FOR SERVICE PERSONNEL ONLY
● Carefully read through the procedures of proper
installation before starting installation work.
● The sales agent should inform customers regarding
the correct operation of installation.
SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit Outdoor Unit
RAK-70PPA RAC-70WPA
SAFETY PRECAUTION
● Read the safety precautions carefully before operating the unit.
● The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
CAUTION ......... Improper installation may result in serious consequence.
!
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of
operating the unit as described in the user’s guide.
!
WARNING
● Please request your sales agent or quali ed technician to install your unit. Water leakage, short circuit or re may occur if
you do the installation work yourself.
● Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and re.
● Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not,
the units may collapse and impose danger
● Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country
● Be sure to use the speci ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
re.
and
● Please use the speci ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock
re may occur.
and
● Be sure to use the speci ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
● When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise,
pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.
● Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with re, a poisonous
gas may occur.
● After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas
leaks into the room, coming into contact with
● Unauthorized modi cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali ed air
conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and
● A circuit breaker or fuse (30A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock
exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
● Do not install the unit near a location where there is ammable gas. The outdoor unit may
catch re if ammable gas leaks around it.
● Please ensure smooth ow of water when installing the drain hose.
● Piping shall be suitable supported with a maximum spacing of 1m between the supports.
.
re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
!
CAUTION
Tools Needed For Installation Work
● + – Screwdriver ● Measuring Tape ● Knife
● Saw ● ø 65mm Power Drill ● Allen Key ( 4mm)
● Wrench (14, 17, 19, 22mm)
● Gas Leakage Detector ● Pipe Cutter
● Plastic Tape ● Pliers ● Flare Tool
.
re, etc.
The Choice of Mounting Site (Please note the following matters and obtain permission from customer before installation).
!
WARNING
● The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
!
● No nearby heat source and no obstruction near the air outlet is
allowed.
● The clearance distances from top, right and left are speci ed in
gure below.
● The location must be convenient for water drainage and pipe
connection with the Outdoor unit.
● To avoid interference from noise please place the unit and its
INDOOR UNIT
remote controller at least 1m from the radio, television and inverter
uorescent lamp.
type
● To avoid any error in signal transmission from the remote controller,
please put the controller far away from high-frequency machines
and high-power wireless systems.
● The installation height of indoor unit must be 2.3m or more.
CAUTION
Names of Indoor Components
QtyNo. Component’s Name
Mounting plate
1
Screw for Mounting Plate
2
Remote Controller Holder
3
AAA Size Battery
4
Screw for Remote
Controller Holder
5
Remote Controller
6
Air Purifying Filter
7
(4.1x32)
1
6
Direction of Piping
1
There are 6 directions
allowed, namely, horizontally
perpendicular to the unit,
2
vertically down from right,
horizontally out from right and
horizontally out to left.
2
Dimension of Mounting Stand
of the Outdoor unit
(unit : mm)
1
2
Names of Outdoor Components
QtyNo. Item
Bush
8
9
10
Bush
Drain Pipe
1
3
1
● The Outdoor unit must be mounted at a location which can sup-
port heavy weight. Otherwise, noise and vibration will increase.
●
Do not expose the unit under direct sunshine or rain. Besides, ventilation
must be good and clear of obstruction.
●
The air blown out of the unit should not point directly to animals or plants.
●
The clearances of the unit from top, left, right and front are speci ed in
gure below. At least 3 of the above sides must be open air.
●
Be sure that the hot air blown out of the unit and noise do not disturb
the neighbourhood.
●
Do not install at a location where there is ammable gas, steam, oil and
smoke.
OUTDOOR UNIT
●
The location must be convenient for water drainage.
●
Place the Outdoor unit and its connecting cord at least 1m away from
the antenna or signal line of television, radio or telephone. This is to
avoid noise interference.
●
Do not install outdoor unit facing strong wind direction. It may damage
the fan motor
Figure showing the Installation of
Indoor and Outdoor Unit
.
