Hitachi RAK25NH4, RAK35NH4, RAK50NH4, RAC25NH4, RAC35NH4 Service manual

...
SM0174
RAK25NH4 RAC25NH4 RAK35NH4 RAC35NH4
SERVICE MANUAL
FOR SERVICE PERSONNEL ONLY
RAK-25NH4 RAK-35NH4 RAK-50NH4
RAC-25NH4 RAC-35NH4 RAC-50NH4
RAK50NH4 RAC50NH4
REFER TO THE FOUNDATION MANUAL
CONTENTS
SPECIFICATIONS ------------------------------------------------------------------- 5
CONSTRUCTION AND DIMENSIONAL DIAGRAM --------------------- 6
MAIN PARTS COMPONENT --------------------------------------------------- 8
WIRING DIAGRAM ---------------------------------------------------------------- 10
CIRCUIT DIAGRAM --------------------------------------------------------------- 12
PRINTED WIRING BOARD LOCATION DIAGRAM ---------------------
BLOCK DIAGRAM ----------------------------------------------------------------- 20
BASIC MODE ----------------------------------------------------------------------- 22
REFRIGERATING CYCLE DIAGRAM --------------------------------------- 35
AUTO SWING FUNCTION ------------------------------------------------------ 37
DESCRIPTION OF MAIN CIRCUIT OPERATION ----------------------- 38
SERVICE CALL Q & A ---------------------------------------------------------- 69
TROUBLE SHOOTING ----------------------------------------------------------- 72
PARTS LIST AND DIAGRAM ------------------------------------------------- 92
18
SPECIFICATIONS
TYPE
MODEL
POWER SOURCE
TOTAL INPUT
COOLING
HEATING
DIMENSIONS (mm)
NET WEIGHT
TOTAL AMPERES
CAPACITY
TOTAL INPUT
TOTAL AMPERES
CAPACITY
(W)
(A)
(kW)
(B.T.U./h)
(W)
(A)
(kW)
(B.T.U./h)
W
H
D
(kg)
INDOOR UNIT
RAK-25NH4 RAC-25NH4
1 PHASE, 50 Hz, 220-230V
695 (155~1,050)
2.50 (0.90 ~ 3.00)
900 (115 ~ 1,400)
3.50 (0.90 ~ 5.00)
860
285
183
9.0
OUTDOOR UNIT
3.20-3.05
8,540
4.15-4.00
11,950
750
570
280
38
DC INVERTER (WALL TYPE)
INDOOR UNIT
RAK-35NH4 RAC-35NH4
1 PHASE, 50 Hz, 220-230V
1,080 (155~1,280)
3.50 (0.90 ~ 4.00)
1,320 (115 ~ 1,920)
4.80 (0.90 ~ 6.60)
860
285
183
9.0
OUTDOOR UNIT
4.94-4.72
11,950
6.04-5.77
16,390
750
570
280
38
INDOOR UNIT
RAK-50NH4 RAC-50NH4
1 PHASE, 50 Hz, 220-230V
1,780 (155~2,200)
5.00 (0.90 ~ 5.20)
1,970 (115 ~ 2,100)
6.50 (0.90 ~ 8.10)
860
285
183
9.0
OUTDOOR UNIT
8.17-7.82
17,070
9.04-8.65
22,200
850
650
298
60
After installation
SPECIFICATIONS AND PARTS ARE SUBJECT TO CHANGE FOR IMPROVEMENT
ROOM AIR CONDITIONER
MAY 2003
Refrigeration & Air-Conditioning Division
INDOOR UNIT + OUTDOOR UNIT
FOR SERVICE PERSONNEL ONLY
Carefully read through the procedures of proper installation before starting installation work.
The sales agent should inform customers regarding the correct operation of installation.
SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
Outdoor Unit RAC-35NH4
HFC
R410A
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as described in the user’s guide.
RAC-25NH4 RAC-50NH4
Tools Needed For Installation Work
+ – Screwdriver
Saw ● ø 65mm Power Drill ● Hexagonal Wrench
Key ( 4mm)
Gas Leakage Detector ● Pipe Cutter
Vinyl Tape ● Pliers ● Flare Tool
Measuring Tape
Wrench (14, 17, 22, 26, 27mm)
Knife
Putty
!
WARNING
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use power cables approved by the authorities of your country.
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock and fire may occur.
Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
!
CAUTION
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists. A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
<
I477: A
>
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
!
WARNING
The Outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.
!
CAUTION
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right and front are specified in figure below. At least 3 of the above sides must be open air.
