop state. When an emergency
stop is required or when the motor should be kept stopped, use of a mechanical brake should be considered.
A max. 400Hz can be selected on the SJ700 / SJ700B Series. However, a two-pole motor can attain up to approx. 24,000 rpm,
which is extremely dangerous. Therefore, carefully make selection and settings by checking the mechanical strength of the motor
and connected machines. Consult the motor manufacturer when it is necessary to drive a standard (general-purpose) motor above
60Hz. A full line of high-speed motors is available from Hitachi.
About the load of a frequent repetition use
About frequent repetition use (crane, elevator, press, washing machine) , a power semiconductor (IGBT, a rectification diode, thyristor) in the inverter may
come to remarkably have a short life by heat exhaustion.
The life can be prolonged by lower a load electric current. Lengthen acceleration / deceleration time. Lower carrier frequency. or increasing capacity of the inverter.
About the use in highlands beyond 1,000m above sea level
When the standard inverter is used at a place beyond 1,000m above sea level because it cool heating element with air, please be careful as follows. But
please inquire for the highlands more than 2,500m separately.
1. Reduction of the inverter rating current
The density of air decreases by 1% whenever rising by 100m when the altitude exceeds 1000m. For example, in the case of 2,000m above sea level, it is
{2,000(m) -Because it becomes 1,000(m)}/100(m) X {-1(%)} =-10(%), please use with 10(%) reduction (0.9* inverter rating electric current) of a rating
current of the inverter.
2. Reduction of the breakdown voltage
When using inverter at a place beyond 1,000m, the breakdown voltage decreases as follows. 1,000m or less:1.00/1,500m:0.95/2,000m:0.90/2,50
0m:0.85. But please do not perform the withstand pressure test as mention of the instruction manual.
33
Installation location and operating environment
Avoid installation in areas of high temperature, excessive humidity, or where moisture can easily collect, as well as areas that are dusty, subject to corrosive
gasses, mist of liquid for grinding, or salt. Install the inverter away from direct sunlight in a well-ventilated room that is free of vibration. The inverter can be
operated in the ambient temperature range from -10 to 50˚C.(Carrier frequency and output current must be reduced in the range of 40 to 50˚C.)
Main power supply
In the following examples involving a general-purpose inverter, a large peak current flows on the main power supply side, and is
able to destroy the converter module. Where such situations are foreseen or the connected equipment must be highly reliable,
install an AC reactor between the power supply and the inverter. Also, where influence of indirect lightning strike is possible,
install a lightning conductor.
(A) The unbalance factor of the power supply is 3% or higher. (Note)
(B) The power supply capacity is at least 10 times greater than the inverter capacity (the power supply capacity is 500 kVA or more).
(C) Abrupt power supply changes are expected.
Installation of an
AC reactor on the
input side
Using a private power
generator
Examples:
(1) Several inverters are interconnected with a short bus.
(2) A thyristor converter and an inverter are interconnected with a short bus.
(3) An installed phase advance capacitor opens and closes.
In cases (A), (B) and (C), it is recommended to install an AC reactor on the main power supply side.
Note: Example calculation with V
RS
V
: R-S line voltage, VST : S-T line voltage, VTR : T-R line voltage
Unbalance factor of voltage =
An inverter run by a private power generator may overheat the generator or suffer from a deformed output voltage waveform of the
generator. Generally, the generator capacity should be five times that of the inverter (kVA) in a PWM control system, or six times
greater in a PAM control system.
RS
= 205V, VST = 201V, VTR = 200V
Max. line voltage (min.) - Mean line voltage
RS
V
=
Mean line voltage
-(VRS+VST+VTR)/3
RS+VST+VTR
(V
)/3
x
100 =
205-202
202
x
100
x
100 =1.5(%)
Notes on Peripheral Equipment Selection
(1) Be sure to connect main power wires with R(L1), S(L2), and T(L3) terminals (input) and motor wires to U(T1), V(T2), and W(T3)
Wiring connections
Electromagnetic
contactor
Wiring
between
inverter and
motor
Thermal relay
Installing a circuit breaker
Wiring distance
Earth leakage relay
Phase advance capacitor
terminals (output). (Incorrect connection will cause an immediate failure.)
(2) Be sure to provide a grounding connection with the ground terminal ( ).
When an electromagnetic contactor is installed between the inverter and the motor, do not perform on-off switching during running
operation.
When used with standard applicable output motors (standard three-phase squirrel-cage four-pole motors), the NE-S1 Series does
not need a thermal relay for motor protection due to the internal electronic protective circuit. A thermal relay, however,
should be used:
• during continuous running outside a range of 30 to 60 Hz.
• for motors exceeding the range of electronic thermal adjustment (rated current).
• when several motors are driven by the same inverter; install a thermal relay for each motor.
• The RC value of the thermal relay should be more than 1.1 times the rated current of the motor. Where the wiring length is 10 m or
more, the thermal relay tends to turn off readily. In this case, provide an AC reactor on the output side or use a current sensor.
Install a circuit breaker on the main power input side to protect inverter wiring and ensure personal safety. Choose an invertercompatible circuit breaker. The conventional type may malfunction due to harmonics from the inverter. For more information, consult
the circuit breaker manufacturer.
The wiring distance between the inverter and the remote operator panel should be 20 meters or less. Shielded cable should be used
on thewiring. Beware of voltage drops on main circuit wires. (A large voltage drop reduces torque.)
If the earth leakage relay (or earth leakage breaker) is used, it should have a sensitivity level of 15 mA or more (per inverter).
Do not use a capacitor for power factor improvement between the inverter and the motor because the high-frequency components
of the inverter output may overheat or damage the capacitor.
High-frequency Noise and Leakage Current
(1) High-frequency components are included in the input/output of the inverter main circuit, and they may cause interference in a transmitter,
radio, or sensor if used near the inverter. The interference can be minimized by attaching noise filters (option) in the inverter circuitry.
(2) The switching action of an inverter causes an increase in leakage current. Be sure to ground the inverter and the motor.
Lifetime of Primary Parts
Because a DC bus capacitor deteriorates as it undergoes internal chemical reaction, it should normally be replaced
every five years. Be aware, however, that its life expectancy is considerably shorter when the inverter is subjected
to such adverse factors as high temperatures or heavy loads exceeding the rated current of the inverter. The
approximate lifetime of the capacitor is as shown in the figure at the right when it is used 12 hours daily (according
"
Instructions for Periodic Inspection of General-Purpose Inverter " (JEMA).) Also, such moving parts as a
to the
cooling fan should be replaced. Maintenance inspection and parts replacement must beperformed by only specified
trained personnel. Please plan to replace new INV depends on the load, ambient condition in advance.
50
40
30
Ambient temperature (˚C)
SJ700
2.5 510
Capacitor lifetime (years)
Precaution for Correct Usage
• Before use, be sure to read through the Instruction Manual to insure proper use of the inverter.
• Note that the inverter requires electrical wiring; a trained specialist should carry out the wiring.
• The inverter in this catalog is designed for general industrial applications. For special applications in fields such as aircraft, outer space,
nuclear power, electrical power, transport vehicles, clinics, and underwater equipment, please consult with us in advance.
•For application in a facility where human life is involved or serious losses may occur, make sure to provide safety devices to avoid a serious accident.
•The inverter is intended for use with a three-phase AC motor. For use with a load other than this, please consult with us.
Information in this brochure is subject to change without notice.
SJ700B
34
Printed in Japan (T) SM-E268P 0712
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.