Hitachi RAS-4HVRNS3E, RAS-10HNPE, RAS-10HNCE, RAS-8HNCE, RAS-8HNPE Installation And Operation Manual

...
UTOPIA IVX PREMIUM / IVX STANDARD Series RAS-(3-10)H(V)NP(1)E / RAS-(8-10)HNCE UTOPIA ES Series RAS-4H(V)RNS3E
INSTALLATION AND OPERATION MANUAL
Specications in this manual are subject to change without notice in order that HITACHI may bring the latest innovations to their customers. Whilst every effort is made to ensure that all specications are correct, printing errors are beyond Hitachi’s control; Hitachi can­not be held responsible for these errors.
ATTENTION: This product shall not be mixed with general house waste at the end of its life and it shall be retired according to the appropriated local or national regulations in a environmentally correct way. Due to the refrigerant, oil and other components contained in Air Conditioner, its dismantling must be done by a professional installer according to the applicable regulations. Contact to the corresponding authorities for more information.
 
English
From 4th July 2007 and following Regulation EC Nº 842/2006 on Certain Fluorinated Greenhouse gases, it is mandatory to ll in the label attached to the unit with the total amount of refrigerant charged on the installation.
Do not vent R410A/R407C into the atmosphere: R410A & R407C are uorinated greenhouse gases covered by the Kyoto protocol global warming potential (GWP) R410A/R407C: = 1975/1652.5.
English
Instructions to ll in the "F-Gas Label":
1.- Fill in the Label with indelible ink the refrigerant amounts:  - Factory Charge,  - Additional Charge &  - Total Charge.
2.- Stick the Protection Plastic Film on the F-Gas Label (delivered in a plastic bag with the Manual). To see Figure nº 2.
Figure 1. F-Gas Label with Protection Plastic Film Figure 2. Protection Plastic Film
Protection Plastic Film
Adhesive Surface
Peel-off Paper
MODELS CODIFICATION
Important note: Please, check, according to the model name, which is your air conditioner type,
how it is abbreviated and referred to in this instruction manual. This Installation and Operation Manual is only related to Indoor Units FSN(H)(2/3/4)(E)(i)(k)(M) combined with Outdoor Units H(V)NP(1)E, HNCE and RAS-4H(V)RNS3E.

IVX Premium series
OUTDOOR UNIT · UNIDAD EXTERIOR · AUßENEINHEIT · UNITÉ EXTÉRIEURE · UNITÀ ESTERNA ·
UNIDADE EXTERIOR · UDENDRS AGGREGAT · BUITENTOESTEL · UTOMHUSENHET · ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ
HEAT PUMP MODELS - MODELOS CON BOMBA DE CALOR
WÄRMEPUMPENMODELLE - MODÈLES POMPE À CHALEUR MODELLI POMPA DI CALORE - MODELOS BOMBA DE CALOR VARMEPUMPEMODELLER - MODELLEN MET WARMTEPOMP
MODELLER ENDAST FÖR KYLNINGSFUNKTION - ΜΟΝΤΕΛΑ ΜΕ ΑΝΤΛΙΑ ΘΕΡΜΟΤΗΤΑΣ
Single Phase - Monofásico - Einphasig - Monophasé - Monofase
Monofásico - Enfaset - Eenfasig - En fas - Μονοφασικά
Three Phase - Trifásico - Dreiphasig -
Triphasé -Trifase - Trifásico
Trefaset - Driefasig - Trefasig - Tριφασικά
1~ 230V 50Hz 3N~ 400V 50Hz
Unit Unit Unit
RAS-3HVNP1E
RAS-4HVNP1E RAS-4HNP1E
RAS-5HVNP1E RAS-5HNP1E
RAS-6HVNP1E RAS-6HNP1E
RAS-8HNPE
RAS-10HNPE

IVX Standard series
OUTDOOR UNIT · UNIDAD EXTERIOR · AUßENEINHEIT · UNITÉ EXTÉRIEURE · UNITÀ ESTERNA ·
UNIDADE EXTERIOR · UDENDRS AGGREGAT · BUITENTOESTEL · UTOMHUSENHET · ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ
HEAT PUMP MODELS - MODELOS CON BOMBA DE CALOR
WÄRMEPUMPENMODELLE - MODÈLES POMPE À CHALEUR MODELLI POMPA DI CALORE - MODELOS BOMBA DE CALOR VARMEPUMPEMODELLER - MODELLEN MET WARMTEPOMP
MODELLER ENDAST FÖR KYLNINGSFUNKTION - ΜΟΝΤΕΛΑ ΜΕ ΑΝΤΛΙΑ ΘΕΡΜΟΤΗΤΑΣ
Three Phase - Trifásico - Dreiphasig - Triphasé -Trifase - Trifásico
Trefaset - Driefasig - Trefasig - Tριφασικά
3N~ 400V 50Hz
RAS-8HNCE
RAS-10HNCE

ES series
OUTDOOR UNIT · UNIDAD EXTERIOR · AUßENEINHEIT · UNITÉ EXTÉRIEURE · UNITÀ ESTERNA ·
UNIDADE EXTERIOR · UDENDRS AGGREGAT · BUITENTOESTEL · UTOMHUSENHET · ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ
HEAT PUMP MODELS - MODELOS CON BOMBA DE CALOR
WÄRMEPUMPENMODELLE - MODÈLES POMPE À CHALEUR MODELLI POMPA DI CALORE - MODELOS BOMBA DE CALOR VARMEPUMPEMODELLER - MODELLEN MET WARMTEPOMP
MODELLER ENDAST FÖR KYLNINGSFUNKTION - ΜΟΝΤΕΛΑ ΜΕ ΑΝΤΛΙΑ ΘΕΡΜΟΤΗΤΑΣ
Single Phase - Monofásico - Einphasig - Monophasé - Monofase -
Monofásico - Enfaset - Eenfasig - En fas - Μονοφασικά
Three Phase - Trifásico - Dreiphasig - Triphasé -Trifase -
Trifásico - Trefaset - Driefasig - Trefasig - Tριφασικά
1~ 230V 50Hz 3N~ 400V 50Hz
Unit Unit
RAS-4HVRNS3E RAS-4HRNS3E
INDEX ÍNDICE
PART I OPERATION
1. GENERAL INFORMATION
2. SAFETY
3. PRODUCT GUIDE
4. IMPORTANT NOTICE
5. TRANSPORTATION AND HANDLING
6. BEFORE OPERATION
7. REMOTE CONTROLLER
8. AUTOMATIC CONTROLS
9. BASIC TROUBLESHOOTING
PART II INSTALLATION
10. NAME OF PARTS
11. REFRIGERANT CYCLE
12. UNITS INSTALLATION
13. REFRIGERANT PIPING & REFRIGERANT CHARGE
14. DRAIN PIPING
15. ELECTRIC WIRING
16. TEST RUNNING
17. SAFETY SUMMARY & CONTROL DEVICE SETTING
18. TROUBLESHOOTING
1ª PARTE: FUNCIONAMIENTO
1. INFORMACIÓN GENERAL
2. SEGURIDAD
3. GUÍA DEL PRODUCTO
4. AVISO IMPORTANTE
5. TRANSPORTE Y MANIPULACIÓN
6. ANTES DEL FUNCIONAMIENTO
7. CONTROL REMOTO
8. CONTROLES AUTOMÁTICOS
9. RESOLUCIÓN DE PROBLEMAS BÁSICOS
2ª PARTE: INSTALACIÓN
10. NOMBRE DE LAS PIEZAS
11. CICLO DE REFRIGERANTE
12. INSTALACIÓN DE LAS UNIDADES
13. TUBERÍA Y CARGA DE REFRIGERANTE
14. TUBERÍA DE DESAGÜE
15. CABLEADO ELÉCTRICO
16. PRUEBAS DE FUNCIONAMIENTO
17. RESUMEN DE SEGURIDAD Y AJUSTE DE LOS DISPOSITIVOS DE CONTROL
18. RESOLUCIÓN DE PROBLEMAS
INHALTSVERZEICHNIS INDEX
TEIL I – BETRIEB
1. ALLGEMEINE INFORMATIONEN
2. SICHERHEIT
3. PRODUKTÜBERSICHT
4. WICHTIGER HINWEIS
5. TRANSPORT UND BEDIENUNG
6. VOR DEM BETRIEB
7. FERNBEDIENUNG
8. AUTOMATISCHE STEUERUNG
9. GRUNDLEGENDE FEHLERBESEITIGUNG
TEIL II – INSTALLATION
10. TEILEBEZEICHNUNG
11. KÜHLKREISLAUF
12. GERÄTEINSTALLATION
13. KÄLTEMITTELROHRE UND KÄLTEMITTELMENGE
14. ABFLUSSLEITUNGEN
15. KABELANSCHLUSS
16. TESTLAUF
17. SICHERHEITSÜBERSICHT UND EINSTELLUNG DER STEUERGERÄTE
18. FEHLERBEHEBUNG
PARTIE I – FONCTIONNEMENT
1. INFORMATIONS GÉNÉRALES
2. SÉCURITÉ
3. GUIDE DU PRODUIT
4. REMARQUES IMPORTANTES
5. TRANSPORT ET MANIPULATION
6. AVANT L’UTILISATION
7. TÉLÉCOMMANDE
8. CONTRÔLES AUTOMATIQUES
9. DÉPANNAGE DE BASE
PARTIE II – INSTALLATION
10. NOMENCLATURE DES PIÈCES
11. CYCLE FRIGORIFIQUE
12. INSTALLATION DES UNITÉS
13. TUYAUTERIE DU FLUIDE FRIGORIGÈNE ET CHARGE DU FLUIDE FRIGORIGÈNE
14. TUYAUTERIE D’ÉVACUATION DES CONDENSATS
15. CÂBLAGE ÉLECTRIQUE
16. TEST DE FONCTIONNEMENT
17. SOMMAIRE DES DISPOSITIFS DE SÉCURITÉ & RÉGLAGE DES ORGANES DE CONTRÔLE
18. DEPANNAGE
INDICE ÍNDICE
PARTE I FUNZIONAMENTO
1. INFORMAZIONI GENERALI
2. SICUREZZA
3. GUIDA DEL PRODOTTO
4. NOTA IMPORTANTE
5. TRASPORTO E MOVIMENTAZIONE
6. PROCEDURA PRELIMINARE
7. CONTROLLO REMOTO
8. CONTROLLI AUTOMATICI
9. RISOLUZIONE DEI PROBLEMI MINORI
PART II INSTALLAZIONE
10. NOMENCLATURA DEI COMPONENTI
11. CICLO DI REFRIGERAZIONE
12. INSTALLAZIONE DELLE UNITÀ
13. LINEA DEL REFRIGERANTE E CARICA DI REFRIGERANTE
14. LINEA DI DRENAGGIO
15. COLLEGAMENTI ELETTRICI
16. COLLAUDO DI PROVA
17. PRECAUZIONI PER LA SICUREZZA E IMPOSTAZIONI DEI DISPOSITIVI DI CONTROLLO
18. RISOLUZIONE DEI PROBLEMI
PARTE I FUNCIONAMENTO
1. INFORMAÇÃO GERAL
2. SEGURANÇA
3. GUIA DO PRODUTO
4. NOTA IMPORTANTE
5. TRANSPORTE E MANUSEAMENTO
6. ANTES DE ARRANCAR A UNIDADE
7. CONTROLO REMOTO
8. CONTROLOS AUTOMÁTICOS
9. RESOLUÇÃO DE PROBLEMAS BÁSICOS
PARTE II INSTALAÇÃO
10. NOME DAS PEÇAS
11. CICLO DE REFRIGERAÇÃO
12. INSTALAÇÃO DAS UNIDADES
13. TUBAGEM E CARGA DE REFRIGERANTE
14. TUBAGEM DE ESGOTO
15. LIGAÇÕES ELÉCTRICAS
16. PROVA DE FUNCIONAMENTO
17. SUMÁRIO DE SEGURANÇA E AJUSTE DE DISPOSITIVO DE CONTROLO
18. RESOLUÇÃO DE PROBLEMAS
INDHOLDSFORTEGNELSE INHOUDSOPGAVE
DEL I - BETJENING
1. GENEREL INFORMATION
2. SIKKERHED
3. PRODUKTVEJLEDNING
4. VIGTIG MEDDELELSE
5. TRANSPORT OG HÅNDTERING
6. FØR DRIFT
7. FJERNBETJENING
8. AUTOMATISK BETJENING
9. BASIS FEJLFINDING
DEL II- MONTERING
10. NAVNE PÅ DELE
11. KØLEKREDSLØB
12. MONTERING AF ENHEDER
13. KØLERØRSYSTEM OG PÅFYLDNING AF KØLEMIDDEL
14. AFLØBSRØR
15. ELEKTRISK LEDNINGSFØRING
16. TESTKØRSEL
17. OVERSIGT OVER INDSTILLINGER FOR SIKKERHEDS- OG KONTROLENHEDER
18. FEJLFINDING
DEEL I BEDIENING
1. ALGEMENE INFORMATIE
2. VEILIGHEID
3. PRODUCTGIDS
4. BELANGRIJKE MEDEDELING
5. TRANSPORT EN HANTERING
6. VOORDAT U HET SYSTEEM IN GEBRUIK NEEMT
7. AFSTANDSBEDIENING
8. AUTOMATISCHE BESTURING
9. ELEMENTAIRE PROBLEMEN OPLOSSEN
DEEL II INSTALLATIE
10. NAMEN VAN ONDERDELEN
11. KOUDEMIDDELCYCLUS
12. INSTALLATIE VAN DE UNITS
13. KOELMIDDELLEIDINGEN & KOELMIDDEL VULLEN
14. AFVOERLEIDING
15. ELEKTRISCHE BEDRADING
16. PROEFDRAAIEN
17. VEILIGHEIDSSAMENVATTING & BESTURINGSINRICHTING
18. PROBLEMEN OPLOSSEN
INNEHALLSFÖRTECKNING ΕΥΡΕΤΗΡΙΟ
DEL I ANVÄNDNING
1. ALLMÄN INFORMATION
2. SÄKERHET
3. PRODUKTGUIDE
4. VIKTIG ANMÄRKNING
5. TRANSPORT OCH HANTERING
6. FÖRE DRIFT
