Model-specific tables for 200V and 400V class inverters
The following tables are specific to SJ100 inverters for the 200V and 400V class model
groups. Note that “General Specifications” on page 1–9 apply to both voltage class
groups. Footnotes for all specifications tables follow the table below.
Item200V Class Specifications
SJ100 inverters,
200V models
Applicable motor size *2kW0.20.40.550.751.1
Rated capacity
(kVA) *12
Rated input voltage1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input
current (A)
Rated output voltage *33-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A)1.62.63.04.05.0
Efficiency at 100% rated output (%)90.592.893.694.195.4
Watt loss,
approximate (W)
Starting torque *6200% or more
Dynamic braking
approx. %
torque, short
time stop *7
CE version002NFE004NFE005NFE007NFE011NFE
UL version002NFU004NFU—007NFU—
HP1/41/23/411.5
230V0.61.01.11.51.9
240V0.61.01.21.62.0
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, and 075LFU 3phase only)
1-phase3.55.86.79.011.2
3-phase2.03.43.95.26.5
at 70% output1521253138
at 100% output1929324151
without resistor,
from 50 / 60 Hz
with resistor150%
100%: ≤ 50Hz
50%: ≤ 60Hz
70%: ≤ 50Hz
50%: ≤ 60Hz
DC brakingVariable operating frequency, time, and braking force
Weightkg0.70.850.851.31.3
lb1.541.871.872.872.87
SJ100 Inverter Specifications
Footnotes for the preceding table and the tables that follow:
Note 1:The protection method conforms to JEM 1030.
Note 2:The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When
using other motors, care must be taken to prevent the rated motor current (50/
60 Hz) from exceeding the rated output current of the inverter.
Note 3:The output voltage decreases as the main supply voltage decreases (except
when using the AVR function). In any case, the output voltage cannot exceed
the input power supply voltage.
Note 4:To operate the motor beyond 50/60 Hz, consult the motor manufacturer for
the maximum allowable rotation speed.
Note 5:When SLV is selected, please set the carrier frequency higher than 2.1 kHz.
Note 6:At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor
(when selecting sensorless vector control—SLV).
Note 7:The braking torque via capacitive feedback is the average deceleration torque
at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not
continuous regenerative braking torque. The average deceleration torque
varies with motor loss. This value decreases when operating beyond 50 Hz. If
a large regenerative torque is required, the optional regenerative braking
resistor should be used.
Note 8:The frequency command is the maximum frequency at 9.8V for input voltage
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic
is not satisfactory for your application, contact your Hitachi sales representative.
Note 9:If operating the inverter at 40 to 50° C, reduce the carrier frequency to 2.1
kHz, derate the output current by 80%, and remove the top housing cover.
Note that removing the top cover will nullify the NEMA rating for the inverter
housing.
Note 10: The storage temperature refers to the short-term temperature during transport.
Note 11: Conforms to the test method specified in JIS C0911 (1984). For the model
types excluded in the standard specifications, contact your Hitachi sales representative.
Note 12: The input voltage of xxLFU is 230V.
SJ100 Inverter Specifications, continued...
