Hitachi RAM-35QH5 Installation manual

Hitachi RAM-35QH5 Installation manual

<IA586: C >

FOR SERVICE PERSONNEL ONLY

SPLIT UNIT AIR CONDITIONER INSTALLATION MANUAL

Outdoor Unit HFC RAM-35QH5

R410A

SAFETY PRECAUTION

Carefully read through the procedures of proper installation before starting installation work.

The sales agent should inform customers regarding the correct operation of installation.

Tools Needed For Installation Work

(Mark is exclusive use tool for R410A)

+ – Screwdriver Measuring Tape Knife Saw ø 65mm Power Drill Hexagonal Wrench Key ( 4mm) Wrench (14, 17, 22, 26mm) Gas Leakage Detector Pipe Cutter Putty Vinyl Tape

Pliers Flare Tool Vacuum Pump Adapter Manifold Valve Charge Hose Vacuum Pump

Read the safety precautions carefully before operating the unit.

The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

!WARNING ........ Incorrect methods of installation may cause death or serious injury.

!CAUTION ......... Improper installation may result in serious consequence.

Make sure to connect earth wire.

This sign in the figures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as described in the user’s guide.

!WARNING

Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.

Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.

Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.

Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use power cables approved by the authorities of your country.

Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fire.

Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock and fire may occur.

Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.

When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.

Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.

After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.

Be sure to connect the earth wire from the power supply wire to the outdoor unit and between the outdoor and indoor

unit. Improper earthing may cause electric shock.

!CAUTION

A circuit breaker must be installed in the house distribution box for the direct connected power supply wire to the outdoor unit. In case of other installations a main switch with a contact gap or more than 3.5mm has to be installed. Without a

circuit breaker, the danger of electric shock exists.

Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable

gas leaks around it. Piping shall be suitable supported with a maximum spacing of 1m between the supports.

Be sure to tighten the flare nut to the specified torque using a torque wrench. If the flare nut is tightened excessively, it may crack as time elapses, cause refrigerant leakage.

Please ensure smooth flow of water when installing the drain hose.

An IEC approved power cord should be used. Power cord type: NYM.

THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).

!WARNING

The Outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.

!CAUTION

Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.

The air blown out of the unit should not point directly to animals or plants.

The clearances of the unit from top, left, right and front are specified in figure below. At least 3 of the above sides must be open air.

Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.

Do not install at a location where there is flammable gas, steam, oil and smoke.

The location must be convenient for water drainage.

Place the Outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone. This is to avoid noise interference.

If you wish to prepare the copper tubes and insulation material in the field, we recommend the following.

No.

 

 

Material

Specification

 

 

 

 

 

 

1

Copper tube

 

2.0-2.5kW

Small dia.

Deoxidized annealed copper pipe with 6.35mm O.D., 0.8mm wall thickness.

 

 

 

Large dia.

Deoxidized annealed copper pipe with 9.52mm O.D., 1.0mm wall thickness.

 

 

 

 

 

 

 

 

 

 

2

Flare nut

 

2.0-2.5kW

Small dia.

Flare nuts with 6.35mm O.D..

 

 

 

Large dia.

Flare nuts with 9.52mm O.D..

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Foamed polyethylene insulation pipe which does not corrode the copper tube.

3

Insulation for refrigerating pipe

Large dia. pipe side: 15mm I.D.., 8mm wall thickness.

 

 

 

 

 

Small dia. pipe side: 8mm I.D., 7mm wall thickness.

 

 

 

 

 

 

4

Connecting cord

 

 

Refer to item 3.3.

 

 

 

 

 

 

5

Vinyl tape

 

 

 

 

 

 

 

 

 

6

Sealer (Putty)

 

 

 

 

 

 

 

 

 

7

Refrigerant oil

 

 

 

 

 

 

 

 

8

Bushing for refrigerating pipes

 

 

 

 

 

 

 

1. Proper place for installation

1.1Outdoor unit

(1)Keep the space around the unit for maintenance and avoiding the effects of hindrance for normal ventilation of the unit.

(2)The northern or eastern side of the building is better to install. At the installation on the southern or western side unavoidably, some blind should be set up for the unit. (In this case, the blind must not obstruct the ventilation of the unit.)

(3)You’d better not put the unit at a place where is full of dirt and at a place where is wet in the rain.

(4)Place as near as possible to the indoor unit.

(5)Install the unit in a stable place to minimize vibration or noise.

(6)After arranging the cords and pipes, secure them in place.

! WARNING

This appliance must be earthed.

