Hitachi SJ700-2 SERIES Service Manual

HITACHI INVERTER
SJ700-2 SERIES
SERVICE MANUAL
After reading this manual, keep it handy for future reference.
NTS204X
Revision History
1 First edition Octover 2007 NTS204X
- The current edition of this Instruction Manual also includes some corrections of simple misprints, missing letters, misdescriptions and certain added explanations other than those listed in the above Revision History table.
Table of contents
Chapter 1 Investigation of the inverter
1.1 Spesification label(Model name,manufacturing number:MFG) ················································1 - 1
1.1.1 Model name, ················································································································1 - 1
1.1.2 MFG number················································································································1 - 1
1.2 Precautions for Data Setting·····································································································1 - 2
1.2.1 Monitor Mode···············································································································1 - 2
1.2.2 Function Mode·············································································································1 - 3
1.2.3 Extended Function Mode ····························································································1 - 4
1.3 Code display system and key operations ·················································································1 - 20
1.3.1 Example of operation in basic display mode(“b037”=”04”[factory setting])·················1 - 21
1.3.2 Example of operation in full display mode(“b037”=”00”[factory setting])·····················1 - 23
1.3.3 Code/data display and key operator in extended function mode U ····························1 - 24
Chapter 2 Troubleshooting
2.1 Inverter trip contents,remedy,advise·························································································2 - 1
2.2 Option board error codes··········································································································2 - 5
2.2.1 Error indications by protective functions with the feedback option board (SJ-FB) mounted
·································································································································2 - 5
2.2.2 Error indications by protective functions with the digital option board (SJ-DG) mounted
·································································································································2 - 6
2.2.3 Error indications by protective functions with the DeviceNet option board (SJ-DN) mounted
·································································································································2 - 7
2.2.4 Error indications by protective functions with the easy sequence function used········2 - 8
2.3 Trip conditions monitoring········································································································2 - 9
2.4 Warning Codes·························································································································2 -10
2.5
Initialization setting················································································································2 -11
Chapter 3 Debug Mode
3.1 Monitor Modes ··························································································································3 - 1
3.2 Function Modes ························································································································3 - 2
3.3 How To Reference the Data Area (d105) Corresponding to Trip History··································3 - 2
3.4 Inverter Setting ·························································································································3 - 3
3.4.1 Setting procedure ········································································································ 3 - 3
3.4.2 Confirming the completion of initialization···································································3 - 4
Chapter 4 The check of control power supply voltage and a control signal
4.1 Control power supply ················································································································4 - 1
4.2 Control signal····························································································································4 - 1
Chapter 5 Maintenance and Inspection
5.1 Precautions for Maintenance and Inspection ···········································································5 - 1
5.1.1 Daily inspection············································································································5 - 1
5.1.2 Cleaning·······················································································································5 - 1
5.1.3 Periodic inspection·······································································································5 - 1
5.2 Daily and Periodic Inspections·································································································5 - 2
5.3 Ground Resistance Test with a Megger···················································································5 - 3
5.4 Withstand Voltage Test·············································································································5 - 3
5.5 Method of Checking the Inverter and Converter Circuits························································· 5 - 4
5.6 Replacing Parts························································································································5 - 5
5.7 Inverter Replacement···············································································································5 - 8
iii
Appendix
Circuit Diagram····························································································································6 - 1 Internal block diagram ·················································································································6 - 2 Structure figure····························································································································6 - 15
iv
1. Investigation of the inverter
1.1 Specification label(Model name,Manufacturing number:MFG)
There is a specification label attached to the inverter as shown in Figure 1-1.
Figure 1-1 Location of the specifications label
Please confirm the model name and MFG number from the specification label as follows.
Maximum applicable motor capacity
Inverter model
Input ratings
Output ratings Serial number
Model: SJ700-150HFF2
kW/(HP): 15/(20)
Input/Entree: 50Hz,60Hz V 1 Ph A
50Hz,60Hz 380-480V 3 Ph 35A
Output/Sortie: 0 -400Hz 380-480V 3 Ph 32A
MFGNo. 77AAT12345 A 001 Date: 0707
Hitachi Industrial Equipment
Systems Co.,Ltd.
Figure 1-2 Contents of the specifications label
1.1.1 Model name
SJ700-150 H F F 2
2:type2
F:with EMC filter F:with digital operator L:3Ø200V class H:3Ø400V class Applicable motor(150:15kW)
Model name
1.1.2 MFG number
77 A T12345 7 001
Serial No.(001-999) Year of production(7:2007 Production No. REV.No.(1 charactor or 2 character)
Production year & month(78:2007/August)
Specification label
MADE IN JAPAN
)
NE
1 - 1
1.2 Precautions for Data Setting
The default display mode limits the screens (parameters) that can be displayed on the monitor. To enable the display of all parameters, specify "00" (full display) for the function code display restriction (b037). To enable the parameters to be changed while the inverter is operating, specify "10" for the software lock mode selection (b031).
1.2.1 Monitoring Mode
Code Function name Monitored data or setting Default d001 Output frequency monitoring 0.00 to 99.99, 100.0 to 400.0 (Hz) d002 Output current monitoring 0.0 to 999.9, 1000 to 9999 (A) d003 Rotation direction minitoring F (forward rotation), o (stopped), r (reverse rotation) d004 Process variable (PV), PID feedback
monitoring
d005 Intelligent input terminal status (Example)
d006 Intelligent output terminal status (Example)
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999. 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
8 7
FW
5
4
3 2 1
6
Terminals FW, 7, 2, and 1: ON Terminals 8, 6, 5, 4, and 3: OFF
Terminals 12 and 11: ON Terminals AL, 15, 14, and 13: OFF
AL 15 14 13 12 11
d007 Scaled output frequency monitoring 0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960) d008 Actual-frequency monitoring -400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) d009 Torque command monitoring -200. to +200. (%) d010 Torque bias monitoring -200. to +200. (%) d012 Torque monitoring -200. to +200. (%) d013 Output voltage monitoring 0.0 to 600.0 (V) d014 Power monitoring 0.0 to 999.9 (kW) d015 Cumulative power monitoring 0.0 to 999.9, 1000. to 9999.
d016 Cumulative operation RUN time
monitoring d017 Cumulative power-on time monitoring d018 Heat sink temperature monitoring d019 Motor temperature monitoring d022 Life-check monitoring 1: Capacitor on main circuit board
d023 Program counter 0 to 1024 d024 Program number monitoring 0000 to 9999
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
0. to 9999., 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000) (hr)
0. to 9999., 1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000) (hr)
-020. to 200.0 (C)
-020. to 200.0 (C)
2: Cooling-fan speed drop
ON OFF
2 1
Note
  
      
 
1 - 2
Code Function name Monitored data or setting Default Note
d025 User monitor 0 -2147483647 to 2147483647 (upper 4 digits including “-“)
d026 User monitor 1 -2147483647 to 2147483647 (upper 4 digits including “-“)
d027 User monitor 2 -2147483647 to 2147483647 (upper 4 digits including “-“)
d028 Pulse counter 0 to 2147483647 (upper 4 digits)
d029 Position setting monitor -1073741823 to 1073741823 (upper 4 digits including “-“)
d030 Position feedback monitor -1073741823 to 1073741823 (upper 4 digits including “-“)
d080 Trip Counter 0. to 9999., 1000 to 6553 (10000 to 65530) (times)
Trip monitoring 1 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d081
Trip monitoring 2 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d082
Trip monitoring 3 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d083
Trip monitoring 4 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d084
Trip monitoring 5 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d085
Trip monitoring 6 Factor, frequency (Hz), current (A), voltage across P-N (V), running time (hours),
d086
d090 Programming error monitoring Warning code
d102 DC voltage monitoring 0.0 to 999.9 (V)
d103 BRD load factor monitoring 0.0 to 100.0 (%)
d104 Electronic thermal overload monitoring 0.0 to 100.0 (%)
power-on time (hours)
power-on time (hours)
power-on time (hours)
power-on time (hours)
power-on time (hours)
power-on time (hours)
1.2.2 Function Mode
Code Function name Monitored data or setting
Output frequency setting 0.0, "start frequency" to "maximum frequency" (or maximum frequency,
F001
F002 Acceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F202 Acceleration (1) time setting, 2nd
motor
F302 Acceleration (1) time setting, 3rd
motor
F003 Deceleration (1) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F203 Deceleration time setting, 2nd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F303 Deceleration time setting, 3rd motor 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
F004 Keypad Run key routing 00 (forward rotation), 01 (reverse rotation) 00
2nd/3rd motors) (Hz)
0.0 to 100.0 (when PID function is enabled)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 30.00
Default
_FF _FEF _FUF
0.00
1 - 3
1.2.3 Extended Function Mode
Code Funct ion name Monitored data or setting
Frequency source setting 00 (keypad potentiometer) (*1), 01 (control circuit terminal block), 02 (digital
A001
Run command source setting 01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option
A002
A003 Base frequency setting 30. to "maximum frequency " (Hz) 60. 50. 60.