7. FJÄRRKONTROLL
8. AUTOMATIK KONTROLLANORDNING
9. GRUNDLÄGGANDE FELSÖKNING
DEL II INSTALLATION
10. DELARNAS NAMN
11. KYLMEDIETS CYKEL
12. INSTALLATION AV ENHETER
13. KYLRÖR & PÅFYLLNING AV KYLMEDIUM
14. DRÄNERINGSRÖR
15. ELEKTRISKA KABLAR
16. PROVKÖRNING
17. SÄKERHETSSAMMANFATTNING OCH SÄKERHETSINSTÄLLNINGAR
18. FELSÖKNING
ΜΕΡΟΣ Ι – ΛΕΙΤΟΥΡΓΙΑ
1. ΓΕΝΙΚΕΣ ΠΛΗΡΟΦΟΡΙΕΣ
2. ΑΣΦΆΛΕΙΑ
3. ΟΔΗΓΟΣ ΠΡΟΪΟΝΤΟΣ
4. ΣΗΜΑΝΤΙΚΗ ΠΑΡΑΤΗΡΗΣΗ
5. ΜΕΤΑΦΟΡΆ ΚΑΙ ΧΕΙΡΙΣΜΌΣ
6. ΠΡΙΝ ΤΗ ΛΕΙΤΟΥΡΓΙΑ
7. ΧΕΙΡΙΣΤΗΡΙΟ
8. ΑΥΤΟΜΑΤΕΣ ΛΕΙΤΟΥΡΓΙΕΣ
9. ΑΝΤΙΜΕΤΩΠΙΣΗ ΠΡΟΒΛΗΜΑΤΩΝ - ΒΑΣΙΚΑ
ΜΕΡΟΣ ΙΙ – ΕΓΚΑΤΑΣΤΑΣΗ
10. ΟΝΟΜΑΤΑ ΕΞΑΡΤΗΜΑΤΩΝ
11. ΚΥΚΛΟΣ ΨΥΞΗΣ
12. ΕΓΚΑΤΑΣΤΑΣΗ ΕΣΩΤΕΡΙΚΩΝ ΜΟΝΑΔΩΝ
13. ΣΩΛΗΝΩΣΕΙΣ ΨΥΚΤΙΚΟΥ & ΠΛΗΡΩΣΗ ΜΕ ΨΥΚΤΙΚΟ ΜΕΣΟ
14. ΣΩΛΗΝΩΣΕΙΣ ΑΠΟΧΕΤΕΥΣΗΣ
15. ΗΛΕΚΤΡΙΚΗ ΚΑΛΩΔΙΩΣΗ
16. ΔΟΚΙΜΑΣΤΙΚΗ ΛΕΙΤΟΥΡΓΙΑ
17. ΣΥΝΟΠΤΙΚΕΣ ΠΡΟΦΥΛΑΞΕΙΣ ΑΣΦΑΛΕΙΑΣ & ΡΥΘΜΙΣΕΙΣ ΣΥΣΚΕΥΩΝ ΕΛΕΓΧΟΥ
18. ΑΝΤΙΜΕΤΩΠΙΣΗ ΠΡΟΒΛΗΜΑΤΩΝ
EN English Original version
ES Español Versión traducida
DE Deutsch Übersetzte Version
FR Français Version traduite
IT Italiano Versione tradotta
PT Português Versão traduzidal
DA Dansk Oversat version
NL Nederlands Vertaalde versie
SV Svenska Översatt version
EL ΕΛΛΗΝΙΚΑ Μεταφρασμένη έκδοση
General information
1
PMML0317A rev.1 - 11/2013
ENGLISH
PART I - OPERATION
1.2 ENVIRONMENT-FRIENDLY UNITS
1 GENERAL INFORMATION
1.1 GENERAL NOTES
No part of this publication may be reproduced, copied, led or transmitted in any shape or form without the permission of HITACHI Air Conditioning Products Europe, S.A.U.
Within the policy of continuous improvement of its products, HITACHI Air Conditioning Products Europe, S.A.U. reserves the right to make changes at any time without prior notication and without being compelled to introducing them into products subse­quently sold. This document may therefore have been subject to amendments during the life of the product.
HITACHI makes every effort to offer correct, up-to-date docu­mentation. Despite this, printing errors cannot be controlled by HITACHI and are not its responsibility.
As a result, some of the images or data used to illustrate this document may not refer to specic models. No claims will be ac­cepted based on the data, illustrations and descriptions included in this manual.
This range of HITACHI outdoor units uses environmentally-friend­ly R410A gas refrigerant, and the RoHS and Greed Dot regula­tions are applied throughout the manufacturing and installation process to reect HITACHI’s awareness of environmental respect and commitment.
2 SAFETY
2.1 APPLIED SYMBOLS
During normal air conditioning system design work or unit instal­lation, greater attention must be paid in certain situations requir­ing particular care in order to avoid injuries an damage to the unit, the installation or the building or property.
Situations that jeopardise the safety of those in the surrounding area or that put the unit itself a risk will be clearly indicated in this manual.
To indicate these situations, a series of special symbols will be used to clearly identify these situations.
Pay close attention to these symbols and to the messages follow­ing them, as your safety and that of others depends on it.
DA N G ER
• Thetextfollowingthissymbolcontainsinformationand instructionsrelatingdirectlytoyoursafetyandphysical wellbeing.
• Nottakingthese instructionsintoaccountcouldleadto serious,veryseriousorevenfatalinjuriestoyouandoth­ersintheproximitiesoftheunit.
In the text following the danger symbol you can also nd informa­tion on safe procedures during unit installation.
CA U T IO N
• The text following this symbol contains information and in­structions relating directly to your safety and physical wellbe­ing.
• Not taking these instructions into account could lead to minor injuries to you and others in the proximities of the unit.
• Not taking these instructions into account could lead to unit damage.
In the text following the caution symbol you can also nd informa­tion on safe procedures during unit installation.
NO T E
• The text following this symbol contains information or instruc­tions that may be of use or that require a more thorough ex­planation.
• Instructions regarding inspections to be made on unit parts or systems may also be included.
2
Product guide
PMML0317A rev.1 - 11/2013
3 PRODUCT GUIDE
DA N G ER
• Donotpourwaterintotheindoororoutdoorunit.These productsareequippedwithelectricalparts.Ifwatercon­tactswithelectricalcomponentsthenitwillcauseaseri­ouselectricalshock.
• Donottouchoradjustsafetydevicesinsidetheindooror outdoorunits.Ifthesedevicesaretouchedoradjusted,it maycauseaseriousaccident.
• Donot open the service cover or access the indoor or outdoorunitswithoutdisconnectingthemainpowersup­ply.
• IncaseofreTurnOFFthemainswitch,putoutthere atonceandcontactyourservicecontractor.
CA U T IO N
• Do not use any sprays such as insecticide, lacquer, hair spray or other ammable gases within approximately one (1) meter from the system.
• If circuit breaker or fuse is often activated, stop the system and contact your service contractor.
• Do not make service or inspections tasks by yourself. This works must be performed by qualied service person.
• Do not put any strange material (sticks, etc...) into the air inlet and outlet. These units have high speed rotating fans and it is dangerous that any object touches them.
• Refrigerant leakage can cause difculty with breathing due to insufcient air.
• This appliance must be used only by adult and capable peo­ple, having received the technical information or instructions to handle properly and safely this appliance.
• Children should be supervised to ensure that they do not play with the appliance.
NO T E
It is recommended to ventilate the room every 3 or 4 hours.
2.2 ADDITIONAL INFORMATION ABOUT SAFETY
3.1 CLASSIFICATION OF IVX OUTDOOR UNITS MODELS
Unit type (Outdoor unit): RAS
Position-separating hyphen (xed)
Compressor power (HP): 3, 4, 5, 6, 8, 10
H = Heat pump
V = Single phase unit (1~ 230V 50Hz)
- = Three phase unit (3N~ 400V 50Hz)
N = R410A refrigerant
P: Premium series C: Standard series
- = Series 0 1 = Series 1
E = Made in Europe
XXX XX H (X) N X (X) X
3.2 CLASSIFICATION OF ES OUTDOOR UNITS MODELS
Unit type (Outdoor unit): RAS
Position-separating hyphen (xed)
Compressor power (HP): 4
H = Heat pump
V = Single phase unit (1~ 230V 50Hz)
- = Three phase unit (3N~ 400V 50Hz)
R = Inverter system
N = R410A refrigerant
S = ES series
Series
E = Made in Europe
XXX XX H (X) R N S 3 X
Important notice
3
PMML0317A rev.1 - 11/2013
ENGLISH
4 IMPORTANT NOTICE
CA U T IO N
This unit is designed for commercial and light industrial applica­tion. If installed in house hold appliance, it could cause electro­magnetic interference.
Start-up and Operation: Check to ensure that all the stop valves are fully opened and no obstacle exists at the inlet/outlet sides before start-up and during the operation.
Maintenance: Periodically check the high pressure side pres­sure. If the pressure is higher than the maximum allowable pres­sure, stop the system and clean the heat exchanger or remove the cause.
Maximum Allowable Pressure and High Pressure Cut-out Value:
Outdoor Unit Model Refrigerant
Maximum Allowable
Pressure (MPa)
High Pressure Switch
Cut-out Value (MPa)
RAS-(3-10)H(V)NP(1)E
RAS-(8-10)HNCE
R410A 4.15 4.00 ~ 4.10
RAS-4H(V)RNS3E R410A 4.15 4.00 ~ 4.10
• Verify, in accordance with the manuals which appear in the outdoor and indoor units, that all the information required for the correct installation of the system is included. If this is not the case, contact your distributor.
• HITACHI pursues a policy of continuing improvement in design and performance of products. The right is therefore reserved to vary specications without notice.
• HITACHI cannot anticipate every possible circumstance that might involve a potential hazard.
• This air conditioner has been designed for standard air condi­tioning for human beings. For use in other applications, please contact your HITACHI dealer or service contractor.
• No part of this manual may be reproduced without written per­mission.
• If you have any questions, contact your service contractor of HITACHI.
• This manual gives a common description and information for this air conditioner which you operate as well as for other models.
• Check and make sure that the explanations of each part of this manual correspond to your air conditioner model.
• Refer to the models codication to conrm the main charac­teristics of your system.
• Signal words (DANGER, WARNING and CAUTION) are used to identify levels of hazard seriousness. Denitions for iden­tifying hazard levels are provided below with their respective signal words.
• It is assumed that this unit will be operated and serviced by English speaking people. If this is not the case, the customer should add safety, caution and operating signs in the native language of the personal.
