PARTS LIST AND DIAGRAM ------------------------------------------------- 92
18
SPECIFICATIONS
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
COOLING
HEATING
DIMENSIONS
(mm)
NET WEIGHT
TOTAL AMPERES
CAPACITY
TOTAL INPUT
TOTAL AMPERES
CAPACITY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H
D
(kg)
INDOOR UNIT
RAK-25NH4RAC-25NH4
1 PHASE, 50 Hz, 220-230V
695 (155~1,050)
2.50 (0.90 ~ 3.00)
900 (115 ~ 1,400)
3.50 (0.90 ~ 5.00)
860
285
183
9.0
OUTDOOR UNIT
3.20-3.05
8,540
4.15-4.00
11,950
750
570
280
38
DC INVERTER (WALL TYPE)
INDOOR UNIT
RAK-35NH4RAC-35NH4
1 PHASE, 50 Hz, 220-230V
1,080 (155~1,280)
3.50 (0.90 ~ 4.00)
1,320 (115 ~ 1,920)
4.80 (0.90 ~ 6.60)
860
285
183
9.0
OUTDOOR UNIT
4.94-4.72
11,950
6.04-5.77
16,390
750
570
280
38
INDOOR UNIT
RAK-50NH4RAC-50NH4
1 PHASE, 50 Hz, 220-230V
1,780 (155~2,200)
5.00 (0.90 ~ 5.20)
1,970 (115 ~ 2,100)
6.50 (0.90 ~ 8.10)
860
285
183
9.0
OUTDOOR UNIT
8.17-7.82
17,070
9.04-8.65
22,200
850
650
298
60
After installation
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
ROOM AIR CONDITIONER
MAY 2003
Refrigeration & Air-Conditioning Division
INDOOR UNIT + OUTDOOR UNIT
FOR SERVICE PERSONNEL ONLY
●
Carefully read through the procedures of proper
installation before starting installation work.
●
The sales agent should inform customers regarding
the correct operation of installation.
SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
Outdoor UnitRAC-35NH4
HFC
R410A
SAFETY PRECAUTION
●
Read the safety precautions carefully before operating the unit.
●
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user’s guide.
RAC-25NH4
RAC-50NH4
Tools Needed For Installation Work
●
+ – Screwdriver
●
Saw ● ø 65mm Power Drill ● Hexagonal Wrench
Key ( 4mm)
●
Gas Leakage Detector ● Pipe Cutter
●
Vinyl Tape ● Pliers ● Flare Tool
●
Measuring Tape
●
Wrench (14, 17, 22, 26, 27mm)
●
Knife
●
Putty
!
WARNING
●
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you
do the installation work yourself.
●
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fire.
●
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the
units may collapse and impose danger.
●
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
●
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and fire.
●
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and fire may occur.
●
Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.
●
When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture
may be caused.
●
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous
gas may occur.
●
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks
into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
●
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
!
CAUTION
●
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
●
Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.
●
Please ensure smooth flow of water when installing the drain hose.
●
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
<
I477: A
>
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
!
WARNING
●
The Outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.
!
CAUTION
●
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
●
The air blown out of the unit should not point directly to animals or plants.
●
The clearances of the unit from top, left, right and front are specified in figure below. At least 3 of the above sides must be open air.
●
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
●
Do not install at a location where there is flammable gas, steam, oil and smoke.
●
The location must be convenient for water drainage.
OUTDOOR UNIT
●
Place the Outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone. This is to
avoid noise interference.
Names of Outdoor Components
QtyNo.Item
Bush
0
(RAC-25NH4,
RAC-35NH4)
(RAC-50NH4)
2
3
Figure showing the Installation of Outdoor Unit.
Drain Pipe
!
1
Bush
#
1
Dimension of Mounting Stand
of the Outdoor unit
(unit: mm)
mounting stand
Dimension of Mounting Stand
of the Outdoor unit
(unit: mm)
mounting stand
●
Please mount the Outdoor unit on stable ground to prevent
12
35
500
12
35
508
(RAC-25NH4,
RAC-35NH4)
57
10
320
340
20
(10)
124
(RAC-50NH4)
57
10
320
340
35
(10)
198
above 100mm
above 700mm
vibration and increase of noise level.
●
Decide the location for piping after sorting out the different types
of pipe available.
●
When removing side cover, please pull the handle after undoing
the hook by pulling it downward.
Please face this side (suction
side) of the unit to the wall.
Please remove side cover
when connecting the piping
and connecting cord.
Pull downward
above 200mm
above 50mm when
installed on the
(
ceiling of balcony
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensed
In order to flow condensed water to the drain, the unit is installed on
At first insert one portion of the hook to the base (Portion A), then
When Using and Installing In Cold Areas
When the air conditioner is used in low temperature and in snowy
conditions, water from the heat exchanger may freeze on the base
surface to cause poor drainage. When using the air conditioner in such
areas, do not install the bushings. Keep a minimum of 250mm between
the drain hole and the ground. When using the drain pipe, consult your
sales agent.
For more details, refer to the installation Manual for Cold Areas.
● The difference in height
between the indoor and
outdoor unit should be
kept max 5m.
