Hitachi RPIH-6.0UNE1NH, RPIL-1.5UNE1NH, RPIM-3.0UNE1NH, RPIH-6.5UNE1NH, PPIL-1.0TNE1NH Service Manual

...
Page 1
SERVICE MANUAL
HPS2017004HA
Page 2
Models
Ducted
Cassette
Floor ceiling
< Indoor Units >
RPIL-1.0UNE1NH RPIL-1.5UNE1NH RPIL-2.0UNE1NH RPIM-3.0UNE1NH RPIH-4.0UNE1NH RPIH-5.0UNE1NH RP
IH-6.0UNE1NH
RPIH-6.5UNE1NH
Heat pump type
RPIL-1.0TNE1NH RPIL-1.5TNE1NH RPIL-2.0TNE1NH RPIM-3.0TNE1NH RPIH-4.0TNE1NH RPIH-5.0TNE1NH RP
IH-6.0TNE1NH
RPIH-6.5TNE1NH
Cooling only type
RCI-1.5UNE1NH RCI-2.0UNE1NH RCI-3.0UNE1NH RCI-4.0UNE1NH RCI-5.0UNE1NH RCI-6.0UNE1NH RCI-6.5UNE1NH
Heat pump type
RCI-1.5TNE1NH RCI-2.0TNE1NH RCI-3.0TNE1NH RCI-4.0TNE1NH RCI-5.0TNE1NH RCI-6.0TNE1NH RCI-6.5TNE1NH
Cooling only type
RCI-1.5UNE1NH RCI-2.0UNE1NH RCI-3.0UNE1NH RCI-4.0UNE1NH RCI-5.0UNE1NH RCI-6.0UNE1NH RCI-6.5UNE1NH
Heat pump type
RCI-1.5TNE1NH RCI-2.0TNE1NH RCI-3.0TNE1NH RCI-4.0TNE1NH RCI-5.0TNE1NH RCI-6.0TNE1NH RCI-6.5TNE1NH
Cooling only type
RAS-1.0UNESNH1 RAS-1.5UNESNH1 RAS-2.0UNESNH1 RAS-3.0UNESNH1 RAS-4.0UNESNH1 RAS-5.0UNESMH1 RAS-6.0UNESMH1 RAS-6.5UNESMH1
Heat pump type
RAS-1.0TNESNH1 RAS-1.5TNESNH1 RAS-2.0TNESNH1 RAS-3.0TNESNH1 RAS-4.0TNESNH1 RAS-5.0TNESMH1 RAS-6.0TNESMH1 RAS-6.5TNESMH1
Cooling type
NOTE:
Heating and electric heating function are not available for cooling only models.
Page 3
DC-Inverter Air Conditioner Service Manual
Table of Contents
1. Option list ..................................................................................................................... 1
1.1Wired Remote Controller ......................................................................................... 1
1.2 Wireless Remote Controller .................................................................................. 10
1.3 IR receiver ............................................................................................................ 15
2.Troubleshooting .............................................................................................................. 16
2.1Trouble guide
........................................................................................................... 16
2.2 Fault codes
............................................................................................................. 21
3.
Checking components ................................................................................................... 31
3.1 Check refrigerant system ...................................................................................... 31
3.2 Check parts unit ................................................................................................... 33
4.
Disassembly and assembly for compressor and motor..................................................... 41
5.
Control logic description................................................................................................. 52
Page 4
11..OOPPTTIIO
O
N
N
LLIISST
T
1. Wired Rmote Controller(ModelHCWA21NEWH)
1.1 Wired remote controller installation
in the grips,
1
Page 5
11..OOPPTTIIOONN LLIISST
T
Custom
Custom
Custom
Temperature measurement unit
Celsius
to access
custom
custom
be displayed
up
custom settings mode
The method of setting the custom parameters:
2
Page 6
11..OOPPTTIIOONN LLIISST
T
enabled
revised
set point
all values will
be flicking at the display, press
all values will be flicking at the display, press.
settings.
remote located at an area with
different temperature than the room
so
correction
start
an offset
3
Page 7
11..OOPPTTIIOONN LLIISST
T
all values will be flicking at the display, press.
Upper cover assembly
the
screen of
1.2Wired
pressing
UP
DOWN
setting values or to set the airflow direction.
setting value.
4
Page 8
11..OOPPTTIIOONN LLIISST
T
operation
swing
swing
revision
setting setting setting
once for
available for specific
for
the
Custom-setting parameters b must be configured by installer or autorized person.
Basic operation
5
Page 9
11..OOPPTTIIOONN LLIISST
T
increases decreases
staff
reaches
increase
decrease
During the appliance in working mode
unabling
is the default setting
swing
swing swing
swing
Function set
Super mode
activated at
activate
with the working unit to activate the
Super mode
Silent mode
silent mode
operation
activate
during appliance operation
activate silent mode
6
Page 10
11..OOPPTTIIOONN LLIISST
T
With
improve comfort.
activate
be displayed
activated.
will disappear
lock buttons users setting overwrite.
disabled
activate
activate
be displayed
;
staff
staff
is displayed
perform
warning prompt.
available
actual
set.
enter
7
Page 11
11..OOPPTTIIOONN LLIISST
T
Single Timer ON/OFF
activate
During
are
setting.
timer
timer
timer
value.
Holding
will appear
appears,
with the same procedure.
Single Timer ON/OFF
timer
cancellation
Single Timer ON/OFF
Single Timer ON/OFF
Single Timer ON/OFF setting
settingSingle Timer ON/OFF
Single Timer ON/OFF
Single Timer ON/OFF
cancellation
cancellation
Daily ON/OFF Timer
Single Timer ON/OFF
The Single, Daily and Weekly timer functions can not be set at the same time, if need TIMER ON/OFF work in the future time, please use WEEKLY TIMER function.
Note:
8
Page 12
11..OOPPTTIIOONN LLIISST
T
set
setting
is displayed
SETTING
SELECTION
SELECTION
setting,
is displayed
are flickering.
selection.
setting.
selection
setting
setting
setting
setting
selected or
hour setting,
to cancel
setting.
setting.
setting.
setting is done with the same procedure as
need to.
setting,
selected
9
Page 13
11..OOPPTTIIOONN LLIISST
T
Remote controller
POWERFUL
Used to start or stop the fast cooling/heating. (Fast cooling operates at high fan speed with 16 set temp. automatically; Fast heating operates at auto fan speed with 30set temp. automatically).
3
ON/OFF
The appliance will be started when it is energized or will be stopped when it is in operation, if you press this button.
4
The remote controller transmits signals to the system.
MODE
Press this button to select the operation mode.
1
AUTO
Used to enter fuzzy logic operation directly.
5
TIMER
Used to set or cancel the timer operation.
7
FAN
Used to select fan speed in sequence auto, quiet low, low, medium and high.
6
SLEEP
Used to set or cancel Sleep Mode operation.
9
Used to stop or start vertical adjustment louver swinging and set the desired left/right airflow direction.
10 LEFT/RIGHT
adjustment louver swinging and set the desired up/ down airflow direction.
Used to stop or start horizontal
8 UP/DOWN
Used to adjust the room temperature and the timer.
2
TEMP.
1
4
2
2
3
7
6
10
8
9
Note: Each mode and relevant function will be further specified in following pages.
Heating and electric heating function are not available in single cooling only models.Pictures in the manual are for reference only, specifications are subject to the physical product.
Indication symbols on LCD:
Cooling indicator
Dry indicator
Fan only indicator
Heating indicator
Auto indicator
High fan speed
Medium fan speed
Low fan speed
Quiet fan speed
Display set temperature
Timer ON/OFF set hour
Signal transmit Battery indicator Timer ON indicator Timer OFF indicator
Button locked indicator
Auto fan speed Run indicator
Sleep indicator
Display set temp.indicator
Fan speed indicator
OFF indicator
5
11
RESET
Back to the factory defaults.