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
Do not install at a location where there is flammable gas, steam, oil and smoke.
The location must be convenient for water drainage.
OUTDOOR UNIT
Place the Outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone. This is to avoid noise interference.
Names of Outdoor Components
QtyNo. Item
Bush
0
(RAC-25NH4, RAC-35NH4)
(RAC-50NH4)
2
3
Figure showing the Installa­tion of Outdoor Unit.
Drain Pipe
!
1
Bush
#
1
Dimension of Mounting Stand
of the Outdoor unit
(unit: mm)
mounting stand
Dimension of Mounting Stand
of the Outdoor unit
(unit: mm)
mounting stand
Please mount the Outdoor unit on stable ground to prevent
12 35
500
12 35
508
(RAC-25NH4, RAC-35NH4)
57
10
320
340
20
(10)
124
(RAC-50NH4)
57
10
320
340
35
(10)
198
above 100mm
above 700mm
vibration and increase of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side cover, please pull the handle after undoing the hook by pulling it downward.
Please face this side (suction side) of the unit to the wall.
Please remove side cover when connecting the piping and connecting cord.
Pull downward
above 200mm
above 50mm when installed on the
(
ceiling of balcony
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There are holes on the base of Outdoor unit for condensedIn order to flow condensed water to the drain, the unit is installed on
At first insert one portion of the hook to the base (Portion A), then
When Using and Installing In Cold Areas
When the air conditioner is used in low temperature and in snowy conditions, water from the heat exchanger may freeze on the base surface to cause poor drainage. When using the air conditioner in such areas, do not install the bushings. Keep a minimum of 250mm between the drain hole and the ground. When using the drain pipe, consult your sales agent.
For more details, refer to the installation Manual for Cold Areas.
The difference in height
between the indoor and outdoor unit should be kept max 5m.
The connecting pipe, no
matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).
The connection of insulated drain hose.
inner diameter ø 16mm
Maximum pipe length 20m
)
above 100mm
Please use insulated drain hose for the indoor piping (commercial product).
give clearance as wide as possible
above 200mm
water to exhaust. a stand or a block so that the unit is 100mm above the ground as
shown figure. Join the drain pipe to one hole. pull the drain pipe in the direction shown by the arrow while inserting
the hook into the base. After installation, check whether the drain pipe cling to the base firmly.
A
BASE
DRAIN PIPE
100 mm ABOVE
10
BUSH
12
11
DRAIN PIPE
BUSH
Preparation of Pipe1
Use a pipe cutter to cut the copper pipe.
Trimming tool
Copper pipe
!
CAUTION
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
Before flaring, please put on the flare nut.
Die
Outer Diameter (mm)
6.35
9.52
12.7
Die
Copper pipe
For R410A tool
0.0
0.5mm
~
0.0
0.5mm
~
0.5mm
0.0
~
A
A (mm)
Recommend to use R410A flaring tool.
For R22 tool
1.0mm
1.0mm
1.0mm
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
Pipe Connection2
In case of removing flare nut of an Indoor unit, first remove a nut
!
CAUTION
Wrench
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage. (Use the detector provided for R410A)
of small diameter side, or a seal cap of big diameter side will fly out. Prevent water from entering into the piping when working.
Torque wrench
Small dia. side Large dia. side
Small dia. side
Valve
head cap
Valve core cap
Large dia. side
Flare nut
Outer
dia.of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Torque N·m
(kgf · cm)
13.7 – 18.6 (140 – 190)
34.3 – 44.1 (350 – 450)
44.1 – 53.9 (450 – 550)
19.6 – 24.5 (200 ~ 250)
19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
Removal Of Air From The Pipe And Gas Leakage Inspection
3
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap of valve core. Then, connect the charge hose. Remove the cap of valve head.
1
Connect the vacuum pump adapter to the vacuum pump and connect the charge hose to the adapter.
Fully tighten the Hi shuttle of the
When the meter reaches - 101KPa (-76cmHg) during pumping, fully tighten the shuttle.
Valve
Meter showing pressure
Charge hose
Lo Hi
Valve
Vacuum pump adapter
manifold valve and completely unscrew the Lo shuttle. Run the vacuum pump
2
for about 10–15 minutes, then completely
AIR REMOVAL
tighten the “Lo” shuttle and switch off the vacuum pump.
Completely unscrew the spindle of the service valve (at 2 places) in anti-
3
clockwise direction to allow the flow of coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the cap of valve head. Check the cap’s
4
periphery if there is any gas leakage. The task is then completed.
When pumping starts, slightly loosen the flare nut to check of air sucked in. Then tighten the flare nut.