● The connecting pipe, no
matter big or small,
should all be insulated
with insulation pipe and
then wrapped with vinyl
tape. (The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
inner diameter ø 16mm
Maximum pipe length 20m
)
above 100mm
Please use insulated drain
hose for the indoor piping
(commercial product).
give clearance as
wide as possible
above 200mm
water to exhaust.
a stand or a block so that the unit is 100mm above the ground as
shown figure. Join the drain pipe to one hole.
pull the drain pipe in the direction shown by the arrow while inserting
the hook into the base. After installation, check whether the drain
pipe cling to the base firmly.
A
BASE
DRAIN PIPE
100 mm ABOVE
10
BUSH
12
11
DRAIN PIPE
BUSH
Preparation of Pipe1
●
Use a pipe cutter to cut the copper pipe.
Trimming tool
Copper pipe
!
CAUTION
●
Jagged edge will cause leakage.
●
Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
●
Before flaring, please put on the flare nut.
Die
Outer
Diameter (mm)
6.35
9.52
12.7
Die
Copper pipe
For R410A tool
0.0
0.5mm
~
0.0
0.5mm
~
0.5mm
0.0
~
A
A (mm)
●
Recommend to use
R410A flaring tool.
For R22 tool
1.0mm
1.0mm
1.0mm
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
Pipe Connection2
In case of removing flare nut of an Indoor unit, first remove a nut
!
CAUTION
Wrench
Gas Leakage Inspection
Please use gas leakage detector to check if
leakage occurs at the connection of Flare
nut as shown on the right.
If gas leakage occurs, further tighten the
connection to stop leakage. (Use the detector
provided for R410A)
of small diameter side, or a seal cap of big diameter side will fly
out. Prevent water from entering into the piping when working.
Torque
wrench
Small dia. side
Large dia. side
Small dia. side
Valve
head cap
Valve core cap
Large dia. side
Flare nut
Outer
dia.of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Torque N·m
(kgf · cm)
13.7 – 18.6 (140 – 190)
34.3 – 44.1 (350 – 450)
44.1 – 53.9 (450 – 550)
19.6 – 24.5 (200 ~ 250)
19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
Removal Of Air From The Pipe And Gas Leakage Inspection
3
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
1
Connect the vacuum pump adapter to
the vacuum pump and connect the
charge hose to the adapter.
Fully tighten the “Hi” shuttle of the
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully
tighten the shuttle.
Valve
Meter showing pressure
Charge hose
Lo Hi
Valve
Vacuum pump
adapter
manifold valve and completely unscrew
the “Lo” shuttle. Run the vacuum pump
2
for about 10–15 minutes, then completely
AIR REMOVAL
tighten the “Lo” shuttle and switch off
the vacuum pump.
Completely unscrew the spindle of the
service valve (at 2 places) in anti-
3
clockwise direction to allow the flow of
coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the
cap of valve head. Check the cap’s
4
periphery if there is any gas leakage.
The task is then completed.
When pumping starts, slightly loosen the
flare nut to check of air sucked in. Then
tighten the flare nut.
The body of
service valve
Cap of
valve core
Hexagonal
Cap of valve head
Wrench Key
Cap of valve head
Closed
R410A
Manifold valve
Vacuum
pump
●
WARNING
!
THIS APPLIANCE MUST BE EARTHED.
Power supply shall be connected at the rated voltage, otherwise the unit will be
broken or could not reach the specified capacity.
Procedures of Wiring
In case that power is supplied from Outdoor Unit
Indoor UnitOutdoor Unit
1.6 or
2.0
Connecting Cord
Strip wires
Outdoor
Unit
GRN + YEL
25mm
10mm
10mm
25mm
10mm
35mm
Power lineControl line
!
WARNING
●
The naked part of the wire core should be 10 mm and fix it to the terminal
tightly. Then try to pull the individual wire to check if the contact is tight. Improper
CONNECTION OF POWER CORD
insertion may burn the terminal.
●
Be sure to use only power cables approved from the authorities in your country.
For example in Germany: Cable type: NYM 3x1.5mm
●
Please refer to the installation manual for wire connection to the terminals of the
units. The cabling must meet the standards of electrical installation.
●
There is a AC voltage of 230V between the L and N terminals. Therefore,
before servicing, be sure to remove the plug from the AC outlet or switch off
the main switch.
<
I477: A
>
DCNLDC
Connecting Cord
2.0
AC 220 - 230V
2
.
Wiring of The Outdoor Unit
●
Please remove the side cover for wire connection.
●
If you cannot attach the side cover due to the connecting cord,
!
WARNING
press the connecting cord in direction to the front panel to fix it.
●
Be sure that the hooks of the side cover is fixed in certainly.
Otherwise water leakage may occur and this causes short circuit
or faults.
●
The connecting cord should not touch to service valve and pipes.
(It becomes high temperature in heating operation.)
Checking for the electric source and the
voltage range
●
Before installation, the power source must be checked and necessary wiring work
must be completed. To make the wiring capacity proper, use the wire gauges list
below for the lead-in from a pole transformer and for the wiring from a switch board
of fuse box to the main switch and outdoor unit in consideration of the locked rotor
current.
IMPORTANT
Cable length
up to 16m
up to 15m
up to 25m
●
Investigate the power supply capacity and
other electrical conditions at the installation
location.
