Hitachi SJ100 Specifications

SJ100 Inverter
SJ100 Inverter Specifications
Model-specific tables for 200V and 400V class inverters
The following tables are specific to SJ100 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page 1–9 apply to both voltage class groups. Footnotes for all specifications tables follow the table below.
Item 200V Class Specifications
SJ100 inverters, 200V models
Applicable motor size *2 kW 0.2 0.4 0.55 0.75 1.1
Rated capacity (kVA) *12
Rated input voltage 1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input current (A)
Rated output voltage *3 3-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A) 1.6 2.6 3.0 4.0 5.0
Efficiency at 100% rated output (%) 90.5 92.8 93.6 94.1 95.4
Watt loss, approximate (W)
Starting torque *6 200% or more
Dynamic braking approx. % torque, short time stop *7
CE version 002NFE 004NFE 005NFE 007NFE 011NFE
UL version 002NFU 004NFU 007NFU
HP 1/4 1/2 3/4 1 1.5
230V 0.6 1.0 1.1 1.5 1.9
240V 0.6 1.0 1.2 1.6 2.0
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, and 075LFU 3phase only)
1-phase 3.5 5.8 6.7 9.0 11.2
3-phase 2.0 3.4 3.9 5.2 6.5
at 70% output 15 21 25 31 38
at 100% output 19 29 32 41 51
without resistor, from 50 / 60 Hz
with resistor 150%
100%: 50Hz
50%: 60Hz
70%: 50Hz 50%: 60Hz
DC braking Variable operating frequency, time, and braking force
Weight kg 0.7 0.85 0.85 1.3 1.3
lb 1.54 1.87 1.87 2.87 2.87
SJ100 Inverter Specifications
Footnotes for the preceding table and the tables that follow:
Note 1: The protection method conforms to JEM 1030. Note 2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole). When
using other motors, care must be taken to prevent the rated motor current (50/ 60 Hz) from exceeding the rated output current of the inverter.
Note 3: The output voltage decreases as the main supply voltage decreases (except
when using the AVR function). In any case, the output voltage cannot exceed the input power supply voltage.
Note 4: To operate the motor beyond 50/60 Hz, consult the motor manufacturer for
the maximum allowable rotation speed.
Note 5: When SLV is selected, please set the carrier frequency higher than 2.1 kHz. Note 6: At the rated voltage when using a Hitachi standard 3-phase, 4-pole motor
(when selecting sensorless vector control—SLV).
Note 7: The braking torque via capacitive feedback is the average deceleration torque
at the shortest deceleration (stopping from 50/60 Hz as indicated). It is not continuous regenerative braking torque. The average deceleration torque varies with motor loss. This value decreases when operating beyond 50 Hz. If a large regenerative torque is required, the optional regenerative braking resistor should be used.
Note 8: The frequency command is the maximum frequency at 9.8V for input voltage
0 to 10 VDC, or at 19.6 mA for input current 4 to 20 mA. If this characteristic is not satisfactory for your application, contact your Hitachi sales representa­tive.
Note 9: If operating the inverter at 40 to 50° C, reduce the carrier frequency to 2.1
kHz, derate the output current by 80%, and remove the top housing cover. Note that removing the top cover will nullify the NEMA rating for the inverter housing.
Note 10: The storage temperature refers to the short-term temperature during transport. Note 11: Conforms to the test method specified in JIS C0911 (1984). For the model
types excluded in the standard specifications, contact your Hitachi sales repre­sentative.
Note 12: The input voltage of xxLFU is 230V.
SJ100 Inverter Specifications, continued...
