SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit
+ – Screwdriver
Measuring Tape
Knife
Saw ● ø 65mm Power Drill ● Hexagonal Wrench
Key ( 4mm) ● Wrench (14, 17, 22, 26, 27mm)
Gas Leakage Detector ● Pipe Cutter
Putty
Vinyl Tape ● Pliers ● Flare Tool
Carefully read through the procedures of proper installation before starting installation work.
The sales agent should inform customers regarding the correct operation of installation.
Tools Needed For Installation Work
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as described in the user’s guide.
!
!
WARNING
!
CAUTION
!
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists. A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use power cables approved by the authorities of your country.
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock and fire may occur.
Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
FOR SERVICE PERSONNEL ONLY
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
WARNING
!
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
CAUTION
!
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specified in figure below.
The location must be convenient for water drainage and pipe connection with the Outdoor unit.
To avoid interference from noise please place the unit and its remote controller at least 1m from the radio, television and inverter type fluorescent lamp.
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency machines and high-power wireless systems.
The installation height of indoor unit must be 2.3m.
INDOOR UNIT
Names of Indoor Components
Hanger
QtyNo. Item
The Length of Indoor Unit
Connecting Cord
Figure showing the Installation of Indoor Unit.
1
Screw for holder of Remote Controller
(3.1x16)
AAA Size Battery
Holder for Remote Controller
(4.1x32)
Remote Controller
Purifying Filter
2
6
3
1
4
2
5
2
6
7
8
1
1
Screw for Hanger
0.9m
1.6m
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
1
CAUTION
!
The draining of the water container inside the indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on wall which is slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe according to the wall thickness.
Empty gap in the sleeve of protection pipe should be completely sealed with putty to avoid dripping of rain water into the room.
Procedures of Installation and Precautions
Procedures to fix the hanger.
1.Drill holes on wall. 2. Push plug into the holes. 3. Fix the hanger on wall (As shown below) (As shown below) with 4.1 x 32 screw
(As shown in figure below)
Procedures to fix the holder of remote control.
1.Drill holes on wall. 2. Push plug into the holes. (As shown below) (As shown below)
Installation of the Indoor Unit
2
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
The upper part of the Indoor unit is hanged on the hanger.
The projection at the lower part of the Indoor unit is hooked onto the hanger.
Please pull the lower part of the Indoor unit outwards to check if the unit is hooked onto the hanger. Improper installation may cause vibration and noise.
!
CAUTION
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown in figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap. (This is an easier way to remove the drain cap).
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fit into the hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical cover. (Refer to CONNECTION OF POWER CORD”)
After adjustment, fit the connecting cord and pipes into the space available under the indoor unit. Use holder to hold them tight.
!
CAUTION
The rubber strap used for fixing the insulator should not be tied with great force. Otherwise, this will damage heat insulation and causes water condensation.
Holder can be attached at the either of 2 places. Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
!
CAUTION
Please fix in the plastic core after flaring to avoid plastic chips entering the pipes.
CAUTION
!
You are free to choose the side (left or right) for the installation of drain hose. Please ensure the smooth flow of condensed water of the Indoor unit during installation. (Carelessness may result in water leakage.)
!
CAUTION
Be sure that the drain hose is not loosely connected or bend.
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse. Unless it seals completely, any air with high humidity flows from outdoor and any dew may drop.
!
WARNING
The refrigerating pipes and connecting cord transform and are attached.
The end of the refrigerating pipes are at locations marked with
symbol.
Installation of Drain Hose
3
Installation
Hang the Indoor unit onto the hanger. Use the temporary stand at the back of the Indoor unit to push its lower part 15cm forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after connecting refrigerating pipe.
Connect the connecting cord after removing electrical cover. (Refer to Connection of Power Cord”)
After adjustment, the connecting cord and refrigerating pipes are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.
INDOOR UNIT
<
IA194: A
>
32mm
20mm
ø4.8mm
ø4.4mm
Wall
1 Hanger
2 Screw
Plug
Wall
above 50mm
Ceiling
4.1 x 32 Screw
Wall
Remote Control Holder
5 Screw
Plug
3
Sleeve of protection pipe
WALL
Protection pipe
Seal with putty
Seal with putty
2 ~ 5mm
OutdoorIndoor
Connecting cords, pipe and drain hose must be laid together with Vinyl tape.