• This air conditioner has been designed for the following tem­perature. Operate the air conditioner within this range:
Temperature
Maximum Minimum
Cooling
Mode
Indoor 32°C DB/23°C WB 21°C DB/15°C WB
Outdoor 46 ºC DB (*) -5 °C DB
Heating
Mode
Indoor 27 °C DB 15 °C DB
Outdoor 15 °C WB -20 °C WB (**)
DB: Dry Bulb Temperature WB: Wet Bulb Temperature (*) 43ºC RAS-4H(V)RNS3E
(**) -10ºC RAS-4H(V)RNS3E
• These operations modes are controlled by the remote control switch.
• This manual should be considered as a permanent part of the air conditioner. This manual gives a common description and information for this air conditioner which you operate as well as for other models.
DA N G ER
Pressure Vessel and Safety Device: This air conditioner is equipped witha highpressure vesselunder PED(Pres­sure Equipment Directive). The pressure vessel has been designed and tested before shipment according to PED.Also, in order to prevent the system from an abnor­mal pressure, a high pressure switch, which needs no eld adjustment, is utilized in the refrigeration system. Therefore, this air conditioner is protected from abnormal pressures. However, if abnormally high pressure is ap­pliedto the refrigerationcycle including thehigh pressure vessel(s),itwillresultinseriousinjuryordeathduetoexplo­sionofthepressurevessel.Donotapplyapressurehigher thanthefollowingpressuretothesystem,bymodifyingor changingthehighpressureswitch.
4
Transportation and handling
PMML0317A rev.1 - 11/2013
NO T E
The label for the vessel under PED are attached on the high pres­sure vessel. The pressure vessel capacity and vessel category are indicated on the vessel.
Location of High Pressure Switch
Compressor
NO T E
The high pressure switch is indicated on the electrical wiring di­agram in the outdoor unit as PSH connected to printed circuit board (PCB1) in the outdoor unit
Structure of High Pressure Switch
Contact Point Pressure Detected
Connected to the electrical wire
DA N G ER
• Donotchangethehigh-pressureswitchlocallyorchange thehighpressurecut-outsetvaluelocally.Ifchanged,it willcauseseriousinjuryordeathduetoexplosion.
• Donotattempttoturnservicevalverodbeyonditsstop.
6 BEFORE OPERATION
CA U T IO N
• Supply electrical power to the system for approximately 12 hours before start-up or a long shutdown. Do not start the system im­mediately after power supply, it may cause a compressor failure because the compressor is not heated well.
• When the system is started after a shutdown longer that ap­proximately 3 months, it is recommended to check the system by your service contractor.
• Turn OFF the main switch when the system is to be stopped for a long period of time: If the main switch is not turned OFF, electricity will be used, because the oil heater is always ener­gised during compressor stopping.
• Make sure that the outdoor unit is not covered with snow or ice. If covered, remove it by using hot water (approximately 50°C). If the water temperature is higher that 50 °C, it will cause damage to plastic parts.
7 REMOTE CONTROLLER
It is advisable to use PC-ART or PC-ARF remote controller (both optional). For more information about it installation and operation, please refer to its corresponding Installation and Operation Manuals.
5 TRANSPORTATION AND HANDLING
When hanging the unit, ensure a balance of the unit, check safety and lift it up smoothly
Do not remove any packing materials.
Hang the unit under packing condition with two ropes.
For safety reasons ensure that the outdoor unit is lifted smoothly and does not lean
Model
Gross
Weight
(kg)
RAS-3HVNP1E 77
RAS-(4-6)H(V)NP1E 116
RAS-4H(V)RNS3E 78
Model
Gross
Weight
(kg)
RAS-8HNPE
152
RAS-8HNCE
RAS-10HNPE
154
RAS-10HNCE
RAS-3HVNP1E RAS-(4-6)H(V)NP1E
RAS-4H(V)RNS3E RAS-(8-10)HNPE
RAS-(8-10)HNCE
0.7 -1.0 m
> 60º
Automatic controls
5
PMML0317A rev.1 - 11/2013
ENGLISH
8 AUTOMATIC CONTROLS
The system is equipped with the following functions.
Three minute guard
The compressor remains off for at least 3 minutes once it has stopped. If the system is started within approximately 3 minutes after it has stopped, the RUN indicator is activated. However, the cooling operation or the heating operation remains off and does not start until after 3 minutes has elapsed.
Operation may stop for 6 minutes maximum to protect compressor.
Frost prevention during cooling operation
When the system is operated in a low temperature room, the cooling operation may be changed to fan operation for a while to avoid frost formation on the indoor heat exchanger.
Automatic restart after power failure
If the power supply is interrupted for short periods of time (up to 2 seconds) the Remote Control switch will retain the settings and the unit will restart when the power is restored. If Automatic Re­start is required after periods of lost power supply in excess of 2 seconds please contact your distributor (optional function).
Slow air control during heating operation
Can be setting than when the compressor is stopped while the thermostat is OFF, or the system is performing the automatic de­frosting operation, the fan speed is set at the slow position.
Automatic defrosting cycle
When the heating operation is stopped by pressing RUN/STOP switch, frosting on the outdoor unit is checked and the defrosting operation may be performed for the maximum of 10 minutes.
Prevention of overload operation
When the outdoor temperature is too high during heating opera­tion, heating operation is stopped due to activation of the outdoor thermistor until the temperature becomes low.
Hot start during heating operation
To prevent cold air discharge, the fan speed is controlled from the slow position to the set position according to the discharge air temperature. At this time the lover is xed horizontally.
9 BASIC TROUBLESHOOTING
CA U T IO N
• When water leakage from the indoor unit occurs, stop the op­eration and contact your contractor
• When you smell or white smoke occurs from the unit, stop the system and contact your contractor.
This is not abnormal
• Sound from deforming Part
During system starting or stopping, and abrading sound might be heard. However, this is due to thermal deformation of plastic parts. It is not abnormal.
• Refrigerant Flow Sound
While the system is being started or stopping, sound from the refrigerant ow may be heard.
• Smells from Indoor Unit
Smell adheres on indoor unit after a long period of time. Clean the air lter and panels or make a good ventilation.
• Steam from Outdoor Heat Exchanger
During defrosting operation, ice on the outdoor heat exchanger is melted, resulting in making steam.
• Dew on Air Panel
When the cooling operation continues for a long period of time under high humidity conditions (higher than 27°C DB/80% R.H.), dew can form on the air panel.
• Dew on Cabinet
When the cooling operation continues for a long period of timer (higher than 27°C DB/80% R.H.), dew can form on the cabinet.
• Sound for the indoor unit heat exchanger
During the cooling operation, a sound may be heard from the in­door unit heat exchanger due to water freezing or melting.
No operation
Check whether the SET TEMPERATURE is set at the correct temperature.
Not cooling well or heating well
- Check for obstruction of air ow of the outside or inside units.
- Check if too much heat source exists in the room.
- Check if the air lter is clogged with dust.
- Check to see if the doors or windows are opened or not.
- Check if the temperature condition is not within the operat­ing range.
Abnormal swing louver’s position
Check if the four louver’s position at the air outlet are in same position.
If trouble still remains...
If the trouble still remains even after checking the above items, contact your service contractor and inform the following data:
- Unit Model Name
- Content of Trouble
- Alarm Code no. on Liquid Crystal Display
NO T E
Except for a long period of shutdown, keep the main switch ON, since the oil heater is energised when the compressor is stopped.
6
Name of parts
PMML0317A rev.1 - 11/2013
PART II - INSTALLATION
10 NAME OF PARTS
10.1 Example of RAS-3HVNP1E / RAS-4H(V)RNS3E
No. Part Name
1 Compressor 2 Accumulator 3 Heat exchanger 4 Propeller fan 5 Fan motor 6 Strainer 7 Distributor 8 Reversing valve
9
Micro-computer control expansion
valve 10 Solenoid valve for hot gas 11 Stop valve for gas line
No. Part Name
12 Stop valve for liquid line 13 Check Joint 14 Electrical box 15 High pressure switch for protection
16
Sensor for refrigerant pressure (RAS-
3HVNP1E only) 17 Pressure switch for control 18 Silencer 19 Crankcase heater 20 Vibration absorbing rubber (3pcs.) 21 Air outlet 22 Air inlet
7T143458
Name of parts
7
PMML0317A rev.1 - 11/2013
ENGLISH
10.2 Example of RAS-(4-6)H(V)NP1E
No. Part Name
1 Compressor 2 Heat exchanger 3 Propeller fan (2pcs.) 4 Fan motor (2pcs.) 5 Strainer 6 Distributor 7 Reversing Valve
8
Micro-computer control expansion valve
9 Solenoid valve
10 Check valve
11 Stop valve for gas line
12 Stop valve for liquid line
No. Part Name
13 Receiver 14 Accumulator 15 Check joint 16 Electrical box 17 High pressure switch for protection 18 Sensor for refrigerant pressure 19 Pressure switch for control 20 Silencer 21 Crankcase heater 22 Vibration absorbing rubber (4pcs.) 23 Air outlet 24 Air inlet
7T143459
8
Refrigerant cycle
PMML0317A rev.1 - 11/2013
11 REFRIGERANT CYCLE
Example of RAS-4H(V)NP1E:
D
C
B
A
E
7S138311
F
Mark Part name
1 Compressor 2 Heat exchanger 3 Accumulator 4 Receiver 5 Micro-computer control expansion valve 6 Reversing valve 7 Solenoid valve for gas bypass 8 Strainer
9 Distributor 10 Check joint 11 High pressure switch for protection 12 Sensor for refrigerant pressure 13 Stop valve for gas line 14 Stop valve for liquid line 15 Check valve 16 Silencer 17 Pressure switch for control
Example of RAS-4H(V)RNS3E:
A
B
C
D
F
F
E
7S136195
No. Part name
1 Compressor 2 Heat exchanger 3 Accumulator 4 Micro-Computer control expansion valve 5 Reversing valve 6 Solenoid valve for gas bypass 7 Strainer 8 Distributor
9 Check joint 10 High pressure switch for protection 11 Pressure switch for control 12 Stop valve for gas line 13 Stop valve for liquid line 14 Silencer
R410A 4.15 MPa
Refrigerant ow
or cooling
Refrigerant ow
for heating
Connection by
are nut
Connection by
welding
Gas refrigerant
Leakage test
pressure
Mark Part name
A Gas line refrigerant piping connection B Liquid line refrigerant piping connection C Outdoor unit D Ambient thermistor E Discharge gas thermistor
F Pipe thermistor
Units installation
9
PMML0317A rev.1 - 11/2013
ENGLISH
12 UNITS INSTALLATION
12.1 OUTDOOR UNITS INSTALLATION
12.1.1 Installation space
(Unit: mm)
Blocked in Inlet Side
Upper Side Open
Single Installation Multiple Installation (Two units or more)
200 or more of the back space is acceptable when the right and left sides are open. Dimensions in ( ) shows numbers especially for RAS-3HVNP1E.
Allow 100 mm of space between units. Leave open both right and left sides. Dimensions in ( ) shows numbers especially for RAS-3HVNP1E.
Be sure to use the fan direction guide. Leave open both right and
left sides.
Be sure to use the fan direction guide. Allow 100 mm of space between units.
Leave open both right and left sides.
CA U T IO N
• Transport the products as close to the installation location as practical before unpacking.
• Do not put any material on the products.
• Apply four lifting wires on to the outdoor, when lifting it by crane
CA U T IO N
• Install the outdoor unit with sufcient clearance around it for operation and maintenance as shown in the next gures. Install the outdoor unit where good ventilation is available
• Do not install the outdoor unit where is a high level of oil mist, salty air or sulphurous atmosphere.
• Install the outdoor unit as far as practical (being at least 3 meters) from electromagnetic wave radiator (such as medical equipment).
• For cleaning, use noninammable and nontoxic cleaning liq­uid. Use of inammable agent may cause explosion or re.
• Work with sufcient ventilation, for working in an enclosed space may cause oxygen deciency. Toxic gas may be pro­duced when cleaning agent is heated to high temperature by, e.g., being exposed to re.
• Cleaning liquid shall be collected after cleaning.
• Pay attention not to clamp cables when attaching the service cover to avoid electric shock or re.
CA U T IO N
• Keep clearance between the units of more than 100mm, and avoid obstacles that may hamper air intake, when installing more than one units together.
• Install the outdoor unit in the shade or not exposed to di­rect sunshine or direct radiation from high temperature heat source.
• Do not install the Outdoor Unit in a space where a seasonal wind directly blows to the Outdoor fan.
• Check to ensure that the foundation is at, level and suf­ciently strong.
• Install the unit in a restricted area not accessible by the gen­eral public
• Aluminium ns have very sharp edges. Pay attention to the ns to avoid injury.
