
SJ100 Series Supplemental Sheet (NBM585XA-12)
ATTENTION
Note 1:
The revision level of the MFG No. distinguishes the following changes in Function Codes A81, C31
and C32
side of the housing. The changes apply to inverters, which carry a revision code per the table below.
When you copy parameters between units manufactured before and after this change with a copy unit,
confirm Function Codes C31 and C32.
Example of MFG No. :
112H
Revision
A…K…1A…1K…2A…2H…
Revision Increment--------
. The Inverter MGF No. is shown on the Specification Label (Nameplate), located on the right
T123451J001
Æ
Inverter Models
SJ100-002NFU 2E 2H
SJ100-004-022NFU 2G 2H
SJ100-037LFU 2E 2H
SJ100-055,075LFU K M
SJ100-004HFU 2F 2H
SJ100-007-040HFU 2G 2H
SJ100-055,075HFU L M
Revision
before change
Applied
Revision
Page
3-18
Changes
OLD DEFAULT SETTING:
“A” Function
Func.
Code
Name Description
A81 AVR function
select
Automatic (output) voltage
regulation, selects from three
Run-
time
Edit
Defaults DOP,DRW,DOP+
EU/
US
02
Units
Func.
Code
- F-03 AVR
types of AVR functions, three
option codes:
00…AVR enabled
01…AVR disabled
02…AVR enabled except
during deceleration
NEW DEFAULT SETTING:
*Inverters manufactured after the revision as defined in Note 1 will have the following settings:
Func.
Code
Name Description
A81 AVR function
select
“A” Function
Automatic (output) voltage
regulation, selects from three
Run-
time
Edit
Defaults DOP,DRW,DOP+
EU/
US
00
Units
Func.
Code
- F-03 AVR
types of AVR functions, three
option codes:
00…AVR enabled
01…AVR disabled
02…AVR enabled except
during deceleration
Name
MODE
Name
MODE
1/2
NBM585XA-12

Page
3-32
Changes
OLD DEFAULT SETTING:
“C” Function
Func.
Code
C31 Reserved Factory use only; do not
Name Description
change
Run-
time
Edit
Defaults DOP,DRW,DOP+
EU/
US
00
Units
Func.
Code
- F-35 OUT-TM
Name
O/C-1
C32 Terminal 11
active state
NEW DEFAULT SETTING:
*Inverters manufactured after the revision as defined in Note 1 will have the following settings:
“C” Function
Func.
Code
C31 Terminal 11
C32 Terminal 12
Name Description
active state
active state
Select logic convention, two
option codes:
00…normally open [NO]
01…normally closed [NC]
Select logic convention, two
option codes:
00…normally open [NO]
01…normally closed [NC]
Select logic convention, two
option codes:
00…normally open [NO]
01…normally closed [NC]
Run-
time
Edit
00
Defaults DOP,DRW,DOP+
EU/
US
00
00
- F-35 OUT-TM
O/C-2
Units
Func.
Code
- F-35 OUT-TM
O/C-1
- F-35 OUT-TM
O/C-2
Name
B-7
OLD DEFAULT SETTING:
“C” Group Parameters Default Setting User Setting
Func. Code Name -FE(Europe) -FU(USA)
C31 Factory-set - -
C32 Terminal 11 active state 00 00
NEW DEFAULT SETTING:
*Inverters manufactured after the revision as defined in Note 1 will have the following settings:
“C” Group Parameters Default Setting User Setting
Func. Code Name -FE(Europe) -FU(USA)
C31 Terminal 11 active state 00 00
C32 Terminal 12 active state 00 00
2/2
NBM585XA-12