Base frequency setting, 2nd
A203
motor
Base frequency setting, 3rd
A303
Basic settings
Analog input and others
Multispeed operation and jogging
.
motor
A004 Maximum frequency setting 30. to 400. (Hz) 60. 50. 60.
Maximum frequency setting, 2nd
A204
motor
Maximum frequency setting, 3rd
A304
motor
[AT] selection 00 (switching between O and OI terminals), 01 (switching between O and O2
A005
[O2] selection 00 (single), 01 (auxiliary frequency input via O and OI terminals)
A006
[O]-[L] input active range start
A011
frequency
[O]-[L] input active range end
A012
frequency
[O]-[L] input active range start
A013
voltage
[O]-[L] input active range end
A014
voltage
[O]-[L] input active range start
A015
frequency selection
External frequency filter time
A016
const.
Easy sequence function
A017
selection
Multispeed operation selection 00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable
A019
A020 Multispeed frequency setting 0.0 or “start frequency” to “maximum frequency” (Hz) 0. 00
Multispeed frequency setting,
A220
2nd motor
Multispeed frequency setting,
A320
3rd motor
A021 Multispeed 1 setting 0.0 or “start frequency” to “1st maximum frequency” (Hz) 0.00
A022 Multispeed 2 setting 0.0 or “start frequency” to “2nd maximum frequency” (Hz) 0.00
A023 Multispeed 3 setting 0.0 or “start frequency” to “3rd maximum frequency” (Hz) 0.00
A024 Multispeed 4 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A025 Multispeed 5 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A026 Multispeed 6 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A027 Multispeed 7 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A028 Multispeed 8 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A029 Multispeed 9 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A030 Multispeed 10 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A031 Multispeed 11 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A032 Multispeed 12 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A033 Multispeed 13 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A034 Multispeed 14 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A035 Multispeed 15 setting 0.0 or “start frequency” to “n-th maximum frequency” (Hz) 0.00
A038 Jog frequency setting "Start frequency" to 9.99 (Hz) 1.00
A039 Jog stop mode
operator), 03 (RS485), 04 (option 1), 05 (option 2), 06 (pulse-string input), 07 (easy sequence), 10 (operation function result)
1), 05 (option 2)
30. to "maximum frequency, 2nd motor" (Hz)
30. to "maximum frequency, 3rd motor" (Hz)
30. to 400. (Hz)
30. to 400. (Hz)
terminals), 02 (switching between O terminal and keypad potentiometer) (*1), 03 (switching between OI terminal and keypad potentiometer) (*1), 04 (switching between O2 and keypad potentiometer) (*1)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals) (reversible), 03 (disabling O2 terminal)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
00 (disabling), 01 (enabling)
with 7 terminals)
0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
00 (free-running after jogging stops [disabled during operation]), 01 (deceleration and stop after jogging stops [disabled during operation]), 02 (DC braking after jogging stops [disabled during operation]), 03 (free-running after jogging stops [enabled during operation]), 04 (deceleration and stop after jogging stops [enabled during operation]), 05 (DC braking after jogging stops [enabled during operation])
Default
_FF _FEF _FUF
02 01 01
02 01 01
60. 50. 60.
60. 50. 60.
60. 50. 60.
60. 50. 60.
00
03
0.00
0.00
0.
100.
01
31.
00
00
0.00
0.00
00
Note
1 - 4
Code Function name Monitored data or setting
A041 Torque boost method selection 00 (manual torque boost), 01 (automatic torque boost) 00
Torque boost method selection,
A241
2nd motor
A042 Manual torque boost value 0.0 to 20.0 (%) 1.0
Manual torque boost value, 2nd
A242
motor
Manual torque boost value, 3rd
A342
motor
Manual torque boost frequency
A043
adjustment
Manual torque boost frequency
A243
adjustment, 2nd motor
Manual torque boost frequency
A343
adjustment, 3rd motor
V/F characteristic curve
A044
selection, 1st motor
V/F characteristic curve
A244
V/f characteristic
DC braking
Frequency upper/lower limit and jump frequency
PID control
selection, 2nd motor
V/F characteristic curve
A344
selection, 3rd motor
A045 V/f gain setting 20. to 100. (%) 100.
Voltage compensation gain
A046
setting for automatic torque boost. 1st motor
Voltage compensation gain
A246
setting for automatic torque boost, 2nd motor
Slippage compensation gain
A047
setting for automatic torque boost, 1st motor
Slippage compensation gain
A247
setting for automatic torque boost, 2nd motor
A051 DC braking enable 00 (disabling), 01 (enabling), 02 (set frequency only) 00
A052 DC braking frequency setting 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.50
A053 DC braking wait time 0.0 to 5.0 (s) 0.0
DC braking force during
A054
deceleration
A055 DC braking time for deceleration 0.0 to 60.0 (s) 0.0
DC braking/edge or level
A056
detection for [DB] input
A057 DC braking force for starting 0. to 100.(%) 0.
A058 DC braking time for starting 0.0 to 60.0( s) 0.0
DC braking carrier frequency
A059
setting
A061 Frequency upper limit setting 0.00 or "1st minimum frequency limit" to "maximum frequency" (Hz) 0.00
Frequency upper limit setting,
A261
2nd motor
A062 Frequency lower limit setting
Frequency lower limit setting,
A262
2nd motor
Jump (center) frequency setting
A063
1
Jump (hystere sis) frequency
A064
width setting 1
Jump (center) frequency setting
A065
2
Jump (hystere sis) frequency
A066
width setting 2
Jump (center) frequency setting
A067
3
Jump (hystere sis) frequency
A068
width setting 3
Acceleration stop frequency
A069
setting
Acceleration stop time frequency
A070
setting
A071 PID Function Enable 00 (disabling), 01 (enabling), 02 (enabling inverted-data output) 00
A072 PID proportional gain 0.2 to 5.0 1.0
A073 PID integral time constant 0.0 to 999.9, 1000. to 3600. (s) 1.0
A074 PID derivative gain 0.00 to 99.99, 100.0 (s) 0.00
A075 PV scale conversion 0.01 to 99.99 1.00
A076 PV source setting
A077 Output of inverted PID deviation 00(OFF), 01 (ON) 00
A078 PID variation range 0.0 to 100.0 (%) 0.00
A079 PID feed forward selection 00 (disabled), 01 (O input), 02 (OI input), 03 (O2 input) 00
00 (manual torque boost), 01 (automatic torque boost) 00
0.0 to 20.0 (%) 1.0
0.0 to 20.0 (%) 1.0
0.0 to 50.0 (%) 5.0
0.0 to 50.0 (%) 5.0
0.0 to 50.0 (%) 5.0
00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control), 04 (0Hz-range sensorless vector), 05 (vector with sensor)
00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control), 04 (0Hz-range sensorless vector)
00(VC), 01(VP) 00
0. to 255. 100.