11
2. Wireless Rmote Controller (ModelHCRA31NEWH)
10
Page 14
11..OOPPTTIIOONN LLIISST
T
How to Use
To operate the room air conditioner, aim the remote controller to the signal receptor. The remote controller will operate the air conditioner at a distance of up to 8m when pointing at signal receptor of indoor unit.
Remote controller
How to Insert the Batteries
Remove the battery cover according to the arrow direction.
Insert new batteries making sure that the (+) and (-) of battery are matched correctly.
Reattach the cover by sliding it back into position.
Note:
Use 2 LR03 AAA(1.5volt) batteries. Do not use rechargeable batteries. Replace batteries with new ones of the same type when the display becomes dim.
If the batteries are not in use for a prolonged period of time, remove the batteries from the battery compartment to avoid the trouble. The battery can be used for about 6 months. If the Remote Control is not operated even when placing it near the receiver, replace 2 batteries with the new ones. Please do not use manganese battery because it may cause mal-function. Avoid extremely hot or cold locations such as placing it near or over a radiator, or in direct sunlight. Also avoid placing under fluorescent light. Do not let children play with the Remote Controller. To avoid interference, the indoor unit and the Remote Control unit should be at least 1m away from a TV set or a radio. In case more than two air conditioners are installed in the same room, it may interrupt individual operation.
CAUTION
Storage and Tips for Using the Remote Controller
The remote controller may be stored mounted on a wall with a holder.
Note: The remote controller holder is an optional part.
remote controller holder fixing.
remote controller mounting.
Note: you have selected.
The shape may differ from that of the remote controller holder
11
Page 15
11..OOPPTTIIOONN LLIISST
T
The operation modes changed in sequence:
The fan speed is changed in sequence:
FAN mode
Heating mode is NOT available for cooling only air conditioner.
At "FAN" mode, only "Auto" is not available. At "DRY" mode, Fan speed is set at "AUTO” automatically, "FAN" button is ineffective in this case.
Setting temperature
Turning on or off
AUTO , POWERFUL , TIMER and SLEEP operation modes will be specified in the following pages.
Changing modes during operation, sometimes the unit does not response at once. Wait 3 minutes.
Wait 3 minutes before restarting the appliance.
During heating operation, air flow is not discharged at the beginning. After 25 minutes, the air flow will be discharged until temperature of indoor heat exchanger rises.
16~30
Range of available set temperature
*HEATING, COOLING, DRY
unable to set
FAN
Note: Heating mode is NOT available for cooling only models.*
Press
Press button can change the unit operating status.
Result :
Result :
Press button once by once
Press button once by once
Auto
High
Medium
FAN
COOL
DRY
HEAT
button
Raise temperature setting by 1℃.
Lower temperature setting by 1.
button Press
Result :
Result :
Low
Quiet Low
PRESS
PRESS
Operation modes
Selecting mode
Press MODE button cancel AUTO mode.
Note: Temperature, airflow and direction are controlled automatically in AUTO mode.
AUTO mode
How to s et AUTO mode ?
Press the AUTO button.
Resu lt : Enters AUTO mode (fuzzy logic operation).
Mode and fan speed are automatically set based on the actual room temperature.
PRE SS
12
Page 16
11..OOPPTTIIOONN LLIISST
T
Your feeling
What you can do in AUTO mode?
Button
Adjust
Uncomfortable because of unsuitable air flow volume.
Uncomfortable because of unsuitable flow direction.
How to cancel the AUTO mode?
Press the
Resu lt :
Indoor fan speed alternates among Auto, Low,Medium and High each time this button is pressed.
Press it once, the horizontal adjustment louver(vertical adjustment louver) swings to change vertical airflow direction(horizontal airflow direction). Press it again, swings stops.
button.
The AUTO mode will be cancelled.
P
PRREESSSS
Note:
POWERFUL button is not available in AUTO mode.
POWERFUL mode
POWERFUL mode is used to start or stop fast cooling or heating only when the unit is on.
How to set POWERFUL mode?
Press POWERFUL button at the cool, dry and fan mode.
Resu lt :
At hig h fa n sp ee d, the set temp er at ure auto ma ti ca lly to 16.
Press POWERFUL button at the heat mode.
Resu lt :
At hig h fa n sp eed, the set temp er at ure auto ma ti ca lly to 30.
How to cancel POWERFUL mode?
Press POWERFUL, MODE, FAN, ON/OFF button.
Resu lt :
The display return to the original mode.
In POWERFUL mode, you can set temperature, airflow direction or timer.
Escape from POWERFUL mode.
PRE SS
PRE SS
Timer mode
It is convenient to set the timer on with TIMER button when you go out in the morning to achieve a comfortable room temperature at the time you get home. You can also set timer off at night to enjoy a good sleep.
13
Page 17
11..OOPPTTIIOONN LLIISST
T
How to canc el SLEE P mode ?
Press AUTO, MODE, SLEEP, ON/OFF or FAN button.
Result :
Escape from SLEEP mode.
PRESS
Note: It is similar to set TIMER OFF , you can make the appliance switch off automatically at your desired time.
Press the or button.
Once to increase or decrease the time setting by 1 hour.
Resu lt :
and stop flashing.
When your desired time displayed on LCD, press the TIMER button and confirm it.
Resu lt :
Press TIMER button when the unit is off.
How to cancel TIMER ON ?
Press the TIMER button.
Resu lt :
The indicator disappears, the timer on mode has been canceled.
How to set TIMER ON ?
Resu lt :
and flash on the LCD.
1.
2.
3.
PRESS
PRESS
PRESS
PRESS
SLEEP mode can be set in COOLING, HEATING or DRYING mode.
This function gives you a more comfortable environment for sleep.
The appliance will stop operation automatically after operating for 8 hours. Fan speed is automatically set at low speed.
SLEEP mode
How to s et SLEE P mode ?
Each time SLEEP button is pressed.
Resu lt :
SLEEP function will be started.
PRESS
14
Page 18
11..OOPPTTIIOONN LLIISST
T
3.
IR Receiver (ModelHRBA31NEGH)
1
2
1
7
2
3
5
4
6
Please carefully read the Installation Manual supplied with the signal receiver, and perform installation in accordance with these instructions properly.
Important Notice
Parts Introduction
Install the receiver onto the wall or ceiling near the indoor unit. Connect it with the indoor unit by the connect wire.It should be used with the wireless remote controller. The wireless remote controller can send commands to the wireless receiver .Name of part is shown as follows:
2.Installation.
Indoor Unit PCB
The connection of the connecting wire
Along the arrow direction into the ceiling that with a hole punched
The Installation of the Receiver
After the Installation is completed
Cut out a hole at the suitable place of the false ceiling with a
diameter of 95mm.
Place
the connecting wire on the false ceiling.
Incert the connecting wire into the indoor unit .
Connect the wires
with the indoor PCB.
Connect the other terminal with the receiver, details please see
the indoor unit wiring diagram.
Adjust the spring
of the receiver and install the receiver into
the hole that have punched . After installation, the appearance as showed in the figure below.
Avoid installing it close to the fluorescent lamp.
1.Selecting the installation location.
Please install it in the ceiling and close to the electronic control box of indoor unit.
The False Ceiling
Signal Receiver
The False Ceiling
1 Run indicator (Red)
It lights on during operation. It lights off during SLEEP mode.
2 Emergency switch
The filter clean indicator when the switch is pressed. The unit will stop operation if pressing the button, if pressing for more than
5s, the unit will operate in cooling mode.
3 Timer indicator (Green)
It lights on when timer is in use. It lights off when timer finishes.
4 Filter clean (Yellow) It lights on when the filter should
be cleaned.
5 Defrost indicator (Green)
It lights on during defrosting. It lights off when defrosting is
finished.
6 Buzzer It rings when the signal from remote controller is received.
7 Infrared receiver Receives signal from the remote controller.
3
How to Install
Sending Commands from Controller The operation commands are sent by pressing the required operation switch by aiming the transmitter of the controller at the receiver of the indoor unit. When the commands are sent correctly, the buzzer on the wireless receiver goes off once. In case that the buzzer does not go off although the commands are sent, the commands are not received by the indoor unit. In such a case, sent the commands again. Sometimes the buzzer does not be heard in case of the noise. In some special cases, the indoor unit does not response to the commands of the wireless remote controller. The buzzer beeps 3 times.