Depending on the model of room air
conditioner to be installed, request the
customer to make arrangements for the
necessary electrical work etc.
The electrical work includes the wiring work
up the outdoor. In localities where electrical
conditions are poor, use of a voltage
regulation is recommended.
Wire cross-section
2
1.5mm
2
2.5mm
2
4.0mm
CD
N
L
Use 16A Time
Delay Fuse
Earth terminal
1
Insulation And Maintenance Of Pipe Connection
●
The connected terminals should be completely sealed with heat insulator and
then tied up with rubber strap.
●
Please tie the pipe and power line together with vinyl tape as shown in the figure
showing the installation of Indoor and Outdoor units. Then fix their position with
holders.
●
To enchance the heat insulation and to prevent water condensation, please
cover the outdoor part of the drain hose and pipe with insulation pipe.
●
Completely seal any gap with putty.
Sleeve of
Insulation material for pipe connection
2
Power Source And Operation Test
protection pipe
Putty
Power Source
!
CAUTION
●
Please use a new socket. Accident may occur due to the use of old socket
because of poor contact.
●
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that
the plug is completely plugged into the socket.
●
Keep additional length for the power cord and do not render the plug under
FINAL STAGE OF INSTALLATION
external force as this may cause poor contact.
●
Do not fix the power cord with U-shape nail.
Operation Test
●
Please ensure that the air conditioner is in normal operating condition during
the operation test.
●
Explain to your customer the proper operation procedures as described in the
user’s manual.
Putty
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2
7
4
5
3
9
Maximum pipe length 20m
Plug
2,300mm or more
1
!
!
!
!
FOR SERVICE PERSONNEL ONLY
!
!
0.9m
1.6m
!
Connection
Horizontallyperpendicularto the unit
inner diameter ø 16mm
HFC
R410A
●
Carefully read through the procedures of proper
installation before starting installation work.
●
The sales agent should inform customers regarding
the correct operation of installation.
SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
RAK-25NH4
Indoor Unit
SAFETY PRECAUTION
●
Read the safety precautions carefully before operating the unit.
●
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the user’s guide.
RAK-35NH4
RAK-50NH4
Tools Needed For Installation Work
●
+ – Screwdriver
●
Saw ● ø 65mm Power Drill ● Hexagonal Wrench
Key ( 4mm)
●
Gas Leakage Detector ● Pipe Cutter
●
Vinyl Tape ● Pliers ● Flare Tool
●
Measuring Tape
●
Wrench (14, 17, 22, 26, 27mm)
●
Knife
●
Putty
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
WARNING
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you
do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the
units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and fire.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and fire may occur.
Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture
may be caused.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous
gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks
into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
CAUTION
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2
7
4
5
3
9
Maximum pipe length 20m
Plug
2,300mm or more
1
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
!
!
0.9m
1.6m
!
Connection
Horizontally
perpendicular
to the unit
inner diameter ø 16mm
WARNING
●
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
CAUTION
●
No nearby heat source and no obstruction near the air outlet is allowed.
●
The clearance distances from top, right and left are specified in figure below.
●
The location must be convenient for water drainage and pipe connection with the Outdoor unit.
●
To avoid interference from noise please place the unit and its remote controller at least 1m from the radio, television and inverter
INDOOR UNIT
type fluorescent lamp.
●
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency
machines and high-power wireless systems.
●
The installation height of indoor unit must be 2.3m or more in a non public area.
Names of Indoor Components
QtyNo.Item
Hanger
1
Screw for Hanger
2
Holder for Remote
Controller
3
AAA Size Battery
4
Screw for holder of
Remote Controller
5
Insulation pipe
6
Remote Controller
7
Purifying Filter
8
(4.1x32)
(3.1x16)
1
6
1
2
2
1
1
1
The Length of Indoor Unit
Connecting Cord
Figure showing the Installation of Indoor Unit.
Be sure to
completely
seal any
gap with
putty.
Direction of Piping
There are 4 directions allowed, namely,
horizontally perpendicular to the unit,
vertically down from right, horizontally out
from right and horizontally out to left.
Don’t form the piping downward at the
left of the unit.
CAUTION
The installation height of indoor
•
unit must be 2.3m or more in
a non public area.
Holder
9
● The difference in height between the indoor and outdoor
unit should be kept max 5m.
● The connecting pipe, no matter big or small, should all
be insulated with insulation pipe and then wrapped with
vinyl tape. (The insulator will deteriorate if it is not wrapped
with tape).
1
The connection of insulated drain hose.
Please use insulated drain hose for the
indoor piping (commercial product).
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commercial
products).
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2
7
4
5
3
9
Maximum pipe length 20m
Plug
2,300mm or more
1
!
!
!
!
!
!
0.9m
1.6m
1
!
!
!
!
!
!
!
External dimension of
indoor unit
160mm
160mm
80mm
860mm
40mm
45mm
30mm
Drain Hose
45mm
298mm
Level
Line
Hole for
pipe
Mark
Weight
Screw for Hanger
Please use more
than 4 screws.
Hanger
32mm
20mm
ø4.8mm
ø4.4mm
Wall
1 Hanger
2 Screw
Plug
Wall
above 50mm
Ceiling
4.1 x 32 Screw
Wall
Remote
Control
Holder
5 Screw
Plug
3
Sleeve of
protection
pipe
WALL
Protection
pipe
Seal with
putty
Seal with
putty
2 ~ 5mm
OutdoorIndoor
Connecting cords,
pipe and drain hose
must be tied together
with Vinyl tape.