0. to 255. 100.
0. to 255. 100.
0. to 255. 100.
0. to 100. (%) 0.
00 (edge operation), 01 (level operation) 01
0.5 to 15.0(kHz) 5.0
0.00 or "2nd minimum frequency limit" to "maximum frequency, 2nd motor" (Hz) 0.00
0.00 or "start frequency" to "maximum frequency limit" (Hz)
0.00 or "start frequency" to "maximum frequency, 2nd motor limit" (Hz)
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 10.00 (Hz) 0.50
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 10.00 (Hz) 0.50
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 10.00 (Hz) 0.50
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.0 to 60.0 (s) 0.0
00 (input via OI), 01 (input via O), 02 (external communication), 03 (pulse-string frequency input), 10 (operation result output)
Default
_FF _FEF _FUF
00
00
0.00
0.00
00
Note
1 - 5
Code Function name Monitored data or setting
A081 AVR function select 00 (always on), 01 (always off), 02 (off during deceleration) 02 00 00
AVR
A082 AVR voltage select
A085 Operation mode selection 00 (normal operation), 01 (energy-saving operation), 02 (fuzzy operation) 00
A086 Energy saving mode tuning 0.1 to 100.0 50.0
A092 Acceleration (2) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 15.00
Acceleration (2) time setting,
A292
2nd motor
Acceleration (2) time setting,
A392
3rd motor
A093 Deceleration (2) time setting 0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 15.00
Deceleration (2) time setting,
A293
2nd motor
Deceleration (2) time setting,
A393
3rd motor
Select method to switch to
A094
Acc2/Dec2 profile
Select method to switch to
A294
Acc2/Dec2, 2nd motor
Acc1 to Acc2 frequency
A095
transition point
Acc1 to Acc2 frequency
A295
transition point, 2nd motor
Dec1 to Dec2 frequency
A096
Operation mode and acceleration/deceleration function
External frequency adjustment
n and
deceleratio
Operation-target frequency
deceleration
Acceleration and
transition point
Dec1 to Dec2 frequency
A296
transition point, 2nd motor
A097 Acceleration curve selection 00 (linear), 01 (S curve), 02 (U curve), 03 (inverted-U curve), 04 (EL-S curve) 00
A098 Deceleration curve setting 00 (linear), 01 (S curve), 02 (U curve), 03 (inverted-U curve), 04 (EL-S curve) 00
[OI]-[L] input active range start
A101
frequency
[OI]-[L] input active range end
A102
frequency
[OI]-[L] input active range start
A103
current
[OI]-[L] input active range end
A104
current
[OI]-[L] input start frequency
A105
enable
[O2]-[L] input active range start
A111
frequency
[O2]-[L] input active range end
A112
frequency
[O2]-[L] input active range start
A113
voltage
[O2]-[L] input active range end
A114
voltage
Acceleration curve constants
A131
setting
Deceleration curve constants
A132
setting
Operation-target frequency
A141
selection 1
Operation-target frequency
A142
selection 2
A143 Operator selection
A145 Frequency to be added 0. 00 to 99.99, 100.0 to 400.0 (Hz) 0.00
Sign of the frequency to be
A146
added
EL-S-curve acceleration
A150
ratio 1
EL-S-curve acceleration
A151
ratio 2
EL-S-curve deceleration
A152
ratio 1
EL-S-curve deceleration
A153
ratio 2
200 V class: 200, 215, 220, 230, 240 (V) 400 V class: 380, 400, 415, 440, 460, 480 (V)
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 15.00
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 15.00
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 15.00
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 15.00
00 (switching by 2CH terminal), 01 (switching by setting), 02 (switching only when rotation is reversed)
00 (switching by 2CH terminal), 01 (switching by setting), 02 (switching only when rotation is reversed)
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0. to "[OI]-[L] input active range end current" (%) 20.
"[OI]-[L] input active range start current" to 100. (%) 100.
00 (external start frequency), 01 (0 Hz) 00
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
-100. to 02 end-frequency rate (%) -100.
"02 start-frequency rate" to 100. (%) 100.
01 (smallest swelling) to 10 (largest swelling) 02
01 (smallest swelling) to 10 (largest swelling) 02
00 (digital operator), 01 (keypad potentiometer), 02 (input via O), 03 (input via OI), 04 (external communication), 05 (option 1), 06 (option 2), 07 (pulse-string frequency input)
00 (digital operator), 01 (keypad potentiometer), 02 (input via O), 03 (input via OI), 04 (external communication), 05 (option 1), 06 (option 2), 07 (pulse-string frequency input)
00 (addition: A141 + A142), 01 (subtraction: A141 - A142), 02 (multiplication: A141 x A142)
00 (frequency command + A145), 01 (frequency command - A145) 00
0. to 50. (%) 25.
0. to 50. (%) 25.
0. to 50. (%) 25.
0. to 50. (%) 25.
Default
Note
_FF _FEF _FUF
200/400 230/400 230/460
00
00
02
03
00
1 - 6
Code Function name Monitored data or setting
b001 Selection of restart mode
Allowable under-voltage power
b002
failure time
b003 Retry wait time before motor restart 0.3 to 100.0 (s) 1.0
Instantaneous power
b004
failure/under-voltage trip alarm enable
Number of restarts on power
b005
failure/under-voltage trip events
b006 Phase loss detection enable 00 (disabling), 01 (enabling) 00
b007 Restart frequency threshold 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
b008 Selection of retry after tripping
b009 Selection of retry after undervoltage 00 (16 times), 01 (unlimited) 00
Selection of retry count after
b010
Restart after instantaneous power failure or tripping
Electronic thermal function
Overload restriction and overcurrent restraint
Software
lock
overvoltage or overcurrent
b011 Retry wait time after tripping 0.3 to 100.0 (s) 1.0
Electronic thermal setting
b012
(calculated within the inverter from current output)
Electronic thermal setting
b212
(calculated within the inverter from current output), 2nd motor
Electronic thermal setting
b312
(calculated within the inverter from current output), 3rd motor
b013 Electronic thermal characteristic
Electronic thermal characteristic, 2nd
b213
motor
Electronic thermal characteristic, 3rd
b313
motor
Free setting, electronic thermal
b015
frequency (1)
Free setting, electronic thermal
b016
current (1)
Free setting, electronic thermal
b017
frequency (2)
Free setting, electronic thermal
b018
current (2)
Free setting, electronic thermal
b019
frequency (3)
Free setting, electronic thermal
b020
current (3)
b021 Overload restriction operation mode
b022 Overload restriction setting 0.20 x "rated current" to 1.00 x "rated current" (A)
Deceleration rate at overload
b023
restriction
Overload restriction operation mode
b024
(2)
b025 Overload restriction setting (2) 0.20 x "rated current" to 2.00 x "rated current" (A)
Deceleration rate at overload restriction
b026
(2)
b027 Overcurrent suppression enable 00 (disabling), 01 (enabling) 01
Active frequency matching, scan
b028
start frequency
Active frequency matching,
b029
scan-time constant
Active frequency matching, restart
b030
frequency select
b031 Software lock mode selection
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03 (tripping after deceleration and stopping with matching frequency), 04 (restarting with active matching frequency)
0.3 to 25.0 (s) 1.0
00 (disabling), 01 (enabling), 02 (disabling during stopping and decelerating to stop)
00 (16 times), 01 (unlimited) 00
00 (tripping), 01 (starting with 0 Hz), 02 (starting with matching frequency), 03 (tripping after deceleration and stopping with matching frequency), 04 (restarting with active matching frequency)
1 to 3 (times) 3
0.20 x "rated current" to 1.00 x "rated current" (A) Rated current of inverter
0.20 x "rated current" to 1.00 x "rated current" (A) Rated current of inverter
0.20 x "rated current" to 1.00 x "rated current" (A) Rated current of inverter
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free setting)
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free setting)
00 (reduced-torque characteristic), 01 (constant-torque characteristic), 02 (free setting)
0. to 400. (Hz) 0.