4
Operation
Max. permission distance up to 8m.
Signal Receiver
Wireless Remote Controller
The figures in this manual are based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner you have selected.
It can be set or canceled by professional after-sale staff.
*
Virtual Line between Transmitter and Receiver
15
Page 19
22.
.
TTR
R
O
O
2.Trou
b
2.1Trou
b
When
remote
c
How
Indo
o
(1)Fault
(2)Faul
Lam
p
fault co
d
fig. belo
w
For
e
DEFRO
S
UUBBLLEES
S
H
H
leshooti
ble guide
the air co
ontroller
o
to check
f
r Unit
codes ind
i
t codes in
d
RUN(LE
D
e ten digi
t
).
xample
f
T contin
u
OOOOTTIIN
N
G
G
ng
nditioner f
a
r display
p
ault code
s
cated by
w
FI
G
icated by
2 ,red) a
n
number, l
a
ault code
e flash 3
t
ilure occ
u
anel.
.1 FAULT CO
LED lam
p
d Lamp
D
mp DEF
R
36: led R
U
imes,repo
r
rs, the fa
u
ired remote
controlle
DE DISPLAY
s on displ
a
EFROST
OST dis
p
N& defro
s
rts No. 36
lt code wi
l
r (see figu
ON WIRE R
E
y panel
LED5 ,g
r
lay fault c
o
t flash 3 ti
m
fault.
l displays
o
re below)
MOT CONT
R
een)flas
h
de single
es at th
e
on control
OLLER
ing,Lam
digit num
same tim
board , wi
p RUN dis
ber (as sh
e, and led
re
play
own
16
Page 20
22.
.
TTR
R
O
O
LED FA
UUBBLLEES
S
H
H
FA LSH CONTRO
OOOOTTIIN
N
G
G
OLflash 300m
mS(T1)off 3000mS(T2)after 2000mS(T3)fauult code repeat ddisplays. (as shown below)
Displlay panel
1
1
2
2
1
2
Run indicator (Red)
Indicates the fault code ten digital number.
Defrost indicator (Green)
Indicates the fault code singal digital number.
D E FR O S T
F I L TE R
T I M E
R U N
E M ER G E N C Y
2
1
2 1
T1 TT2
Fig.222 LED ALSHH CONTROL
T3
17
Page 21
22.
.
TTR
R
O
O
LED1
outdo
Whe
n
When
When
Failure
Syste
LED la
UUBBLLEES
S
H
H
indicate fau
or drive cont
n LED3 is off,
n LED3 is on,
n LED3 is flic
es display w
m protect co
amps will off
OOOOTTIIN
N
G
G
lt code ten d
trol fault .
, LED1 and L
, LED1 and L
kering and L
with 5s interva
odes display
f when there
digit number,
LED 2 indicat
LED 2 indica
LED1,LED 2
al .It means L
method is th
is no failure
LED2 indica
te main cont
te drive cont
are all off, in
LED will off 5
he same with
e ,protect or p
te fault code
trol failure co
trol failure co
dicate comp
5s to report n
main contro
preheating.
e single digit
ode.
ode.
ressor is pre
next failure c
ol failure code
number and
eheating .
code .
e .
LED3 indicaate
Fault
Outddoor Unit
DC-Innverter split
code displa
aairconditone
r 1.0/1.5/2.0/3.0
yys by LED laamps on out
Hp(Main
control boar
ddoor main coontrol board.
d upside-
doww
n)
There are 3 LED laamps on control board, LEED1,LED2 aand LED3.
18
Page 22
22.
.
TTR
R
O
O
For e
x
For e
x
(2)
Fault
UUBBLLEES
S
H
H
ample, outd
ample, outd
INVERTER
code will di
s
OOOOTTIIN
N
G
G
oor main co
n
oor drive fa
u
play on digi
t
trol fault 32
lt 32:
SPLIT AIR CONDITI
al tube boa
r
:
ONER
d.
(4.0/5.0/6.0/6.5HP)
Digital T
u
Outdoo
r
be
Control Board
19
Page 23
22.
.
TTR
R
O
O
UUBBLLEES
S
H
H
OOOOTTIIN
N
G
G
20
Page 24
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
2.2 Fault codes
The following is the fault code table of outdoor.
Sheet 1 Outdoor Fault code
Fault code
Fault Description Possible Reason of Abnormality How to Deal With Remarks
1
Outdoor ambient temperature sensor fault
1.The outdoor ambient temperature sensor connect loose;
2.The outdoor ambient temperature sensor is failure;
3.The sampling circuit is failure
1.Reconnect the outdoor ambient temperature sensor;
2.Replace the outdoor ambient temperature sensor omponents;
3.Replace the outdoor control board components.
2
Outdoor coil temperature sensor fault
1.The outdoor coil temperature sensor connect loose;
2.The outdoor coil temperature sensor is failure;
3.The sampling circuit is failure
1.Reconnect the outdoor coil temperature sensor;
2.Replace the outdoor coil temperature sensor components;
3.Replace the outdoor control board components.
3
The unit over-current turn off fault
1.Control board current sampling circuit is failure;
2.The current is over high because of the
supply voltage is too low;
3.The compressor is blocked;
4. Overload in cooling mode;
5.Overload in heating mode.
1. Replace the electrical control board components;
2. Normally protection;
3. Replace the compressor;
4. Please see the Note 3;
5. Please see the Note 4.
4 EEprom Data error
1.EE components is failure; 2.EE components control circuit failure;
3.EE components insert incorrect
1.Replace the EE components;
2.Replace the outdoor control board components;
3.Reassembly the EE components.
5
Cooling freezing protection(the indoor coil temperature is too low) or heating overload(indoor coil temperature is too high)
1.The indoor unit can not blow air normally;
2.The room temperature is too low in cooling mode or the room temperature is too high in heating;
3.The filter is dirty;
4.The duct resistance is too high to
result in low air flow;
5.The setting fan speed is too low;
6. The indoor unit is not standard
installed, air inlet is too near with air outlet .
1.Check the indoor fan, indoor fan motor and evaporator whether normally;
2. Normally protection;
3.Clean the filter;
4.Check the volume control
valve,duct length etc;
5.Set the speed with high speed;
6.Reinstall the indoor unit refer to
the user manual to change the distance between the indoor unit and the wall or ceiling.
21
Page 25
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Fault code
Fault Description Possible Reason of Abnormality How to Deal With Remarks
7
The communication fault between the indoor unit and outdoor unit
1.The connection cable connect wrong between the indoor unit and outdoor unit;
2.The communication cable connect loose;
3.The communication cable is fault;
4.The indoor control board is fault;
5.The outdoor control board is fault;
6.Communication circuit fuse open;
7.The specification of communication cable is incorrect.
1.Reconnect the connection cable refer to the wiring diagram;
2.Reconnect the communication cable;
3.Replace the communication cable;
4.Replace the indoor control board;
5.Replace the outdoor control board;
6.Check the communication circuit, adjust the DIP switch and the short-circuit fuse.
7.Choose suitable communication cable refer to the user manual
12
voltage absent phase
1.Three-phase power is abnormal;
2.The outdoor wiring connect wrong;
3.The outdoor control board is failure.
1. Normally protection
2. Check the wiring connection refer to
the wiring diagram;
3. Replace the outdoor control board
Application of three-phase power supply models
13
Compressor overheat protector device
1.The wiring of the overload protector connect loose.