!
WARNING
!
CAUTION
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commersial
products).
● The difference in height
between the indoor and
outdoor unit should be
kept max 20m.
● The connecting pipe,
no matter big or small,
should all be insulated
with insulation pipe and
then wrapped with vinyl
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
1
Installation of Mounting Plate, Wall Penetration and Installation of Protection Pipe
!
● The draining of the water container inside the indoor unit can be done from the left.
Therefore the mounting plate must be
side of drain hose. Otherwise, condensed water may over ow the water container.
Direct Mounting On The Wall
● Please use hidden beams in the wall to hold the mounting plate.
Procedures of Installation and Precautions
● Procedures to x the mounting plate.
1. Drill holes on wall. 2.
(As shown below)
CAUTION
xed horizontally or slightly tilted towards the
Push plug into the holes. 3. Fix the mounting plate on
(As shown below) wall with 4.1 x 32 screw
(As shown in gure below)
INDOOR UNIT
● Procedures to x the holder of remote control.
1. Drill holes on wall. 2. Push plug into the holes.
(As shown below)
Wall Penetration and Installation of Protection Pipe
● Drill a ø 80mm hole on
wall which is slightly tilted
towards the outdoor side.
Drill the wall at a small
angle.
● Cut the protection pipe
according to the wall
thickness.
● Empty gap in the sleeve
of protection pipe should
be completely sealed with
putty to avoid dripping of
rain water into the room.
(As shown below)
WARNING
!
Be sure that the wire is not
in contact with any metal
in the wall. Please use
the protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
2
Installation of the Indoor Unit
DIRECTLY BACKWARD AND DOWNWARD PIPING
Preparation
● Connect connecting cord.
● Pull out the pipe, connecting cord and drain hose.
● Arrange a drain hose in lowest part of a wall hole.
Installation
● The upper part of the Indoor unit is hanged on the mounting plate.
● The projection at the lower part of the Indoor unit is hooked onto the mounting plate.
CAUTION
!
Please pull the lower part of
the Indoor unit outwards to
check if the unit is hooked
onto the mounting plate.
Improper installation may
cause vibration and noise.
HOW TO REMOVE INDOOR UNIT FROM HANGER
● Push up PUSH section on the bottom of indoor
unit, then claws are released from hanger
(Indicated by 2 arrows in the drawing on the
right.)
.
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
●
Exchange the location of drain hose and drain cap during horizontal piping as shown in
gure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
● Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
CAUTION
!
Condensed water may leak out if not inserted properly.
Horizontal & Downward Piping – Making Openings
● During horizontal or downward piping, use a knife to cut
openings as shown in
openings with a le.
gure.
Then smoothen the edges of
● Turn the piping while holding down the lower
portion of pipe-support by hand.
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
● The refrigerating pipes should be adjusted to t
into the hole on the wall and then ready for further
connection.
● The terminals of 2 connected pipes must be covered
with insulator used for terminal connection.
pipes are wrapped with insulation pipe.
● Connect the connecting cord after removing electrical
cover. (Refer to “CONNECTION OF POWER CORD”)
● After adjustment, t the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
Layout of pipe
● Holder can be attached at the either of 2 places.
Please select the easier position.
Then the
Layout of pipe
!
CAUTION
●
The rubber strap used for
xing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
● The refrigerating pipes and connecting cord
transform and are attached.
● The end of the refrigerating pipes are at locations
marked with
” symbol.
“
Installation
Hang the Indoor unit onto the mounting plate. Use the temporary
stand at the back of the Indoor unit to push its lower part 15cm
forwards.
● Place the drain hose through the hole on the wall.
● Wrap the refrigerating pipes with insulation pipe after connecting
refrigerating pipe.
● Connect the connecting cord after removing electrical cover.
(Refer to “Connection of Power Cord”)
● After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit. Use
holder to hold them tight.
