MODEL : R-Z570ERU9 (SLS) ……………………………………..
HITACHI
SERVICE MANUAL
PT
NO. 2104E
R-Z570ERU9 (SLS)
TABLE
PARTS LIST
1
2
2
3
4
5
6
7-9
10-13
SPECIFICATIONS
TYPEDOUBLE DOOR
MODEL
POWER SOURCE 1Ø,220-240V,50Hz
POWER INPUT ( W )
TOTAL CURRENT ( A )
NET475L
VOLUME
GROSS531L
W740
DIMENSIONS
(mm)
NET WEIGHT ( Kgs )81
D736
H1795
R-Z570ERU9
106
0.6
R-Z570ERU9 (SLS)
NO. 2104E
REFRIGERATOR
JAN '11
H.C.P.T.
![](/html/48/480f/480f787c3a965db16e79ce71afe602c026333789b332c35fee5239f776e606a4/bg2.png)
In order to disassemble and repair the
unit in question, be sure to disconnect
the power cord plug from the power
outlet before starting the work.
If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and the
replacement must be effected in correct manner according to the instructions in the Service Manual of the unit.
After completion of repairs, the initial state should be restored.
Lead wires should be connected and laid as in the initial state.
Modification of the unit by the user himself should absolutely be
Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
In installing the unit having been repaired, be careful to prevent the occurrence of any accident such as electrical
shock, leak of current, or bodily injury due to the drop of any part.
To check the insulation of the unit, measure the insulation resistance between the power cord plug and grounding
The insulation resistance should be
MΩ or more as measured by a
.9.The initial location of installation such as window, floor or the other should be checked for being safe enough to
support the repaired unit again.
If it is found not so strong and safe, the unit should be installed at the initial location after reinforced or at a new location.
Any inflammable object must not be placed
about the location of installation.
Check the grounding to see whether it is proper
or not, and if it is found improper, connect the
grounding terminal to the earth.
SAFETY DURING REPAIR WORK
If the contacts of electrical parts are
without trying to repair them.
defective, replace the electrical parts
First, I must disconnect
the power cord plug
1
![](/html/48/480f/480f787c3a965db16e79ce71afe602c026333789b332c35fee5239f776e606a4/bg3.png)
SPECIFICATION
MODEL
COMPRESSORPTR-Z660EMX 018 (FL15S68NAD)
STARTING DEVICEPTR-Z481EMS 003 (PGN6SBT)
OVERLOAD RELAYPTR-Z481EMS 002 (P1.6C37A1)
RUNNING CAPACITORPTR-480ET5 005 (AC400V-4UF)
UP HINGE SENSORPTR-Z400V 050
REFRIGERATOR SENSORR (0°C) = 6.35 k Ω ± 2 %
REFRIGERATOR CHARGING R-134a (kg)0.155 kg
TEMPERATURE FRESH FOODELECTRONIC CONTROL
CONTROL FREEZERELECTRONIC CONTROL
DEFROSTING WAYHEATER
DEFROSTING INITIATIONF:AUTOMATIC , R:AUTOMATIC
SYSTEM TERMINATIONF:AUTOMATIC , R:AUTOMATIC
PTR-Z610EMX 027
R-Z570ERU9
R (21°C) = 12 k Ω ± 3 %
R (25°C) = 10 k Ω ± 2 %
FREEZER * * * *
MAIN PARTS COMPONENTS
COMPRESSOR
PHASE
RATE VOLTAGE ( V )
RATE FREQUENCY ( Hz )
POLE NUMBER
CONNECTION
EVAPORATIONFORCED
YES
PTR-Z660EMX 018 (FL15S68NAD)
SINGLE PHASE
220-240V
50Hz
2
MS
MAIN COIL
C
STARTING COIL
M - C = 16.5 Ω
RESISTANCE VALUE 75°C
S - C = 23.9 Ω
STARTING CURRENT (A)7.91 A
2
![](/html/48/480f/480f787c3a965db16e79ce71afe602c026333789b332c35fee5239f776e606a4/bg4.png)
●Power
Basic operation(time chart) of 508L-550L REF.
supply
●F-Room
Temp.
●Comp.
●R-Fan
3
●R-Room
Temp.
●Damper
●Evaporator
Temp.
●Defrost
heater
●R-Door
●R-Lamp
(R-Door sw)
On
-8℃
High temp.(-16℃)
Low temp.(-22℃)
25s
On
On
High temp.(4℃)
Low temp.(2℃)
Open
8.5℃
On
Open
On
~~~~~~~~~
F-sensor
Off-time
10min
t1t2t3t4
30s30s
R-sensor
~~
Off-time
10min
Comp. On-time:
t1+t2+t3+t4+…≧12h
Pre-Cool
D-sensor
Pre-Cool time≦30min
Off-time
10min
Defrosting
ConditionComp.
Off-timeOff
DefrostingOff
On
F-sensor≦Low temp.Off
ConditionR-Fan
R-Door openOff
Comp. onOn
Comp. offOff
ConditionDamper
Comp. offClose
R-sensor≧High temp.Open
R-sensor≦Low temp.Close
High
Priority
High
Priority
High
Priority
![](/html/48/480f/480f787c3a965db16e79ce71afe602c026333789b332c35fee5239f776e606a4/bg5.png)
TC-sensorF-sensorR-sensorD-sensor
Temp.ResistanceTemp.ResistanceTemp.ResistanceTemp.Resistance
(℃)(Ω)(
~~~~~~~~
-57241.87k-2019.23k-58271.14k-20105.38k
~~~~~~~~
-2525.58k-1514.26k-2019.17k-1582.03k
-2018.9k-1010.78k-1010.83k-1060.86k
-1514.13k-58.23k-58.27k-545.67k
-1010.68k06.35k06.38k034.62k
)(Ω)(
℃
℃
)(Ω)(
)(Ω)
℃
Abnormal
range
Display
Error code
4
-58.15k54.94k54.97k526.52k
06.29k103.88k103.90k1020.50k
54.90k153.08k153.09k1515.99k
103.85k202.46k202.47k2012.00k
153.05k251.98k251.98k259.97k
202.43k301.60k301.61k307.97k
251.96k351.31k401.08k356.42k
Normal
range
301.59k401.07k500.74k405.20k
~~~~~~~~
610.51k600.51k610.50k622.32k
~~~~~~~~
Abnormal
range
Display
Error code