2. The overload protector is failure .
3. The refrigerant is not enough;
4. The installation pipe is too long than normal, but not add the enough refrigerant;
5. The expansion valve is failure;
6. The outdoor control board is failure
1. Reconnect the wiring of the overload protector;
2. Replace the overload protector;
3. Check the welding point of the unit to confirm whether it is leakage, and then recharge the refrigerant;
4. Add the refrigerant;
5. Replace expansion valve;
6. Replace the outdoor control board.
14
the high pressure switch operate or the unit turn off for high pressure protection
1.The wiring of the high pressure protector connect loose;
2.The high pressure protector is failure;
3.The outdoor control board is abnormal;
4. Overload in cooling;
5. Overload in heating.
1.Reconnect the wiring the high pressure protector;
2. Replace the high pressure protector;
3. Replace the outdoor control board;
4. Please refer to the Note 3;
5. Please refer to the Note 4.
Applied to models with high pressure switch or pressure sensor
15
the low pressure switch protection or the unit turn off for low pressure protection
1.The wiring of the low pressure switch connect loose ;
2.The low pressure switch is failure;
3.The refrigerant is not enough;
4.The expansion valve failure in heating mode;
5.The outdoor control board is abnormal.
1. Reconnect the wiring of the low pressure switch;
2. Replace the low pressure switch;
3.Check the welding point to confirm whether the unit is leakage, and then add some refrigerant;
4. Replace the expansion valve;
5. Replace the outdoor control board.
Applied to models with low pressure switch or pressure sensor
16
overload protection in cooling mode
System overload Please refer to the Note 3.
17
Discharge temperature sensor fault
1.The wiring of the discharge temperature sensor connect loose;
2.The discharge temperature sensor is failure;
3.The sampling circuit is abnormal.
1.Reconnect the wiring of the discharge temperature sensor;
2.Replace the discharge temperature sensor;
3.Replace the outdoor control board.
22
Page 26
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Fault code
Fault Description Possible Reason of Abnormality How to Deal With Remarks
18
AC voltage is abnormal
1.The AC voltage>275V or <160V.
2.The AC voltage of sampling circuit on the driver board is abnormally
1. Normally protection, please check the supply power;
2. Replace the driver board.
19
Suction temperature sensor fault
1.The wiring of the suction temperature sensor connect loose;
2. The suction temperature sensor is failure;
3. The sampling circuit is abnormally.
1.Reconnect the wiring of the suction temperature sensor;
2.Replace the suction temperature sensor;
3.Replace the outdoor control board.
22
The defrosting sensor fault
1.The wiring of the defrosting sensor connect loose;
2.The defrosting sensor is failure;
3.The sampling circuit is abnormally
1. Reconnect the wiring of the defrosting
sensor;
2. Replace the defrosting sensor;
3. Replace the outdoor control board.
45 IPM fault
There are many reasons for this failure, If you need further analysis, fault code of the driver board is needed by watching the driver board fault led. Analysis can be further to know why and how to operate. Specific see table 5, table 6.
See attached "analysis of the driving board fault".
46
IPM and control board communication fault
1.The cable between the control board and the driver board connect loose;
2.The cable between the control board and the driver board is failure;
3.The driver board is failure
4.The control board is failure
1.Reconnect the cable between the control board and the driver board;
2.Replace the communication cable between the control board and the driver board;
3.Replace the driver board;
4.Replace the control board.
47
Discharge temperature too high fault
1. The refrigerant of the unit is not enough;
2.The refrigerant of the unit is not enough due to add the length of the installation pipe
3.Throttling service is failure;
4.The outdoor ambient temperature is too high.
1.Check the welding point to confirm whether the unit has exist leakage point, and then add some refrigerant.
2.Add some refrigerant refer to the installation user manual;
3.Replace the throttling service(such as capillary, expansion valve)
4. Normally protection.
48
the outdoor DC fan motor fault (upper fan motor)
1.The wiring of the up DC fan motor connect loose;
2. The cord of the up DC fan motor is failure;
3.The up DC fan motor is failure;
4.The drive circuit of the up DC fan motor is failure;
5. The outdoor fan has been blocked.
1.Reconnect the wiring of the up DC fan motor;
2.Replace the up DC fan motor;
3. Replace the up DC fan motor;
4.Replace the driver board of the fan motor;
5. Check the outdoor fan and ensure the outdoor fan can run normally.
49
the outdoor DC fan motor fault (down fan motor)
1.The wiring of the down DC fan motor connect loose;
2.The cord of the down DC fan motor is failure;
3. The down DC fan motor is failure;
4. The drive circuit of the down DC fan motor is failure;
5. The outdoor fan has been blocked.
1. Reconnect the wiring of the down DC fan motor;
2. Replace the down DC fan motor;
3.Replace the down DC fan motor;
4.Replace the driver board of the fan motor;
5. Check the outdoor fan and ensure the outdoor fan can run normally.
91
The unit turn off due to the IPM board over heating fault
1.The outdoor ambient is too high;
2. The speed of the out fan motor is too low if the fan motor is AC fan motor;
3.The outdoor unit has been installed without standard;
4.The supply power is too low.
1. Normally protection;
2. Check the fan capacitor, and replace the fan capacitor if it is failure;
3. Reinstalled the outdoor unit refer to the installation user manual;
4.Normally protection.
23
Page 27
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Fault code
Fault Description Possible Reason of Abnormality How to Deal With Remarks
96
the refrigerant of the unit is not enough fault
The refrigerant of the unit is not enough
Discharge the refrigerant and charge the refrigerant refer to the rating label
97
4-way valve commutation failure fault
1.The wiring of the 4-way valve coil connect loose;
2.The 4-way valve coil is failure;
3.The 4-way valve is failure;
4.The driver board of the 4-way valve is failure
1. Reconnect the wiring of the 4-way valve;
2. Replace the 4-way valve coil;
3. Replace the 4-way valve;
4.Replace the driver board of the 4-way valve.
24
Page 28
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
The following is the fault code table of indoor.
Sheet 2 Indoor fault code
Fault
code
Fault Description Possible Reason of Abnormality How to Deal With Remarks
51
Drainage protection
1. The water level of the drain pan exceed safe level;
2. The cable of the water level switch connect loose;
3.The water level switch is failure;
4. The control board is failure.
1.1 Check whether there are something to block the drain hose or the height of the drain hose is too high;
1.2 Check the water pump and replace the water pump if the water pump is failure;
2. Reconnect the cable of the water level switch refer to the wiring diagram;
3. Replace the water level switch;
4. Replace the control board.
64
Communication between Indoor & Outdoor unit Fault
1. The connection cable between the indoor unit and the outdoor unit connect wrong;
2.The communication cable connect
loose;
3.The communication cable between
the indoor unit and the outdoor unit is failure or the cable between the indoor control board to terminal is failure or the cable between the outdoor control board to the terminal is failure;
4. The indoor control board is failure;
5. The outdoor control board is failure.
1. Reconnect the connection cable refer to the indoor and outdoor wiring diagram;
2. Reconnect the communication cable refer to the indoor and outdoor wiring diagram;
3. Replace the communication cable refer to the indoor and outdoor wiring diagram;
4. Replace the indoor control board;
5. Replace the outdoor control board.
72
Indoor fan motor fault
1. The cable of the indoor fan motor connect loose;
2. The cable of the indoor fan motor is failure;
3.The indoor fan motor is failure;
4. The indoor control board is failure.
1. Reconnect the cable of the fan motor;
2. Replace the cable of the fan motor;
3. Replace the fan motor;
4. Replace the indoor control board;
5. Check the indoor fan and ensure the indoor fan can run normally.
73
Indoor EEPROM Data 1 fault
1.Indoor EE components is failure;
2.The control circuit of the EE
components is failure;
3.The EE components has been inserted with opposite direction.
1. Replace the EE components;
2. Replace the indoor control board;
3. Reassembly the EE components of the indoor control board.
74
Indoor EEPROM Data 2 error
EE in MCU is failure,the unit can run ,but the function user has set is ineffective.
Replace EE data in MCU.