10
Units installation
PMML0317A rev.1 - 11/2013
Blocked in Inlet Side
Upper Side Blocked
Single Installation Multiple Installation (Two units or more)
100 mm or more of the side space is acceptable on the service cover side.
Allow 100 mm of space between units. Leave open both right and left sides..
Leave open both right and left sides.
Be sure to use the fan direction guide. Allow 100 mm of space between units. Leave open both right and left sides. No more than 2 units for multiple installation.
The length A is as shown in the following table:
L A 0 < L ≤ 1/2H 600 or greater 1/2H < L≤ H 1400 or greater
When L > H use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
Outlet Side Blocked
Upper Side Open
Single Installation Multiple Installation (Two units or more)
Allow 100 mm of space between units. Both right and left sides shall be open.
Be sure to use the fan direction guide. Leave open both right and left sides.
Be sure to use the fan direction guide. Allow 100 mm of space between units. Leave open both right and left sides. No more than 2 units for multiple installation.
The length A is as shown in the following table:
L A 0 < L ≤ 1/2H 600 or greater 1/2H < L≤ H 1400 or greater
When L > H use a base for outdoor unit to make L ≤ H.
Close the base not to allow the outlet air bypassed.
Units installation
11
PMML0317A rev.1 - 11/2013
ENGLISH
12.1.2 Installation place provision
Concrete Foundation
1 Foundation could be on at and is recommended be 100-300
mm higher than ground level.
2 Install a drainage around foundation for smooth drain 3 When installing the outdoor unit x the unit by anchor bolts
of M10.
4 When installing the unit on a roof or a veranda, drain water
sometimes turns to ice on a cold morning. Therefore, avoid draining in an area that people often use because it is slippery.
* Space for downward piping space
Description
Outdoor Unit
Cut this portion of bolt If not, it’s difcult to remove Service Cover
Mortar Hole (Ø100xDepth 150)
Anchor Bolt M10 (Ø12.5 Hole)
Drainage (Wide 100xDepth 150)
Drainage
Vibration-proof rubber
NO T E
When the mark * dimension is secured, piping work from bottom side is easy without interference of foundation.
5 The whole of the base of the outdoor unit should be installed
on a foundation. When using vibration-proof mat, it should also be positioned the same way. When installing the outdoor unit on a eld supplied frame, use metal plates to adjust the frame width for stable installation as shown in below gure.
70 mm Base width of outdoor unit
Outdoor unit is unstable
Frame
60mm
Frame with (Field supplied)
INCORRECT
CORRECT
Outdoor unit is stable
70 mm
Base width of outdoor unit
Frame
100mm or more
Metal plate
Recommended Metal Plate Size
- (Field-Supplied) Material: Hot-Rolled Mild Steel
- Plate (SPHC) Plate Thickness: 4.5 T
12
Units installation
PMML0317A rev.1 - 11/2013
Fix Unit to the wall
1. Fix the Unit onto the wall as the g­ure indicates. (eld supplied stay)
2. Ensure the foundation so that avoid the deforming and noise.
3. In case of prevention from vibration transfer to the building, use rubber Mat.
Rubber Material (Field Supplied)
Mark Dimension
Model
RAS-3HVNP1E
RAS-4H(V)RNS3E
RAS-(4-10)H(V)NP(1)E
A (mm) 529 1109
Suspended unit
1. Suspend the unit as the drawing indicates.
2. Ensure that wall can resist the Out­door unit weight indicated in speci­cation label plate.
3. It is recommended to select each foot support to bear the full weight of the unit (in order to consider stress fatigue applied when unit is working too).
Wall bracket (*)
Anchor Bolts (*)
(*) Field supplied
CAUTION
Pay attention to the following for installation:
• Installation shall ensure that outdoor unit will not incline, vibrate, make noise or fall down by a blast of wind or in an earthquake. Calculate quake-resistance strength to ensure that installation is strong enough against falling. Fix the unit with wires (eld supplied) when installing in a location without walls or windbreak and likely exposed to a blast of wind.
• To use a vibration-proof mat, x four places to the front and back.
Installing location where the unit will be exposed to strong wind.
Follow the instructions below to install on the rooftop or a location without sur­rounding buildings, where strong wind is expected against the product.
1. Choose a location where the outlet or inlet side of the product will not be exposed to strong wind.
2. When the outlet is exposed to strong wind: Direct strong wind may cause lack of air ow and adversely affect to the operation.
CAUTION
Excessive strong wind against the outdoor unit outlet may cause inverse rotation and damage the fan and motor.
Units installation
13
PMML0317A rev.1 - 11/2013
ENGLISH
Air ow guide wind guard and snow protection hood
RAS-3HVNP1E/RAS-4H(V)RNS3E
Optional parts Model
Air ow guide AG-335A
1 Air ow guide 2 Wind Guard 3 Snow protection hood
Wind guard WSP-335A
Snow protection hood
Zinc plate
Air outlet ASG-NP335F Air inlet of rear side ASG-NP80B Air inlet of side face ASG-NP80L
Stainless plate (SUS304)
Air outlet ASG-NP335F52 Air inlet of rear side ASG-NP160BS2
Air inlet of side face ASG-NP160LS2
1. Fixing screw (Accessories).
2. Rear suction hood
3. Wire rope (Optional. For overturning protection)
4. Air discharge grille
5. Left suction hood
6. Air discharge hood
A. Left side
B. Front side
C. Rear side
RAS-(4-6)H(V)NPE / RAS-(8-10)HN(P/C)E
Optional parts Model
Air ow guide AG-335A X 2
1 2
3
1 Air ow guide 2 Wind Guard 3 Snow protection hood
Wind guard WSP-335A X 2
Snow protection hood
Zinc plate
Air outlet ASG-NP335F X 2 Air inlet of rear side ASG-NP280B Air inlet of side face ASG-NP280L
Stainless plate
(NSSC 180)
Air outlet ASG-NP335FS 2X 2 Air inlet of rear side ASG-280BS2
Air inlet of side face ASG-NP280LS2
1. Left suction hood
2. Fixing screw (Accessories)
3. Rear suction hood Upper side
4. Wire rope (Optional. For overturning protection)
5. Rear suction hood Lower side
6. Air discharge hood
7. Air discharge grille
A. Front side
B. Left side
C. Rear side
14
Refrigerant piping & refrigerant charge
PMML0317A rev.1 - 11/2013
13 REFRIGERANT PIPING & REFRIGERANT CHARGE
13.1 PIPING MATERIALS
1 Prepare locally-supplied copper pipes. 2 Select the piping size with the correct thickness and correct
material which can have sufcient pressure strength.
3 Select clean copper pipes. Make sure there is no dust and
moisture inside. Blow the inside of the pipes with oxygen free nitrogen to remove any dust and foreign materials before con­necting pipes.
NO T E
• A system with no moisture or oil contamination will give maxi­mum performance and lifecycle compared to that of a poorly prepared system. Take particular care to ensure all copper piping is clean and dry internally.
• There is no refrigerant in the cycle of the indoor unit.
CA U T IO N
• Cap the end of the pipe when pipe is to be inserted through a hole.
• Do not put pipes on the ground directly without a cap or vinyl tape at the end of the pipe
• If piping installation is not completed until next day or over a longer period of time, braze off the ends of the piping and charge with oxygen free nitrogen through a Schrader valve type access tting to prevent moisture and particle contami­nation.
• Do not use insulation material that contains NH3 because it can damage cooper pipe material and can be a source of fu­ture leakage.
• Completely insulate both refrigerant gas piping and liquid pip­ing between the indoor unit(s) and the outdoor unit.
• If not insulated, dew will ocur on the piping surface
13.2 SUSPENSION OF REFRIGERANT PIPING
Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc…
(If touched, abnormal sound may occur due to the vibration of the piping. Pay special attention in case of short piping length).
1~15m
Indoor unit
Fire-Proof
Section Treatment
Do not x the refrigerant piping directly with the metal ttings (The refrigerant piping may expand and contract).
Some examples for suspension method are shown below.
For Suspending Heavies
For piping along the wall
For instant installation work
Refrigerant piping & refrigerant charge
15
PMML0317A rev.1 - 11/2013
ENGLISH
13.3 PIPING CONNECTION FOR OUTDOOR UNIT
1 The pipes can be connected from 4 directions. Make holes in
the piping cover or cabinet for taking out pipes. Take the pip­ing cover away from the unit, and make holes by cutting along the guideline at the rear of the cover or punching with a driver. Remove the burr with a cutter, and place a insulation (eld supplied) to protect cables and pipes.
(picture as example)
Description
Rear side piping work
Pipe Cover
Right side piping work
Bottom side piping work (Knock out hole)
Front side piping work
Piping work
Stop Valve
Removing Direction for Service Cover
CA U T IO N
Notes to open/close the service cover:
• Remove the screws following the instructions to the above gure.
• Slowly press down the cover.
NOTE
Hold the cover with a hand to remove screws as the cover may fall down.
Service cover
Hook (three places): two fans Hook (two places): one fan
(picture as example)
For the front and side piping
Front piping hole
Side piping hole
To use racking or conduit tubes, check the size and remove part following the slit.
NO T E
Place insulation (eld supplied) to protect cables and pipes from being damaged by plate edges.
For the downward piping
Gas piping
Knock-out hole
Bottom base
Cables
Liquid piping
NO T E
Cables shall not contact directly to the pipes.
For the rear side piping
Rear Cover
NO T E
Remove the rear pipe cover under the rear cover and remove
part following the slit.
16
Refrigerant piping & refrigerant charge
PMML0317A rev.1 - 11/2013
2 Mount the piping cover in order to avoid water entering into
the unit. Seal the holes where pipes and wires are inserted, by using a insulation (eld-supplied).
3 If the eld-supplied piping is connected with stop valves di-
rectly, it is recommended use a tube bender.
4 Check to ensure that the stop valves are closed completely
before connecting pipes.
5 Connect the eld supplied refrigerant pipes to the indoor unit
and outdoor unit. Apply the oil thinly at the seat are nut and pipe before tightening.
The required tightening torque is as follows:
Pipe Size Tightening Torque (Nm)
Ø 6.35 mm (1/4) 20
Ø 9.52 mm (3/8) 40 Ø 12.70 mm (1/2) 60 Ø 15.88 mm (5/8) 80 Ø 19.05 mm (3/4) 100
6 After connecting the refrigerant piping, seal the open space
between knockout hole and refrigerant pipes by using insula­tion material.
Unit Side
Description
Insulation Material
Insulation Material
Field Supplied
Insulation Material
7 Operation of stop valve should be performed according to the
gure below.
Close before shipment
Outdoor unit stop valve
Spindle Type Ball Type
Liquid
RAS-(4-10)H(V)NP(1)E
RAS-(8/10)HNCE
Liquid and Gas RAS-3HVNP1E
RAS-4H(V)RNS3E
Gas
RAS-(4-10)H(V)NP(1)E
RAS-(8/10)HNCE
(a)
Spindle valve
Flare nut
Cap
Check joint for service port
Tightening Torque (Nm)
Liquid valve 7-9
40
10HP: 60
33-42
14-18
Gas valve 9-11
80
8/10HP: 100
3HP: 33-42
4/5/6HP: P=20-25 S=33-42
8/10HP:20-25
Spindle Type Ball Type
(a) (b)
Description Remarks
Cap
Allen wrench Hex 4 mm
Refrigerant Piping Field Supplied
Flare nut
Refrigerant Pressure To Outdoor Unit
Seat Surface Fully closed position
Check Joint Only the charging those can be connected
Charge port cap
O-Ring Rubber
Spindle valve
Open – Counterclockwise Close – Clockwise
«
Shaft
¬
Pin
Stopper
(a)
Closed
This valve is opened or closed with rotating 90 degrees at the ball valve part. Rotate the shaft until the pin touches the stopper. Do not apply the extra force. Use a slotted screwdriver to control
the shaft. Do not leave the ball valve partly open
(b)
Opened
Do not apply two spanners at this position. If applied, leakage will occur.
Stop valve (Spindle type)
Flare nut
Use two spanners here for pipe con­nection
Do not work with two spanners here.
Refrigerant leakage shall occur
Position to apply spanners
Don not apply two spanners work here
Spindle type Ball type
CA U T IO N
• At the test run, fully open the spindle and ball stop valve.
• If not fully opened, the devices will be damaged.
• Do not attempt to turn service valve rod beyond its stop.
• Do not loosen the stop ring. If the stop ring is loosened, it is dangerous since the spindle will hop out.
