After reading this manual, keep it handy for future reference.
NTS204X
Revision History
No. Revision content Date of issue Manual code
1 First edition Octover 2007 NTS204X
- The current edition of this Instruction Manual also includes some corrections of simple misprints,
missing letters, misdescriptions and certain added explanations other than those listed in the above
Revision History table.
・There is a specification label attached to the inverter as shown in Figure 1-1.
Figure 1-1 Location of the specifications label
・Please confirm the model name and MFG number from the specification label as follows.
Maximum applicable motor capacity
Inverter model
Input ratings
Output ratings
Serial number
Model: SJ700-150HFF2
kW/(HP): 15/(20)
Input/Entree: 50Hz,60Hz V 1 Ph A
50Hz,60Hz 380-480V 3 Ph 35A
Output/Sortie: 0 -400Hz 380-480V 3 Ph 32A
MFGNo. 77AAT12345 A 001 Date: 0707
Hitachi Industrial Equipment
Systems Co.,Ltd.
Figure 1-2 Contents of the specifications label
1.1.1 Model name
SJ700-150 H F F 2
2:type2
F:with EMC filter
F:with digital operator
L:3Ø200V class
H:3Ø400V class
Applicable motor(150:15kW)
Model name
1.1.2 MFG number
77 A T12345 7 001
Serial No.(001-999)
Year of production(7:2007
Production No.
REV.No.(1 charactor or 2 character)
Production year & month(78:2007/August)
Specification
label
MADE IN JAPAN
)
NE
1 - 1
1.2 Precautions for Data Setting
The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable the display
of all parameters, specify "00" (full display) for the function code display restriction (b037).
To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock mode
selection (b031).
1.2.1 Monitoring Mode
Code Function name Monitored data or setting Default
d001 Output frequency monitoring 0.00 to 99.99, 100.0 to 400.0 (Hz)
d002 Output current monitoring 0.0 to 999.9, 1000 to 9999 (A)
d003 Rotation direction minitoring F (forward rotation), o (stopped), r (reverse rotation)
d004 Process variable (PV), PID feedback
monitoring
d005 Intelligent input terminal status (Example)
d006 Intelligent output terminal status (Example)
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
8 7
FW
5
4
3 2 1
6
Terminals FW, 7, 2, and 1: ON
Terminals 8, 6, 5, 4, and 3: OFF
Terminals 12 and 11: ON
Terminals AL, 15, 14, and 13: OFF
AL 15 14 13 12 11
d007 Scaled output frequency monitoring 0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
d008 Actual-frequency monitoring -400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)
d009 Torque command monitoring -200. to +200. (%)
d010 Torque bias monitoring -200. to +200. (%)
d012 Torque monitoring -200. to +200. (%)
d013 Output voltage monitoring 0.0 to 600.0 (V)
d014 Power monitoring 0.0 to 999.9 (kW)
d015 Cumulative power monitoring 0.0 to 999.9, 1000. to 9999.