81
Indoor ambient Temperature Sensor Fault
1. The cable of the room temperature sensor connect loose;
2. The room temperature sensor is failure;
3. The sampling circuit is abnormally.
1.Reconnect the cable of the room temperature sensor;
2. Replace the room temperature sensor;
3. Replace the indoor control board.
25
Page 29
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Fault
code
Fault Description Possible Reason of Abnormality How to Deal With Remarks
83
Evaporator Middle Temperature Sensor Fault
1.The cable of the coil temperature sensor of the evaporator is failure;
2. The coil temperature sensor of the evaporator is failure;
3. The sampling circuit is abnormally
1. Reconnect the cable of the coil temperature sensor of the evaporator;
2. Replace the coil temperature sensor of the evaporator;
3. Replace the indoor control board.
FE
(254)
Communication
between main
control board
&Wiring remote
controller Fault
display on
wiring remote
controller
1. The wiring between the wiring controller to the indoor control board connect loose;
2. The sequence of the wiring between the wiring controller to the indoor control board is wrong;
3. The wiring between the wiring controller to the indoor control board is failure;
4.The wiring controller is failure;
5. The indoor control board is abnormally
1.Reconnect the wiring between the wiring controller to the indoor control board;
2.Replace the wiring between the wiring controller to the indoor control board;
3.Replace the wiring between the wiring controller to the indoor control board;
4. Replace the wiring controller;
5. Replace the indoor control board
ER
Communication
between main
control board
&display board
Fault(displays on
display board
1.The wiring between the display board to the indoor control board connect loose;
2.The sequence of the wiring between the display board to the indoor control board is wrong;
3.The wiring between the display board to the indoor control board is failure;
4. The display board is failure;
5. The indoor control board is failure.
1. Reconnect the between the display board to the indoor control board;
2. Replace the wiring between the display board to the indoor control board;
3. Replace the wiring between the display board to the indoor control board;
4. Replace the display board;
5. Replace the indoor control board.
NOTE 1:
If the indoor unit can not turn on or the indoor unit turn off itself after 30s, at the same time the unit do
not display the fault code, please check the fire and the socket of the control board.
Note 2:
If the indoor unit display the 75,76,77,78 fault code after you turn on the unit, please check the TEST
seat of the indoor control board or the TEST detection circuit whether exists short circuit.
26
Page 30
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Note 3:Overload in cooling mode
overload in cooling mode
sr. The root cause Corrective measure
1 The refrigerant is excessive
Discharge the refrigerant, and recharge the refrigerant refer
to the rating label
2 The outdoor ambient temperature is too high Please use within allowable temperature range
3
The air outlet and air inlet of the outdoor unit is
short-circuit
Adjust the installation of the outdoor unit refer to the user
manual
4 The outdoor heat exchanger is dirty, such as condenser
Clean the heat exchanger of the outdoor unit, such as
condenser
5 The speed of the outdoor fan motor is too low Check the outdoor fan motor and fan capacitor
6 The outdoor fan is broken or the outdoor fan is blocked Check the outdoor fan
7 The air inlet and outlet has been blocked Remove the blocked thing
8 The expansion valve or the capillary is failure Replace the expansion valve or the capillary
Note 4:Over load in heating mode
Overload in heating mode
sr. The root cause Corrective measure
1 The refrigerant is excessive
Discharge the refrigerant, and recharge the refrigerant refer
to the rating label
2 The indoor ambient temperature is too high Please use within allowable temperature range
3
The air outlet and air inlet of the indoor unit is
short-circuit
Adjust the installation of the indoor unit refer to the user
manual
4 The indoor filter is dirty Clean the indoor filter
5 The speed of the indoor fan motor is too low Check the indoor fan motor and fan capacitor
6 The indoor fan is broken or the outdoor fan is blocked Check the indoor fan
7 The air inlet and outlet has been blocked Remove the blocked thing
8 The expansion valve or the capillary is failure Replace the expansion valve or the capillary
Sheet 3 Overload in cooling mode
Sheet 4 Overload in heating mode
27
Page 31
22.
.
TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Sheet 5 Drive Fault code(1.0/1.5/2.0/3.0HP
Fault code
Fault Description
Possible Reason of Abnormality
How to Deal With
1 Inverter DC voltage overload fault
1.Power supply input too high or too low;
2.Driver board fault.
1.Check power supply
2.Change driver board.
2 Inverter DC low voltage fault 3 Inverter AC current overload fault 4 Out-of-step detection
1.Compressor phase lost
2.Bad driver board components
3.The compressor insulation fault
1.Check compressor wire connect
2.Change driver board
3.Change compressor.
5
Loss phase detection fault (speed pulsation)
6
Loss phase detection fault (current imbalance)
7 Inverter IPM fault (edge) 1.System overload or current
overload;
2.Driver board fault.
3.Compressor oil shortage, serious
wear of crankshaft ;
4.The compressor insulation fault
1.Check the system .
2.Change driver board;
3.Change the compressor;
4.Change the compressor.
8 Inverter IPM fault (level) 9 PFC_IPM IPM fault (edge)
10 PFC_IPM IPM fault (level)
11 PFC power detection of failure
1.The power supply is not stable ;
2.The instantaneous power failure ;
3.Driver board failure.
1.Check the power supply.
2.Not abnormal.
3.Change the driver board.
12
PFC overload current detection of
failure.
1.System overload, current too high;
2.Driver board failure
3.PFC failure
1.Check the system;
2.Change the driver board;
3.Change the PFC.
13 DC voltage detected abnormal .
1.Input voltage is too high or too low;
2.Driver board failure
1.Check the power supply.
2.Change the driver board;
14 PFC LOW voltage detected failure. 15 AD offset abnormal detected failure.
Driver board failure. Change the driver board.
16 Inverter PWM logic set fault. 17 Inverter PWM initialization failure 18 PFC_PWM logic set fault. 19 PFC_PWM initialization fault. 20 Temperature abnormal.
21
Shunt resistance unbalance adjustment fault
22 Communication failure.
1.Communication wire connect not well.
2.Driver board failure.
3.Control board failure.
1.Check the wiring.
2.Change the driver board.
3.Change the control board.
23 Motor parameters setting of failure Initialization abnormal. Reset the power supply.
25 EE data abnormal Driver board EEPROM abnormal
1.Change EEPROM
2.Change driver board.
26 DC voltage mutation error
1.Power input changes suddenly
2.Driver board failure
1.Check power supplyto provide stable power supply
2. Change driver board.
27 D axis current control error
1.System overloadphase current is
too high;
2.Driver board failure
1.Check system if normally.
2.Check stop valve if is open;
3. Change driver board.
28 q axis current control error
1.System overloadphase current is too high
2.Driver board failure
1.Check system if normally.
2.Check stop valve if is open;
3. Change driver board.
29
Saturation error of d axis current control integral
1. System overload suddenly;
2. Compressor parameter not suitable;
3. Driver board failure
1.Check system if normally.
2.Check stop valve if is open;
3. Change driver board.
30
Saturation error of q axis current control integral
1. System overload suddenly;
2. Compressor parameter not
suitable;
3. Driver board failure
1.Check system if normally.
2.Check stop valve if is open;
3. Change driver board.
28
Page 32
22..TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Sheet 6 Drive Fault code (4.0/5.0/6.0/6.5HP)
Fault code
Fault Description
Possible Reason of Abnormality
How to Deal With
1
Q axis current detection, step out of failure
1. compressor wire connect not well;
2. Bad driver board components;
3. Compressor start load is too large;
4.Compressor demagnetization;
5.Compressor oil shortage, serious wear of crankshaft.;
6.The compressor insulation fault
1. Check compressor wire;
2. Change driver board ;
3.Turn on the machine after pressure balance again;
4. Change Compressor;
5. Change the Compressor;
6. Change the Compressor.
2
Phase current detection, out of step
1.Compressor voltage default phase;
2.Bad driver board components;
3.The compressor insulation fault
1.Check compressor wire connection;
2.Change the driver board;
3.Change the Compressor.
3
Initialization, phase current imbalance
Bad driver board components. Change driver board .
4
Speed estimation, step out of failure
1.Bad driver board components;
2.Compressor shaft clamping;
3.The compressor insulation fault.
1.Change driver board ;
2.Change the Compressor ;
3.Change the Compressor .
5 IPM FO output fault
1.System overload or current overload.
2.Driver board fault;
3. Compressor oil shortage,serious wear of crankshaft;
4.The compressor insulation fault.