• An excess or a shortage of refrigerant is the main cause of trouble to the units. Charge the correct refrigerant quantity according to the description of label at the inside of service cover.
• Check for refrigerant leakage in detail. If a large refrigerant leakage occurs, it will cause difculty with breathing or harmful gases would occur if a re was being used in the room.
Refrigerant piping & refrigerant charge
17
PMML0317A rev.1 - 11/2013
ENGLISH
Evacuation and refrigerant charge
- Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valve.
- Check for any gas leakage at the are nut connection, by using nitrogen gas to increase the pressure at 4.15 MPa for outdoor units inside of the eld-supplied piping.
- Operate the vacuum pump for 1 to 2 hours until the pres­sure decreases lower than a pressure of 756 mmHg in vacuum.
- For charging refrigerant, connect the gauge manifold us­ing charging hoses with a refrigerant charging cylinder to the check joint of the liquid line stop valve.
- Charge the proper quantity of refrigerant according to the piping length (Calculate the quantity of the refrigerant charge).
- Fully open the gas line stop valve, and slightly open the liquid line stop valve.
- Charge refrigerant by opening the gauge manifold valve.
- Charge the required refrigerant within the difference range of ±0.5kg by operating the system in cooling.
- Fully open the liquid line stop valve after completing refrig­erant charge.
- Continue cooling operation for more than 10 minutes to circulate the refrigerant.
Thermal insulation
Gas line
Cover the are nut and union of the piping connection with thermal insulation
Liquid line
Liquid stop valve
Gas stop valve
Nitrogen tank
(For air Tight test & Nitrogen blow during brazing)
Vacuum cylinder
Ma nif old gauge
Outdoor unit
Insulate the liquid pipe for prevention of the capacity decrease according to the ambient air conditions and the dewing on the pipe sur­face by the low pressure
Example of Evacuation and Refrigerant Charge.
13.4 REFRIGERANT PIPING LENGTH
The refrigerant piping between the indoor unit and the outdoor unit should be designed using the following table.
Piping length specication for header branch
(Example for header branch)
1 indoor unit system
(O.U. IVX Series from 3 to 10 HP
and O.U. ES Series 4 HP)
2 indoor units system
(O.U. IVX Series from 3 to 10 HP
and O.U. ES Series 4 HP)(*)
3 indoor units system
(O.U. IVX Series from 4 to 10 HP)(*)
4 indoor units system (O.U. IVX Series from 4 to 10 HP)(*)
(pictures are as example) (*) Connections including Indoor Units 8 and 10 HP are not possible
18
Refrigerant piping & refrigerant charge
PMML0317A rev.1 - 11/2013
Maximum refrigerant piping length
IVX Premium series
(m)
Outdoor Unit 3HP 4HP 5HP 6HP 8HP 10HP
Maximum piping Length be-
tween the outdoor unit and
the farthest indoor unit
Actual Length (L) 50 75 100
Equivalent Length (EL) 70 95 125
Total piping length
2 units (A+B+C) 60 85 100 115
3 units (A+B+C+D) -- 95 100 130
4 units
(A+B+C+D+E+F+G+)
-- 95 100 145
Maximum piping line
after rst branch
2 and 3 units (B, C, D) 10 15
4 units
(B+D, B+E, C+F, C+G)
-- 10 15
Main piping length A A > B, C, D, E, F, G
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height difference Indoor / Indoor 10
Maximum height difference:
branch pipe/Indoor (2, 3 and 4 units system)
branch pipe/branch pipe (4 units system)
3
(B-C) / (B-D) / (C-D) / (C+G)-(B+E) / (C+G)-(B+D)
(C+F)-(B+E) / (C+F)-(B+D)
< 8
IVX Standard series
(m)
Outdoor Unit 8HP 10HP
Maximum piping Length
between the outdoor unit
and the farthest indoor
unit
Actual Length (L) 100
Equivalent Length (EL) 125
Total piping length
2 units (A+B+C) 100 115
3 units (A+B+C+D) 100 130
4 units
(A+B+C+D+E+F+G+)
100 145
Maximum piping line
after rst branch
2 and 3 units (B, C, D) 15
4 units
(B+D, B+E, C+F, C+G)
15
Main piping length A A > B, C, D, E, F, G
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height difference Indoor / Indoor 3
Maximum height difference:
branch pipe/Indoor (2, 3 and 4 units system)
branch pipe/branch pipe (4 units system)
3
(B-C) / (B-D) / (C-D) / (C+G)-(B+E) / (C+G)-(B+D)
(C+F)-(B+E) / (C+F)-(B+D)
< 8
Refrigerant piping & refrigerant charge
19
PMML0317A rev.1 - 11/2013
ENGLISH
ES series
(m)
Outdoor Unit 4HP
Maximum piping Length between the outdoor unit and the indoor unit
Actual Length (L) 50 Equivalent Length (EL) 70
Maximum height difference Outdoor / Indoor (H) (Outdoor Unit is Higher / Lower)
30 /20
Maximum height difference Indoor / Indoor 0.5 Maximum total piping length Twin (A + B + C) 60 Maximum piping line after branch Twin (B, C) 10 (B-C) < 8
NO T E
• The liquid piping and the gas piping must be of the same piping length and run along the same route.
• Install the branch piping as much as possible near the indoor units
• Install Multikits at the same horizontal level.
Example for line branch (Only allowed for IVX series)
OU 3 HP 4 HP 5 HP 6 HP 8 HP 10 HP
IU quantity allowed
IVX Premium 2 -3 2 - 5 2 - 6 2 - 8
IVX Standard -- - - - 2 - 4
1 2 4 53
(picture is as example)
Connections including Indoor Units 8 and 10 HP are not possible
Maximum refrigerant piping length (Line branch system)
IVX Premium series
(m)
Outdoor Unit 3HP 4HP 5HP 6HP 8HP 10HP
Maximum piping length between the outdoor unit and the farthest
indoor unit
Actual Length (L1) 50 75 100
Equivalent Length (EL) 70 95 125
Maximum piping length from rst branch to each indoor unit (L2) 20 30 40
Maximum piping length from branch to indoor unit (L3) 10 15
Maximum piping length L4 + (L3
1
+L32+L33....) 60 95 100 145
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height Difference Indoor / Indoor 10
Maximum height difference:
Branch pipe/Indoor
Branch pipe/branch pipe
3
20
Refrigerant piping & refrigerant charge
PMML0317A rev.1 - 11/2013
IVX Standard series
(m)
Outdoor Unit 8HP 10HP
Maximum piping length
between the outdoor unit
and the farthest indoor
unit
Actual Length (L1) 100
Equivalent Length (EL) 125
Maximum piping length from rst branch to each indoor unit (L2) 25
Maximum piping length from branch to indoor unit (L3) 15
Maximum piping length L4 + (L3
1
+L32+L33....) 100 145
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height Difference Indoor / Indoor 3
Maximum height difference:
Branch pipe/Indoor
Branch pipe/branch pipe
3
13.4.1 Refrigerant piping size and multikit/distributor
Select the piping connection sizes according to the following procedures:
• Between outdoor unit and branch pipe: Select the same pipe connection size as the pipe size of the outdoor unit.
• Between branch pipe and indoor unit: Select the same pipe connection size as the pipe size of the indoor unit.
1 indoor unit system
(mm)
Outdoor Unit HP
Pipe Size (L)
Gas Liquid
2 / 2.5 Ø12.70 Ø6.35
3 - 6 Ø15.88 Ø9.52
8 Ø25.40 Ø9.52
10 Ø25.40 Ø12.70
2 indoor units system
(mm)
Outdoor Unit HP
Pipe Size (A) Branch pipe
Gas Liquid IVX Series ES Series
2 / 2.5 Ø12.70 Ø6.35 TE-03N1 -
3 / 4 Ø15.88 Ø9.52
3HP:TE-03N1 4HP:TE-04N1
4 HP: TE-04N1
5 / 6 Ø15.88 Ø9.52 TE-56N1- -
8 Ø25.40 Ø9.52 TE-08N -
10 Ø25.40 Ø12.70 TE-10N -
(mm)
Indoor Unit capacity
Pipe Size (B, C)
Gas Liquid
≤ 1.5 HP Ø12.70 Ø6.35
1.8/2.0HP Ø15.88 Ø6.35 ≥ 2.3 HP Ø15.88 Ø9.52
Connections including Indoor Units 8 and 10 HP are not
possible
Refrigerant piping & refrigerant charge
21
PMML0317A rev.1 - 11/2013
ENGLISH
3 indoor units system (Only allowed for IVX series)
(mm)
Outdoor Unit HP
Pipe Size (A) Header Branch
Gas Liquid IVX Series
4 / 5 / 6 Ø15.88 Ø9.52 TRE-46N1
8 Ø25.40 Ø9.52 TRE-812N1
10 Ø25.40 Ø12.70 TRE-812N1
(mm)
Indoor Units capacity
Pipe Size (B, C, D)
Gas Liquid
≤ 1.5 HP Ø12.70 Ø6.35
1.8/2.0HP Ø15.88 Ø6.35
≥ 2.3 HP Ø15.88 Ø9.52
Connections including Indoor Units 8 and 10 HP are
not possible
4 indoor units (Only allowed for IVX series)
1
2
1 2
3
4
(mm)
Outdoor
Unit HP
Pipe Size (A)
Branch line
(1) In case that total pipe length (A+B+D or A+B+E or A+C+F or A+C+G) exceeds of 70m in 8 HP unit, please use a Ø12.7 pipe as a liquid pipe.
(2) When is used Multi-kit model QE-812N1 it is not ne­cesary the multi.kit 2.
F
G
Gas Liquid IVX Series
4 / 5 / 6 Ø15.88 Ø9.52
4HP: TE-04N1
5/6HP: TE-56N1
8 Ø25.40 Ø9.52
(1)
TE-08N
QE-812N1
(2)
10 Ø25.40 Ø12.70
TE-10N
QE-812N1
(2)
(mm)
Branch line
Indoor Unit
capacity
Pipe Size (D,E,F,G)
Branch pipe after total
capacity of indoor units
1+2 or 3+4
Pipe Size
(B,C)
IVX Series
Gas Liquid
Gas Liquid ≤ 1.5 HP Ø12.70 Ø6.35
≤ 1.5 HP Ø12.70 Ø6.35 TE-03N1 1.8/2.0 HP Ø15.88 Ø6.35
from 1.8 to 2.0 HP Ø15.88 Ø6.35 TE-03N1 ≥ 2.3 HP Ø15.88 Ø9.52
≥ 2.3 HP Ø15.88 Ø9.52
<4: TE-03N1
=4HP: TE-04N1
≥ 5HP: TE-56N1
Connections including Indoor Units 8
and 10 HP are not possible
22
Refrigerant piping & refrigerant charge
PMML0317A rev.1 - 11/2013
Line branch system (Only allowed for IVX series)
A
B
D
c
(mm)
Multi Kit Model A
Multi Kit Model B
Outdoor
Unit HP
Pipe Size (C, D) (L4)
IVX Series
Gas Liquid
3 / 4 / 5 / 6 Ø15.88 Ø9.52 E-102SN(2/3) E-102SN(2/3)
8 Ø25.40 Ø9.52
(1)
E-162SN(2/3) E-102SN(2/3)
10 /12 Ø25.40 Ø12.70 E-162SN(2/3) E-102SN(2/3) (1) In case that pipe length exceeds 70m in 8 HP, please use a
Ø12.7 pipe as a liquid pipe.
Indoor Unit capacity
Pipe Size (L3)
Gas Liquid
≤ 1.5 HP Ø12.70 Ø6.35
from 1.8 to 2.0 HP Ø15.88 Ø6.35
≥ 2.3 HP Ø15.88 Ø9.52
Connections including Indoor Units 8 and 10 HP are not possible
13.4.2 System Installation (examples)
Height Difference Between Indoor Units and Distributor
It is recommended to install all indoor units at the same height. When the height difference between the indoor units due to build­ing construction is necessary, this should be less than the value indicated in the gure
10m (IVX-P)
3m (IVX-C)
ืืืื
20m
ืืืื
30m
IU1
IU4
IU3
IU2
OU1
OU1
3m
3m
3m
3m
3m
3m
(
6m)
O.U higher
O.U lower
10m (IVX-P)
3m (IVX-C)
ืื
ืื
ืื
ืื
ืื
ืื
High difference O.U/IU
O.U higher ≤30m
O.U lower ≤20m
Installing Distributor
1 Install the Distributor supplied by HITACHI on request.
A tee can not be installed instead of a branch pipe.