Power is supplied through outdoor unit, do not connect power source to indoor unit.

 

 

 

2.In the electrical installation a separator with a contact gap of more than 3mm has to be installed. During cleaning or service the set has to be switched off with this separator.

3.Installation procedure and notice

Especially, the selection of installation place need great care for the split type air conditioner, because it is very difficult to move from place to place after the first installation.

3.1Wiring

(1)Connect the electrical wiring between the Indoor and Outdoor unit, as shown in Fig. 3-1. Never connect the wiring by mistake.

In case of wrong connection, the unit does not operate properly and it may cause malfunction.

(2)The connecting cord must be fixed by the band which is located near the terminal board.

Procedures of Wiring

3.2Connection of the connecting cords and power cord

(1)Cut off the connecting cord, the power cord and strip the insulation of the wire, as shown in Fig. 3-2.

(2)Connect the connecting cord and power cord to the terminal board. (Fig. 3-3)

(3)Fix the connecting cords and power cord with steel band certainly. (Fig. 3-3)

30mm

Green-and-yellow (ground)

10mm

10mm 55mm

Power cord and connecting cord

Wiring Pattern

Indoor Unit

 

 

 

 

Indoor unit No. 1

 

 

 

 

 

Indoor unit No. 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screw for ground, earth screw

 

 

Screw for ground, earth screw

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal board

 

 

 

 

 

 

 

Terminal board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

D

 

 

 

 

 

 

 

 

 

 

C

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting cord

 

 

 

 

 

 

Green-and-

 

 

 

 

 

 

Green-and-

 

 

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

Yellow

 

 

 

 

Ø1.6 or 2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting cord

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ø1.6 or 2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C1

D1

 

 

 

 

 

 

 

 

 

 

C2

D2

 

 

 

 

 

 

 

Terminal board

 

 

 

Screw for ground,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

N

 

 

 

 

 

Terminal board

 

 

 

 

 

Terminal board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

earth screw

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screw for ground, earth screw

 

 

Screw for ground, earth screw

Green-and-Yellow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For Indoor unit No. 1

 

 

 

 

 

For Indoor unit No. 2

 

 

 

 

Detail of cutting power cord and

For Indoor Unit No. 1 (C1, D1)

 

 

 

 

60mm

Green-and-yellow (ground)

10mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10mm

 

85mm

Connecting cord

 

 

 

 

For Indoor Unit No. 2 (C2, D2)

Fig. 3-2

Outdoor Unit

Power cord

Fig. 3-1

!WARNING

The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is tight. Improper insertion may burn the terminal.

Be sure to use only power cables approved from the authorities in your country. For example in Germany: Cable type: NYM 3x1.5mm2. (fuse = 16A time delay)

Please refer to the installation manual for wire connection to the terminals of the units. The cabling must meet the standards of electrical installation.

There is a AC voltage of drop between the L and N terminals. Therefore, before servicing, be sure to switch off the main switch.

Wiring of The Outdoor Unit

Please remove the side cover for wire connection.

Names of Outdoor Components

Figure showing the Installation of Outdoor Unit.

 

No.

Item

Qty

Height difference

 

 

Piping length

 

Bush

 

Height difference between indoor units should

 

Indoor unit 1

Indoor unit 2

10

 

2

not be more than 5m.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit 2

 

 

 

 

Drain Pipe

 

Indoor unit 1

 

Outdoor unit

L1

L2

 

 

 

 

 

 

11

 

1

 

 

 

 

 

 

 

 

Outdoor unit

20

 

 

 

 

 

 

 

 

 

 

 

Bush

 

 

 

(L1 + L2) = Maximum 35m

12

 

1

 

 

 

 

 

Minimum piping length for each indoor unit is 5m.

 

 

 

 

 

 

 

 

 

Maximum piping length for one indoor unit is 25m.

 

 

 

above 200mm

 

Additional charge of refrigerant is not required.

 

 

 

 

 

 

 

Dimension of Mounting Stand

above 50mm when

)

of the Outdoor unit

(ceilinginstalledofonbalconythe

(unit: mm)

mounting stand

57

<![if ! IE]>

<![endif]>10

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>320

<![if ! IE]>

<![endif]>340

above 100mm

 

 

<![if ! IE]>

<![endif]>20

 

 

12

 

<![if ! IE]>

<![endif]>(10)

 

 

35

 

 

 

500

124

 

 

above 700mm

 

 

 

 

[Outdoor unit installation]

Mount the Outdoor unit on stable ground to prevent vibration and increase of noise level.

Decide the location for piping after sorting out the different types of pipe available.