Hanger
Hook
Refrigerating
Pipe
Connecting
Cord
Drain Hose
Protection
Pipe
Lift the body
of the unit
upwards and
then force
it downwards.
Hanger
Projection
Screw driver
Claw of indoor unit
Circle hole
2
1
!
Drain hoseDrain cap
Drain cap
Please insert
until here
Drain hose
Please insert
until here
Pipe
support
Pull up the pipe after
bending downward
Openings
Pipe
Connecting cord
Drain hose
Insulation pipe (must be wrapped with
vinyl tape at every 120mm).
Holder
9
Insulation pipe
6
Pipe
Rubber strap tied with great force
below
5mm
Please bend at a small
radius to form an arc
about 15cm
Projection
Temporary stand
Connected
section
Holder
Connecting cord
Drain hose
Protection
pipe
Bending
upwards
Condensed
water pond
Ditch
Condensed
water pond
!
Connection
Horizontallyperpendicularto the unit
inner diameter ø 16mm
HFC
R410A
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
●
The draining of the water container inside the indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
●
Please use hidden beams in the wall to hold the hanger.
Procedures of Installation and Precautions
●
Procedures to fix the hanger.
1. Drill holes on wall.2. Push plug into the holes.3. Fix the hanger on wall
(As shown below)(As shown below)with 4.1 x 32 screw
(As shown in figure below)
INDOOR UNIT
●
Procedures to fix the holder of remote control.
1. Drill holes on wall.2. Push plug into the holes.
(As shown below)(As shown below)
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
●
Connect connecting cord.
●
Pull out the pipe, connecting cord and drain hose.
Installation
●
The upper part of the Indoor unit is hanged on the hanger.
●
The projection at the lower part of the Indoor unit is hooked onto the hanger.
CAUTION
Please pull the lower part of
the Indoor unit outwards to
check if the unit is hooked
onto the hanger. Improper
installation may cause
vibration and noise.
HOW TO REMOVE INDOOR UNIT FROM HANGER
●
Pull down PULL section on the bottom of indoor
unit and pull it towards you, then claws are
released from hanger. (Indicated by 2 arrows in
the drawing on the right.)
●
When bottom face of indoor unit cannot be
pulled due to obstacles, etc. Remove front cover,
insert screw driver into circle hole, pull claws
down and pull indoor unit towards you.
●
Please check how to remove and attach front
cover in this instruction manual.
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
●
Exchange the location of drain hose and drain cap during horizontal piping as shown in
figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
●
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain cap).
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
●
The refrigerating pipes should be adjusted to fit into
the hole on the wall and then ready for further
connection.
●
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
●
Connect the connecting cord after removing electrical
cover. (Refer to “CONNECTION OF POWER CORD”)
●
After adjustment, fit the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
CAUTION
●
The rubber strap used for
fixing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
●
Holder can be attached at the either of 2 places.
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
●
The refrigerating pipes and connecting cord
transform and are attached.
●
The end of the refrigerating pipes are at locations
marked with “
” symbol.
Installation
Hang the Indoor unit onto the hanger. Use the temporary stand
at the back of the Indoor unit to push its lower part 15cm
forwards.
●
Place the drain hose through the hole on the wall.
●
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
●
Connect the connecting cord after removing electrical cover.
(Refer to “Connection of Power Cord”)
●
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
●
The projection of Indoor unit must hook to the hanger.
CAUTION
●
Please fix in the plastic core
after flaring to avoid plastic
chips entering the pipes.
Wall Penetration and Installation of Protection Pipe
●
Drill a ø 65mm hole on
wall which is slightly tilted
towards the outdoor side.
Drill the wall at a small
angle.
●
Cut the protection pipe
according to the wall
thickness.
●
Empty gap in the sleeve
of protection pipe should
be completely sealed
with putty to avoid
dripping of rain water into
the room.
<
I477: A
>
WARNING
Be sure that the wire is not
in contact with any metal
in the wall. Please use the
protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
CAUTION
Condensed water may leak out if not inserted properly.
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
●
During horizontal or downward piping, use a knife to cut
openings as shown in figure. Then smoothen the edges of
openings with a file.
●
Turn the piping while holding down the lower
portion of pipe-support by hand.
Heat insulation pipe
Connecting
cord
Refrigerating pipe
3
Installation of Drain Hose
Pull this to the front
during the connection
of refrigerating pipes
to ease task.
You are free to choose the side (left or right) for the installation of drain
CAUTION
hose. Please ensure the smooth flow of condensed water of the Indoor
unit during installation. (Carelessness may result in water leakage.)
CAUTION
Be sure that the
drain hose is not
loosely connected
or bend.
1
!
!
Copper pipe
Trimming tool
A
Die
Die
Copper pipe
Wrench
Torque
wrench
Flare nut
!
Lo Hi
The body of
service valve
Cap of
valve core
Hexagonal
Wrench Key
Cap of valve head
Cap of valve head
30mm
10mm
10mm
70mm
!
CD
AUTO
RESTART
SWITCH
Preparation of Pipe
●
Use a pipe cutter to cut the copper pipe.