● The projection of Indoor unit must hook to the mounting plate.
Heat insulation pipe
Connecting
cord
Refrigerating pipe
3
Installation of Drain Hose
You are free to choose the side (left or right) for the installation of drain
!
CAUTION
hose. Please ensure the smooth ow of condensed water of the Indoor
unit during installation. (Carelessness may result in water leakage.)
Pull this to the front
during the connection
of refrigerating pipes
to ease task.
CAUTION
!
● Please x in the plastic core
after
aring to avoid plastic
chips entering the pipes.
CAUTION
!
Be sure that the
drain hose is not
loosely connected
or bend.
<
IA926: A
>
● Please mount the outdoor unit on
stable ground to prevent vibration
and increase of noise level.
● Decide the location for piping after
sorting out the different types of
pipe available.
● Open the side plate by unscrewing
the screws as shown below.
CAUTION
!
Please make sure to remove all
spacers inside the unit.
● Open the Top, Back and Side
cover of the unit.
● Pull out the spacers inside.
(Spacers are only for transportation
purpose).
If not remove, vibration and noise
will occur.
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed water to exhaust.
In order to ow condensed water to the drain, the unit is installed on a stand
or a block so that the unit is 100mm above the ground as shown gure.
Join the drain pipe to one hole.
OUTDOOR UNIT
At rst insert one portion of the hook to the base (Portion A), then pull the
drain pipe in the direction shown by the arrow while inserting the hook into
the base. After installation, check whether the drain pipe cling to the base
rmly.
BASE
DRAIN PIPE
When using in cold region, etc.
In cold region with severe cold climate and heavy snow, water discharged
from heat exchanger freeze on the base surface and this may affect
drainage. In such a region, remove bush on the bottom face of outdoor unit
for better drainage. When using drainpipe, consult our dealer.
Please face this side
(suction side) of the
unit to the wall.
Pull
downward
Top cover
Please
remove side
cover when
connecting
the piping
and
connecting
cord.
Back cover
Side cover
1
Preparation of Pipe
● Use a pipe cutter to cut the copper pipe.
CAUTION
!
● Jagged edge will cause leakage.
● Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
● Before aring, please put on the are nut.
● Please use exclusive tool
Outer
Diameter
mm (inch)
6.35 (1/4")
9.52 (3/8")
12.70 (1/2")
15.88 (5/8")
2
Pipe Connection
CAUTION
!
● Please be careful when bending the copper pipe.
● Screw in manually while adjusting the center. After that, use of torque wrench to
tighten the connection.
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
Thickness
In case of removing are nut of an Indoor unit, rst remove a nut
of small diameter side, or a seal cap of big diameter side will y
out. Prevent water from entering into the piping when working.
(mm)
0.8
0.8
0.8
1.0
Small dia. side
Large dia. side
Valve
head cap
Valve core cap
Flare tool for R410A
Clutch type
~ 0.5
0.0
~ 0.5
0.0
0.0
~ 0.5
~ 0.5
0.0
Small dia. side
Large dia. side
A (mm)
Conventional are tool
Clutch type
1.0 ~ 1.5
1.0 ~ 1.5
1.0 ~ 1.5
1.0 ~ 1.5
Outer
dia.of pipe
6.35 (1/4")
9.52 (3/8")
12.70 (1/2")
15.88 (5/8")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
14.0 – 18.0 (140 – 180)
33.0 – 42.0 (330 – 420)
50.0 – 62.0 (500 – 620)
63.0 – 77.0 (630 – 770)
19.6 – 24.5 (200 ~ 250)
19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
Wing nut type
1.5 ~ 2.0
1.5 ~ 2.0
1.5 ~ 2.5
1.5 ~ 2.5
Torque N·m
·
(kgf
cm)
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
As shown in right gure, remove the cap of
valve core. Then, connect the charge hose.
Remove the cap of valve head. Connect the
1
vacuum pump adapter to the vacuum pump
and connect the charge hose to the adapter.