1.Check the air-conditioner system;
2.Change the driver board;
3.Change the Compressor;
4. Change the Compressor.
6
Communication between driver board and control board fault
1.Communication wire connect not well;
2.Driver board fault;
3.Control board fault;
1.Check compressor wire connect.
2.Change the driver board;
3.Change the control board ;
7
AC voltage,overload voltage
1.Supply voltage input too high or too low;
2.Driver board fault;
1.Check power supply;
2.Change the driver board;
8
DC voltage,overload voltage
1.Supply voltage input too high ;
2.Driver board fault;
1.Check power supply;
2.Change the driver board;
9 AC voltage imbalance Driver board fault; Change the driver board;
10
The PFC current detection circuit fault before compressor is ON
Bad driver board components; Change the driver board
11
AC voltage supply in outrange
1.Power supply abnormal, power frequency out of range;
2.Driver board fault;
1.Check the system;
2.Change the driver board;
12
Products of single-phase PFC over-current, FO output low level
1.System overload, current too large;
2.Driver board fault;
3.PFC fault.
1.Check the system;
2.Change the driver board;
3.Change PFC.
Inverter over current (3-phase power supply air conditioners)
1.System overload, current too large;
2.Driver board fault;
3.Compressor oil shortage, serious
wear of crankshaft;
4.The compressor insulation fault.
1.Check the system;
2.Change the driver board;
3.Change the Compressor;
4.Change the Compressor.
13 Inverter over current
1.System overload, current too large;
2.Driver board fault;
3.Compressor oil shortage,serious wear of crankshaft;
4.The compressor insulation fault.
1.Check the system;
2.Change the driver board;
3.Change the Compressor;
4.Change the Compressor.
14
PFC over current(single-phase air-conditioner)
1.System overload, current too large;
2.Driver board fault;
3.PFC fault.
1.Check the system;
2.Change the driver board;
3.Change PFC. Phase imbalance or phase lacks or the instantaneous power failure (only for 3-phase power supply air conditioners)
1.3-Phase voltage imbalance;
2.The 3-phase power supply phase lost;
3.Power supply wiring wrong;
4.Driver board fault.
1,Check the power supply;
2.Check the power supply;
3.Check the power
supply
wiring
connect;
4.Change the driver board.
15
The instantaneous power failure detection
1.The power supply is not stable ;
2.The instantaneous power failure ;
3.Driver board fault;
1.Check the power supply.
2.Not fault.
3.Change the driver board;
29
Page 33
22..TTRROOUUBBLLEESSHHOOOOTTIINNG
G
Fault code
Fault Description
Possible Reason of Abnormality
How to Deal With
16 Low DC voltage 200V
1.Voltage input too low ;
2.Driver board fault.
1.Check the power supply.
2.Change the driver board.
18
Driver board read EE data error
1.EEPROM has no data or data error;
2.EEPROM circuit fault.
1,Change EEPROM component; 2,Change the driver board.
19
PFC chip receive data fault
Abnormal communication loop Change the drive board.
20
PFC soft start abnormal
Abnormal PFC drive loop Change the drive board.
21
The compressor drive chip could not receive data from PFC chip.
Communication loop fault. Change the drive board.
30
Page 34
3. Chec
k
3.1 Che
c
TEST SYS
T
Con
d
Tool:
Te ch
n
3.CHECKING COMPONENTS
ing com
k refrig
e
T
EM FLO
W
itions: ①
C② T
Pressure
G
ique: ①
s
SEE
FEEL
TEST
ponents
rant sys
t
ompressor
he air con
d
auge
ee ② f
e
----- Tub
e
----- The
d
----- Test
em
is running.
ition should
el ③ test
defrost.
ifference
b
pressure.
be installe
d
etween tub
e
in good v
e
’s tempera
t
ntilation.
ure.
31
Page 35
3
.. CCHHEECCKKIINNGG CCOOMMPPOONNEENNTTS
S
Test system flow
Cooling mode
Test system
pressure.Does the low
pressure normal at
service part ?
The pressure on the high side.
The pressure on the low side.
Recharge refrigerant
after air purging with
the vacuum
pump.Does the low
pressure nomal over
again?
Air remaining at the refrigerant system.
yes
The system wants
refrigerant.The service
people must be ration
refrigeran.Is the low
pressure rise ?
NO
Recharge refrigerant .
yes
The refrigerant system
blocked.Please check
the Cap illary Tube or
electronic expansion
valve)Is it blocked?
Unsold er the capillary tube ASS'Y(or electronic expansion valve).T he capilla ry tube1 is blo wn by N
2
.
Check check valve and 4­way valve.
If the pressure is
close to static
pressure?
NO
NO
4-way valve collude or compressor exhaust very ebb.
yes
NO
yes
Heating mode
Test system pressure.Does the high pressure normal at service part ?
The pressure on the high side.
The pressure on the low side.
Recharge refrigerant after air purging with the vacuum pump.Does the high pressure normal over again?
Air remaining at the refrigerant system.
yes
The system wants refrigerant.The service people must be ration refrigerant .Is the high pressure rise in heating mode?
NO
Recharge refrigerant
yes
If the pressure is close to static pressure?
4-way valve collude or compressor exhaust every ebb.
yes
Check heat exchanger and 4-way valve.
NO
The capillary tube blocked.Unsolder the capillary tube ASS'Y.The capillary tube1 and capillary tube2 is blown by N
2
.
NO
Remove the back panel."see"the capillary tube1 and capillary tube2.Is it defrosting?
yes
NO
32
Page 36
3.2 Che
c
1.
k parts
u
INDOOOR FAN MOTOR
Ducted
1.0/1.5/3.0/4.0/5.0/6.0/6.5HP--DC motor
2.0HP--- AC motor
1.0/1.5HP Motor m
3.0HPMotor mode
4.0/5.06.0/6.5HP
2.0HP
nit
odel:SIC-
lSIC-70
Motor
m
Motor mode
lYSK11
-68CVL-F1
CW-F195-
modelSI
C
0-40-4-A
40-1
-1
-101CW-F1250-4
33
3.CHECKING COMPONENTS
Page 37
BLAC
K
YELL
O
BRO
W
YELL
O
RED-
B
BLUE
-
Casset
25
-YELLO
W
W-BRO
W
N-ORAN
G
W-RED:
6
LUE: 63
±
WHITE: 1
te
1.5HP-D
C
MOTOR
2.0HP-AC
MOTOR M
3.0/4.0HP DC-MOT
O
5.0/6.0/6.5HP DC-
M
:146±1
5
N:33±15
E: 43±1
5
3±15%
Ω
15%Ω
19±15%
Ω
MODEL:YDK
OR MODEL
MOTOR MOD
%Ω
%Ω
%Ω
K95-28-4-B
:
EHDS50A
DEL:
SIC-7
AQH
72FW-D8124-2B
34
3.CHECKING COMPONENTS
Page 38
Test in resi
s
TOOL: Mul
t
Test the re
s
0(short cir
c
Test in volt
a
2.0HP DC MOTOR MOD
3.0HP DC MOTOR MOD
4.0HP DC MOTOR MOD
5.0/6.0/6.5HP
tance.
imeter.
istance of
uit)or(op
e
ge
EL: SIC-52F
EL:
SIC-70C
EL: SIC-70C
DC MOTO R MODE
L
the main
w
n circuit).
FV
-F130-3
CW-F1100-6
CW-F1140-3
L: SIC-101CW
inding. The
6
3
W-F1181-2
indoor fan
m
otor is fault if the resiistance of main windin
g
Floor ceiling
35
3.CHECKING COMPONENTS
Page 39
TOOL: Multimeter.
Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure
voltage “YELLOW” and “GND” on motor. The voltage repeat 0V DC and 5V DC.
Notes:
Please don’t hold motor by lead wires.
Please don’t plug IN/OUT the motor connecter while power ON.
Please don’t drop hurl or dump motor against hard material. Malfunction may not be observed at early
stage after such shock. But it may be found later, this type of mishandling void our warranty.