Lift the body of the unit upwards and then force it downwards.
Hanger
Refrigerating Pipe
Protection Pipe
Drain Hose
Connecting Cord
Hanger
1
Projection
2
!
CAUTION
Condensed water may leak out if not inserted properly.
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
During horizontal or downward piping, use a knife to cut openings as shown in figure. Then smoothen the edges of openings with a file.
Turn the piping while holding down the lower portion of pipe-support by hand.
Drain hoseDrain cap
Drain cap
Please insert until here
Drain hose
Please insert until here
Pipe support
Pull up the pipe after bending downward
Openings
Pipe
Connecting cord
Drain hose
Pipe
Rubber strap tied with great force
below 5mm
Please bend at a small radius to form an arc
about 15cm
Hook
Projection
Protection pipe
Connecting cord
Holder
Connected section
Drain hose
H
IT
A
C
H
I
Heat insulation pipe
Connecting cord
Refrigerating pipe
Pull this to the front during the connection of refrigerating pipes to ease task.
Bending upwards
Condensed water pond
Ditch
Condensed water pond
Holder
1
0.85m
RAK-18NH6 RAK-25NH6 RAK-35NH6 RAK-50NH6
!
CAUTION
The installation height of indoor
unit must be 2.3m.
Direction of Piping
There are 4 directions allowed, namely, horizontally perpendicular to the unit, vertically down from right, horizontally out from right and horizontally out to left. Dont form the piping downward at the left of the unit.
Connection
Horizontally perpendicular to the unit
Be sure to completely seal any gap with putty.
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
inner diameter ø 16mm
The difference in height between the indoor and outdoor
unit should be kept max 10m.
The connecting pipe, no matter big or small, should all
be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commersial products).
HFC
R410A
1
125mm
45mm
200mm
60mm
80mm
780mm
125mm
280mm
45mm 115mm
450mm
Level
Hanger
Hole for pipe
Weight
Mark
Line
Please use more than 4 screws.
Screw for Hanger
[Push] mark positions
HOW TO REMOVE INDOOR UNIT
Push up the (PUSH) sections at the bottom of the indoor unit and pull the bottom plate towards you. Then the claws are released from the stationary plate. (The (PUSH) sections are indicated by 2 arrows in the right figure)
Insulation pipe (must be wrapped with vinyl tape at every 120mm).
8
Holder
Removal Of Air From The Pipe And Gas Leakage Inspection
FINAL STAGE OF INSTALLATION
Insulation And Maintenance Of Pipe Connection
1
The connected terminals should be completely sealed with heat insulator and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown in the figure showing the installation of Indoor and Outdoor units. Then fix their position with holders.
To enchance the heat insulation and to prevent water condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
Installation Of Remote Controller
2
Power Source And Operation Test
3
The remote controller can be placed in its holder which is fixed on wall or beam.
To operate the remote controller at its holder, please ensure that the unit can receive signal transmitted from the controller at the place where the holder is to be fixed. The unit will beep when signal is received from the remote controller. The signal transmission is weaken by the fluorescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting location of the holder.
Power Source
CAUTION
!
Please use a new socket. Accident may occur due to the use of old socket because of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
Operation Test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the user’s manual.
<
IA194: A
>
The controller must be hooked onto the hook at the lower part of the holder. Push in the remote controller in the direction as shown in figure below.
3
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap of valve core. Then, connect the charge hose. Remove the cap of valve head. Connect the vacuum pump adapter to the vacuum pump and connect the charge hose to the adapter.
Fully tighten the “Hi” shuttle of the manifold valve and completely unscrew the “Lo” shuttle. Run the vacuum pump for about 10–15 minutes, then completely tighten the “Lo” shuttle and switch off the vacuum pump.
Completely unscrew the spindle of the service valve (at 2 places) in anti-clockwise direction to allow the flow of coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the cap of valve head. Check the cap’s periphery if there is any gas leakage. The task is then completed.
Preparation of Pipe
1
Use a pipe cutter to cut the copper pipe.