Fully tighten the “Hi” knob of the manifold
valve and completely unscrew the “Lo” knob.
Run the vacuum pump for about 10~15
2
minutes, then completely tighten the “Lo” knob
and switch off the vacuum pump.
Remove the charge hose and tighten the cap
of valve core. Check the cap’s periphery if
3
there is any gas leakage.
AIR REMOVAL
Completely unscrew the spindle of the
service valve (at 2 places) in anti-clockwise
4
direction to allow the ow of refrigerant (using
Hexagonal Wrench key).
Re-cap the service valve and tighten using
wrench. Check the cap’s periphery if there is
5
any gas leakage. The task is then completed.
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully
tighten the shuttle.
Valve
When pumping starts, slightly loosen the
are nut to check of air sucked in. Then
tighten the are nut.
Charge hose
Meter showing pressure
Vacuum pump
adapter
Gas Leakage Inspection
Please use gas leakage detector to check if leakage
occurs at the connection of Flare nut as shown on
the right.
If gas leakage occurs, further tighten the connection
to stop leakage.
Valve
Closed
R410A
Manifold valve
Vacuum
pump
WARNING
!
● THIS APPLIANCE MUST
BE EARTHED.
Procedures of Wiring
In case that power is supplied from Indoor Unit
Power line Control line
Indoor
Unit
GRN + YEL
Strip wires
Outdoor
Unit
GRN + YEL
CONNECTION OF POWER CORD
●
The naked part of the wire core should be 10 mm and x
it to the terminal tightly. Then try to pull the individual wire
to check if the contact is tight. Improper insertion may burn
the terminal.
●
Be sure to use only power cables approved from the
authorities in your country. For example in Germany: Cable
type: NYM 3x1.5mm
●
Please refer to the installation manual for wire connection
to the terminals of the units. The cabling must meet the
standards of electrical installation.
●
There is a AC voltage of 220-240V between the L, N, A and
B terminals. Therefore, before servicing, be sure to remove
the plug from the AC outlet or switch off the main switch.
WARNING
!
2
, (fuse = 30A time delay)
Wiring Of The Indoor Unit
●
For wire connection of the Indoor unit, you need to remove
front panel and electrical cover.
Method to remove front panel
●
Refer to “FINAL STAGE OF INSTALLATION – How to Remove
The Front Cover”.
Method to remove electrical cover
●
Remove the screw and electrical cover.
●
Insert the connecting cord (A, B, C, D) from the bottom of unit.
●
Fixed the wire to terminal wires rmly as shown in gure at
right side.
ScrewElectrical coverScrew
Wiring of The Outdoor Unit
● Please remove the side cover for wire connection.
● If you cannot attach the side cover
due to the connecting cord, press the
connecting cord in direction to the front
!
WARNING
panel to x it.
● Be sure that the hooks of the side cover
is xed in certainly. Otherwise water
leakage may occur and this causes short
circuit or faults.
● The connecting cord should not touch
to service valve and pipes. (It becomes
high temperature in heating operation.)
Checking for the electric source
and the voltage range
● Before installation, the power source must be checked and
necessary wiring work must be completed. To make the
wiring capacity proper, use the wire gauges list below for
the lead-in from a pole transformer and for the wiring from
a switch board of fuse box to the main switch and outdoor
unit in consideration of the locked rotor current.
IMPORTANT
Cable length
16m
up to
up to 15m
up to 25m
Wire cross-section
2
1.5mm
2
2.5mm
2
4.0mm
Connect the
earth cord
After remove the screw
and band, put the
connecting cords and x
the band with screw.
● Investigate the power supply capacity and other
electrical conditions at the installation location.
Depending on the model of room air conditioner to be
installed, request the customer to make arrangements
for the necessary electrical work etc.
The electrical work includes the wiring work up the
outlet. In localities where electrical conditions are
poor, use of a voltage regulation is recommended.
