Hitachi RAK-35RPC, RAK-50RPC Installation manual

1
EN
FOR
SERVICE
PERSONNEL ONLY
INDOOR UNIT
RAK-35RPC
MODEL
RAK-50RPC
SAFETY PRECAUTION
s Read the safety precautions carefully before operating the unit. s The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION .......... Improper installation may result in serious consequence.
Make sure to connect earth line. This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
WARNING
s Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
s Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.
s Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.
s Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.
s Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.
s Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.
Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
s
When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)
s
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
s Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.
s After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
s Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
s Be sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause electric shocks.
s When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
s When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
s
The electric cables should neither be reworked nor added. Make sure to use an exclusive circuit breaker. Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
Make sure to connect cables to terminal properly and terminal cover should close firmly.
s
Otherwise, over heating at terminal contact, fire or electric shock might occur. Make sure that there is no dust on any connected points of electric cables and fix firmly.
s
Otherwise, fire or electric shock might occur.
1 Installation of Hanger , Wall Penetration and Installation of Protection Pipe
CAUTION
s The draining of the water container inside the Indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
s Please use hidden beams in the wall to hold the hanger.
Visible outline of the
Indoor Unit
100 mm
295 mm
42.5 mm
180 mm
Line
Level
Weight
275 mm
668 mm
550 mm
284 mm 772 mm 900 mm
23 mm
160 mm
115 mm
Screw for Hanger
Hanger
Wall hole
100 mm
37 mm
39 mm
193 mm
Drain Hose
Screw the hanger at the positions possibly near the upper and lower hooks where the indoor unit is hung. Use 4 or more screws to fix the hanger.
42.5 mm
Procedures of Installation and Precautions
s Procedures to fix the hanger.
1.Drill holes on wall. (As shown below)
Wall
.4
32mm
ømm8
s Procedures to fix the holder of remote control.
1.Drill holes on wall.
Wall
.4 ømm4
2.Push plug into the holes. (As shown below)
Hanger
1
Screw
2
Wall
(As shown below)
20mm
3.Fix the hanger on wall with 4.1 x 32 screw.
Plug (Procure locally)
(As shown in figure below)
Ceiling
2.Push plug into the holes.
Remote
7
Control Holder
Screw
8
Plug (Procure locally)
(As shown below)
Installation Of Remote Controller
s
The remote controller can be placed in its holder which is fixed on wall or beam. To operate the remote controller at its holder, please ensure that the
s
unit can receive signal transmitted from the controller at the place where the holder is to be fixed.The unit will beep when signal is received from the remote controller . The signal transmission is weaken by the fluorescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting of
the holder
.
Remote Controller
The remote controller must be slide in the remote controller holder, in the direction as shown in the figure,
Remote Controller Holder
Screw (2 pieces)
until it hooks at the lower end of the remote controller holder.
Wall Penetration and Installation of Protection Pipe
s Drill a ø65mm hole on wall which is
slightly tilted towards the outdoor side. Drill the wall at a small angle.
s
Cut the protection pipe according to the wall thickness. Empty gap in the sleeve of protection
s
pipe should be completely sealed with putty to avoid dripping of rain water into the room. Please ensure smooth flow of water
s
when installing the drain hose. Improper installing may wet your funiture.
s
An IEC approved power cord should be used. Power cord type: NYM.
Indoor
Seal with putty
Protection pipe
WARNING
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse. Unless it seals completely,any air with high humidity flows from outdoor and any dew may drop.

CAUTION
s
A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other
installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas.
s
The outdoor unit may catch fire if flammable gas leaks around it.
s
Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your fu niture.
An IEC approved power cord should be used. Power cord type:
s
r
NYM.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation.)
WARNING
The unit should be mounted at stable, non-vibratory location which can provide
s
full support to the unit.
CAUTION
s No nearby heat source and no obstruction near the air outlet is allowed. s
The clearance distances from top, right and left are specified in figure
below.
The location must be convenient for water drainage and pipe connection
s
with the Outdoor unit.
s To avoid interference from noise, please place the unit and its remote
controller at least 1m from the radio and television. To avoid any error in signal transmission from the remote controller, please
s
put the controller far away from high-frequency machines and high-power
wireless systems.
The installation height should be at least 2300 mm or more
s
Figure showing the Installation
Be sure to completely seal any gap with
above
above
50mm
1
50mm
2
from the floor.
of Indoor Unit.
putty.
Names of Indoor Components
No. Item Qty
above
mm003 tuoba
dneb
ton tsu
m
9
4
3
about 450mm
The indoor piping should be insulated with the enclosed insulation pipe. (If the
please use commercial products.)