Pipe Connection
2
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
AIR REMOVAL
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the main switch and outdoor unit in consideration of the locked rotor current.
THIS APPLIANCE MUST BE EARTHED.
Procedures of Wiring
In case that power is supplied from Indoor Unit
CONNECTION OF POWER CORD
WARNING
!
Recommend to use R410A flaring tool.
CAUTION
!
In case of removing flare nut of an Indoor unit, first remove a nut of small diameter side, or a seal cap of big diameter side will fly out. Prevent water from entering into the piping when working.
Copper pipe
Trimming tool
A
Die
Die
Copper pipe
Wrench
Torque wrench
Flare nut
Sleeve of protection pipe
Putty
Putty
Insulation material for pipe connection
Remote
Controller
Holder for Remote Controller
Screw (2 pieces)
Wiring Of The Indoor Unit
For wire connection of the Indoor unit, you need to remove front panel and electrical cover.
Method to remove front panel
Refer to FINAL STAGE OF INSTALLATION – How to Remove The Front Cover”.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the specified capacity.
Outer Diameter (mm)
6.35
9.52
12.7
For R410A tool
0.0 ~ 0.5mm
0.0
~
0.5mm
0.0
~
0.5mm
For R22 tool
A (mm)
1.0mm
1.0mm
1.0mm
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
Before flaring, please put on the flare nut.
CAUTION
!
Outer
dia.of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Valve
head cap
Torque N·m
(kgf · cm)
13.7 – 18.6 (140 – 190)
34.3 – 44.1 (350 – 450)
44.1 – 53.9 (450 – 550)
19.6 – 24.5 (200 ~ 250)
19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
Small dia. side
Large dia. side
Valve core cap
Small dia. side
Large dia. side
The body of service valve
Cap of
valve core Hexagonal Wrench Key
Cap of valve head
Cap of valve head
1
2
3
4
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage. (Use the detector provided for R410A).
GRN + YEL
Strip wires
30mm
10mm
10mm
70mm
The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is tight. Improper insertion may burn the terminal.
Be sure to use only power cables approved from the authorities in your country. For example in Germany: Cable type: NYM 3x1.5mm2.
Please refer to the installation manual for wire connection to the terminals of the units. The cabling must meet the standards of electrical installation.
There is a AC voltage of 230V between the L and N terminals. Therefore, before servicing, be sure to remove the plug from the AC outlet or switch off the main switch.
WARNING
!
IMPORTANT
Cable length
up to 16m
up to 15m
up to 25m
Wire cross-section
1.5mm
2
2.5mm
2
4.0mm
2
Indoor Unit
Connect the earth cord
Method to remove the low cover
Pull the cover at 1 and 2 in the directions as shown by arrows to remove the cover.
D
C
After remove the screw and cover, and put the connecting cords and fix the cover with screw.
How to Remove The Front Cover
1 Remove the front panel.
Please remove and attach the front panel by both hands.
After opening the front panel by both hands.
11
11
1
Undo the right arm while pushing it inside.
22
22
2
Slide the front panel to right as shown in figure. Then remove while pulling it to front.
2 Remove the filters.
3 After removing two screws, pull the center of the front
cover towards you and release the claws.
4 Pull the side faces (lower sections) of the front cover
towards you as shown in the figure and remove the cover.
How to Attach the Front Cover
1 Check that the drain pan is securely attached.
2 After installing the front cover onto the unit, hook three
claws at upper side of the cover securely. Then, push the center of the front cover to lock the claws.
3 Tighten the two screws.
4 Install the filter.
5 Slide the shafts of the right and left arms on the washable
panel along the steps to insert the shafts into the holes till they stop. After checking that the shafts are securely inserted, close the panel.
HITACHI
D
C
IN
V
E
RT
E
R
Step
Shaft
Hole
H
ITACH
I
D
C
IN
V
E
R
T
E
R
Lo Hi
Stop valve
Charge hose
Stop valve
Vacuum pump adapter
Meter showing pressure
When the meter reaches -101KPa (-76cmHg) during pumping, fully tighten the shuttle.
Closed
Vacuum pump
R410A Manifold valve
When pumping starts, slightly loosen the flare nut to check of air sucked in. Then tighten the flare nut.