CAUTION
●
Jagged edge will cause leakage.
●
Point the side to be trimmed downwards during trimming to
prevent copper chips from entering the pipe.
●
Before flaring, please put on the flare nut.
●
Recommend to use
R410A flaring tool.
Outer
Diameter (mm)
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
6.35
9.52
12.7
For R410A tool
0.0
0.5mm
~
0.0
0.5mm
~
0.0
0.5mm
~
A (mm)
For R22 tool
1.0mm
1.0mm
1.0mm
2
Pipe Connection
CAUTION
Small dia. side
Large dia. side
Small dia. side
Valve
head cap
Valve core cap
Large dia. side
In case of removing flare nut of an
Indoor unit, first remove a nut of small
diameter side, or a seal cap of big
diameter side will fly out. Prevent
water from entering into the piping
when working.
Outer
dia.of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Torque N·m
(kgf · cm)
13.7 – 18.6 (140 – 190)
34.3 – 44.1 (350 – 450)
44.1 – 53.9 (450 – 550)
19.6 – 24.5 (200 ~ 250)
19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap of valve core. Then, connect the charge
hose. Remove the cap of valve head. Connect the vacuum pump adapter to the
1
vacuum pump and connect the charge hose to the adapter.
Fully tighten the “Hi” shuttle of the manifold valve and completely unscrew the
“Lo” shuttle. Run the vacuum pump for about 10–15 minutes, then completely
2
tighten the “Lo” shuttle and switch off the vacuum pump.
Completely unscrew the spindle of the service valve (at 2 places) in anti-clockwise
3
AIR REMOVAL
direction to allow the flow of coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the cap of valve head. Check the cap’s
4
periphery if there is any gas leakage. The task is then completed.
Gas Leakage Inspection
Please use gas leakage detector to check if leakage
occurs at the connection of Flare nut as shown on
the right.
If gas leakage occurs, further tighten the connection
to stop leakage. (Use the detector provided for
R410A).
When the meter reaches - 101KPa
(-76cmHg) during pumping, fully
tighten the shuttle.
Valve
When pumping starts, slightly loosen the
flare nut to check of air sucked in. Then
tighten the flare nut.
Meter showing pressure
Charge hose
Vacuum pump
adapter
Valve
Closed
R410A
Manifold valve
Vacuum
pump
●
WARNING
THIS APPLIANCE MUST BE EARTHED.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the
specified capacity.
Procedures of Wiring
In case that power is supplied from Indoor Unit
Indoor Unit
GRN + YEL
Strip wires
WARNING
●
The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the
individual wire to check if the contact is tight. Improper insertion may burn the terminal.
●
Be sure to use only power cables approved from the authorities in your country. For example in Germany:
Cable type: NYM 3x1.5mm
CONNECTION OF POWER CORD
●
Please refer to the installation manual for wire connection to the terminals of the units. The cabling must
meet the standards of electrical installation.
●
There is a AC voltage of 230V between the L and N terminals. Therefore, before servicing, be sure to
remove the plug from the AC outlet or switch off the main switch.
2
.
Wiring Of The Indoor Unit
●
For wire connection of the Indoor unit, you need to remove front panel and electrical cover.
Method to remove front panel
●
Refer to “FINAL STAGE OF INSTALLATION – How to Remove The Front Cover”.
Method to remove electrical cover
●
Remove the screw and electrical cover.
●
Insert the connecting cord (C, D) from the bottom of
unit.
●
Fixed the wire to terminal wires firmly as shown in
figure at right side.
Electrical cover
Screw
Connect the
earth cord
After remove the screw
and band, put the
connecting cords and fix
the band with screw.
Checking for the electric source and the voltage range
●
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire
gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the main switch and outdoor unit in
consideration of the locked rotor current.
IMPORTANT
Cable length
up to 16m
up to 15m
up to 25m
Wire cross-section
2
1.5mm
2
2.5mm
2
4.0mm
1
!
!
!
Copper pipe
Trimming tool
A
Die
Die
Copper pipe
Wrench
Torquewrench
Flare nut
Sleeve of
protection pipe
Putty
Putty
Insulation material for pipe connection
Remote
Controller
Holder for
Remote Controller
Screw (2 pieces)
1
2
!
LoHi
The body ofservice valve
Cap of
valve coreHexagonalWrench Key
Cap of valve head
Cap of valve head
30mm
10mm
10mm
70mm
!
CD
AUTORESTARTSWITCH
Insulation And Maintenance Of Pipe Connection
●
The connected terminals should be completely sealed with
heat insulator and then tied up with rubber strap.
●
Please tie the pipe and power line together with vinyl tape as
shown in the figure showing the installation of Indoor and
Outdoor units. Then fix their position with holders.
●
To enchance the heat insulation and to prevent water
condensation, please cover the outdoor part of the drain hose
and pipe with insulation pipe.
●
Completely seal any gap with putty.
3
Power Source And Operation Test
Power Source
FINAL STAGE OF INSTALLATION
●
Please use a new socket. Accident may occur due to the use of old
socket because of poor contact.
●
Please plug in and then remove the plug for 2 – 3 times. This is to
ensure that the plug is completely plugged into the socket.