Item200V Class Specifications, continued
SJ100 Inverter
SJ100 inverters,
200V models
Applicable motor size *2kW1.52.23.75.57.5
Rated capacity
(kVA) *12
Rated input voltage1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input
current (A)
Rated output voltage *33-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A)8.011.017.52432
Efficiency at 100% rated output (%)94.795.195.196.196.2
Watt loss,
approximate (W)
Starting torque *6200% or more180% or more
Dynamic braking
approx. %
torque, short
time stop *7
CE version015NFE022NFE———
UL version015NFU022NFU037LFU055LFU075LFU
HP2357.510
230V3.14.36.99.512.7
240V3.04.57.29.913.3
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, 075LFU 3-phase only)
1-phase17.524.0———
3-phase10.014.022.030.040.0
at 70% output5778130152204
at 100% output79107181216288
without resistor,
from 50 / 60 Hz
with resistor150%100%80%
70%: ≤ 50Hz
50%: ≤ 60Hz
20%: ≤ 50Hz
20%: ≤ 60Hz
DC brakingVariable operating frequency, time, and braking force
Weightkg2.22.82.85.55.7
lb4.856.176.1712.1312.57
SJ100 Inverter Specifications
Item400V Class Specifications
SJ100 inverters,
400V models
Applicable motor size *2kW0.40.751.52.2
Rated capacity (460V) kVA1.11.92.94.2
Rated input voltage3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A)2.03.35.07.0
Rated output voltage *33-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A)1.52.53.85.5
Efficiency at 100% rated output (%)92.093.795.795.8
Watt loss,
approximate (W)
Starting torque *6200% or more
Dynamic braking
approx. %
torque, short
time stop *7
DC brakingVariable operating frequency, time, and braking force
CE version004HFE007HFE015HFE022HFE
UL version004HFU007HFU015HFU022HFU
HP1/2123
at 70% output25334868
at 100% output32446592
without resistor,
from 50/60 Hz
with resistor150%100%
100%: ≤ 50Hz
50%: ≤ 60Hz
70%: ≤ 50Hz
20%: ≤ 60Hz
Weightkg1.31.71.71.8
lb2.873.753.753.97
SJ100 Inverter
Item400V Class Specifications, continued
SJ100 inverters,
400V models
Applicable motor size *2kW3.04.05.57.5
Rated capacity (460V) kVA6.26.610.312.7
Rated input voltage3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A)10.011.016.520.0
Rated output voltage *33-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A)7.88.61316
Efficiency at 100% rated output (%)95.496.296.096.5
Watt loss,
approximate (W)
Starting torque *6180% or more
Dynamic braking
approx. %
torque, short time
stop *7
DC brakingVariable operating frequency, time, and braking force
CE version030HFE040HFE055HFE075HFE
UL version—040HFU055HFU075HFU
HP457.510
at 70% output100108156186
at 100% output138151219261
without resistor,
from 50/60 Hz
with resistor100%80%
20%: ≤ 50Hz
20%: ≤ 60Hz
Weightkg2.82.85.55.7
lb6.176.1712.1312.57
General Specifications
The following table applies to all SJ100 inverters.
ItemGeneral Specifications
Protective housing *1IP20
Control methodSine wave pulse-width modulation (PWM) control
Output frequency range *40.5 to 360 Hz
Frequency accuracyDigital command: 0.01% of the maximum frequency
Analog command: 0.1% of the maximum frequency (25°C ± 10°C)
Frequency setting resolutionDigital: 0.1 Hz; Analog: max. frequency/1000
Volt./Freq. characteristic *5V/f optionally variable, V/f control (constant torque, reduced
torque), sensorless vector control
Overload current rating150%, 60 seconds
Acceleration/deceleration time0.1 to 3000 sec., (linear accel/decel), second accel/decel setting
available
SJ100 Inverter Specifications
ItemGeneral Specifications
Input
signal
Freq.
setting
Operator panelUp and Down keys / Value settings
PotentiometerAnalog setting
External signal *80 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input
impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)
FWD/
REV
Run
Intelligent input
terminal
Operator panelRun/Stop (Forward/Reverse run change by command)
External signalForward run/stop, Reverse run/stop
FW (forward run command), RV (reverse run command), CF1~CF4
(multi-stage speed setting), JG (jog command), 2CH (2-stage accel./
decel. command), FRS (free run stop command), EXT (external
trip), USP (startup function), SFT (soft lock), AT (analog current
input select signal), RS (reset), PTC (thermal protection), DB (external DC braking command), SET (2nd setting selection), UP (remote
control, accel.), DWN (remote control, decel.)
Output
signal
Intelligent output
terminal
RUN (run status signal), FA1,2 (frequency arrival signal), OL
(overload advance notice signal), OD (PID error deviation signal),
AL (alarm signal)
Frequency monitorPWM output; Select analog output frequency monitor, analog output
current monitor or digital output frequency monitor
Alarm output contactON for inverter alarm (1C contacts, both normally open or closed
avail.)