2 Installing the distributor
Fix the branch pipe horizontally to the pillar, wall or ceiling. Pip­ing must not be xed rigidly to the wall as thermal expansion and contraction can cause pipe fracture.
Horizontal
To Indoor Unit
To Outdoor unit
Vertical
To Indoor unit
Fixing the branch pipe to the surface of pillar or wall
Horizontal
Horizontal
Fixing the branch pipe to ceiling or beam
(pictures as example)
NO T E
Fix the piping from outside of insulation or inserting absorber be­tween the pipe and a xing metal.
3 Correct position of distributor (available also for quad instal-
lation)
• This is the correct position:
G r ea t e r than 0.5 m
Main pipe
Refrigerant direction
Up
Branch pipe
Main pipe
Refrigerant di­rection
Down
• This is wrong position.
Main pipe
Refrigerant direction
Branch pipe
Branch pipe
Refrigerant di­rection
Branch pipe
Main pipe
(pictures as example)
Refrigerant piping & refrigerant charge
23
PMML0317A rev.1 - 11/2013
ENGLISH
4 Correct position of Triple Branch Pipe (Standard series only).
• Install the header horizontally
Sample: Triple Branch pipe
Gas piping
Liquid piping
13.4.3 Brazing work
CA U T IO N
• Use nitrogen gas for blowing during pipe brazing. If oxygen, acetylene or uorocarbon gas is used, it will cause an explo­sion or poisonous gas.
• A lot of oxidation lm will occur inside of tubes if no nitrogen gas blowing is performed during brazing work. This lm will be ecked off after operation and will circulate in the cycle, resulting in clogged expansion valves, etc. This will cause bad inuence to the compressor.
• Use a reducer valve when nitrogen gas blowing is performed during brazing. The gas pressure should be maintained within
0.03 to 0.05 Mpa. If a excessively high pressure is applied to a pipe, it will cause an explosion.
13.4.4 Refrigerant charge
CA U T IO N
• Do not charge OXYGEN, ACETYLENE, or other ammable and poisonous gases into the refrigerant because an explo­sion can occur. It is recommended that oxygen free nitrogen be charged for these types of tests cycle when performing a leakage test or an airtight test. These types of gases are extremely dangerous,
• Insulate the unions and are-nuts at the piping connection part completely.
• Insulate the liquid piping completely to avoid a decrease of performance; if not, it will cause sweating on the surface of the pipe.
• Charge refrigerant correctly. Overcharging or insufcient charging could cause a compressor failure.
• Check for refrigerant leakage in detail. If a large refrigerant leakage occurred, it would cause difculty with breathing or harmful gases would occur if a re were being used in the room.
• If the are nut is tigthened too hard, the are nut may crack after a long time and cause refrigerant leakage.
13.6 REFRIGERANT CHARGING QUANTITY
When the pressure is measured, use the check joint of gas stop valve (A), and use the check joint of liquid piping (B) in the gure below.
At that time, connect the pressure gauge according to the follow­ing table because of high pressure side and low pressure side changes by operation mode.
Cooling
Operation
Heating
Operation
Check Joint for Gas Stop Valve “A” Low Pressure High Pressure
Check Joint for Piping “B” High Pressure Low Pressure
Check Joint for Liquid Stop Valve “C”
Exclussive for Vacuum Pump
and Refrigerant Charge
NO T E
Be careful that refrigerant and oil do not splash to the electrical parts at removing the charge hoses.
C
B
A
The gas stayed at O-ring sc r e w p ar t i s o p en e d and may make soun d whe n remov ing the cap. Ho we ver , it is no t g as leakage.
13.5 CAUTION OF THE PRESSURE BY CHECK JOINT
Outdoor Units has been charged with refrigerant for 30m of actual piping length. An additional refrigerant charged is required in sys­tems with actual piping length longer than 30m.
1 Determine an additional refrigerant quantity according to the
following procedure, and charge it into the system.
2 Record the additional refrigerant quantity to facilitate service
activities thereafter.
CA U T IO N
• When charging refrigerant accurately measure refrigerant to be charged.
• Overcharging or undercharging of refrigerant can cause com­pressor trouble
• In case of actual piping length less than 5 m, consult your distributor.
24
Refrigerant piping & refrigerant charge
PMML0317A rev.1 - 11/2013
13.6.1 Refrigerant charge before shipment (W0 (kg))
W0 is the outdoor unit refrigerant charge before shipment ex­plained before, and it’s shown in the following table:
IVX Premium series
Model
Refrigerant charge
before shipment
(W0 (kg))
Additional refrigerant charge (P)
(g/m)
Maximum
additional
charge
(kg)
RAS-3HVNP1E 2.3 40 1.2 RAS-4HVNP1E 4.1 60 3.9 RAS-5HVNP1E 4.2 60 3.9 RAS-6HVNP1E 4.2 60 3.9
RAS-4HNP1E 4.1 60 3.9 RAS-5HNP1E 4.2 60 3.9 RAS-6HNP1E 4.2 60 3.9
RAS-8HNPE 5.7 (1) 10.3
RAS-10HNPE 6.2 (1) 12.1
(1) need to be calculate
IVX Standard series
Outdoor unit
Refrigerant charge
before shipment
(W0 (kg))
Additional refrigerant
charge
(g/m)
Maximum additional
charge
(kg)
RAS-8HNCE 5.7 (1) 10.3
RAS-10HNCE 6.2 (1) 12.1
(1) need to be calculate
ES series
Outdoor unit
Refrigerant charge
before shipment
(W0 (kg))
Additional
refrigerant
charge
(g/m)
Maximum additional
charge
(kg)
RAS-4HVRNS3E 2.9 40 1.6
RAS-4HRNS3E 2.9 40 1.6
CA U T IO N
• When charging refrigerant, measure the amount precisely.
• Overloading or underloading of refrigerant may cause com­pressor problems.
• If the actual piping length is less than 5 m consult your dealer.
Additional refrigerant charge calculation method
For all UTOPIA units RAS-(3-6)H(V)NP(1)E and RAS-4H(V)RNS3E
Use the following formula:: W1 = (L-30) x P
For UTOPIA units RAS-(8-10)HNPE and RAS-(8-10) HNCE
The additional refrigerant charge for RAS-(8-10)HNPE and RAS­(8-10)HNCE units must be calculated by multiplying the total pip­ing length of each diameter per its calculation factor according to the following table. The result is the additional refrigerant charge subtracting 1.6 for 8 HP or 2.0 for 10 HP. (Fill the table with the values)
Pipe size (mm)
Additional refrigerant
charge factor (kg/m)
Ø15.88 x 0.19
Ø12.7 x 0.12 Ø9.52 x 0.065 Ø6.35 x 0.065
Setting of Pipe Length DSW.
DSW2 setting will be required only when the refrigerant pipe length is shorter than 5 m or longer than 30 m. Pipe length setting shall be performed as shown below.
(The side in the table below shows the DSW location)
DSW2 on Outdoor PCB1
Factory setting Pipe Length ≤ 5m Pipe Length ≥ 30m
When the refrigerant should be collected into the outdoor unit due to indoor/outdoor unit relocation, collect the refrigerant as follows:
1 Attach the manifold gauge to the gas stop valve and the liquid
stop valve
2 Turn ON the power source 3 Set the DSW1-1 pin of the outdoor unit PCB at the “ON” side
for cooling operation. Close the liquid stop valve and collect the refrigerant.
4 When the pressure at lower pressure side (gas stop valve)
indicates -0.01 MPa (-100 mmHg), perform the following pro­cedures immediately.
- Close the gas stop valve.
- Set the DSW1-1 pin at the “OFF” side (To stop the unit operation).
5 Turn OFF the power source.
CA U T IO N
Measure the low pressure by the pressure gauge and keep it not to decrease than -0.01 MPa. If the pressure is lower than -0.01 MPa, the compressor may be faulty.
13.7 REFRIGERANT PUMP DOWN
Drain piping
25
PMML0317A rev.1 - 11/2013
ENGLISH
14 DRAIN PIPING
15 ELECTRICAL WIRING
1 Ensure that the eld-supplied electrical components (mains
power switches, circuit breakers, wires, connectors and wire terminals) have been properly selected according to the elec­trical data indicated. Make sure that they comply with national and regional electrical codes.
2 Following the Council Directive 2004/108/EC(89/336/EEC),
relating to electromagnetic compatibility, next table indicates: Maximum permissible system impedance Z
max
at the interface
point of the user’s supply, in accordance with EN61000-3-11
MODEL Z max (Ω) MODEL Z max (Ω)
RAS-3HVNP1E - - ­RAS-4HVNP1E - RAS-4HNP1E -
RAS-4HVRNS3E 0.27 RAS-4HRNS3E -
RAS-5HVNP1E - RAS-5HNP1E ­RAS-6HVNP1E - RAS-6HNP1E -
- - RAS-8HNPE -
- - RAS-8HNCE -
- - RAS-10HNPE -
- - RAS-10HNCE -
3 Harmonics situation of each model regarding IEC 61000-3-2
and IEC 61000-3-12 is as follows:
MODELS SITUATION REGARDING IEC 61000-3-2 AND IEC 61000-3-12
Ssc “xx”
MODELS
Ssc “xx”
(KVA)
Equipment complying with IEC 61000-3-2 (professional use)
RAS-(4-6)HNP1E
RAS-4H(V)RNS3E
Equipment complying with IEC 61000-3-12 RAS-(3-6)HVNP1E -
Installation restrictions may be applied by au­thorities regarding the power supply in relation to harmonics
RAS-(8/10)HNPE RAS-(8/10)HNCE
4 Check to ensure that the power supply voltage is within +/-
10% of the rated voltage.
5 Check to ensure that power supply has an impedance low
enough to warranty not reduce the starting voltage more than 85% of the rated voltage.
6 Check to ensure that the ground wire is connected. 7 Connect a fuse of specied capacity.
NO T E
Check and test to ensure that if there is more than one source of power supply, that all are turned OFF.
CA U T IO N
• Check to ensure that screws for terminal block are tightly
tightened.
• Check to ensure that the indoor fan and the outdoor fan have stopped before electrical wiring work or periodical check is performed.
• Protect the wires, drain pipe, electrical parts, from rats or other small animals. If not protected, rats may damage unprotected parts, and at the worst, a re will occur.
• Wrap the accessory packing around the wires, and plug the wiring connection hole with the seal material to protect the product from any condensed water and insects.
• Tightly secure the wires with the cord clamp inside the indoor unit.
• Lead the wires through the knockout hole in the side cover when using conduit.
• Secure the cable of the remote control switch with the cord clamp inside the electrical box.
• Electrical wiring must comply with national and local codes. Contact your local authority in regards to standards, rules, regulations, etc.
• Check that the ground wire is securely connected.
• Connect a fuse of specied capacity.
DA N G ER
• Donotconnect of adjust any wiring or connectionsun­lessthemainpowerswitchisOFF.
• Checkthattheearthwire is securelyconnected,tagged andlockedinaccordancewithnationalandlocalcodes.
14.1 DRAIN DISCHARGING BOSS
When the base of the outdoor unit is temporarily utilized as a drain receiver and the drain water in it is discharged, this drain boss is utilized to connect the drain piping.
Model Applicable Model
DBS-26 All units
Connecting procedure
1 Insert the rubber cap into the drain boss up to the extruded
portions.
2 Insert the boss into the unit base and turn approximately 40
degree counterclockwise.
3 Size of the drain boss is 32 mm (O.D.). 4 A drain pipe should be eld-supplied.
NO T E
Do not use this drain boss set in a cold area, because the drain water may freeze.
This drain boss is not sufcient to collect all the drain water. If collecting drain water is completely required, provide a drain-pan that is bigger than the unit base and install it under the unit with
drainage.
Rubber cap
Drain Boss
Extruded portion
Drain pipe
Drain pipe
Drain hole of Base
15.1 GENERAL CHECK
26
Electrical wiring
PMML0317A rev.1 - 11/2013
The electrical wiring connection for the outdoor unit is
shown in gure below:
RAS-3HVNP1E
RAS-(4-6)HVNP1E
RAS-4HVRNS3E
RAS-4HRNS3E
RAS-(4-10)HNP(1)E
RAS-(8-10)HNCE
Power supply
1~ 230V
Control cable (5V)
Power supply
3N~ 400V
Control cable (5V)
Table for Terminal Connection between units
Wiring System
Units type
Connection of terminals
Power Supply DC inverter
O.U. to O.U.
L1 to L1, L2 to L2, L3 to L3, N to N
I.U. to I.U.