36
3.CHECKING COMPONENTS
Page 40
2. OUTDO
O
DC MOTO
R
-
2.0/3.0HP-
3. COMPR
E
R FAN M
O
1.0/1.5HP--
MOTOR M
O
MOTOR
M
OR MODEL
4.0HP—MOT
5.0HP—MOT
OR MODEL
6.0/6.5HP:
SSOR
2.0HP: ATM150D23UFZ
3.0HP:ATF235D43UMT
4.0/5.0HP: ATF310D43UMT
6.0/6.5HP:ATH356SDPC9FL
TOR
ODEL:
SIC-
ODEL: SI
C
L:SIC-71FW
L:SIC-81FW
MOTOR MOD
EL:SIC-71
52FV-F130-
-61FV-F16
1
W-D8121-1
W-F1138-1
FW-D8121-
-3
-1
-1+ SIC-71F
FW-D8121-2
COMPRESSOR EXAMINE AND REPAIR
1.0HPASD088SKNA8JT
1.5HP ASN108D43UFZA
37
3.CHECKING COMPONENTS
Page 41
Test in resistance.
TOOL: Multimeter.
Test the resistance of the winding.
The compressor is fault if the resistance of winding 0(short
circuit)oropen circuit
Familiar error:
1Compressor motor lock.
2Discharge pressure value approaches static pressure value .
3Compressor motor winding abnormality.
Notes
1Don’t put a compressor on its side or turn over.
2) Please assembly the compressor in your air conditioner rapidly after removing the plugs. Don’t place
the comp. In air for along time.
3Avoiding compressor running in reverse caused by connecting electrical wire incorrectly.
4Warning! In case AC voltage is impressed to compressor, the compressor performance will below
because of its rotor magnetic force decreasing.
4. INDUCTANCE
Familiar error:
1Sound abnormality
2Insulation resistance disqualification.
5. STEP MOTOR
5
4
2
1
38
3.CHECKING COMPONENTS
Page 42
Test in resistance.
TOOL: Multimeter.
Test the resistance of winding. The stepper motor is fault if the resistance of winding 0(short circuit)or
open circuit.
6. FUSE
Checking continuity of fuse on PCB ASS’Y.
Remove the PCB ASS’Y from the electrical component box. Then pull out the fuse from the PCB ASS’Y
(Fig.1)
Fuse
PCB Ass'Y
Fig.1
Check for continuity by a multimeter as shown in Fig
.2.
Fuse
Fig.2
7.CAPACIT
OR
R
emove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals
as shown in Fig.3.
Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the
maximum value.
* The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its
original position.
* The range of deflection and deflection time differ according to the capacity of the capacitor.
39
3.CHECKING COMPONENTS
Page 43
Compressor motor capacitor
Fan motor capacitor
Multimeter
Fig.3
40
3.CHECKING COMPONENTS
Page 44
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
Outdoor unit
The special tools for compressor & motor disassembly and assembly
Tool
1
Hexagon Screwdriver
2
Hexagon Socket
Outdoor unit
1.0/1.5/2.0/3.0HP Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
Step Illustration Handling Instruction
external 1.Remove
casing
1.Remove the top cover, handle and valve cover;
2.Remove the outer case and right side plate.
2.Remove motor
1.Remove the blade nut and then remove the blade;
2.Remove the motor from motor supporter
3.Remove compressor
1.Reclaim the refr
igerant
from the entire system.
2.Unsolder the 4-way valve piping a
ssy from
compressor;
3.Remove the compressor mounting bolts by using hexagon
socket;
4.Carefully remove the
compressor from chassis.
4.Assemble unit
Assemble the unit in the reverse order of disassembly.
41
Page 45
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
4.0HP Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
Step Illustration Handlin Instructiong
1.Remove external casing
1.Remove the top cover, handle and valve cover;
2.Remove the outer case and right side plate.
2.Remove motor
1.Remove the blade nut and then remove the blade;
2.Remove the motor from motor supporter
3.Remove compressor
1.Reclaim the refrigerant from the entire system.
2.Unsolder the 4-way valve piping assy from compressor;
3.Remove the compressor mounting bolts by using hexagon socket;
4.Carefully remove the
compressor from chassis.
4.Assemble unit
Assemble the unit in the reverse order of disassembly.
42
Page 46
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
6.0/6.5HP Important: Before disassembly and assembly, make sure that the power to the system has been disconnected and verified as voltage free.
Step Illustration Handling Instruction
external 1.Remove
casing
1.Remove the top cover, handle and valve cover;
2.Remove the outer case and right side plate.
2.Remove motor
1.Remove the blade nut and then remove the blade;
2.Remove the motor from motor supporter
3. Remove gas liquid separator
1.Reclaimthe refrigerant from the entire system.
2.Unsolder the 4-way valve piping assy from gas liquid separator;
3.Remove the gas liquid separator.
4.Remove compressor
1.Reclaim the refrigerant From the entire system.
2.
Unsolder the 4-way valve piping assy from compressor.
3.
Remove the compressor mounting bolts by using
hexagon socket.
4.Carefully remove the
compressor from chassis.
5.Assemble unit
Assemble the unit in the reverse order of disassembly.
43
Page 47
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
Indoor unit Ducted1.0/1.5HP
Removal and Assembly of Fan Motor Important: Before removing the fan, make sure power to the system is disconnected. Step Illustration Handling Instruction
1. Unplug the motor cables
Use screwdriver to remove the electric box cover and un
plug the motor cables in electric box.
2. Remove the base board
Loose and take out the screws fixing
the base board, then remove the base board.
3. Remove the screws on fan sub-assembly.
Remove the screws on fan sub-assembly.
4. Removing the fan cage enclosure
Rotate the fan cage housing toward supply opening and remove.
5. Loosen the fan and motor.
Loosen the screws holding the fan cage to the motor shaft by using hexagon screwdriver. Remove outer housing holding motor in place.
6. Replace the motor
Remove the motor from the support bracket. Then remove the fan cages from the motor shafts. Remove the motor from the air inlet and replace with new motor. Be sure to tighten the cages onto the motor shafts.
7. Reassembly of the unit
Reassemble the unit in the reverse order
of disassembly and test operation.
44
Page 48
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
2.0HP
Removal and Assembly of Fan Motor Important: Before removing the fan, make sure power to the system is disconnected. Step Illustration Handling Instruction
1. Unplug the motor cables
Use screwdriver to remove the electric box cover and unplug the motor cables in electric box.
2. Remove the base board
Loose and take out the screws fixing the base board, then remove the base board.
3. Remove the screws on fan sub-assembly.
Remove the screws on fan sub-assembly.
4. Removing the fan cage enclosure
Rotate the fan cage housing toward supply opening and remove.
5. Loosen the fan and motor
Loosen the screws holding the fan cage to the motor shaft by using hexagon screwdriver. Remove outer housing holding motor in place.
6. Replace the motor
Remove the motor from the support bracket. Then remove the fan cages and crosshead from the motor shafts. Remove the motor from the air inlet and replace with new motor. Be sure to tighten the cages onto the motor shafts.
7. Reassembly of the unit
Reassemble the unit in the reverse order of disassembly and test operation.
45
Page 49
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
4.0/5.0/6.0/6.5HP
Removal and Assembly of Fan Motor Important: Before removing the fan, make sure power to the system is disconnected. Step Illustration Handling Instruction
1. Unplug the motor cables
Use screwdriver to remove the electric box
cover and unplug
the motor cables in electric box.
2. Loosen the fan and motor.
Use a offset spanner to loosen the screws holding the fan cage to the motor shaft. Remove outer housing holding motor in place.
3. Remove the diversion circle and support brac
ket.
Use screwdriver to remove the diversion circle and support bracket.
4. Replace the motor
Remove the fan cage from the motor shaft.
Remove the motor from the air inlet and replace with new motor. Be sure to tighten the cages onto the motor shafts.
5. Reassembly of the unit
Reassemble the unit in the reverse order of disassembly and test operation.