!CAUTION

Make sure to connect to two indoor units.

<![if ! IE]>

<![endif]>port

<![if ! IE]>

<![endif]>Indoorunit 1

<![if ! IE]>

<![endif]>connection

<![if ! IE]>

<![endif]>Outdoorunit pipe

One unit of 1.8kW, 2.5kW, 3.5kW

<![if ! IE]>

<![endif]>Indoorunit 2

 

One unit of 1.8kW, 2.5kW, 3.5kW

To the outdoor unit, up to two indoor units can be connected until the total nominal cooling capacity not more than 6.0 kW.

The pipe connection ports of the outdoor unit and connectable indoor units are shown below.

<IA586: C >

above 100mm

When removing side cover, pull the handle

give clearance as

after releasing the hook by pulling it

wide as possible

downward.

 

 

Face this side (suction side) of

 

the unit to the wall.

above 200mm

Remove side cover

 

when connecting the

 

piping and connecting

 

cord.

 

Pull downward

CONDENSED WATER DISPOSAL OF OUTDOOR UNIT

There are holes on the base of Outdoor unit for condensed water to exhaust.

In order to flow condensed water to the drain, the unit is installed on a stand or a block so that the unit is 100mm above the ground as shown figure. Join the drain pipe to one hole.

At first insert one portion of the hook to the base (Portion A), then pull the drain pipe in the direction shown by the arrow while inserting the hook into the base. After installation, check whether the drain pipe cling to the base firmly.

A

<![if ! IE]>

<![endif]>ABOVE

 

BASE

<![if ! IE]>

<![endif]>100 mm

 

 

 

DRAIN PIPE

10 BUSH

DRAIN PIPE /

 

11

 

12

BUSH

When Using and Installing In Cold Areas

When the air conditioner is used in low temperature and in snowy conditions, water from the heat exchanger may freeze on the base surface to cause poor drainage. When using the air conditioner in such areas, do not install the bushings. Keep a minimum of 250mm between the drain hole and the ground. When using the drain pipe, consult your sales agent.

For more details, refer to the installation Manual for Cold Areas.

If you cannot attach the side cover due to the connecting cord, press the connecting cord in direction to the front panel to fix it.

!Be sure that the hooks of the side cover is fixed in certainly. Otherwise water leakage may occur and this causes short

circuit or faults.

WARNING The connecting cord should not touch to service valve and pipes. (It becomes high temperature in heating operation.)

3.3 Checking for the electric source and the voltage range

Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the main switch and outdoor unit in consideration of the locked rotor current.

IMPORTANT

Cable length

Wire cross-section

 

! WARNING

up to 16m

1.5mm2

 

Connect the Connecting Cord to C1 and D1 “Indoor 1” for indoor unit 1,

up to 15m

2.5mm2

 

C2 and D2 “Indoor 2” for indoor unit 2.

up to 25m

4.0mm2

 

 

Bind connecting cords to make them fit between the convex sections.

Connect the earth cord

 

!

CAUTION

 

Arrange power cord so they do

 

not touch service valve.

 

After remove the screw and

 

cover, put the connecting

 

cords and fix the cover with

 

screw.

 

Earth line

 

 

Type of grounding rod

Length

Fig. 3-3

SP-EB-2

900mm

 

AC 220V~240V ONLY

L N

INDOOR 1

INDOOR 2

C D

C D

Grounding rod (optional)

(Earth wire and grounding rod are not supplied. Please use optional items below.)

Investigate the power supply capacity and other electrical conditions at the installation location.

Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary electrical work etc.

The electrical work includes the wiring work up the outlet. In localities where electrical conditions are poor, use of a voltage regulation is recommended.

IMPORTANT

Fuse Capacity

16A time delay fuse

INS RAM-35QH5

1

31/3/09, 12:26

4.Preparation of Pipe

Use a pipe cutter to cut the copper pipe.

 

! CAUTION

Trimming tool

Jagged edge will cause leakage.

 

Point the side to be trimmed downwards during trimming to

Copper

prevent copper chips from entering the pipe.

pipe

 

Before flaring, please put on the flare nut.

Die

Die

A

 

 

 

Recommend to use

 

 

R410A flaring tool.

 

 

Copper pipe

5. Pipe Connection

5.1Pipe connection

Connecting the pipe to outdoor unit

(1)Remove the flare nut and seal cap from the service valve.

(2)Apply refrigerator oil to the service valve and the flared portion of the pipe.

(3)Using a wrench, security tighten.