0.0 to rated current (A) 0.0
0. to 400. (Hz) 0.
0.0 to rated current (A) 0.0
0. to 400. (Hz) 0.
0.0 to rated current (A) 0.0
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling during constant speed), 03 (enabling during acceleration and deceleration (increasing the speed during regeneration))
0.10 to 30.00 (s) 1.00
00 (disabling), 01 (enabling during acceleration and deceleration), 02 (enabling during constant speed), 03 (enabling during acceleration and deceleration (increasing the speed during regeneration))
0.10 to 30.00 (s) 1.00
0.20 x "rated current" to 2.00 x "rated current" (A) Rated current of inverter
0.10 to 30.00 (s) 0.50
00 (frequency at the last shutoff), 01 (maximum frequency), 02 (set frequency)
00 (disabling change of data other than "b031" when SFT is on), 01 (disabling change of data other than "b031" and frequency settings when SFT is on), 02 (disabling change of data other than "b031"), 03 (disabling change of data other than "b031" and frequency settings), 10 (enabling data changes during operation)
Default
_FF _FEF _FUF
00
00
00
00 01 01
00 01 01
00 01 01
01
Rated current of inverter x
1.50
01
Rated current of inverter x
1.50
00
01
Note
1 - 7
Code Function name Monitored data or setting
b034 Run/power-on warning time 0. to 9999. (0 t o 99990), 1000 to 6553 (10000 to 655300) (hr) 0.
b035 Rotational direction restriction
b036 Reduced voltage start selection
b037 Function code display restriction
Others
b038 Initial-screen selection
Automatic us er-parameter
b039
setting function enable
b040 Torque limit selection
Torque limit (1) (forward-driving
b041
in 4-quadrant mode)
Torque limit (2)
b042
(reverse-regenerating in 4-quadrant mode)
Torque limit (3) (reverse-driving
b043
Torque limitation
failure
Non-stop operation at momentary power
Window comparator
in 4-quadrant mode)
Torque limit (4)
b044
(forward-regenerating in 4-quadrant mode)
b045 Torque limit LADSTOP enable 00 (disabling), 01 (enabling) 00
b046 Reverse Run protection enable 00 (disabling), 01 (enabling) 00
Controller deceleration and stop
b050
on power loss
DC bus voltage trigger level
b051
during power loss
Over-voltage threshold during
b052
power loss
Deceleration time setting during
b053
power loss
Initial output frequency decrease
b054
during power loss
Proportional gain setting for
b055
nonstop operation at power loss
Integral time setting for nonstop
b056
operation at power loss
Maximum-limit level of window
b060
comparators O
Minimum-limit level of window
b061
comparators O
Hysteresis width of window
b062
comparators O
Maximum-limit level of window
b063
comparators O I
Minimum-limit level of window
b064
comparators O I
Hysteresis width of window
b065
comparators O I
Maximum-limit level of window
b066
comparators O I
Minimum-limit level of window
b067
comparators O/OI/O2
Hysteresis width of window
b068
comparators O/OI/O2
Operation level at O
b070
disconnection
Operation level at OI
b071
disconnection
Operation level at O2
b072
disconnection
00 (enabling both forward and reverse rotations), 01 (enabling only forward rotation), 02 (enabling only reverse rotation)
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start time)
00 (full display), 01 (function-specific display), 02 (user setting), 03 (data comparison display), 04 (basic display)
00 (screen displayed when the STR key was pressed last), 01 (d001), 02 (d002), 03 (d003), 04 (d007), 05 (F001)
00 (disabling), 01 (enabling) 00
00 (quadrant-specific setting), 01 (switching by terminal), 02 (analog input), 03 (option 1), 04 (option 2)
0. to 200. (%), no (disabling torque limitation) 150.
0. to 200. (%), no (disabling torque limitation) 150.
0. to 200. (%), no (disabling torque limitation) 150.
0. to 200. (%), no (disabling torque limitation) 150.
00 (disabling), 01 (nonstop deceleration to stop), 02 (DC voltage constant control, with resume), 03 ( without resume)
0.0 to 999.9, 1000. (V) 220/440
0.0 to 999.9, 1000. (V) 360/720
0.01 to 99.99, 100.0 to 999.9, 1000. to 3600. (s) 1.00
0.00 to 10.00 (Hz) 0.00
0.00 to 2.55 0.20
0.000 to 9.999 /10.00 to 65.53 (s) 0.100
0. to 100. (lower limit : b061 + b062 / 2) (%) 100
0. to 100. (lower limit : b060 - b062 / 2) (%) 0
0. to 10. (lower limit : b061 - b062 / 2) (%) 0
0. to 100. (lower limit : b064 + b066 / 2) (%) 100
0. to 100. (lower limit : b063 - b066 / 2) (%) 0
0. to 10. (lower limit : b063 - b064 / 2) (%) 0
-100. to 100. (lower limit : b067 + b068 / 2) (%) 100
-100. to 100. (lower limit : b066 - b068 / 2) (%) 0
0. to 10. (lower limit : b066 - b067 / 2) (%) 0
0. to 100. (%) or "no" (ignore) no
0. to 100. (%) or "no" (ignore) no
-100. to 100. (%) or "no" (ignore) no
Default
_FF _FEF _FUF
00
6
04
01
00
00
Note
1 - 8
Code Function name Monitored data or setting
Cumulative input power data
b078
clearance
Cumulative input power display
b079
gain setting
b082 Start frequency adjustment 0.10 to 9.99 (Hz) 0.50
b083 Carrier frequency setting 0.5 to 15.0 (kHz) (subject to derating) 5.0
Initialization mode (parameters or
b084
trip history)
b085 Country code for initialization 00 (Japan), 01 (EU), 02 (U.S.A.) 00 01 02
Frequency scaling conversion
b086
factor
b087 STOP key enable 00 (enabling), 01 (disabling), 02 (disabling only the function to stop) 00
b088 Restart mode after FRS
Others
Free setting of V/f characteristic
Others
Automatic carrier frequency
b089
reduction
b090 Dynamic braking usage ratio 0.0 to 100.0 (%) 0.0
b091 Stop mode selection 00 (deceleration until stop), 01 (free-run stop) 00
b092 Cooling fan control
b095 Dynamic braking control
b096 Dynamic braking activation level 330 to 380, 660 to 760(V)
Thermistor for thermal protection
b098
control
b099 Thermal protection level setting
b100 Free-setting V/f frequency (1) 0. to "free-setting V/f frequency (2)" (Hz) 0.
b101 Free-setting V/f voltage (1) 0.0 to 800.0 (V) 0.0
b102 Free-setting V/f frequency (2) 0. to "free-setting V/f frequency (3)" (Hz) 0.
b103 Free-setting V/f voltage (2) 0.0 to 800.0 (V) 0.0
b104 Free-setting V/f frequency (3) 0. to "free-setting V/f frequency (4)" (Hz) 0.
b105 Free-setting V/f voltage (3) 0.0 to 800.0 (V) 0.0
b106 Free-setting V/f frequency (4) 0. to "free-setting V/f frequency (5)" (Hz) 0.
b107 Free-setting V/f voltage (4) 0.0 to 800.0 (V) 0.0
b108 Free-setting V/f frequency (5) 0. to "free-setting V/f frequency (6)" (Hz) 0.