ABCD
N
L
A
B
C
D
Earth terminal
IMPORTANT
Fuse Capacity
30A time delay fuse
CAUTION
Outdoor supply cords shall not be lighter than
polychloroprene sheathed exible cord with code
designation 60245 IEC 57.
How To Connect The Optional Parts
(RAC Adapter, Wired Remote Controller)
H-LINK
[For all optional part, please refer catalog for part number]
As for connecting to H-Link, a separately purchased
RAC Adapter is required.
● To install the wiring the electrical box cover must be opened.
● Connect the connector of RAC adapter to CN1101.
● Assemble back the cover of electrical box.
● Please refer to the respective user manual of RAC Adapter
for further details.
● Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
WIRED REMOTE CONTROLLER
[For all optional part, please refer catalog for part number]
Connection to the electrical box:
● Remove the cover of electrical box.
● Connect the connector of wired remote controller to CN1102.
● Assemble back the cover of electrical box.
● Please refer to the respective user manual of wired remote
controller for further details.
● Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
1
Insulation And Maintenance Of Pipe Connection
● The connected terminals should be completely sealed with
heat insulator and then tied up with rubber strap.
● Please tie the pipe and power line together with vinyl tape
as shown in the gure showing the installation of Indoor and
Outdoor units. Then x their position with holders.
● To enchance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose
and pipe with insulation pipe.
● Completely seal any gap with putty.
3
Power Source And Operation Test
Power Source
!
FINAL STAGE OF INSTALLATION
● Please use a new socket. Accident may occur due to the use
of old socket because of poor contact.
● Please plug in and then remove the plug for 2 – 3 times. This
is to ensure that the plug is completely plugged into the socket.
● Keep additional length for the power cord and do not render
the plug under external force as this may cause poor contact.
● Do not x the power cord with U-shape nail.
<
IA926: A
>
CAUTION
2
Installation Of Remote Controller
● The remote controller can be placed in its holder which is
xed on wall or beam.
● To operate the remote controller at its holder, please ensure
that the unit can receive signal transmitted from the controller
at the place where the holder is to be xed. The unit will beep
when signal is received from the remote controller. The signal
transmission is weaken by the uorescent light. Therefore,
during the installation of the remote control holder, please
switch on the light, even during day time, to determine the
mounting location of the holder.
The remote controller
must be slide in
the remote controller
holder, in the direction
as shown in the gure,
until it hooks at the
lower end of the remote
controller holder.
Screw (2 pieces)
Remote
Controller
Remote
Controller
Holder
Operation Test
● Please ensure that the air conditioner is in normal operating
condition during the operation test.
● Explain to your customer the proper operation procedures
as described in the user’s manual.
How to remove the Front Cover
1 Open the front panel.
● Please remove and attach the
front panel by both hands.
2
● After opening the front panel by both hands.
1 Undo the right arm while pushing it inside.
2 Slide the front panel to right as shown in gure. Then
remove while pulling it to front.
2 Remove the lters.
Cap
3 Remove the caps and screws
at the lower portion of the
front cover.
4 Pull the front cover upward as far
as the location where the lower
portion of the front cover is on
the de ector.
Lower portion of front cover
5 Remove while pulling the front
cover in direction to arrow as
shown in gure to hold the both
sides of front cover.
1
Screw
De ector
How to attach the Front Cover
1 After covering the front cover to the unit, certainly hook
at the upper portion (four places). Then, check that the
drain pan is certainly attached. Push the front cover in
the direction of arrow at the
portion of hooks.
2 Hook the front cover at lower portion to the drain pan and
then x them by screws and attach the caps.
3 Attach the front panel.
● Certainly insert the left shaft of the front panel to the hole
of the front cover. Next insert the right shaft as same as
the left.
4 Attach the lters which are placed the surface written
“FRONT” up.
● After attaching the lters, push the front panel at three
arrow portion as shown in gure and close it.
Hole
Shaft
Guide