The body of service valve
Cap of valve core
Hexagonal
Cap of valve head
Wrench Key
Cap of valve head
Closed R410A
Manifold valve
Vacuum pump
WARNING
!
THIS APPLIANCE MUST BE EARTHED.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the specified capacity.
Procedures of Wiring
In case that power is supplied from Outdoor Unit
Indoor Unit Outdoor Unit
1.6 or
2.0
Connecting Cord
Strip wires
Outdoor
Unit
GRN + YEL
25mm
10mm
10mm
25mm
10mm
35mm
Power line Control line
!
WARNING
The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is tight. Improper
CONNECTION OF POWER CORD
insertion may burn the terminal.
Be sure to use only power cables approved from the authorities in your country. For example in Germany: Cable type: NYM 3x1.5mm
Please refer to the installation manual for wire connection to the terminals of the units. The cabling must meet the standards of electrical installation.
There is a AC voltage of 230V between the L and N terminals. Therefore, before servicing, be sure to remove the plug from the AC outlet or switch off the main switch.
<
I477: A
>
DCNLDC
Connecting Cord
2.0 AC 220 - 230V
2
.
Wiring of The Outdoor Unit
Please remove the side cover for wire connection.
If you cannot attach the side cover due to the connecting cord,
!
WARNING
press the connecting cord in direction to the front panel to fix it.
Be sure that the hooks of the side cover is fixed in certainly. Otherwise water leakage may occur and this causes short circuit or faults.
The connecting cord should not touch to service valve and pipes. (It becomes high temperature in heating operation.)
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the main switch and outdoor unit in consideration of the locked rotor current.
IMPORTANT
Cable length
up to 16m up to 15m up to 25m
Investigate the power supply capacity and other electrical conditions at the installation location. Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary electrical work etc. The electrical work includes the wiring work up the outdoor. In localities where electrical conditions are poor, use of a voltage regulation is recommended.
Wire cross-section
2
1.5mm
2
2.5mm
2
4.0mm
CD
N
L
Use 16A Time Delay Fuse
Earth terminal
1
Insulation And Maintenance Of Pipe Connection
The connected terminals should be completely sealed with heat insulator and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown in the figure showing the installation of Indoor and Outdoor units. Then fix their position with holders.
To enchance the heat insulation and to prevent water condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
Sleeve of
Insulation material for pipe connection
2
Power Source And Operation Test
protection pipe
Putty
Power Source
!
CAUTION
Please use a new socket. Accident may occur due to the use of old socket because of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the plug under
FINAL STAGE OF INSTALLATION
external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
Operation Test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the users manual.
Putty
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2
7
4
5
3
9
Maximum pipe length 20m
Plug
2,300mm or more
1
!
!
!
!
FOR SERVICE PERSONNEL ONLY
!
!
0.9m
1.6m
!
Connection
Horizontally perpendicular to the unit
inner diameter ø 16mm
HFC
R410A
Carefully read through the procedures of proper installation before starting installation work.
The sales agent should inform customers regarding the correct operation of installation.
SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
RAK-25NH4
Indoor Unit
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as described in the user’s guide.
RAK-35NH4 RAK-50NH4
Tools Needed For Installation Work
+ – Screwdriver
Saw ● ø 65mm Power Drill ● Hexagonal Wrench
Key ( 4mm)
Gas Leakage Detector ● Pipe Cutter
Vinyl Tape ● Pliers ● Flare Tool
Measuring Tape
Wrench (14, 17, 22, 26, 27mm)
Knife
Putty
WARNING
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the
units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and fire may occur. Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults. When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture
may be caused. Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous
gas may occur. After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks
into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock exists. A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose. Piping shall be suitable supported with a maximum spacing of 1m between the supports.
CAUTION
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2
7
4
5
3
9
Maximum pipe length 20m
Plug
2,300mm or more
1
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
!
!
0.9m
1.6m
!
Connection
Horizontally perpendicular to the unit
inner diameter ø 16mm
WARNING
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specified in figure below.
The location must be convenient for water drainage and pipe connection with the Outdoor unit.
To avoid interference from noise please place the unit and its remote controller at least 1m from the radio, television and inverter
INDOOR UNIT
type fluorescent lamp.
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency machines and high-power wireless systems.
The installation height of indoor unit must be 2.3m or more in a non public area.