46
Page 50
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
Cassette type
1.5/2.0HP
Step Illustration Handling Instruction
1. Loosen the screws holding the
electric bo
x cover and remove the plate.
Use screwdriver to loosen the electric box and the plate.
2. Loosen the bolts holding the fan blades in place and Remove the fan blade.
Use a wrench or socket to carefully remove the fan blade bolts.
3. Loosen the screws holding the motor in place and Remove the motor and replace it.
Use screwdriver to loosen the screws holding the motor.
47
Page 51
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
3.0/4.0/5.0/6.0/6.5HP
Step Illustration Handling Instruction
1.Loosen the screws holding the e
lectric bo
x
cover and electric box.
Use screwdriver to loosen the Electric box.
2. Loosen the screws holding cond
ensat
e pan and Remove the condensate pan.
Use screwdriver to loosen the screws holding the drain pan in place.
3. Loosen the bolts holding the fan blade
s in place an
d
Remove the fan blade.
Use a wrench or socket to carefully remove the fan blade bolts.
4. Loosen the screws holding the motor in place and Remove the motor and replace it.
Use screwdriver to loosen the screws holding the motor.
48
Page 52
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
Floor ceiling
Removal of the motor
Step Illustration Handling Instruction
Disassembly of
the down front
panel assembly
Slide open the 4 decorative covers, loose and take out the 4 screws, then open the down front panel assembly.
Loose and take out the 4 screws fixing the hinge, then remove the down front panel assembly.
Disassembly of
the mounting
Plate
Loose and take out the 2 screws fixing the mounting Plate, then remove it.
Disassembly of
the electric box
Loose and take out the 3 screws fixing the electric box, then take it.
49
Page 53
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
Removal of the motor
Step Illustration Handling Instruction
Disassembly of
the motor shaft
Remov e the 2 screws fixing the motor shaft and fan blade by allen screwdriver.
Disassembly of
the motor
(2.0/3.0HP)
Remove the fasteners between the up shell and the below shell; Take out of the motor and centrifugal fan blade; Remove the 2 screws fixing the centrifugal fan blade and get the motor.
Disassembly of
(4.0HP)
Remove the fasteners between the up shell and the below shell on both sides of the motor; Remove the 2 screws fixing the Crosshead and take it away from the motor; Take out of the motor and centrifugal fan blade; Remove the 2 screws fixing the centrifugal fan blade and get the
50
Page 54
44..DDIISSAASSSSEEMMBBLLYY AANNDD AASSSSEEMMBBLLYY FFOORR CCOOMMPPRREESSSSOORR AANNDD MMOOTTOOR
R
Removal of the motor
Step Illustration Handling Instruction
motor.
Disassembly of
the motor
(5.0/6.0/6.5HP)
Remove the fasteners between the up shell and the below shell on both sides of the motor; Remove the 2 screws fixing the Crosshead and take it away from the motor; Take out of the motor.
51
Page 55
5
. CONTROL LOGIC DESCRIPTIO
N
52
5 ( ( d ( 5
h T T
u
Contr55.
11)
22) Tempe isplayed.
33) Indoor f
Inn Inn
igh, (medi
he auto fa 1 is indoo
CCompress OO WW shh
p.
OOutdoor fa OO SS ww DD byy the rule
ool logic
.1 Fan Onlly Mode
Outdoorr
rrature sett
aan can be
Mode .2 Cooling door fan rrunning rul cooling mmode, indo
uum), low a
n:
rr room te
oor and outd
nce the coompresso
hen indooo
ut off. Whh
nn running r
nce the ouutdoor fan
ingle outdoo
ill regulatee ouble outddoor fan: If
s, and th
fan and coompresso
ing functi
es: or fan run
nnd auto.
oor fan ru
rr starts up,
r room temmp.T1 is l
en T1 is hhigher tha
ules:
start up, it
or fan: Firrst, it will r
the speedd by the o
ddescriptioon
rr stop.
set to highh/medium/l
mmperature. TT
it will follo
nn Ts+1, the
will follow
uun in an in
it has twoo
ee downer ffan speed
oon is disaabled, and
ss all the timm
s is settingg
nnning ruless:
ww the belo
oower than TTs, the com
compress
the below
vvariable s
temperatuu
outdoor faans, the u
no settin
ow, but cann
e and thee
temperatture.
ww rules:
rules:
ppeed for a
uutdoor-coil re.
lower thaan the up
not be seet to auto.
speed caan be sele
pressor annd outdoo or and outtdoor fan
ppper fan reggulates th
pper fan sp
g temperaature is
cted as
rr fan will wwill start
sshort time;; Then it
ee speed
eed for
0
44
T1-Ts
High
Medium
Low
Page 56
5
. CONTROL LOGIC DESCRIPTIO
N
53
5 I I
t s T T
300
nn several
wwill not run
eeveral min
he auto fa 1 is indoo
OOutdoor fa OO SS ww DD byy the rule 300
rpm~60rppm.
.3 Heatingg Mode
nndoor fan rrunning rul
eemperaturee. Th a t i s
utes, the s n:
nn running r
nce the ouutdoor fan ingle outdoo ill regulatee ouble outddoor fan: If
s, and th
rpm~60rppm.
es:
mminutes aftter the he
until the hheat exch
because
rr room temm
ules:
start up, it
or fan: Firrst, it will r
the speedd by the in
cold air
peed can bb
pprevention
e selecte
perature. TTs is settin
will follow
uun in an in
it has twoo
ee downer ffan speed
0
2
aating modee is starte
aanger of thhe indoor
d as high,
gg tempera
the below
vvariable s
outdoor faans, the u
4
(medium),
tture.
rules:
ppeed for a
eemperatureeddoor-coil t .
lower thaan the up
dd, the fan oof the ind uunit reachees a high
system iss
ppper fan reggulates th
pper fan sp
ooor unit
enough operatingg. After low and auto.
sshort time;; Then it
ee speed
eed for
Low
Mediuum
Hiigh
TTs-T1
Page 57
5
. CONTROL LOGIC DESCRIPTIO
N
T
T
55
his mode caa Inn acc
Inndoor fan ass in relev seetting tem aggain.
55
DD AAC will ent CCondition:
CC seeconds, th
E6, the co
.4 Auto MMode
can be c
n be channged betw
auto moode, the
cording too
Δ
-3
wwill run at aant mode.
.5 Evapoorator Lo
InverterrC-
ooling moode: When
mpressor
hhosen wit
eeen 16~3
mmachine
ΔT (ΔT ==T1-Ts).
ΔTT=T1-Ts
T > 3
ΔTT -3
auto fan
pperature iss modified,
eer T2 protecc
e compresssor and
TE6
T2
TE5
hh remote
00.
wwill choos
ΔT 3
If the commpressor
the mach
ww-temperr
tion if anyy of the fol
the indooo
aand outdooo
On
Off
ee cooling,
Ruu
Cooling
Fan-only
Heating
oof the relevvant mode
ature Prootection
r coil temmp. T2 kee
ooutdoor fann will shut
r fan will rrestart up.
ccontroller aa
nning moode
. The louv ping for 1 keep stop
ine will chooose mod
lowing conn
off. When
nd the see
heating oo
eer operate
ee accordin
dition is saatisfied.
ps lower tthan TE5
tting tempperature
r fan-onlyy mode
s same
0 minutess or the
g to ΔT
for 120
T2 is highher than
Page 58
5
. CONTROL LOGIC DESCRIPTIO
N
55
5.6 Condenser High-temperature Protection
DC-Inverter outdoor unit AC will enter T3 protection if any of the following conditions is satisfied.
Condition1: Cooling mode: When the outdoor coil temp. T3 keeps higher than T2 for 10 seconds, the compressor and outdoor fan will shut off. When T3 is lower than T1, the compressor and outdoor fan will restart up. Condition2: Heating mode: When the indoor coil temp. T3 keeps higher than T2 for 10 seconds, the compressor and outdoor fan will shut off. When T3 is lower than T1, the compressor and outdoor fan will restart up.
T3
TE10
Off
On
TE11
Page 59
Loading...