L1 to L1, N to N)
Operating DC inverter
O.U. to I.U. or I.U. toI.U.
1 to1, 2 to 2
Remote Control DC inverter
I.U. to I.U.
A to A, B to B
O.U.: Outdoor Unit; I.U.: Indoor unit
15.2.1 Setting of DIP Switches for Outdoor Unit
Quantity and Position of DIP Switches.
The location is as follows:
RAS-3HVNP1E, RAS-(4-10)H(V)NP(1)E, RAS-(8-10)HNCE
and RAS-4H(V)RNS3E
DSW1: For Test Run
Factory setting
DSW2: Optional Function Setting
Factory setting
Piping length ≤ 5m
Piping lenght ≥ 30m
Control to support existing pipes or when using Ø19,05 gas pipe (soft-annealed), switch ON DSW2 pin 4 in the outdoor unit PCB
Optional function setting mode (The optional function selection mode become available)
1 2 3 4 5 6
ON
External input/output setting mode (The input / output signals selection mode becomes avaliable).
15.2 ELECTRICAL WIRING CONNECTION FOR OUTDOOR UNITS
Electrical wiring
27
PMML0317A rev.1 - 11/2013
ENGLISH
DSW3: Capacity
Factory setting
RAS-3HVNP1E
RAS-4HVNP1E
RAS-4HVRNS3E
RAS-5HVNP1E RAS-6HVNP1E
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
RAS-4HNP1E
RAS-4HRNS3E
RAS-5HNP1E RAS-6HNP1E
RAS-8HNPE RAS-8HNCE
RAS-10HNPE RAS-10HNCE
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
DSW5: Transmission Setting of End Terminal Resistance
Factory setting
Cancellation
In the case that the outdoor units quantity in the same H-LINK is 2 or more, set No. 1 pin of DSW5 at “OFF” side from the 2nd refrigerant group outdoor unit. If only one outdoor unit is used, no setting is required.
DSW4 / RSW1: Refrigerant Cycle No. Setting
Factory setting (Setting for the ten digit).
Factory setting
(Setting for the last digit).
0
9
8
7
6
5
4
3
2
1
DSW6: Optional function setting (IVX series only)
For individual operation
(factory setting position) For IVX series
For simultaneous operation
DSW6: Only for ES series
Factory setting
Example of DSW5 setting
1 2
DSW5
1 2
DSW5
1 2
DSW5
1 2
DSW5
( H-LINK) ( H-LINK)
( H-LINK)
28
Electrical wiring
PMML0317A rev.1 - 11/2013
15.3 COMMON WIRING
CA U T IO N
All the eld wiring and electrical components must comply with local codes.
15.3.1 Electrical wiring between indoor unit and outdoor unit
• Connect the electrical wires between the indoor unit and the outdoor unit, as shown below.
• Follow local codes and regulations when performing electrical wiring.
• If the refrigerant piping and the control wiring are connected to the units in the same refrigerant cycle.
• Use twist pair wire (more than 0.75 mm²) for operation wiring between outdoor unit and indoor unit, and operation wiring between indoor unit and indoor unit.
• Use 2-core wire for the operating line (Do not use wire with more than 3 cores).
• Use shielded wires for intermediate wiring to protect the units from noise obstacle at length of less than 300 m and size complied with local code.
• Open a hole near the connection hole of power source wiring when multiple outdoor units are connected from one power source line.
• The recommended breaker sizes are detailed in the Wire size section.
• In the case that a conduit tube for eld-wiring is not used, x rubber bushes with adhesive on the panel.
• All the eld wiring and equipment must comply with local and international codes.
• H-LINK twist pair shielded cable must be grounded in the out­door unit side.
CA U T IO N
Pay attention to the connection of the operating line. Incorrect connection may cause the failure of PCB.
Power source from the outdoor IVX unit
to the indoor unit (example)
Independent power source of outdoor IVX unit
and indoor unit (example)
3
3
3
L1 L2 L3 NL1 L2 L3 N
L1 L2 L3 N
No. 0 System Outdoor unit
No. 0 System Outdoor unit
Operating Line (Shielded Pair Cable)
5V (Non-Pole Transmission, H-LINK System)
Remote Control Switch (Twisted Shielded Pair Cable)
Operating Line (Twisted Shielded Pair Cable)
5V (Non-Pole Trans­mission, H-LINK System)
Indoor Unit
Indoor Unit
Terminal board Circuit Breaker Earthleakage Breaker Field Wiring Field supplied Optional Accessory
Remote Control Switch (Twisted Shielded Pair Cable)
Indoor Unit
Indoor Unit
Wiring example (IVX series only)
Basic combinations (in the case of twin combination)
1 2
ON
DSW6
1 2
ON
DSW6
1 2
ON
DSW6
Operating line
Operating line Operating line
Remote control line
Remote control line
Remote control line
Individual control Running ON/OFF individually Thermo.ON/OFF individually
Individual control Running ON/OFF simultaneously Thermo.ON/OFF individually
Simultaneous control Running ON/OFF simultaneously Thermo.ON/OFF simultaneously
Electrical wiring
29
PMML0317A rev.1 - 11/2013
ENGLISH
15.3.2 Wire size
Connection wiring
Recommended minimum sizes for eld provided wires:
Model Power supply
Power source
cable size
Transmitting
cable size
EN60 335-1 EN60 335-1
All Indoor Units
1~ 230V 50Hz
0.75 mm²
0.75 mm²
RAS-3HVNP1E
4.0 mm²
RAS-(4-6)HVNP1E
6.0 mm
2
RAS-4HVRNS3E
6.0 mm
2
RAS-(4-6)HNP1E
3N~ 400V 50Hz
2.5 mm
2
RAS-4HRNS3E
4 mm
2
RAS-(8-10)HNPE
6.0 mm
2
RAS-(8-10)HNCE
6.0 mm
2
NO T E
• Follow local codes and regulations when selecting eld wires, Circuit breakers and Earth Leakage breakers
• Use the wires which are not lighter than the ordinary polychlo­roprene sheathed exible cord (code designation H05RN-F)
Main switch protection
Select the main switches in according to the next table:
Model Power supply
Max. current
(A)
CB (A)
ELB (no.
poles/A/mA)
All Indoor Units 1~ 230V 50Hz 5.0 6 2/40/30
ELB: Earth switch; CB: Circuit braker
IVX Premium series
Outdoor unit
MC
(A)
CB (A)
ELB
RAS-3HVNP1E
21.5 25
2/40/30
RAS-4HVNP1E
30.5 40
RAS-5HVNP1E
30.5 40
RAS-6HVNP1E
30.5 40
RAS-4HNP1E
14.0 20
4/40/30
RAS-5HNP1E
14.0 20
RAS-6HNP1E
16.0 20
RAS-8HNPE
24.0 30
RAS-10HNPE
24.0 30
IVX Standard series
Outdoor unit
MC (A)
CB (A)
ELB
RAS-8HNCE 24.0 30
4/40/30
RAS-10HNCE 24.0 30
ES series
Outdoor unit
MC (A)
CB (A)
ELB
RAS-4HVRNS3E 28.0 32 2/40/30
RAS-4HRNS3E 15.0 20 4/40/30
15.3.3 H-LINK II System
NO T E
The H-LINK II system can not be applied to the cycle with the old H-LINK model.
1 Application
The new H-LINK II connecting each indoor unit and outdoor unit for up to 64 refrigerant cycles (up to 160 indoor unit per H-LINKII), and connecting wires for all indoor units and all outdoor units in series.
2 Specications
- Transmission Wire: 2-Wire.
- Polarity of Transmission Wire: Non-Polar Wire.
- Maximum Outdoor Units To Be Connected: 64 Units per H-LINK II system.
- Maximum Indoor Units To Be Connected: 160 Units per H-LINK II system.
- Maximum Wiring Length: Total 1000m (including CS-NET). In case that the total wiring length is longer than 1000m, contact the Hitachi dealer.
- Recommended Cable: Twist Pair Cable with Shield, over 0.75mm2 (Equivalent to KPEV-S).
- Voltage: 5V.
NO T E
Do not make a wiring in a loop.
3 Dip Switch Setting of Indoor PCB and Outdoor PCB.
It is required to set dip switches of every indoor unit and outdoor unit.
30
Electrical wiring
PMML0317A rev.1 - 11/2013
15.3.4 System installation DIP Switch Setting
Dip Switch Setting of Indoor PCB and Outdoor PCB for H-LINK II
It is required to set dip switches of every indoor unit and outdoor unit and match of the transmission circuit impedance.
• Dip Switch Setting Example:
Cycle nº 0
DSW5
Terminating Resistance
DSW4
Refrigerant Cycle Nº (Setting for ten digit)
RSW1
Refrigerant Cycle Nº (Setting for last digit)
Outdoor units
Indoor units
DSW5
Refrigerant Cycle Nº (Setting for ten digit)
RSW2
Refrigerant Cycle Nº (Setting for last digit)
DSW6
Indoor unit Address (Setting for ten digit)
RSW1
Indoor unit Address (Setting for last digit)
Cycle nº 1
Cycle nº 2
Unit Name of Dip Switch Mark
Setting Before
Shipment
Function
Outdoor Unit
Refrigerant Cycle
DSW4
RSW1
DSW4 RSW1
For setting refrigerant cycle address of Outdoor Unit. Set the DSW4 and RSW1 not to overlap the setting of other Outdoor units in the same H-LINK system
Terminating Resistance DSW5
For matching impedance of transmission circuit, set the DSW5 accord­ing to the quantity of outdoor units in the H-LINK system.
Indoor Unit
Refrigerant Cycle
DSW5
RSW2
DSW5 RSW2
For setting refrigerant cycle address of indoor units. Set the DSW5 and RSW2 corresponding to the address of outdoor unit in the same refriger­ant cycle.
Indoor Unit Address
DSW6
RSW1
DSW6 RSW1
For setting indoor unit address. Set the DSW6 and RSW1 not to overlap the setting of other indoor units in the same refrigerant cycle. (If not set, the automatic address function is performed).
Test running
31
PMML0317A rev.1 - 11/2013
ENGLISH
16 TEST RUNNING
When installation is completed, perform test run according to the following procedure, and hand over the system to the customer. Perform test run regarding indoor units one by one in order, and conrm that the electrical wiring and the refrigerant piping are correctly connected.
Test run should be performed according to the Test Run Proce-
dure on next page.
CA U T IO N
Do not operate the system until all the check points have been cleared:
• Check to ensure that the electrical resistance is more than 1 MΩ, by measuring the resistance between ground and the terminal of the electrical parts. If not, do not operate the sys­tem until the electrical leakage is found and repaired. Do not impress the voltage on the terminals for transmission 1 and 2.
• Check to ensure that the stop valves of the outdoor unit are fully opened, and then start the system.
• Check to ensure that the switch on the main power source has been ON for more than 12 hours, to warm the compressor oil by the oil heater
Pay attention to the following items while the system is running:
• Do not touch any of the parts by hand at the discharge gas side, since the compressor chamber and the pipes at the dis­charge side are heated higher than 90°C.
• DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES), it will cause a serious accident.
• Do not touch any electrical components for more than three minutes after turning OFF the main switch
• Conrm that the gas line stop valve and the liquid line stop valve are fully open.
• Conrm that the leakage of the refrigerant does not exist. The are nuts are sometimes loosened by vibration during trans­portation.
• Check that the refrigerant piping and the electrical wiring con­form to the same system.
• Conrm that the dip switch setting on the printed circuit board of the indoor units and the outdoor units are correct.
• Check whether or not the electrical wiring of the indoor units and the outdoor units are connected as shown in the chapter
Electrical Wiring.
CA U T IO N
Conrm that eld-supplied electrical components (main switch fuse, fuse-free breaker, earth leakage breakers, wires, conduit connectors and wire terminals) have been properly selected ac­cording to the electrical data given in the Technical Catalog of the unit and ensure that the components comply with national and local codes.
NO T E
• For more reference check Troubleshooting chapter on Opera- tion Part.
• For twin, triple and quad check the indoor unit outlet air tem­perature at test run. If the temperature difference is large (aprox. 10 deg. or more (cooling) 20 deg. or more (heating) recheck the refrigerant piping, Installation may have some problem.
• In the case of anual cooling optional function, cut JP1 out and set the DSW6-1 to OFF. (Individual control is not available when anual cooling is selected).