d016 Cumulative operation RUN time
monitoring
d017 Cumulative power-on time monitoring
d018 Heat sink temperature monitoring
d019 Motor temperature monitoring
d022 Life-check monitoring 1: Capacitor on main circuit board
d023 Program counter 0 to 1024
d024 Program number monitoring 0000 to 9999
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
0. to 9999., 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000) (hr)
0. to 9999., 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000) (hr)
-020. to 200.0 (C)
-020. to 200.0 (C)
2: Cooling-fan speed drop
ON
OFF
2 1
Note
1 - 2
Code Function name Monitored data or setting Default Note
d025 User monitor 0 -2147483647 to 2147483647 (upper 4 digits including “-“)
d026 User monitor 1 -2147483647 to 2147483647 (upper 4 digits including “-“)
d027 User monitor 2 -2147483647 to 2147483647 (upper 4 digits including “-“)
d028 Pulse counter 0 to 2147483647 (upper 4 digits)
d029 Position setting monitor -1073741823 to 1073741823 (upper 4 digits including “-“)
d030 Position feedback monitor -1073741823 to 1073741823 (upper 4 digits including “-“)
d080 Trip Counter 0. to 9999., 1000 to 6553 (10000 to 65530) (times)
Trip monitoring 1 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d081
Trip monitoring 2 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d082
Trip monitoring 3 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d083
Trip monitoring 4 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d084
Trip monitoring 5 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d085
Trip monitoring 6 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d086
d090 Programming error monitoring Warning code
d102 DC voltage monitoring 0.0 to 999.9 (V)
d103 BRD load factor monitoring 0.0 to 100.0 (%)
d104 Electronic thermal overload monitoring 0.0 to 100.0 (%)
power-on time (hours)
power-on time (hours)
power-on time (hours)
power-on time (hours)
power-on time (hours)
power-on time (hours)
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
1.2.2 Function Mode
Code Function name Monitored data or setting
Output frequency setting 0.0, "start frequency" to "maximum frequency" (or maximum frequency,
F001
F002 Acceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F202 Acceleration (1) time setting, 2nd
motor
F302 Acceleration (1) time setting, 3rd
motor
F003 Deceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F203 Deceleration time setting, 2nd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F303 Deceleration time setting, 3rd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
terminals), 02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1), 04
(switching between O2 and keypad potentiometer) (*1)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals)
(reversible), 03 (disabling O2 terminal)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
00 (disabling), 01 (enabling)
with 7 terminals)
0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
00 (free-running after jogging stops [disabled during operation]), 01
(deceleration and stop after jogging stops [disabled during operation]), 02 (DC
braking after jogging stops [disabled during operation]), 03 (free-running after
jogging stops [enabled during operation]), 04 (deceleration and stop after
jogging stops [enabled during operation]), 05 (DC braking after jogging stops
[enabled during operation])
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04
(restarting with active matching frequency)
0.3 to 25.0 (s) 1.0
00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating
to stop)
00 (16 times), 01 (unlimited) 00
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03
(tripping after deceleration and stopping with matching frequency), 04
(restarting with active matching frequency)
1 to 3 (times) 3
0.20 x "rated current" to 1.00 x "rated current" (A) Rated current of inverter
0.20 x "rated current" to 1.00 x "rated current" (A) Rated current of inverter
0.20 x "rated current" to 1.00 x "rated current" (A) Rated current of inverter
00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
deceleration (increasing the speed during regeneration))
0.10 to 30.00 (s) 1.00
00 (disabling), 01 (enabling during acceleration and deceleration), 02
(enabling during constant speed), 03 (enabling during acceleration and
deceleration (increasing the speed during regeneration))
0.10 to 30.00 (s) 1.00
0.20 x "rated current" to 2.00 x "rated current" (A) Rated current of inverter
0.10 to 30.00 (s) 0.50
00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set
frequency)
00 (disabling change of data other than "b031" when SFT is on), 01 (disabling
change of data other than "b031" and frequency settings when SFT is on), 02
(disabling change of data other than "b031"), 03 (disabling change of data
other than "b031" and frequency settings), 10 (enabling data changes during
operation)
Default
_FF _FEF _FUF
00
00
00
00 01 01
00 01 01
00 01 01
01
Rated current of inverter x
1.50
01
Rated current of inverter x
1.50
00
01
Note
1 - 7
Code Function name Monitored data or setting
b034 Run/power-on warning time 0. to 9999. (0 t o 99990), 1000 to 6553 (10000 to 655300) (hr) 0.
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor)
0.00 to 99.99 (s) 0.00
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2
(enabling resetting only upon tripping [resetting when RS is on])
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting
with active matching frequency),03(resetting only trip)
Default
_FF _FEF _FUF
01
Rated current of
inverter
01
Rated current of
inverter
120.