Outer

 

 

A (mm)

 

Diameter (Ø)

For R410A tool

 

For R22 tool

 

 

 

6.35

(1/4”)

0

~ 0.5mm

 

1.0mm

9.52

(3/8”)

0

~ 0.5mm

 

1.0mm

Tighten all the way by hand.

Do not tighten all at once, but tighten it while fitting the flared surface to the pipe.

In case of removing flare nut of a indoor unit, first remove a nut of small diameter side, or seal cap of large diameter side will fly out. Free from water into the piping when working.

!CAUTION During connection, keep away from water.

Be sure to tighten the flare nut to the specified torque using a torque wrench. If the flare nut is tightened excessively, it may crack as time elapses, causing refrigerant leakage.

Please be careful when bending the copper pipe.

Screw in manually while adjusting the center. After that, use of torque wrench to tighten the connection.

 

 

 

 

Outer diameter of pipe (Ø)

Torque N·m (kgf · cm)

 

Flare nut

Small diameter side

6.35

(1/4”)

13.7-18.6 (140-190)

 

 

Large diameter side

9.52

(3/8”)

34.3-44.1

(350-450)

Wrench

Torque

Valve head

Small diameter side

6.35

(1/4”)

19.6-24.5

(200-250)

 

 

 

 

 

 

wrench

cap

Large diameter side

9.52

(3/8”)

19.6-24.5

(200-250)

 

 

 

Valve core cap

 

 

12.3-15.7

(125-160)

Install the unit in a stable place to minimize vibration or noise.

After arranging the cords and pipes, secure them in place.

Connecting cord should have arranged with piping using tape previously.

Pipe connection port for Indoor unit No. 1

Pipe connection port for Indoor unit No. 2

Indoor unit No. 1

Indoor unit No. 2

Gas leakage inspection

Please use gas leakage detector to check if leakage occurs at connection of flare nut as shown on the right.

If gas leakage occurs, further tighten the connection to stop leakage. (Use the detector provided for R410A)

<IA586: C >

6. Removal Of Air From The Pipe And Gas Leakage Inspection

6.1 Air purging by using vacuum pump

Remove the valve cap of valve core.

 

Air purging by vacuum pump

 

 

 

 

 

Connect the charge hoses to the

When the meter reaches -101KPa (-76cmHg) during

pumping, fully tighten the shuttle.

vacuum pump and the charge port of

 

 

 

 

 

the valve core large dia. pipe side

 

 

Meter showing pressure

service valve, respectively.

 

 

 

 

Closed

 

 

 

 

 

 

 

 

 

Lo Hi

 

 

Charge hose

 

R410A Manifold valve

 

 

 

Fully open the LO knob of the

Stop valve

 

Stop

Vacuum pump

manifold valve.

 

valve

 

Run the vacuum pump.

 

 

 

Vacuum pump adapter

 

 

 

 

 

Vacuum for more

When

pumping

starts,

 

than 10 min.

slightly

loosen the

flare

Be sure the stop valve

Close the LO knob of the manifold

nut to

check

of

air

is always fully opened.

sucked in. Then tighten

 

valve.

 

the flare nut.

 

 

 

 

 

 

 

Stop the vacuum pump.

Remove the valve cap from the spindle of the service valve.

Turn the spindles of each large and small dia. pipe side service valves full counterclockwise until they are securely tightened. Then retighten them more than 10 degrees [using a hexagon wrench key (4mm ) without fail].

Fig. 6-1

Valve cap of valve core

Valve cap

Valve cap

Disconnect the charge hose from the service valve.

Tighten the valve cap of valve core. [Torque 12.3 - 15.7 N¥m (125 - 160 kgf¥cm)]

Attach the valve cap to the spindles of each large and small dia. pipe side service valves.

Tighten the valve cap of the spindle. [Torque 19.6 - 24.5 N¥m (200 - 250 kgf¥cm)]

7. Operation test

Fig. 6-2

 

Valve cap

Stopper

Valve cap of

O-Ring

valve core

Pipe

Seal cap

Valve core

Pipe

Flare nut

Spindle

 

Fig. 6-3

The refrigerant channel is opened so that the refrigerant will flow from the outdoor unit into the indoor unit.

Please ensure that the air conditioner is in normal operating condition during the operation test.

Explain to your customer the proper operation procedures as described in the user’s manual.

If the indoor unit does not operate, check to see that the connections are correct.

!CAUTION

Trial run should be conducted on one unit at a time to check for incorrect wiring of connecting cord.

INS RAM-35QH5

2

31/3/09, 12:26