8
50mm
2300 mm or more
insulator is insufficient,
Plug
7
Direction of Piping
Backward piping from left
Connection
There are 6 directions allowed,namely,backward piping, backward piping from left,horizontally piping from right,horizontally piping from left,vertically down from right,vertically down from left.
Hanger
1
Screw for Hanger
2
AAA size Battery
3
Remote Controller
4
Wasabi-Nano Titanium Air Cleaning Mesh
5
C-case
6
Remote Controller Holder
7
Screw for Remote Controller Holder
8
Insulation sheet
9
2
2
2
2
2 Installation Of The Indoor Unit
Cutting Low Cover bush
s
While installing the pipe from the right, left or bottom
side, use a knife to cut openings as shown in figure.
Then smoothen the edges of openings with a file.
WALL
location
Outdoor
2-5mm
Seal with putty
Sleeve of protection pipe
Openings
1
PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Connect connecting cord.
s s
Pull out the pipe, connecting cord and drain hose.
Installation
Insert the pipe through the wall hole.
s
1 The
upper part of the Indoor unit
is hanged on the hanger.
2
The projection at the lower part
of the Indoor unit is hooked onto
the hanger.
Hanger
1
Lift the body of the unit upwards and then force it downwards.
Connecting Cord
Protection Pipe
Refrigerating Pipe
Drain Hose
Openings
Connecting cords, pipe and drain hose must be laid together with Vinyl tape.
Wall hole
Pipe
2
1
1
Projection
Drain hose
Hanger
Cable
Drain layout of backward piping
2
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
Changed of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap while installing the pipe from the left side as
s
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
s Please use pliers to pull out the drain cap .
(This is an easier way to remove the drain cap).
Drain cap
Drain cap
Drain Hose Remove low cover
s s
Insert drain cap up to the location securely till the cap stops.
s
Push the pipe deeply until the insulating section of the drain hose end gets over the rib at the indoor unit side.
CAUTION
Insufficient insert may result in water leakage.
1 Preparation of Pipe
s Use a pipe cutter to cut the copper pipe and remove burr.
s Remove burr and jagged edge will cause leakage. s Point the side to be trimmed downwards during
trimming to prevent copper chips from entering the pipe.
s Before flaring, please put on the flare nut.
Die
CAUTION
s
The rubber strap used for fixing the insulator should not
be tied with great force. Otherwise,this will damage heat
insulation and causes water condensation.
Pipe
Rubber strap tied with great force
s Please pull the lower part of the Indoor unit outwards to
check if the unit is hooked onto the hanger. Improper
installation may cause vibration and noise.
s Transform the piping while holding down the
lower portion
of pipe-support by hand.
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
s The refrigerating pipe should be adjusted to fit into
the hole on the wall and then ready for further connection.
s The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
s Connect the connecting cord after removing low
Pipe support
Pipe
Transform after bending downward.
Drain hose
Connecting cord
2 Pipe Connection
s In case of removing flare nut of a indoor unit, first remove
a nut of small diameter side, or a seal cap of big diameter side will fly out. Free from water into the piping when working.
s Be sure to tighten the flare nut to the specified torque with
a torque wrench. If the flare nut is overtightened, the nut may be split after a long period has passed, and may cause a refrigerant leak.
cover. (Refer to "CONNECTION OF POWER CORD")
s After adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to hold them tight.
s Holder can be attached at the either of 2 places.
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
Insulation pipe (must be wrapped with vinyl tape at every 120 mm)
Detail of Cutting the Connecting Cord
The end of the refrigerating pipes are at locations marked with “
” symbol.
WARNING
s The refrigerating pipes and connecting cord
transform and are attached.
Installation
Please bend at a small radius to form an arc
Hang the indoor unit onto the hanger. Use the temporary stan at the back of the Indoor unit to push its lower part 15cm forwards.
s Place the drain hose through the hole on the wall. s Wrap the refrigerating pipes with insulation pipe afte
connecting refrigerating pipe.
s Connect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")
s After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
d
Projection
r
about 15cm
below
5mm
Hook
s
Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the cord band.
Secure the connecting cord along the coated part of the wire using
s
the cord band. Do not exert pressure on the wire as this may cause overheating or fire.
Wiring of The Indoor Unit
s
For wire connection of the Indoor unit, you need to remove the front cover, the
s
Remove the cover from the terminal base and screw the cable.
s The projection of Indoor unit must hook to the hanger.
Wall hole
Pipe
Cable
Drain layout of backward piping from left
Drain hose
Connecting cord
Refrigerating pipe
Heat insulation pipe
Pull this to the front during the connection of refrigerating pipe to ease task.