●
Keep additional length for the power cord and do not render the
plug under external force as this may cause poor contact.
●
Do not fix the power cord with U-shape nail.
CAUTION
2
Installation Of Remote Controller
●
The remote controller can be placed in its holder which is
fixed on wall or beam.
●
To operate the remote controller at its holder, please ensure
that the unit can receive signal transmitted from the controller
at the place where the holder is to be fixed. The unit will beep
when signal is received from the remote controller. The signal
transmission is weaken by the fluorescent light. Therefore,
during the installation of the remote control holder, please
switch on the light, even during day time, to determine the
mounting location of the holder.
The controller must
be hooked onto the
hook at the lower
part of the holder.
Push in the remote
controller in the
direction as shown
in figure below.
Operation Test
●
Please ensure that the air conditioner is in normal
operating condition during the operation test.
●
Explain to your customer the proper operation
procedures as described in the user’s manual.
How to Remove The Front Cover
1 Remove the front panel.
●
Please remove and attach the front panel by both hands.
●
After opening the front panel by both hands.
11
Undo the right arm while pushing it inside.
1
1122
2
Slide the front panel to right as shown in figure. Then
22
remove while pulling it to front.
2 Remove the filters.
3 Remove the caps and screws at the lower portion of the
front cover.
Cap
Screw
4 Pull the front cover upward as far as the location where
the lower portion of the front cover is on the deflector.
Lower portion of front cover
5 Remove while pulling the front cover in direction to arrow
as shown in figure to hold the both sides of front cover.
Deflector
How to Attach the Front Cover
11
1
After covering the front cover to the unit, certainly hook at
11
the upper portion (three places). Then, check that the drain
pan is certainly attached. Push the center of front cover in
the direction of arrow.
22
2
Fix the front cover at lower portion by screws and attach
22
the caps.
33
3
Attach the front panel.
33
●
Certainly insert the left shaft of the front panel to the hole
of the front cover. Next insert the right shaft as same as
the left.
44
4
Attach the filters which are placed the surface written
44
“FRONT” up.
●
After attaching the filters, push the front panel at three
arrow portion as shown in figure and close it.
Hole
Shaft
Guide
<
I477: A
>
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair
the unit in question, be sure to
disconnect the power cord plug
from the power outlet before starting
the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and
the replacement must be effected in correct manner according to the instructions in the Service Manual of
the unit.
If the contacts of electrical parts
are defective, replace the
electrical parts without trying to
repair them.
First, I must disconnect
the power cord plug
from the power outlet.
3. After completion of repairs, the initial state
should be restored.
4. Lead wires should be connected and laid as
in the initial state.
5. Modification of the unit by user himself should
absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as
electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and
grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V
DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe
enough to support the repaired unit again.
If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new
location.
10. Any inflammable thing should never
be placed about the location of
installation.
DANGER
11. Check the grounding to see whether
it is proper or not, and if it is found
improper, connect the grounding
terminal to the earth.
– 1 –
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope
The standards provide for items to be generally observed in carrying and handling semiconductors in relative
manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods
such as rejected goods being returned).
2. Object parts
(1) Micro computer
(2) Integrated circuits (IC)
(3) Field-effect transistors (FET)
(4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling
(1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
A conductive polyvinyl bag
IC
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through
a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken.
(4) Be sure to place a part on a metal plate with grounding.
(5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
IC
Conductive sponge
Body earth
(Elimik conductive band)
1M
Fig. 2. Body Earth
Clip for connection with a
grounding wire
– 2 –
(6) Use a three wire type soldering iron including a grounding wire.
Metal plate (of aluminium, stainless steel, etc.)
Staple
Bare copper wire (for body earth)
Fig. 3. Grounding of the working table
Working
table
Resistor of 1 M (1/2W)
Earth wire
Soldering iron
2
Screw stop at the screwed
part using a rag plate
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
Grounding
wire
– 3 –
CAUTION
!
1.In quiet operation or stopping the running, slight flowing noise of refrigerant in the refrigerating cycle is
heard occasionally, but this noise is not abnormal for the operation.
2.When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug
from the power outlet for safety.
3.The room air conditioner does not start automatically after recovery of the electric power failure for
preventing fuse blowing. Re-press START/STOP button after 3 minutes from when unit stopped.
4.If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment,
there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal
and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no
danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5.This room air conditioner should not be used at the cooling operation when the outside temperature is
below 10°C (50°F).
6.This room air conditioner (the reverse cycle) should not be used when the outside temperature is below
–10°C (14°F).