Item 200V Class Specifications, continued
SJ100 Inverter
SJ100 inverters, 200V models
Applicable motor size *2 kW 1.5 2.2 3.7 5.5 7.5
Rated capacity (kVA) *12
Rated input voltage 1-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
Rated input current (A)
Rated output voltage *3 3-phase: 200 to 240V (corresponding to input voltage)
Rated output current (A) 8.0 11.0 17.5 24 32
Efficiency at 100% rated output (%) 94.7 95.1 95.1 96.1 96.2
Watt loss, approximate (W)
Starting torque *6 200% or more 180% or more
Dynamic braking approx. % torque, short time stop *7
CE version 015NFE 022NFE
UL version 015NFU 022NFU 037LFU 055LFU 075LFU
HP 2 3 5 7.5 10
230V 3.1 4.3 6.9 9.5 12.7
240V 3.0 4.5 7.2 9.9 13.3
3-phase: 200 to 240V +5/-10%, 50/60 Hz ±5%,
(037LFU, 055LFU, 075LFU 3-phase only)
1-phase 17.5 24.0
3-phase 10.0 14.0 22.0 30.0 40.0
at 70% output 57 78 130 152 204
at 100% output 79 107 181 216 288
without resistor, from 50 / 60 Hz
with resistor 150% 100% 80%
70%: 50Hz 50%: 60Hz
20%: 50Hz 20%: 60Hz
DC braking Variable operating frequency, time, and braking force
Weight kg 2.2 2.8 2.8 5.5 5.7
lb 4.85 6.17 6.17 12.13 12.57
SJ100 Inverter Specifications
Item 400V Class Specifications
SJ100 inverters, 400V models
Applicable motor size *2 kW 0.4 0.75 1.5 2.2
Rated capacity (460V) kVA 1.1 1.9 2.9 4.2
Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A) 2.0 3.3 5.0 7.0
Rated output voltage *3 3-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A) 1.5 2.5 3.8 5.5
Efficiency at 100% rated output (%) 92.0 93.7 95.7 95.8
Watt loss, approximate (W)
Starting torque *6 200% or more
Dynamic braking approx. % torque, short time stop *7
DC braking Variable operating frequency, time, and braking force
CE version 004HFE 007HFE 015HFE 022HFE
UL version 004HFU 007HFU 015HFU 022HFU
HP 1/2 1 2 3
at 70% output 25 33 48 68
at 100% output 32 44 65 92
without resistor, from 50/60 Hz
with resistor 150% 100%
100%: 50Hz
50%: 60Hz
70%: 50Hz 20%: 60Hz
Weight kg 1.3 1.7 1.7 1.8
lb 2.87 3.75 3.75 3.97
SJ100 Inverter
Item 400V Class Specifications, continued
SJ100 inverters, 400V models
Applicable motor size *2 kW 3.0 4.0 5.5 7.5
Rated capacity (460V) kVA 6.2 6.6 10.3 12.7
Rated input voltage 3-phase: 380 to 460V ±10%, 50/60 Hz ±5%
Rated input current (A) 10.0 11.0 16.5 20.0
Rated output voltage *3 3-phase: 380 to 460V (corresponding to input voltage)
Rated output current (A) 7.8 8.6 13 16
Efficiency at 100% rated output (%) 95.4 96.2 96.0 96.5
Watt loss, approximate (W)
Starting torque *6 180% or more
Dynamic braking approx. % torque, short time stop *7
DC braking Variable operating frequency, time, and braking force
CE version 030HFE 040HFE 055HFE 075HFE
UL version 040HFU 055HFU 075HFU
HP 4 5 7.5 10
at 70% output 100 108 156 186
at 100% output 138 151 219 261
without resistor, from 50/60 Hz
with resistor 100% 80%
20%: 50Hz 20%: 60Hz
Weight kg 2.8 2.8 5.5 5.7
lb 6.17 6.17 12.13 12.57
General Specifications
The following table applies to all SJ100 inverters.
Item General Specifications
Protective housing *1 IP20
Control method Sine wave pulse-width modulation (PWM) control
Output frequency range *4 0.5 to 360 Hz
Frequency accuracy Digital command: 0.01% of the maximum frequency
Analog command: 0.1% of the maximum frequency (25°C ± 10°C)
Frequency setting resolution Digital: 0.1 Hz; Analog: max. frequency/1000
Volt./Freq. characteristic *5 V/f optionally variable, V/f control (constant torque, reduced
torque), sensorless vector control
Overload current rating 150%, 60 seconds
Acceleration/deceleration time 0.1 to 3000 sec., (linear accel/decel), second accel/decel setting
available
SJ100 Inverter Specifications
Item General Specifications
Input signal
Freq. setting
Operator panel Up and Down keys / Value settings
Potentiometer Analog setting
External signal *80 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input
impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W)
FWD/ REV Run
Intelligent input terminal
Operator panel Run/Stop (Forward/Reverse run change by command)
External signal Forward run/stop, Reverse run/stop
FW (forward run command), RV (reverse run command), CF1~CF4 (multi-stage speed setting), JG (jog command), 2CH (2-stage accel./ decel. command), FRS (free run stop command), EXT (external trip), USP (startup function), SFT (soft lock), AT (analog current input select signal), RS (reset), PTC (thermal protection), DB (exter­nal DC braking command), SET (2nd setting selection), UP (remote control, accel.), DWN (remote control, decel.)
Output signal
Intelligent output terminal
RUN (run status signal), FA1,2 (frequency arrival signal), OL (overload advance notice signal), OD (PID error deviation signal), AL (alarm signal)
Frequency monitor PWM output; Select analog output frequency monitor, analog output
current monitor or digital output frequency monitor
Alarm output contact ON for inverter alarm (1C contacts, both normally open or closed
avail.)