b109 Free-setting V/f voltage (5) 0.0 to 800.0 (V) 0.0
b110 Free-setting V/f frequency (6) 0. to "free-setting V/f frequency (7)" (Hz) 0.
b111 Free-setting V/f voltage (6) 0.0 to 800.0 (V) 0.0
b112 Free-setting V/f frequency (7) 0. to 400. (Hz) 0.
b113 Free-setting V/f voltage (7) 0.0 to 800.0 (V) 0.0
b120 Brake Control Enable 00 (disabling), 01 (enabling) 00
b121 Brake Wait Time for Release 0.00 to 5.00 (s) 0.00
b122 Brake Wait Time for Acceleration 0.00 to 5.00 (s) 0.00
b123 Brake Wait Time for Stopping 0.00 to 5.00 (s) 0.00
b124 Brake Wait Time for Confirmation 0.00 to 5.00 (s) 0.00
b125 Brake Release Frequency Setting 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
b126 Brake Release Current Setting 0.0 to 2.00 x "rated current" Rated current of inverter
b127 Braking frequency 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
b130 Overvoltage suppression enable
b131 Overvoltage suppression level 330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
Acceleration and deceleration
b132
rate at overvoltage suppression
Overvoltage suppression
b133
propotional gain
Overvoltage suppression Integral
b134
time
Clearance by setting "01" and pressing the STR key 00
1. to 1000. 1.
00 (clearing the trip history), 01 (initializing the data), 02 (clearing the trip history and initializing the data)
0.1 to 99.0 1.0
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting with active matching frequency)
00: invalid, 01: valid 00
00 (always operating the fan), 01 (operating the fan only during inverter operation [including 5 minutes after power-on and power-off])
00 (disabling), 01 (enabling [disabling while the motor is topped]), 02 (enabling [enabling also while the motor is topped])
00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02 (enabling the thermistor with NTC)
0. to 9999. (Ω)
00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling acceleration)
0.10 to 30.00 (s) 1.00
0.00 to 2.55 0.50
0.000 to 9.999 / 10.00 to 65.53 (s) 0.060
Default
_FF _FEF _FUF
00
00
00
00
360/
720
00
3000.
00
380/
760
Note
1 - 9
Code Function name Monitored data or setting
C001 Terminal [1] function (*2)
C002 Terminal [2] function 16
C003 Terminal [3] function (*2)
C004 Terminal [4] function 11
C005 Terminal [5] function 09
C006 Terminal [6] function 03 03 13
C007 Terminal [7] function 02
C008 Terminal [8] function
Intelligent input terminals
C011 Terminal [1] active state 00 (NO) / 01 (NC) 00
C012 Terminal [2] active state 00 (NO) / 01 (NC) 00
C013 Terminal [3] active state 00 (NO) / 01 (NC) 00
C014 Terminal [4] active state 00 (NO) / 01 (NC) 00
C015 Terminal [5] active state 00 (NO) / 01 (NC) 00
C016 Terminal [6] active state 00 (NO) / 01 (NC) 00
C017 Terminal [7] active state 00 (NO) / 01 (NC) 00
C018 Terminal [8] active state 00 (NO) / 01 (NC) 00
C019 Terminal [FW] active state 00 (NO) / 01 (NC) 00
01 (RV: Reverse RUN), 02 (CF1: Multispeed 1 setting), 03 (CF2: Multispeed 2 setting), 04 (CF3: Multispeed 3 setting), 05 (CF4: Multispeed 4 setting), 06 (JG: Jogging), 07 (DB: external DC braking), 08 (SET: Set 2nd motor data), 09 (2CH: 2-stage acceleration/deceleration), 11 (FRS: free-run stop), 12 (EXT: external trip), 13 (USP: unattended start protection), 14: (CS: commercial power source enable), 15 (SFT: software lock), 16 (AT: analog input voltage/current select), 17 (SET3: 3rd motor control), 18 (RS: reset), 20 (STA: starting by 3-wire input), 21 (STP: stopping by 3-wire input), 22 (F/R: forward/reverse switching by 3-wire input), 23 (PID: PID disable), 24 (PIDC: PID reset), 26 (CAS: control gain setting), 27 (UP: remote control UP function), 28 (DWN: remote control DOWN function), 29 ( DWN: remote control data clearing), 31 (OPE: forcible operation), 32 (SF1: multispeed bit 1), 33 (SF2: multispeed bit 2), 34 (SF3: multispeed bit 3), 35 (SF4: multispeed bit 4), 36 (SF5: multispeed bit 5), 37 (SF6: multispeed bit 6), 38 (SF7: multispeed bit 7), 39 (OLR: overload restriction selection), 40 (TL: torque limit enable), 41 (TRQ1: torque limit selection bit 1), 42 (TRQ2: torque limit selection bit 2), 43 (PPI: P/PI mode selection), 44 (BOK: braking confirmation), 45 (ORT: orientation), 46 (LAC: LAD cancellation), 47 (PCLR: clearance of position deviation), 48 (STAT: pulse train position command input enable), 50 (ADD: trigger for frequency addition [A145]), 51 (F-TM: forcible-terminal operation), 52 (ATR: permission of torque command input), 53 (KHC: cumulative power clearance), 54 (SON: servo-on), 55 (FOC: forcing), 56 (MI1: general-purpose input 1), 57 (MI2: general-purpose input 2), 58 (MI3: general-purpose input 3), 59 (MI4: general-purpose input 4), 60 (MI5: general-purpose input 5), 61 (MI6: general-purpose input 6), 62 (MI7: general-purpose input 7), 63 (MI8: general-purpose input 8), 65 (AHD: analog command holding), 66 (CP1: multistage position settings selection 1 ), 67 (CP2: multistage position settings selection 2), 68 (CP3: multistage position settings selection 3), 69 (ORL: Zero-return limit function), 70 (ORG: Zero-return trigger function), 71 (FOT: forward drive stop), 72 (ROT: reverse drive stop), 73 (SPD: speed / position switching), 74 (PCNT: pulse counter), 75 (PCC: pulse counter clear), no (NO: no assignment)
Default
_FF _FEF _FUF
18
(*2)
06
(*2)
01
Note
1 - 10
Code Function name Monitored data or setting
C021 Terminal [11] function 01
C022 Terminal [12] function 00
C023 Terminal [13] function 03
C024 Terminal [14] function 07
C025 Terminal [15] function 40
C026 Alarm relay terminal function
Intelligent output terminals
C027 [FM] siginal selection
C028 [AM] siginal selection
Analog monitoring
C029 [AMI] siginal selection
Digital current monitor reference
C030
value
C031 Terminal [11] active state 00 (NO) / 01 (NC) 00
C032 Terminal [12] active state 00 (NO) / 01 (NC) 00
C033 Terminal [13] active state 00 (NO) / 01 (NC) 00
C034 Terminal [14] active state 00 (NO) / 01 (NC) 00
terminals
C035 Terminal [15] active state 00 (NO) / 01 (NC) 00
Intelligent output
C036 Alarm relay active state 00 (NO) / 01 (NC) 01
00 (RUN: running), 01 (FA1: constant-speed reached), 02 (FA2: set frequency overreached), 03 (OL: overload notice advance signal (1)), 04 (OD: output deviation for PID control), 05 (AL: alarm signal), 06 (FA3: set frequency reached), 07 (OTQ: over-torque), 08 (IP: instantaneous power failure), 09 (UV: undervoltage), 10 (TRQ: torque limited), 11 (RNT: operation time over), 12 (ONT: plug-in time over), 13 (THM: thermal alarm signal), 19 (BRK: brake release), 20 (BER: braking error), 21 (ZS: 0 Hz detection signal), 22 (DSE: speed deviation maximum), 23 (POK: positioning completed), 24 (FA4: set frequency overreached 2), 25 (FA5: set frequency reached 2), 26 (OL2: overload notice advance signal (2)), 27 (Odc: Analog O disconnection detection), 28 (OIDc: Analog OI disconnection detection), 29 (O2Dc: Analog O2 disconnection detection), 31 (FBV: PID feedback comparison), 32 (NDc: communication line disconnection), 33 (LOG1: logical operation result 1), 34 (LOG2: logical operation result 2), 35 (LOG3: logical operation result 3), 36 (LOG4: logical operation result 4), 37 (LOG5: logical operation result 5), 38 (LOG6: logical operation result 6), 39 (WAC: capacitor life warning), 40 (WAF: cooling-fan speed drop), 41 (FR: starting contact signal), 42 (OHF: heat sink overheat warning), 43 (LOC: low-current indication signal), 44 (M01: general-purpose output 1), 45 (M02: general-purpose output 2), 46 (M03: general-purpose output 3), 47 (M04: general-purpose output 4), 48 (M05: general-purpose output 5), 49 (M06: general-purpose output 6), 50 (IRDY: inverter ready), 51 (FWR: forward rotation), 52 (RVR: reverse rotation), 53 (MJA: major failure), 54(WCO: window comparator O), 55(WCOI: window comparator OI), 56 (WCO2: window comparator O2) (When alarm code output is selected for "C062", functions "AC0" to "AC2" or "AC0" to "AC3" [ACn: alarm code output] are forcibly assigned to intelligent output terminals 11 to 13 or 11 to 14, respectively.)