If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7.When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not
trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
– 4 –
SPECIFICATIONS
MODEL
RAK-25NH4
RAK-35NH4
RAK-50NH4
RAC-25NH4RAC-50NH4RAC-35NH4
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
PWM DC35V
NO
NO
–
NO
NO
NO
NO
NO
NO
YES
40 W
NO
NO
JU1012DJU1013D
NO
YES
YES
3.0A
G4A
NO
NO
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
REFRIGERANT CHARGING
VOLUME
(Refrigerant 410A)
UNIT
PIPES (MAX. 20m)
NO
NO
NO
NO
YES(IC)
YES
----------
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
450NR
YES(IC)
1150g1150g
YES
NO
YES
NO
1400g
– 5 –
CONSTRUCTION AND DIMENSIONAL DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
Air suction grill
Mounting plate
183
860
Top air suction grill
Front panel
Cabinet
285
About
380
350
About
View from back
(Pipe lead-out)
6.560
47
47
31120.5
Drain outlet
6060
240170450
Horizontal deflectorDischarge grill
Drain hose
Hole on the wall
for ø 65mm pipe
P
47
Drain
Narrow pipe
Vertical deflector
7070140
Drain cap
connection port
147
5617.5
28
47
When piping is
drawn horizontally,
exchange the drain
hose for the drain cap
BLU : BLUEYEL : YELLOWBRN : BROWNWHT : WHITE
GRY : GRAYORN : ORANGEGRN : GREENRED : RED
BLK : BLACKPNK : PINKVIO : VIOLET
– 8 –
COMPRESSOR MOTOR
Compressor Motor Specifications
MODEL
COMPRESSOR MODEL
RAC-25NH4RAC-50NH4RAC-35NH4
JU1012DJU1013D
PHASESINGLE
RATED VOLTAGEAC 220 ~ 230 V
RATED FREQUENCY50 Hz
POLE NUMBER4
(U)
WHITE
CONNECTION
M
M
M
(W)
(V)
YELLOW
RESISTANCE VALUE
20°C
(68°F)
2M = 1.05
RED
75°C
(167°F)
YELLOW
2M = 1.28
WHITE
RED
!
CAUTION
( )
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed
or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the
color has been changed conspicuously, replace the compressor.
– 9 –
WIRING DIAGRAM
BLU
POWER
RELAY
COIL
NF
COIL 1
C003
C001
C002
VARISTOR1
L001
CT1
VARISTOR3
SURGE
ABSORBER
DIODE
STACK
R010
L002
R011
C011
C010
FAN
MOTOR
VARISTOR2
CN6
WHT
C008
C013
C015
M
WHT YEL
RED
WHT YEL
YEL
YEL
YEL
DIODE
STACK
RED
UVW
REACTOR
SYSTEM POWER
MODULE 2
L2
L1
CN14
CN13
CN11
C503
C502C501
10
CN14
CN10
RED
CN9
BLU
CN8
WHT
CN15
WHT
CN13
CN11
5
5
CN12
CN12
RED
GRY
2A FUSE
ICP RELAY
R008R007
3A FUSE
25A
FUSE
C006
R001
BLKGRNWHT
(WHT)(BRN)(RED)(BLK)
CONNECTING
CORD
BRNRED
BLK
BLK
GRN
RED
BLK
WHT
YEL
BLU
POWER
CIRCUIT
TERMINAL
BOARD
(GRN+YEL)
LNCD
SINGLE PHASE
AC220~230V
50Hz
(GRN+YEL)
THERE ARE SOME LEAD WIRES
WHICH HAVE SPIRAL STRIPES
WITH WHITE IN ADDITION TO
THE ORIGINAL COLOR
1. The indoor fan also stops when the
compressor is in stop status.
Set to “Hi” in modes other than when the
compressor stops.
Set to “Med” in modes other than when the
compressor stops.
Set to “Lo” in modes other than when the
compressor stops.
See page 53.
• Same as at left
• See page 53.
Stop
StartStop
(Off-timer during stop)
(On-timer during operation)
ONONONOFFOFFOFFONOFF
(Off->On timer)(On->Off timer) (On->Off timer)
(Change in reserved time)
during operation)
(Off->On timer)
during stop)
Set to “ultra-Lo”, “Lo”, “Med”, “Hi”, “ultra-Hi” or “stop” depending on the room temperature,
time and heat exchange temperature. Set to “stop” if the room temperature is 18˚C in the
“ultra-Lo” mode other than during preheating (cooling is recovered at 18.33˚C).
When the compressor is running at maximum speed
during hot dash or when recovered from defrosting.
˚C
42. 66
37. 66
32. 66
29. 66
Hi or ultra-HI
(fan speed set
to “auto”)
Med
Lo
In modes other than
left
Heat exchanger
temperature
Set to “ultra-Lo”, “Lo”, “Med”, “Hi”, “ultra-Hi” or “stop” depending on the room temperature, and
time. Set to “stop” if the room temperature is 18˚C in the “ultra-Lo” mode other than during
preheating (cooling is recovered at 18.33˚C).
Set to “ultra-Hi” when the compressor is running at maximum speed during hot dash or when
recovered from defrosting.
Set to “ultra-Lo”, “Lo”, “Med” or “stop” depending on the room temperature and time. Set to“stop” if the room temperature is 18˚C in the “ultra-Lo” mode other than during preseating
(cooling is recovered at 18.33˚C).
Set to “ultra-Lo”, “Lo”, or “stop” depending on the room temperature and time. Set to “stop” if
the room temperature is 18˚C in the “ultra-Lo” mode other than during preseating (cooling is
recovered at 18.33˚C). The fan speed is controlled by the heat exchanger temperature; the
overload control is executed as in the following diagram:
KAFON
KAFOF
“Med” with overload
“Lo”
Heat exchanger temperature
See page 55.
• Same as at left
• See page 57.
N&F autoHeatingCooling
The neuro & fuzzy control allows device to determine optimum
operation mode and set temperature. However, during auto
cooling, the new cool rhythm starts when the room temperature
is less than the set temperature plus 0.66˚C, after dash is
finished.