Other functionsAVR function, curved accel/decel profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency, carrier
frequency change (0.5 to 16 kHz) frequency jump, gain and bias
setting, process jogging, electronic thermal level adjustment, retry
function, trip history monitor, 2nd setting selection, auto tuning, fan
ON/OFF selection
low temperature, CPU error, memory error, ground fault detection at
startup, internal communication error, electronic thermal, CT error
Operating
Environ
ment
TemperatureOperating (ambient): -10 to 50°C (*9) / Storage: -25 to 70°C (*10)
Humidity20 to 90% humidity (non-condensing)
Vibration *11
5.9 m/s
2
(0.6G), 10 to 55 Hz
LocationAltitude 1,000 m or less, indoors (no corrosive gasses or dust)
Coating colorMunsell 8.5YR6.2/0/2, cooling fins in base color of aluminum
OptionsRemote operator unit, copy unit, cables for the units, braking unit,
braking resistor, AC reactor, DC reactor, noise filter, DIN rail
mounting
Derating Curves
The maximum available inverter current output is limited by the carrier frequency and
ambient temperature. The carrier frequency is the inverter’s internal power switching
frequency, settable from 0.5 kHz to 16 kHz. Choosing a higher carrier frequency tends to
decrease audible noise, but it also increases the internal heating of the inverter, thus
decreasing (derating) the maximum current output capability. Ambient temperature is
the temperature just outside the inverter housing—such as inside the control cabinet
where the inverter is mounted. A higher ambient temperature decreases (derates) the
inverter’s maximum current output capacity.
Use the following derating curves to help determine the optimal carrier frequency setting
for your inverter, and to find the output current derating. Be sure to use the proper curve
for your particular SJ100 inverter model number.
Legend:
SJ100–002NFE/NFU
SJ100 Inverter
Standard ratings at 40°C
Ratings at 50°C max. with top cover removed
Ratings at 55°C max. with top cover removed
100%
% of rated
output current
SJ100–004NFE/NFU
100%
% of rated
output current
95%
90%
85%
80%
75%
70%
0.5246810121416
Carrier frequency
95%
90%
85%
kHz
80%
75%
70%
0.5246810121416
Carrier frequency
kHz
SJ100 Inverter Specifications
Derating curves, continued...
SJ100–007NFE/NFU
100%
95%
90%
% of rated
output current
SJ100–0015NFE/NFU
% of rated
output current
85%
80%
75%
70%
100%
95%
90%
85%
80%
75%
kHz
0.5246810121416
Carrier frequency
70%
SJ100–022NFE/NFU
100%
95%
90%
% of rated
output current
85%
80%
75%
70%
kHz
0.5246810121416
Carrier frequency
kHz
0.5246810121416
Carrier frequency
Derating curves, continued...
SJ100–037LF/LFU
100%
90%
80%
SJ100 Inverter
% of rated
output current
SJ100–055LFU
% of rated
output current
70%
60%
50%
40%
0.5246810121416
Carrier frequency
100%
95%
90%
85%
80%
75%
kHz
SJ100–075LFU
% of rated
output current
70%
0.5246810121416
Carrier frequency
100%
95%
90%
85%
80%
75%
70%
0.5246810121416
Carrier frequency
kHz
kHz
SJ100 Inverter Specifications
Derating curves, continued...
SJ100–004HFE/HFU
100%
90%
80%
% of rated
output current
SJ100–007HFE/HFU
% of rated
output current
70%
60%
50%
40%
100%
90%
80%
70%
60%
50%
kHz
0.5246810121416
Carrier frequency
40%
SJ100–015HFE/HFU
100%
90%
80%
% of rated
output current
70%
60%
50%
40%
kHz
0.5246810121416
Carrier frequency
kHz
0.5246810121416
Carrier frequency
Derating curves, continued...
SJ100–022HFE/HFU
100%
90%
80%
SJ100 Inverter
% of rated
output current
SJ100–040HFE/HFU
% of rated
output current
70%
60%
50%
40%
100%
90%
80%
70%
60%
50%
kHz
0.5246810121416
Carrier frequency
40%
SJ100–055HFE/HFU
100%
95%
90%
% of rated
output current
85%
80%
75%
70%
kHz
0.5246810121416
Carrier frequency
kHz
0.5246810121416
Carrier frequency
SJ100 Inverter Specifications
Derating curves, continued...
SJ100–075HFE/HFU
100%
95%
90%
% of rated
output current
85%
80%
75%
70%
0.5246810121416
Carrier frequency
kHz