00 (output frequency), 01 (output current), 02 (output torque), 03 (digital output frequency), 04 (output voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD frequency), 08 (digital current monitoring), 09 (motor temperature), 10 (heat sink temperature), 12 (general-purpose output YA0)
00 (output frequency), 01 (output current), 02 (output torque), 04 (output voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD frequency), 09 (motor temperature), 10 (heat sink temperature), 11 (output torque [signed value]), 13 (general-purpose output YA1)
00 (output frequency), 01 (output current), 02 (output torque), 04 (output voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD frequency), 09 (motor temperature), 10 (heat sink temperature), 14 (general-purpose output YA2)
0.20 x "rated current" to 2.00 x "rated current" (A) (Current with digital current monitor output at 1,440 Hz)
Default
_FF _FEF _FUF
05
00
00
00
Rated current of
inverter
Note
1 - 11
Code Function name Monitored data or setting
Low-current indication signal
C038
output mode selection
Low-current indication signal
C039
detection level
C040 Overload signal output mode
C041 Overload level setting 0.0 to 2.00 x "rated current" (A)
C042 Frequency arrival setting for accel. 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
C043 Frequency arrival setting for decel. 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
C044 PID deviation level setting 0.0 to 100.0 (%) 3.0
Frequency arrival setting for
C045
acceleration (2)
Frequency arrival setting for
C046
deceleration (2)
C052 Maximum PID feedback data 0.0 to 100.0 (%) 100.0
C053 Minimum PID feedback data 0.0 to 100.0 (%) 0.0
Over-torque (forward-driving) level
C055
setting
Levels and output terminal status
Communication function
Adjustment
Others
Meter
adjustment
Over-torque (reverse
C056
regenerating) level setting
Over-torque (reverse driving) level
C057
setting
Over-torque (forward
C058
regenerating) level setting
Electronic thermal warning level
C061
setting
C062 Alarm code output 00 ( disabling), 01 (3 bits), 02 (4 bits) 00
C063 Zero speed detection level 0.00 to 99.99, 100.0 (Hz) 0.00
C064 Heat sink overheat warning level
C071 Communication speed selection
C072 Node allocation 1. to 32. 1.
Communication data length
C073
selection
C074 Communication parity selection 00 (no parity), 01 (even parity), 02 (odd parity) 00
C075 Communication stop bit selection 1 (1 bit), 2 (2 bits) 1
Selection of the operation after
C076
communication error
Communication timeout limit
C077
before tripping
C078 Communication wait time 0. to 1000. (ms) 0.
C079 Communication mode selection 00(ASCII), 01(Modbus-RTU) 00
C081 [O] input span calibration 0. to 9999., 1000 to 6553(10000 to 65530) Factory setting
C082 [OI] input span calibration 0. to 9999., 1000 to 6553(10000 to 65530) Factory setting
C083 [O2] input span calibration 0. to 9999., 1000 to 6553(10000 to 65530) Factory setting
C085 Thermistor input tuning 0.0 to 999.9, 1000. Factory setting
C091 Debug mode enable (Do not change this parameter, which is intended for factory adjustment.) 00
C101 Up/Down memory mode selection 00 (not storing the frequency data), 01 (storing the frequency data) 00
C102 Reset mode selection
C103 Restart mode after reset
C105 FM gain adjustment 50. to 200. (%) 100.
C106 AM gain adjustment 50. to 200. (%) 100.
C107 AMI gain adjustment 50. to 200. (%) 100.
C109 AM bias adjustment 0. to 100. (%) 0.
C110 AMI bias adjustment 0. to 100. (%) 20.
00 (output during acceleration/deceleration and constant-speed operation), 01 (output only during constant-speed operation)
0.0 to 2.00 x "rated current" (A)
00 (output during acceleration/deceleration and constant-speed operation), 01 (output only during constant-speed operation)
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00
0. to 200. (%) 100.
0. to 200. (%) 100.
0. to 200. (%) 100.
0. to 200. (%) 100.
0. to 100. (%) 80.
0. to 200.0 (°C)
02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06 (19,200 bps)
7 (7 bits), 8 (8 bits) 7
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors), 03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
0.00 to 99.99 (s) 0.00
00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2 (enabling resetting only upon tripping [resetting when RS is on])
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting with active matching frequency),03(resetting only trip)
Default
_FF _FEF _FUF
01
Rated current of
inverter
01
Rated current of
inverter
120.
