Hitachi SJ100 Specifications

SJ100 Inverter
SJ100 Inverter Specifications
Model-specific tables for 200V and 400V class inverters
The following tables are specific to SJ100 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page 1–9 apply to both voltage class groups. Footnotes for all specifications tables follow the table below.
Item 200V Class Specifications
SJ100 inverters, 200V models
Applicable motor size *2 kW 0.2 0.4 0.55 0.75 1.1
Rated capacity (kVA) *12
Rated input voltage 1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input current (A)
Rated output voltage *3 3-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A) 1.6 2.6 3.0 4.0 5.0
Efficiency at 100% rated output (%) 90.5 92.8 93.6 94.1 95.4
Watt loss, approximate (W)
Starting torque *6 200% or more
Dynamic braking approx. % torque, short time stop *7
CE version 002NFE 004NFE 005NFE 007NFE 011NFE
UL version 002NFU 004NFU 007NFU
HP 1/4 1/2 3/4 1 1.5
230V 0.6 1.0 1.1 1.5 1.9
240V 0.6 1.0 1.2 1.6 2.0
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, and 075LFU 3phase only)
1-phase 3.5 5.8 6.7 9.0 11.2
3-phase 2.0 3.4 3.9 5.2 6.5
at 70% output 15 21 25 31 38
at 100% output 19 29 32 41 51
without resistor, from 50 / 60 Hz
with resistor 150%
100%: 50Hz
50%: 60Hz
70%: 50Hz 50%: 60Hz
DC braking Variable operating frequency, time, and braking force
Weight kg 0.7 0.85 0.85 1.3 1.3
lb 1.54 1.87 1.87 2.87 2.87
SJ100 Inverter Specifications
Footnotes for the preceding table and the tables that follow:
Note 1: The protection method conforms to JEM 1030. Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When
using other motors, care must be taken to prevent the rated motor current (50/ 60 Hz) from exceeding the rated output current of the inverter.
Note 3: The output voltage decreases as the main supply voltage decreases (except
when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for
the maximum allowable rotation speed.
Note 5: When SLV is selected, please set the carrier frequency higher than 2.1 kHz. Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor
(when selecting sensorless vector control—SLV).
Note 7: The braking torque via capacitive feedback is the average deceleration torque
at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average deceleration torque varies with motor loss. This value decreases when operating beyond 50 Hz. If a large regenerative torque is required, the optional regenerative braking resistor should be used.
Note 8: The frequency command is the maximum frequency at 9.8V for input voltage
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not satisfactory for your application, contact your Hitachi sales representa­tive.
Note 9: If operating the inverter at 40 to 50° C, reduce the carrier frequency to 2.1
kHz, derate the output current by 80%, and remove the top housing cover. Note that removing the top cover will nullify the NEMA rating for the inverter housing.
Note 10: The storage temperature refers to the short-term temperature during transport. Note 11: Conforms to the test method specified in JIS C0911 (1984). For the model
types excluded in the standard specifications, contact your Hitachi sales repre­sentative.
Note 12: The input voltage of xxLFU is 230V.
SJ100 Inverter Specifications, continued...
Item 200V Class Specifications, continued
SJ100 Inverter
SJ100 inverters, 200V models
Applicable motor size *2 kW 1.5 2.2 3.7 5.5 7.5
Rated capacity (kVA) *12
Rated input voltage 1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input current (A)
Rated output voltage *3 3-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A) 8.0 11.0 17.5 24 32
Efficiency at 100% rated output (%) 94.7 95.1 95.1 96.1 96.2
Watt loss, approximate (W)
Starting torque *6 200% or more 180% or more
Dynamic braking approx. % torque, short time stop *7
CE version 015NFE 022NFE
UL version 015NFU 022NFU 037LFU 055LFU 075LFU
HP 2 3 5 7.5 10
230V 3.1 4.3 6.9 9.5 12.7
240V 3.0 4.5 7.2 9.9 13.3
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, 075LFU 3-phase only)
1-phase 17.5 24.0
3-phase 10.0 14.0 22.0 30.0 40.0
at 70% output 57 78 130 152 204
at 100% output 79 107 181 216 288
without resistor, from 50 / 60 Hz
with resistor 150% 100% 80%
70%: 50Hz 50%: 60Hz
20%: 50Hz 20%: 60Hz
DC braking Variable operating frequency, time, and braking force
Weight kg 2.2 2.8 2.8 5.5 5.7
lb 4.85 6.17 6.17 12.13 12.57
SJ100 Inverter Specifications
Item 400V Class Specifications
SJ100 inverters, 400V models
Applicable motor size *2 kW 0.4 0.75 1.5 2.2
Rated capacity (460V) kVA 1.1 1.9 2.9 4.2
Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A) 2.0 3.3 5.0 7.0
Rated output voltage *3 3-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A) 1.5 2.5 3.8 5.5
Efficiency at 100% rated output (%) 92.0 93.7 95.7 95.8
Watt loss, approximate (W)
Starting torque *6 200% or more
Dynamic braking approx. % torque, short time stop *7
DC braking Variable operating frequency, time, and braking force
CE version 004HFE 007HFE 015HFE 022HFE
UL version 004HFU 007HFU 015HFU 022HFU
HP 1/2 1 2 3
at 70% output 25 33 48 68
at 100% output 32 44 65 92
without resistor, from 50/60 Hz
with resistor 150% 100%
100%: 50Hz
50%: 60Hz
70%: 50Hz 20%: 60Hz
Weight kg 1.3 1.7 1.7 1.8
lb 2.87 3.75 3.75 3.97