Protection
pipe
Drain hose
Connecting cord
Connected section
3 Heat Insulation and Finish of the Piping
s The connected terminals should be completed sealed
with heat insulator and then tied up with rubber strap.
s Do not tie the terminals with the tape too tight.
If any clearance or over-tightening may cause condensation.
s Please tie the pipe and power line together with vinyl
tape as shown in the figure showing the installation of Indoor and Outdoor units.
s To enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
s Completely seal any gap with putty.
Insulation material for pipe connection
Sleeve of protection pipe
Putty
Putty
How to remove the front cover
1
4 Installation of Drain Hose
CAUTION
Bending upwards
CAUTION
Ditch
Condensed water pond
Condensed water pond
You are free to choose the side (left or right) for the installation of drain hose. Please ensure the smooth flow of condensed water of the Indoor unit during installation. (Careless may result in water leakage.)
Be sure that the drain hose is not loosely connected bend or proper condition like left figure.
1
2
2 3
4
HOW TO REMOVE INDOOR UNIT
s
Push up the [PUSH] sections at the bottom of the indoor unit and pull the bottom plate towards you. Then the claws are released from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)
[PUSH] mark positions
Trimming tool
Copper pipe
CAUTION
Die
Copper pipe
Outer A (mm) Rigid Flaring Tool Diameter (Ø) For R410A tool For R22 tool
6.35 (1/4") 0 - 0.5 1.0
9.52 (3/8") 0 - 0.5 1.0 0 - 0.5 1.012.7 (1/2")
A
s Please use
exclusive tool for refrigerant R410A.
CAUTION
s THIS APPLIANCE MUST BE EARTHED.
Indoor Unit
Strip wires
10mm
70mm
10mm
45mm
1
2
3
Green + Yellow (ground)
Connecting cord
WARNING
low cover under the body of the unit and terminal cover.
3
2
1
Earth
After remove the screw and terminal cover, and put the connecting cords and fix the terminal cover with screw.
Connecting cord
Cord band
FINAL STAGE OF INSTALLATION
Remove the front panel
Arm
Push the end of the right-side arm outward to release the tab. Move the left-side arm outward to release the left tab, and then pull the panel towards you.
Remove the filters. After removing three screws, pull the center of
the front cover towards you and release the claws. Pull the side faces (lower sections) of the front
cover towards you as shown in the figure and remove the cover.

2
1
Push
Arm
s Please be careful when bending the copper pipe. s Screw in manually while adjusting the center.
After that, use a torque wrench to tighten the connection.
Flare nut
Wrench
Small diameter side
Large diameter side
Valve head cap
Small diameter side
Large diameter side
Valve core cap
Torque wrench
Outer diameter
of pipe (ø)
6.35 (1/4”) 13.7 – 18.6 (140 – 190)
2/1( 7.21
Torque N·m
(kgf·cm)
)”2/1( 7.21
44.1 – 53.9 (450 – 550)
12.3 – 15.7 (125 – 160)
Gas leakage inspection
Please use gas leakage detector to check if
leakage
occurs at
as shown further tighten the connection
OP FO NOITCENNOC
Method to remove the low cover
s
Pull at the 1 and the directions as shown by arrows to remove the cover.
connection of Flare nut
in below.
If gas leakage occurs,
DROC REW
2
in
2
to stop leakage.
1
How to connect the optional parts
(H-LINK RAC Adapter, Dry contact, Wired Remote Controller)
s For cable connection to control P.W.B., you need to
remove front cover and electrical box cover.
Each connecting location is as below.
1
Dry contact: CN6
2
H-LINK RAC AdapterCN7
3
Wired Remote Control : CN20
s Please check and confirm manuals attached to each
optional parts for more connection details.
s You can refer to this installation manual how to remove
and re-attach the front cover.
s Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
CN20
CN7
ler
CN21
CN7
CN6
CN6
How to Attach the Front Cover
1
Check that the drain pan is securely attached. After installing the front cover onto the unit, hook three claws
2
at upper side of the cover securely. Then, push the center of the front cover to lock the claws.
Tighten the three screws.
3
Install the filter.
4
5
Attaching the Front Panel
Insert the shaft of the left arm along the step on the unit into
s
the hole.
Securely insert the shaft of the right arm along the step on
s
the unit into the hole.
s
Make sure that the front panel is securely attached, and then
close the front panel.
Arm
Step
Arm
Step
)054 – 053( 1.44 – 3.43 )”8/3( 25.9
)052 – 002( 5.42 – 6.91 )”4/1( 53.6 )052 – 002( 5.42 – 6.91 )”8/3( 25.9
)053 – 003( 3.43 – 4.92 )”
Loading...