04
02
00
00
Note
1 - 12
Code Function name Monitored data or setting
C111 Overload setting (2) 0.0 to 2.00 x "rated current" (A)
inal
Ter m
C121 [O] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting
C122 [OI] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting
ment
Adjust
C123 [O2] input zero calibration 0. to 9999., 1000 to 6553 (10000 to 65530) Factory setting
C130 Output 11 on-delay time 0.0 to 100.0 (s) 0.0
C131 Output 11 off-delay time 0.0 to 100.0 (s) 0.0
C132 Output 12 on-delay time 0.0 to 100.0 (s) 0.0
C133 Output 12 off-delay time 0.0 to 100.0 (s) 0.0
C134 Output 13 on-delay time 0.0 to 100.0 (s) 0.0
C135 Output 13 off-delay time 0.0 to 100.0 (s) 0.0
C136 Output 14 on-delay time 0.0 to 100.0 (s) 0.0
C137 Output 14 off-delay time 0.0 to 100.0 (s) 0.0
C138 Output 15 on-delay time 0.0 to 100.0 (s) 0.0
C139 Output 15 off-delay time 0.0 to 100.0 (s) 0.0
C140 Output RY on-delay time 0.0 to 100.0 (s) 0.0
C141 Output RY off-delay time 0. 0 to 100.0 (s) 0.0
C142 Logical output signal 1 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C143 Logical output signal 1 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 1 operator
C144
selection
C145 Logical output signal 2 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C146 Logical output signal 2 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 2 operator
C147
selection
C148 Logical output signal 3 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C149 Logical output signal 3 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Output terminal operation function
Input terminal response
Logical output signal 3 operator
C150
selection
C151 Logical output signal 4 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C152 Logical output signal 4 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 4 operator
C153
selection
C154 Logical output signal 5 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C155 Logical output signal 5 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 5 operator
C156
selection
C157 Logical output signal 6 selection 1 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
C158 Logical output signal 6 selection 2 Same as the settings of C021 to C026 (except those of LOG1 to LOG6) 00
Logical output signal 6 operator
C159
selection
Input terminal response time
C160
setting 1
Input terminal response time
C161
setting 2
Input terminal response time
C162
setting 3
Input terminal response time
C163
setting 4
Input terminal response time
C164
setting 5
Input terminal response time
C165
setting 6
Input terminal response time
C166
setting 7
Input terminal response time
C167
setting 8
Input terminal response time
C168
setting FW
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
00 (AND), 01 (OR), 02 (XOR) 00
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
0. to 200. ( ¯2ms) 1
Default
_FF _FEF _FUF
Rated current of
inverter
Note
Multistage speed/position
C169
Other
determination time
0. to 200. ( ¯10ms) 0
1 - 13
Code Function name Monitored data or setting
H001 Auto-tuning Setting
H002 Motor data selection, 1st motor
H202 Motor data selection, 2nd motor
H003 Motor capacity, 1st motor 0.20 to 75.00 (kW) Factory setting
H203 Motor capacity, 2nd motor 0.20 to 75.00 (kW) Factory setting
H004 Motor poles setting, 1st motor 2, 4, 6, 8, 10 (poles) 4
H204 Motor poles setting, 2nd motor 2, 4, 6, 8, 10 (poles) 4
H005 Motor speed constant, 1st motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1.590
H205 Motor speed constant, 2nd motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1. 590
Motor stabilization constant, 1st
H006
motor
Motor stabilization constant, 2nd
H206
motor
Motor stabilization constant, 3rd
H306
motor
H020 Motor constant R1, 1st motor
H220 Motor constant R1, 2nd motor
H221 Motor constant R2, 1st motor
H221 Motor constant R2, 2nd motor
Control constants
H222 Motor constant L, 1st motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H222 Motor constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H223 Motor constant Io 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H223 Motor constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H224 Motor constant J 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
H224 Motor constant J, 2nd motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
H030 Auto constant R1, 1st motor
H230 Auto constant R1, 2nd motor
H231 Auto constant R2, 1st motor
H231 Auto constant R2, 2nd motor
H232 Auto constant L, 1st motor 0. 01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H232 Auto constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
H233 Auto constant Io, 1st motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H233 Auto constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
H234 Auto constant J, 1st motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
H234 Auto constant J, 2nd motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
00 (disabling auto-tuning), 01 (auto-tuning without rotation), 02 (auto-tuning with rotation)
00 (Hitachi standard data), 01 (auto-tuned data), 02 (auto-tuned data [with online auto-tuning function])
00 (Hitachi standard data), 01 (auto-tuned data), 02 (auto-tuned data [with online auto-tuning function])
0. to 255. 100.
0. to 255. 100.
0. to 255. 100.
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
0.001 to 9.999, 10.00 to 65.53 (Ω)
Default
Note
_FF _FEF _FUF
00
00
00
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
Depending on motor capacity
1 - 14
Code Function name Monitored data or setting
H050 PI proportional gain for 1st motor 0.0 to 999.9, 1000. 100.0
H250 PI proportional gain for 2nd motor 0.0 to 999.9, 1000. 100.0
H051 PI integral gain for 1st motor 0.0 to 999.9, 1000. 100.0
H251 PI integral gain for 2nd motor 0.0 t o 999.9, 1000. 100.0
P proportional gain setting for 1st
H052
motor
P proportional gain setting for 2nd
H252
motor
H060 Zero LV lmit for 1st motor 0.0 to 100.0 100.0
H260 Zero LV lmit for 2nd motor 0.0 to 100.0 100.0
Zero LV starting boost current for
H061
Control constants
1st motor
Zero LV starting boost current for
H261
2nd motor
Terminal selection PI proportional
H070
gain setting
Terminal selection PI integral gain
H071
setting
Terminal selection P proportional
H072
gain setting
H073 Gain switching time 0. to 9999. (ms) 100.
0.01 to 10.00 1. 00
0.01 to 10.00 1. 00
0. to 50. (%) 50.
0. to 50. (%) 50.
0.0 to 999.9, 1000. 100.0
0.0 to 999.9, 1000. 100.0
0.00 to 10.00 1. 00
Default
Note
_FF _FEF _FUF
1 - 15
Code Function name Monitored data or setting
Operation mode on expansion card
P001
1 error
Operation mode on expansion card
P002
2 error
Encoder pulse-per-revolution
P011
(PPR) setting
P012 Control pulse setting 00 ( ASR), 01 (APR), 02 (APR2), 03 (HAPR) 00
P013 Pulse train mode setting 00 (mode 0), 01 (mode 1), 02 (mode 2) 00
P014 Home search stop position setting 0. to 4095. 0.
P015 Home search speed setting "start frequency" to "maximum frequency" (up to 120.0) (Hz) 5.00
P016 Home search direction setting 00 (forward), 01 (reverse) 00
Home search completion range
P017
setting
Home search completion delay
P018
time setting
Electronic gear set position
P019
selection
Electronic gear ratio numerator
P020
setting
Electronic gear ratio denominator
P021
setting
P022 Feed-forward gain setting 0.00 to 99.99, 100.0 to 655.3 0.00
P023 Position loop gain setting 0.00 to 99.99, 100.0 0.50
P024 Position bias setting -204 (-2048.) / -999. to 2048. 0.
Temperature compensation
P025
thermistor enable
Over-speed error detection level
P026
setting
Speed deviation error detection
P027
level setting
P028 Numerator of motor gear ratio 0. to 9999. 1.
P029 Denominator of motor gear ratio 0. to 9999. 1.
P031 Accel/decel time input selection 00 (digital operator), 01 (option 1), 02 (option 2), 03 (easy sequence) 00
Positioning command input
P032
Optional functions
selection
P033 Torque command input selection 00 (O terminal), 01 (OI terminal), 02 (O2 terminal), 03 (digital operator) 00
P034 Torque command setting 0. to 200. (%) 0.
Polarity selection at the torque
P035
command input via O2 terminal
P036 Torque bias mode 00 (disabling the mode), 01 (digital operator), 02 (input via O2 terminal) 00
P037 Torque bias value -200. to +200. (%) 0.
P038 Torque bias polarity selection 00 (as indicated by the sign), 01 (depending on the operation direction) 00
Speed limit for torque-controlled
P039
operation (forward rotation)
Speed limit for torque-controlled
P040
operation (reverse rotation)
P044 DeviceNet comm watchdog timer 0.00 to 99.99 (s) 1.00
Inverter action on DeviceNet comm
P045
error
DeviceNet polled I/O: Output
P046
instance number
DeviceNet polled I/O: Input
P047
instance number
Inverter action on DeviceNet idle
P048
mode
DeviceNet motor poles setting for
P049
RPM
P055 Pulse-string frequency scale 1.0 to 50.0 (kHz) 25. 0
Time constant of pul se-string
P056
frequency filter
P057 Pulse-string frequency bias -100. to +100. (%) 0.
P058 Pulse-string frequency limit 0. to 100. (%) 100.
00 (tripping), 01 (continuing operation) 00
00 (tripping), 01 (continuing operation) 00
128. to 9999., 1000 to 6553(10000 to 65535) (pulses) 1024.
0. to 9999., 1000 (10000) (pulses) 5.
0.00 to 9.99 (s) 0.00
00 (feedback side), 01 (commanding side) 00
0. to 9999. 1.
0. to 9999. 1.