32
Test running
PMML0317A rev.1 - 11/2013
16.1 TEST RUN PROCEDURE BY REMOTE CONTROL SWITCH (PC-ART EXAMPLE)
Turn ON the power source of the Indoor and Outdoor Units
Counting number of connected units
05
Operation lamp
Set the TEST RUN mode by remote control switch.
Depress the “MODE” and the “
OK” switches simultaneously
for more than 3 seconds.
a. If “TEST RUN” and the counting number of the connect-
ed units to the remote control switch (for example
05”)
are indicated on the remote control switch, the connec­tion of remote control cable is correct.→Go to
b.
If no indication appear or the number of the units indicat­ed is smaller than the actual number of the units, some
abnormalities exist.→Go to
Remote Control
Switch Indication
Wrong Portions Inspection Points after Power Source OFF
No indication
The power source of Outdoor Unit is not turned ON.
The connection of the remote control cable is incorrect.
1 Connecting Points of Remote Control Cable terminal board of Remote
Control switch and indoor unit.
2 Contact of Terminals of Remote Control Cable
The connecting wires of power supply line are incorrect or loosened.
3 Connection Order of each Terminal Board 4 Screw Fastening of each Terminal Boards.
Counting number of connected units is incorrect
The power source of Outdoor Unit is not turned ON.
The operating line wiring between indoor unit and outdoor unit is not connected.
The connection of control cables between each indoor units are incorrect. (When one remote control switch controls multiple units)
5 Dip Switch Setting on Printed Circuit Board 6 Connecting on the PCB
7 This is the same as item 1, 2 , and 3.
Back to
after checking
Select TEST RUNNING MODE by depressing MODE Switch (COOL OR HEAT)
Depress RUN/STOP switch.
The TEST RUN operation will be started. (The 2 hours OFF-TIMER will be set and the TEST RUN operation will be nished after 2 hours unit operation or by depressing the RUN/STOP switch again).
NOTE
TEST RUN operation ignores the temperature limitation and ambient temperature during heating operation to have a continuous operation, but the protections are alive. Therefore, the protection may activate when the heating TEST RUN operation is performed in high ambient temperature.
TEST RUN operation time can be modifyed / increased depressing the time switch in the Remote Control.
If the unit do not start or the operation lamp on the remote control switch is ickered, some abnormalities exist. →Go to
Test running
33
PMML0317A rev.1 - 11/2013
ENGLISH
Remote Control
Switch Indication
Unit Condition Wrong Portions
Inspection Points after
Power Source OFF
The operation lamp ick­ers. (1 time/1 sec.) And the Unit No. and Alarm Code “03” icker
The unit does not start.
The power source of Outdoor Unit in not turned ON.
The connecting wires of operating line are incorrect or loosened.
1 Connecting Order of each Terminal
Board.
2 Screw fastening of each Terminal
Boards.
NO T E
Recovering method of FUSE for oper­ating circuit. There is a fuse (FUSE4 on Indoor Unit PCB1, EF1 on Outdoor Unit PCB1) to protect operating cir­cuit on the PCB, when the power lines are connected to operating lines. If fuse is melted, operating circuit can be recovered once by setting the dip
switch on the PCB as shown in
The operation lamp ick­ers. (1 time/2 sec.)
The unit does not start.
Remote control cable is broken.
Contact of connectors is not good.
The connection of remote control cable is incorrect
This is the same as item
1 and 2
Indication of Flicker except above
The unit does not start, or start once and then stops
The connection of thermistor or other connectors are incorrect. Tripping of protector exists, or else.
Check by the abnormality mode table in the Technical Catalogue (Do it by serv­ice people).
The operation lamp Flickers. (1 Time/1s)
Unit No.
00, Alarm
Code  and Unit Code
00 icker
The unit does not start.
The connection of the remote control cable between Indoor Units is incorrect.
Check by the abnormality mode table in the Technical Catalog (Do it by service people).
Back to
after checking
Instructions fot the recovery when the fuse of the transmission circuit is blown out:
1 Correct the wiring to the terminal board. 2 Set the 1st pin of DSW7 on the indoor unit PCB to ON.
16.2 TEST RUN FROM OUTDOOR UNIT SIDE
The procedure of test run from outdoor unit side is indicated be­low. Setting of this DIP switch is available with the power source ON.
Setting of Dip Switch
DSW1
Switch for setting of Serivice Operation and Function
1 Test Run 2 COOL/HEAT
Setting ON: Heat Operation
3 Cooling/Heating for intermediate
season
4 Manual Compressor stop
CA U T IO N
• Do not touch any other electrical parts when operating switch­es on the PCB
• Do not attach or detach service cover when the power source for the outdoor unit is ON and the outdoor unit is operated.
• Turn all DIP switches of DSW1 OFF when the test run opera­tion is completed.
34
Test running
PMML0317A rev.1 - 11/2013
Operation Dip Switch Setting Operation Remarks
Test Run
Setting of Operation Mode:
Cooling: Set DSW1-2 OFF.
Heating: Set DSW1-2 ON.
Starting Test Run:
Set DSW1-1 ON and the operation is started after a few ~20 seconds.
Cooling Heating
The indoor unit automatically start to operate when the test run of the outdoor unit is set.
The ON/OFF operation can be per­formed from the remote control switch or DSW1-1 of the outdoor unit.
Continuous operation during 2 hours is performed without Thermo-OFF.
NO T E
TEST RUN operation time can be
increased depressing the time switch in the Remote Control.
If is setting DSW1-3 ON, cool-
ing/heating intermediate season mode is activaded.
Take care that the indoor units start op-
eration in accord with the test run opera­tion of the outdoor unit.
The test run is started from the outdoor
unit and stopped from the remote con­trol switch, the test run function of the remote control switch is cancelled. How­ever, the test run function of the outdoor unit is not cancelled
In case that the plural indoor units are
connected with one remote control switch, all the units start test run opera­tion at the same time, therefore, turn the power source OFF for the indoor units not to operate test run. In this case, the “TEST RUN” indication of the remote control switch may icker, and this is not abnormal.
The setting of DSW1 is not required
for the test run from the remote control switch.
Manual OFF of Compressor
Setting:
Compressor Manual OFF:
Set DSW1-4 ON.
Compressor ON:
Set DSW1-4 OFF.
When DSW1-4 is ON during com­pressor operation, the compressor stops to operate immediately and the indoor unit is under the condition of Thermo­OFF.
When DSW1-4 is OFF, the com­pressor starts to operate after the can­cellation of 3-minutes guard.
Do not repeat compressor ON/OFF fre-
quently.
Manual Defrost
Manual Defrost Operation Starts
Press PSW1 for more than 3 seconds during heating operation, the defrost operation is started after 2 minutes.This function is not available within 5 minutes after starting heating operation
Manual Defrost Operation Finishes
Defrost operation is automatically ended and the heating operation is started.
Defrost operation is available re­gardless of frosting condition and total time of heating operation.
Defrost operation in not performed when the temperature of outdoor heat exchanger is higher than 10°C, high pressure is higher than 3.3 MPa (33kgf/ cm
2
G) or Thermo-OFF.
Do not repeat defrost operation frequent-
ly.
Safety summary & control device setting
35
PMML0317A rev.1 - 11/2013
ENGLISH
17 SAFETY SUMMARY & CONTROL DEVICE SETTING
Compressor Protection
High Pressure Switch:
This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
Fan Motor Protection
When the thermistor temperature is reached to the setting, motor output is decreased.
The other way, when the temperature becomes lower, limitation is cancelled.
Model RAS-3HVNP1E
RAS-(4-6)HVNP1E
RAS-4HVRNS3E
RAS-(4-6)HNP1E
RAS4HRNS3E
RAS-(8-10)HNPE RAS-(8-10)HNCE
For Compressor
Automatic Reset, Non-Adjustable (each one for each compressor)
Pressure Switches
-0.05 -0.05 -0.05 -0.05
High Cut-Out MPa 4.15 4.15 4.15 4.15
-0.15 -0.15 -0.15 -0.15
Cut-In MPa 3.20±0.15 3.20±0.15 3.20±0.15 3.20±0.15
For Control
Fuse
1~ 230V 50Hz
A 40
50
(RAS-4HVNCE = 40)
3N~ 400V 50Hz
A 2 X 20 2 X 40
CCP Timer
min.
Non-Adjustable
Setting Time 3 3 3 3
For Condenser Fan Motor
Automatic Reset, Non-Adjustable (each one for each motor)
Internal Thermostat
Cut-Out ºC - - - -
For Control Circuit
A 5 5 5 5
Fuse Capacity on PCB
18 TROUBLESHOOTING
Alarm Code Indication of Remote Control Switch:
Abnormal Indoor Unit No.
Abnormal Ref. Cycle No. Alarm Code Model Code
Connected No. of Indoor Units
Alarm Code
Model Code
Indication Model
Heat-Pump
COOL
MED
ADDS. RN
A/C ALARM
Indicated for a sec-
ond alter-
nately
COOL
MED
ADDS. RN
A/C ALARM
Inverter
Multi (Set-Free)
Cooling Only
Others
2, 3 and 4 indoor units system
36
Troubleshooting
PMML0317A rev.1 - 11/2013
Code
No.
Category Content of Abnormality Leading Cause
01 Indoor Unit Tripping of Protection Device
Failure of Fan Motor, Drain Discharge, PCB, Relay, Float Switch Activated
02 Outdoor Unit Tripping of Protection Device Activation of PSH, Locked Motor
03
Transmission
Abnormality between Indoor (or Outdoor) and Outdoor (or Indoor)
Incorrect Wiring, Failure of PCB, Tripping of Fuse, Power Supply OFF
04 Abnormality between Inverter and Control PCB Failure in Transmission between PCBs for Inverter
05 Power Supply Abnormality power supply Abnormal wave form of power supply.
06 Voltage Drop
Voltage Drop by Excessively Low or High Volt­age to Outdoor Unit
Voltage Drop of Power Supply. Incorrect Wiring or insufcient Capac­ity of Power Supply Wiring
07
Cycle
Decrease in Discharge Gas Superheat Excessive Refrigerant Charge, Expansion Valve Open Lock
08 Increase in Discharge Gas Temperature
Insufcient Refrigerant, Ref. Leakage, Clogging or Expansion Valve Close Lock
11
Sensor on
Indoor Unit
Inlet Air Thermistor
Failure of Thermistor, Sensor, Connection.
12 Outlet Air Thermistor
13 Freeze Protection Thermistor
14 Gas Piping Thermistor
19 Tripping of Protection Device for Fan Motor Failure of Fan Motor
20
Sensor on
Outdoor Unit
Compressor Thermistor
Failure of Thermistor, Sensor, Connection
(Incorrect Wiring, disconnecting wiring, breaking wire, short circuit)
21 High Pressure Sensor
22 Out+door Air Thermistor
24 Evaporating Thermistor
31
System
Incorrect Setting of Outdoor and Indoor Unit Incorrect Setting of Capacity Code.
35 Incorrect Setting in Indoor Unit No.
Duplication of Indoor Unit number, Nº of Indoor unit over specica­tions.
38 Abnormality of Protective Circuit in Outdoor Unit
Failure of Indoor Unit PCB. Incorrect wiring. Connection to PCB in Indoor Unit.
45
Pressure
Activation of High Pressure Increase Protection Device
Overload Operation (Clogging, Short-Pass), Pipe Clogging, Exces­sive Refrigerant, Inert Gas Mixing
47
Activation of Low Pressure Decrease Protection Device
Stoppage by Excessively Decrease of evaporating Temperature (Te < -35ºC) is activated 3 times in one hour, Locked Motor in Heat­ing Operation.
48
Inverter
Activation of overload protection
Failure of IPM or PCB2, heat exchanger clogged, locked compres­sor, EVI/EVO failure or overcharge.
51 Abnormality of Current Sensor for Inverter Failure of Control PCB, Inverter Module.
53 Protection Activation of Transistor Module
Transistor Module Abnormality. Failure of Compressor, clogging of Heat Exchanger.
54 Inverter Fin Temperature Increase
Abnormal Inverter Fin Thermistor.
Clogging of Heat Exchanger
Abnormal Outdoor Fan
55 Inverter Module Abnormality Failure of Inverter Module.
57 Outdoor Fan Fan Motor Abnormality
Disconnected wire of Incorrect wiring between Control PCB and Inverter PCB.
Incorrect Wiring or Fan Motor Abnormality
b1
Indoor unit No.
setting
Incorrect address No. Setting or refrigerant cycle
Over 64 indoor units setting by No. or indoor unit address.
EE Compressor Compressor protection alarm Failure of compressor.
PMML0317A rev.1 - 11/2013
Printed in Spain
Loading...