04
02
00
00
Note
1 - 12
Code Function name Monitored data or setting
C111 Overload setting (2) 0.0 to 2.00 x "rated current" (A)
inal
Ter m
C121 [O] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting
C122 [OI] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting
ment
Adjust
C123 [O2] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting
C130 Output 11 on-delay time 0.0 to 100.0 (s) 0.0
C131 Output 11 off-delay time 0.0 to 100.0 (s) 0.0
C132 Output 12 on-delay time 0.0 to 100.0 (s) 0.0
C133 Output 12 off-delay time 0.0 to 100.0 (s) 0.0
C134 Output 13 on-delay time 0.0 to 100.0 (s) 0.0
C135 Output 13 off-delay time 0.0 to 100.0 (s) 0.0
C136 Output 14 on-delay time 0.0 to 100.0 (s) 0.0
C137 Output 14 off-delay time 0.0 to 100.0 (s) 0.0
C138 Output 15 on-delay time 0.0 to 100.0 (s) 0.0
C139 Output 15 off-delay time 0.0 to 100.0 (s) 0.0
C140 Output RY on-delay time 0.0 to 100.0 (s) 0.0
C141 Output RY off-delay time 0. 0 to 100.0 (s) 0.0
C142 Logical output signal 1 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C143 Logical output signal 1 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 1 operator
C144
selection
C145 Logical output signal 2 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C146 Logical output signal 2 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 2 operator
C147
selection
C148 Logical output signal 3 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C149 Logical output signal 3 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Output terminal operation function
Input terminal response
Logical output signal 3 operator
C150
selection
C151 Logical output signal 4 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C152 Logical output signal 4 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 4 operator
C153
selection
C154 Logical output signal 5 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C155 Logical output signal 5 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 5 operator
C156
selection
C157 Logical output signal 6 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C158 Logical output signal 6 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 6 operator
C159
selection
Input terminal response time
C160
setting 1
Input terminal response time
C161
setting 2
Input terminal response time
C162
setting 3
Input terminal response time
C163
setting 4
Input terminal response time
C164
setting 5
Input terminal response time
C165
setting 6
Input terminal response time
C166
setting 7
Input terminal response time
C167
setting 8
Input terminal response time
C168
setting FW
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
Default
_FF _FEF _FUF
Rated current of
inverter
Note
Multistage speed/position
C169
Other
determination time
0. to 200. ( ¯10ms) 0
1 - 13
Code Function name Monitored data or setting
H001 Auto-tuning Setting
H002 Motor data selection, 1st motor
H202 Motor data selection, 2nd motor
H003 Motor capacity, 1st motor 0.20 to 75.00 (kW) Factory setting
H203 Motor capacity, 2nd motor 0.20 to 75.00 (kW) Factory setting
H004 Motor poles setting, 1st motor 2, 4, 6, 8, 10 (poles) 4
H204 Motor poles setting, 2nd motor 2, 4, 6, 8, 10 (poles) 4
H005 Motor speed constant, 1st motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1.590
H205 Motor speed constant, 2nd motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1. 590
Motor stabilization constant, 1st
H006
motor
Motor stabilization constant, 2nd
H206
motor
Motor stabilization constant, 3rd
H306
motor
H020 Motor constant R1, 1st motor
H220 Motor constant R1, 2nd motor
H221 Motor constant R2, 1st motor
H221 Motor constant R2, 2nd motor
Control constants
H222 Motor constant L, 1st motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H222 Motor constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H223 Motor constant Io 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H223 Motor constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H224 Motor constant J 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
H224 Motor constant J, 2nd motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
H030 Auto constant R1, 1st motor
H230 Auto constant R1, 2nd motor
H231 Auto constant R2, 1st motor
H231 Auto constant R2, 2nd motor
H232 Auto constant L, 1st motor 0. 01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H232 Auto constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H233 Auto constant Io, 1st motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H233 Auto constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H234 Auto constant J, 1st motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
H234 Auto constant J, 2nd motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
00 (disabling auto-tuning), 01 (auto-tuning without rotation), 02 (auto-tuning
with rotation)
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
0. to 255. 100.
0. to 255. 100.
0. to 255. 100.