Room
temperature
Outdoor
temperature
Calendar
Humidity
Neuro
pattern
recognition
Fuzzy
control
Operation mode
Set temperature
Notes:
(1) The set temperature can be varied ±3˚C using the
temperature setting buttons and .
v
v
(2) If operation is started by tele-control or by temporary switch
in status where remote control has not been used after
power was supplied, the operation mode will be as follows
(since there is no stored calendar data):
Room temparature at
operation start (˚C)
Cooling
Dehumidifying
Heating
Set temperature: 28˚C
Fan mode: Auto
Set temperature: Room temperature at operation
Fan mode: Auto
Set temperature: 22˚C
Fan mode: Auto
start
• Same as at left.
• Performs the sleep operation of each operation mode.
Special auto (not normally used)
The special auto mode is based on N&F
auto, but the following is different:
Operation mode
N&F auto
Special auto
Mode change during
operation
Does not change as long as
outdoor temperature or
calendar data does not
change greatly.
The operation mode will be
judged the same as at
operation start every hour.
The special auto operation mode is
entered when operation is started in the
following status:
<Start condition>
Power is supplied white the tele-control
signal is being input. (Operation starts
automatically.)
<End condition>
The remote control restores the normal
operation mode.
Note
(1) Since there is no stored calendar
data, N&F control is not determined.
See Note (2) of N&F auto.
– 17 –
Table 1 Mode data file
RAK-25NH4RAK-35NH4RAK-50NH4
LABEL NAMEVALUE
WMAX4500 min
WMAX24600 min
WSTD3250 min
WBEMAX2600 min
CMAX2900 min
CMAX23000 min
CSTD2500 min
CKYMAX2200 min
CJKMAX2000 min
CBEMAX1800 min
WMIN1200 min
CMIN1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
5500 min
5600 min
4350 min
2800 min
3700 min
3800 min
3550 min
2800 min
2500 min
2200 min
1200 min
1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
6200 min
6250 min
5200 min
2600 min
5700 min
5800 min
5200 min
3550 min
2700 min
2000 min
1200 min
1500 min
Notes:
(1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 7) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode.
(3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP.
(6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX.
(7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX.
(8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX.
(9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Table 2 ∆TCMAX
TemperatureCalculated
differencecompressor rpm
1.662265 min
22435 min
2.332600 min
2.662765 min
32935 min
3.333100 min
3.663265 min
43435 min
4.333600 min
4.663765 min
53935 min
5.334100 min
5.664265 min
64435 min
6.334600 min
6.664765 min
74935 min
7.335100 min
7.665265 min
85435 min
8.335600 min
8.665765 min
95935 min
9.336100 min
9.666265 min
106435 min
10.336600 min
10.666765 min
116935 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
Note:
1. See the data in Table 1 on
page 47 for each constant in
capital letters in the diagrams.
– 19 –
New Cool Rhythm
Cooling Sleep Operation
Final set temperature
(Cooling/dehumidifying set
temperature
(temperature set by remote
control (+) SHIFTC)
Set temperature during rhythm
(temperature set by remote
control (+) SFTRZM)
Thermo judgment
Hi
Indoor
fan
New cool rhythm
Outdoor fan
Lo
Rhythm Med
Rhythm Lo
Med
Room temperature
See basic operation.
Lo
Minimum
5min.
5 sec.5 sec.
Minimum 5min.Minimum 5min.
5min.
1 cycle
2.5 sec.2.5 sec.
4.5 sec.
2.5 sec.
5min.
Minimum
5min.
5min.
Minimum
5min.
Thermo OFF
15 sec.
Minimum
5min.5min.
5min.
Lo
Final set temperature
(Cooling/dehumidifying set
temperature (+) sleep shift)
(Cooling/dehumidifying set
temperature = Remote control set
temperature (+) SHIFTC)
Sleep key
Operation lamp
Timer lamp
Indoor fan
Outdoor fan
Horizontal air
deflector
Hi
Med
Lo (sleep)
Shut
Horizontal
Facing down
See basic operation
Lo
Set to 7 hours
0.5hr
1.5hr
2.5hr3.5hr6hr7hr
3hr
Maximum speed
P1
Compressor speed
Notes:
(1) New cool rhythm is engaged when the fan speed is “auto” and the room temperature is less than
set one plus 0.66˚C in the “auto” operation mode or cooling mode.
(2) The minimum new cool rhythm time is 10 minutes when the temperature falls and rises.
(3) Cool rhythm is not engaged during Nice temperature, Sleep operation.
(4) Pl control is engaged during new cool rhythm: the speed limit is the same as during normal operation.
(5) The new cool rhythm set temperature is also shifted during thermo OFF.
Compressor speed
Notes:
(1) The sleep operation starts when the sleep key is pressed.
(2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to “sleep Lo”.
(3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached.
(4) The sleep shift upper value of set temperature is 28˚C.
(5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min.
(6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point when
switching is made.
(7) The indoor fan speed does not change even when the fan speed mode is changed.
(8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted.
(9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted.
(10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Reverse cycle period
MAX. 12min.
min–1
3000
fixed
– 20 –
Loading...
+ 66 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.