00 (no compensation), 01 (compensation) 00
0.0 to 150.0 (%) 135.0
0.00 to 99.99, 100.0 to120.0 (Hz) 7.50
00 (digital operator), 01 (option 1), 02 (option 2) 00
00 (as indicated by the sign), 01 (depending on the operation direction) 00
0.00 to "maximum frequency" (Hz) 0.00
0.00 to "maximum frequency" (Hz) 0.00
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors), 03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
20, 21, 100 21
70, 71, 101 71
00 (tripping), 01 (tripping after decelerating and stopping the motor), 02 (ignoring errors), 03 (stopping the motor after free-running), 04 (decelerating and stopping the motor)
0, 2, 4, 6, 8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34, 36, 38 (poles)
0.01 to 2.00 (s) 0.10
Default
Note
_FF _FEF _FUF
01
01
0
1 - 16
Code Function name Monitored data or setting
P060 Multistage position setting 0
P061 Multistage position setting 1
P062 Multistage position setting 2
P063 Multistage position setting 3
P064 Multistage position setting 4
P065 Multistage position setting 5
P066 Multistage position setting 6
P067 Multistage position setting 7
P068 Zero-return mode selection 00(Low) / 01 (Hi1) / 00 (Hi2) 00
Absolute position control
P069 Zero-return direction selection 00 (FW) / 01 (RV) 00
P070 Low-speed zero-return frequency 0.00 to 10.00 (Hz) 0.00
High-speed zero-return
P071
frequency
Position rang e specificatio n
P072
(forward)
Position rang e specificatio n
P073
(reverse)
P074 Teaching selection
Easy sequence user parameter U
P100
(00)
Easy sequence user parameter U
P101
(01)
Easy sequence user parameter U
P102
(02)
Easy sequence user parameter U
P103
(03)
Easy sequence user parameter U
P104
(04)
Easy sequence user parameter U
P105
(05)
Easy sequence user parameter U
P106
(06)
Easy sequence user parameter U
P107
(07)
Easy sequence user parameter U
P108
(08)
Easy sequence user parameter U
P109
Easy sequence function
(09)
Easy sequence user parameter U
P110
(10)
Easy sequence user parameter U
P111
(11)
Easy sequence user parameter U
P112
(12)
Easy sequence user parameter U
P113
(13)
Easy sequence user parameter U
P114
(14)
Easy sequence user parameter U
P115
(15)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
Position setting range reverse side to forward side (upper 4 digits including “-“)
0.00 to 99.99 / 100.0 to Maximum frequency setting, 1st motor (Hz) 0.00
0 to 268435455 (when P012 = 02) 0 to 1073741823 (when P012 = 03) (upper 4 digits)
-268435455 to 0 (when P012 = 02)
-1073741823 to 0 (when P012 = 03) (upper 4 digits)
00 (X00) / 01 (X01) / 02 (X02) / 03 (X03) / 04 (X04) / 05 (X05) / 06 (X06) / 07 (X07) /
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
Default
_FF _FEF _FUF
0
0
0
0
0
0
0
0
268435455
-268435455
00
Note
1 - 17
Code Function name Monitored data or setting
Easy sequence user parameter U
P116
(16)
Easy sequence user parameter U
P117
(17)
Easy sequence user parameter U
P118
(18)
Easy sequence user parameter U
P119
(19)
Easy sequence user parameter U
P120
(20)
Easy sequence user parameter U
P121
(21)
Easy sequence user parameter U
P122
(22)
Easy sequence user parameter U
P123
(23)
Easy sequence user parameter U
P124
(24)
Easy sequence user parameter U
P125
Easy sequence function
(25)
Easy sequence user parameter U
P126
(26)
Easy sequence user parameter U
P127
(27)
Easy sequence user parameter U
P128
(28)
Easy sequence user parameter U
P129
(29)
Easy sequence user parameter U
P130
(30)
Easy sequence user parameter U
P131
(31)
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
0. to 9999., 1000 to 6553 (10000 to 65535) 0.
Default
Note
_FF _FEF _FUF
1 - 18
Code Function name Monitored data or setting
U001 User-selected function 1 no/d001 to P131 no
U002 User-selected function 2 no/d001 to P131 no
U003 User-selected function 3 no/d001 to P131 no
U004 User-selected function 4 no/d001 to P131 no
U005 User-selected function 5 no/d001 to P131 no
U006 User-selected function 6 no/d001 to P131 no
U007 User-selected function 7 no/d001 to P131 no
U008 User-selected function 8 no/d001 to P131 no
User parameters
U009 User-selected function 9 no/d001 to P131 no
U010 User-selected function 10 no/d001 to P131 no
U011 User-selected function 11 no/d001 to P131 no
U012 User-selected function 12 no/d001 to P131 no
Default
_FF _FEF _FUF
Note
1 - 19
1.3 Code display system and key operations
This section describes typical examples of digital operator operation (in basic and full display modes) and an example of special digital operator operation in extended function mode U.
The initial display on the monitor screen after power-on depends on the setting of function "b038". For details, see Section 4.2.81, "Initial-screen selection," (on page 4-76).
When the setting of function "b038" is "01" (factory setting), the monitor initially shows as
the setting of function "d001" (output frequency monitoring). Pressing the key in this status
changes the display to .
Note: The display contents on the monitor depend on the settings of functions "b037" (function code
display restriction), "b038" (initial-screen selection), and "b039" (automatic setting of user parameters). For details, see Sections 4.2.80, "Function code display restriction," (on page 4-74),
4.2.81, "Initial-screen selection," (on page 4-76), and 4.2.82, "Automatic user-parameter setting," (on page 4-77).
Item Function code Data Description
00 Full display
Function code display
restriction
Initial-screen selection
(Initial display at
power-on)
user-parameter settings
*1 Not displayed with the factory setting
b037
b038
(*1)
b039
(*1)
01 Function-specific display 02 User setting 03 Data comparison display 04 Basic display (factory setting)
00
01 d001 (output frequency monitoring) 02 d002 (output current monitoring) 03 d003 (rotation direction minitoring) 04 d007 (Scaled output frequency monitoring) 05 F001 (output frequency setting) 00 Disable Selection of automatic 01 Enable
Screen displayed when the [STR] key was pressed last (same as the operation on the SJ300 series)
* The following procedure enables you to turn the monitor display back to or (*1)
regardless of the current display mode:
- Hold down the key for 3 seconds or more. The monitor shows and (*1)
FUNC
alternately.
During this status, press the key. The monitor will show only or (*1),
which is shown when the is pressed.
FUNC
FUNC
*1 The monitor shows only when the motor driven by the inverter is stopped. While the
motor is running, the monitor shows an output frequency.
FUNC
1 - 20
1.3.1 Example of operation in basic display mode ("b037" = "04" [factory setting])
- Only basic parameters can be displayed in basic display mode. (All parameters in monitor mode, four parameters in function mode, or 20 parameters in extended function mode)
- Other parameters are not displayed. To display all parameters, select the full display mode ("b037" = "00").
<Displayable parameters and sequence of display>
No. Display code Item
1 d001 to d104 Monitor display 2 F001 Output frequency setting 3 F002 Acceleration (1) time setting 4 F003 Deceleration (1) time setting 5 F004 Operation direction setting 6 A001 Frequency source setting 7 A002 Run command source setting 8 A003 Base frequency setting
9 A004 Maximum frequency setting 10 A005 [AT] selection 11 A020 Multispeed frequency setting 12 A021 Multispeed 1 setting 13 A022 Multispeed 2 setting 14 A023 Multispeed 3 setting 15 A044 1st control method 16 A045 V/f gain setting 17 A085 Operation mode selection 18 b001 Selection of restart mode 19 b002 Allowable under-voltage power failure time 20 b008 Retry-after-trip selection 21 b011 Retry wait time after trip 22 b037 Function code display restriction 23 b083 Carrier frequency setting 24 b084 Initialization mode selection
25 b130
26 b131 Setting of overvoltage suppression level 27 C021 Setting of intelligent output terminal 11 28 C022 Setting of intelligent output terminal 12 29 C036 Alarm relay active state
Selection of overvoltage suppression function
Note:
If a desired parameter is not displayed, check the setting of function "b037" (function code display restriction). To display all parameters, specify "00" for "b037".
1 - 21