Other functions AVR function, curved accel/decel profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency, carrier frequency change (0.5 to 16 kHz) frequency jump, gain and bias setting, process jogging, electronic thermal level adjustment, retry function, trip history monitor, 2nd setting selection, auto tuning, fan ON/OFF selection
Protective function Over-current, over-voltage, under-voltage, overload, extreme high/
low temperature, CPU error, memory error, ground fault detection at startup, internal communication error, electronic thermal, CT error
Operat­ing Environ ment
Temperature Operating (ambient): -10 to 50°C (*9) / Storage: -25 to 70°C (*10)
Humidity 20 to 90% humidity (non-condensing)
Vibration *11
5.9 m/s
2
(0.6G), 10 to 55 Hz
Location Altitude 1,000 m or less, indoors (no corrosive gasses or dust)
Coating color Munsell 8.5YR6.2/0/2, cooling fins in base color of aluminum
Options Remote operator unit, copy unit, cables for the units, braking unit,
braking resistor, AC reactor, DC reactor, noise filter, DIN rail mounting
Derating Curves
The maximum available inverter current output is limited by the carrier frequency and ambient temperature. The carrier frequency is the inverter’s internal power switching frequency, settable from 0.5 kHz to 16 kHz. Choosing a higher carrier frequency tends to decrease audible noise, but it also increases the internal heating of the inverter, thus decreasing (derating) the maximum current output capability. Ambient temperature is the temperature just outside the inverter housing—such as inside the control cabinet where the inverter is mounted. A higher ambient temperature decreases (derates) the inverter’s maximum current output capacity.
Use the following derating curves to help determine the optimal carrier frequency setting for your inverter, and to find the output current derating. Be sure to use the proper curve for your particular SJ100 inverter model number.
Legend:
SJ100–002NFE/NFU
SJ100 Inverter
Standard ratings at 40°C
Ratings at 50°C max. with top cover removed
Ratings at 55°C max. with top cover removed
100%
% of rated
output current
SJ100–004NFE/NFU
100%
% of rated
output current
95%
90%
85%
80%
75%
70%
0.5246810121416
Carrier frequency
95%
90%
85%
kHz
80%
75%
70%
0.5246810121416
Carrier frequency
kHz
SJ100 Inverter Specifications
Derating curves, continued...
SJ100–007NFE/NFU
100%
95%
90%
% of rated
output current
SJ100–0015NFE/NFU
% of rated
output current
85%
80%
75%
70%
100%
95%
90%
85%
80%
75%
kHz
0.5246810121416
Carrier frequency
70%
SJ100–022NFE/NFU
100%
95%
90%
% of rated
output current
85%
80%
75%
70%
kHz
0.5246810121416
Carrier frequency
kHz
0.5246810121416
Carrier frequency
Derating curves, continued...
SJ100–037LF/LFU
100%
90%
80%
SJ100 Inverter
% of rated
output current
SJ100–055LFU
% of rated
output current
70%
60%
50%
40%
0.5246810121416
Carrier frequency
100%
95%
90%
85%
80%
75%
kHz
SJ100–075LFU
% of rated
output current
70%
0.5246810121416
Carrier frequency
100%
95%
90%
85%
80%
75%
70%
0.5246810121416
Carrier frequency
kHz
kHz
SJ100 Inverter Specifications
Derating curves, continued...
SJ100–004HFE/HFU
100%
90%
80%
% of rated
output current
SJ100–007HFE/HFU
% of rated
output current
70%
60%
50%
40%
100%
90%
80%
70%
60%
50%
kHz
0.5246810121416
Carrier frequency
40%
SJ100–015HFE/HFU
100%
90%
80%
% of rated
output current
70%
60%
50%
40%
kHz
0.5246810121416
Carrier frequency
kHz
0.5246810121416
Carrier frequency
Derating curves, continued...
SJ100–022HFE/HFU
100%
90%
80%
SJ100 Inverter
% of rated
output current
SJ100–040HFE/HFU
% of rated
output current
70%
60%
50%
40%
100%
90%
80%
70%
60%
50%
kHz
0.5246810121416
Carrier frequency
40%
SJ100–055HFE/HFU
100%
95%
90%
% of rated
output current
85%
80%
75%
70%
kHz
0.5246810121416
Carrier frequency
kHz
0.5246810121416
Carrier frequency
SJ100 Inverter Specifications
Derating curves, continued...
SJ100–075HFE/HFU
100%
95%
90%
% of rated
output current
85%
80%
75%
70%
0.5246810121416
Carrier frequency
kHz