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
Default
Note
_FF _FEF _FUF
00
00
00
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
1 - 14
Code Function name Monitored data or setting
H050 PI proportional gain for 1st motor 0.0 to 999.9, 1000. 100.0
H250 PI proportional gain for 2nd motor 0.0 to 999.9, 1000. 100.0
H051 PI integral gain for 1st motor 0.0 to 999.9, 1000. 100.0
H251 PI integral gain for 2nd motor 0.0 t o 999.9, 1000. 100.0
P proportional gain setting for 1st
H052
motor
P proportional gain setting for 2nd
H252
motor
H060 Zero LV lmit for 1st motor 0.0 to 100.0 100.0
H260 Zero LV lmit for 2nd motor 0.0 to 100.0 100.0
00 (as indicated by the sign), 01 (depending on the operation direction) 00
0.00 to "maximum frequency" (Hz) 0.00
0.00 to "maximum frequency" (Hz) 0.00
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor)
20, 21, 100 21
70, 71, 101 71
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02
(ignoring errors), 03 (stopping the motor after free-running), 04
(decelerating and stopping the motor)
This section describes typical examples of digital operator operation (in basic and full display modes) and
an example of special digital operator operation in extended function mode U.
The initial display on the monitor screen after power-on depends on the setting of function "b038". For
details, see Section 4.2.81, "Initial-screen selection," (on page 4-76).
When the setting of function "b038" is "01" (factory setting), the monitor initially shows as
the setting of function "d001" (output frequency monitoring). Pressing the key in this status
changes the display to .
Note: The display contents on the monitor depend on the settings of functions "b037" (function code
display restriction), "b038" (initial-screen selection), and "b039" (automatic setting of user
parameters). For details, see Sections 4.2.80, "Function code display restriction," (on page 4-74),
4.2.81, "Initial-screen selection," (on page 4-76), and 4.2.82, "Automatic user-parameter setting," (on
page 4-77).
Item Function code Data Description
00 Full display
Function code display
restriction
Initial-screen selection
(Initial display at
power-on)
user-parameter settings
*1 Not displayed with the factory setting
b037
b038
(*1)
b039
(*1)
01 Function-specific display
02 User setting
03 Data comparison display
04 Basic display (factory setting)
00
01 d001 (output frequency monitoring)
02 d002 (output current monitoring)
03 d003 (rotation direction minitoring)
04 d007 (Scaled output frequency monitoring)
05 F001 (output frequency setting)
00 Disable Selection of automatic
01 Enable
Screen displayed when the [STR] key was pressed last
(same as the operation on the SJ300 series)
* The following procedure enables you to turn the monitor display back to or (*1)
regardless of the current display mode:
- Hold down the key for 3 seconds or more. The monitor shows and (*1)
FUNC
alternately.
During this status, press the key. The monitor will show only or (*1),
which is shown when the is pressed.
FUNC
FUNC
*1 The monitor shows only when the motor driven by the inverter is stopped. While the
motor is running, the monitor shows an output frequency.
FUNC
1 - 20
1.3.1 Example of operation in basic display mode ("b037" = "04" [factory setting])
- Only basic parameters can be displayed in basic display mode. (All parameters in monitor mode,
four parameters in function mode, or 20 parameters in extended function mode)
- Other parameters are not displayed. To display all parameters, select the full display mode ("b037" =
"00").
<Displayable parameters and sequence of display>
No. Display code Item
1 d001 to d104 Monitor display
2 F001 Output frequency setting
3 F002 Acceleration (1) time setting
4 F003 Deceleration (1) time setting
5 F004 Operation direction setting
6 A001 Frequency source setting
7 A002 Run command source setting
8 A003 Base frequency setting
9 A004 Maximum frequency setting
10 A005 [AT] selection
11 A020 Multispeed frequency setting
12 A021 Multispeed 1 setting
13 A022 Multispeed 2 setting
14 A023 Multispeed 3 setting
15 A044 1st control method
16 A045 V/f gain setting
17 A085 Operation mode selection
18 b001 Selection of restart mode
19 b002 Allowable under-voltage power failure time
20 b008 Retry-after-trip selection
21 b011 Retry wait time after trip
22 b037 Function code display restriction
23 b083 Carrier frequency setting
24 b084 Initialization mode selection
25 b130
26 b131 Setting of overvoltage suppression level
27 C021 Setting of intelligent output terminal 11
28 C022 Setting of intelligent output terminal 12
29 C036 Alarm relay active state
Selection of overvoltage suppression
function
Note:
If a desired parameter is not displayed, check
the setting of function "b037" (function code
display restriction). To display all parameters,
specify "00" for "b037".
1 - 21