Names of Indoor Components
QtyNo. Item
Hanger
1
Screw for Hanger
2
Holder for Remote Controller
3
AAA Size Battery
4
Screw for holder of Remote Controller
5
Insulation pipe
6
Remote Controller
7
Purifying Filter
8
(4.1x32)
(3.1x16)
1
6
1
2
2
1
1
1
The Length of Indoor Unit
Connecting Cord
Figure showing the Installation of Indoor Unit.
Be sure to completely seal any gap with putty.
Direction of Piping
There are 4 directions allowed, namely, horizontally perpendicular to the unit, vertically down from right, horizontally out from right and horizontally out to left. Dont form the piping downward at the left of the unit.
CAUTION
The installation height of indoor
unit must be 2.3m or more in a non public area.
Holder
9
The difference in height between the indoor and outdoor
unit should be kept max 5m.
The connecting pipe, no matter big or small, should all
be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).
1
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commercial products).
above 50mm
above 100mm
above
0.45m
above 300mm
must not bend
above 100mm
2
7
4
5
3
9
Maximum pipe length 20m
Plug
2,300mm or more
1
!
!
!
!
!
!
0.9m
1.6m
1
!
!
!
!
!
!
!
External dimension of
indoor unit
160mm
160mm
80mm
860mm
40mm
45mm
30mm
Drain Hose
45mm
298mm
Level
Line
Hole for pipe
Mark
Weight
Screw for Hanger
Please use more than 4 screws.
Hanger
32mm
20mm
ø4.8mm
ø4.4mm
Wall
1 Hanger
2 Screw
Plug
Wall
above 50mm
Ceiling
4.1 x 32 Screw
Wall
Remote Control Holder
5 Screw
Plug
3
Sleeve of protection pipe
WALL
Protection pipe
Seal with putty
Seal with putty
2 ~ 5mm
OutdoorIndoor
Connecting cords, pipe and drain hose must be tied together with Vinyl tape.
Hanger
Hook
Refrigerating Pipe
Connecting Cord
Drain Hose
Protection Pipe
Lift the body of the unit upwards and then force it downwards.
Hanger
Projection
Screw driver
Claw of indoor unit
Circle hole
2
1
!
Drain hoseDrain cap
Drain cap
Please insert until here
Drain hose
Please insert until here
Pipe support
Pull up the pipe after bending downward
Openings
Pipe
Connecting cord
Drain hose
Insulation pipe (must be wrapped with vinyl tape at every 120mm).
Holder
9
Insulation pipe
6
Pipe
Rubber strap tied with great force
below 5mm
Please bend at a small radius to form an arc
about 15cm
Projection
Temporary stand
Connected section
Holder
Connecting cord
Drain hose
Protection
pipe
Bending upwards
Condensed water pond
Ditch
Condensed water pond
!
Connection
Horizontally perpendicular to the unit
inner diameter ø 16mm
HFC
R410A
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
The draining of the water container inside the indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Procedures of Installation and Precautions
Procedures to fix the hanger.
1. Drill holes on wall. 2. Push plug into the holes. 3. Fix the hanger on wall (As shown below) (As shown below) with 4.1 x 32 screw
(As shown in figure below)
INDOOR UNIT
Procedures to fix the holder of remote control.
1. Drill holes on wall. 2. Push plug into the holes. (As shown below) (As shown below)
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
The upper part of the Indoor unit is hanged on the hanger.
The projection at the lower part of the Indoor unit is hooked onto the hanger.
CAUTION
Please pull the lower part of the Indoor unit outwards to check if the unit is hooked onto the hanger. Improper installation may cause vibration and noise.
HOW TO REMOVE INDOOR UNIT FROM HANGER
Pull down PULL section on the bottom of indoor unit and pull it towards you, then claws are released from hanger. (Indicated by 2 arrows in the drawing on the right.)
When bottom face of indoor unit cannot be pulled due to obstacles, etc. Remove front cover, insert screw driver into circle hole, pull claws down and pull indoor unit towards you.
Please check how to remove and attach front cover in this instruction manual.
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown in figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap. (This is an easier way to remove the drain cap).
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fit into the hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical cover. (Refer to CONNECTION OF POWER CORD”)
After adjustment, fit the connecting cord and pipes into the space available under the indoor unit. Use holder to hold them tight.
CAUTION
The rubber strap used for fixing the insulator should not be tied with great force. Otherwise, this will damage heat insulation and causes water condensation.
Holder can be attached at the either of 2 places. Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord transform and are attached.
The end of the refrigerating pipes are at locations marked with
symbol.
Installation
Hang the Indoor unit onto the hanger. Use the temporary stand at the back of the Indoor unit to push its lower part 15cm forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after connecting refrigerating pipe.
Connect the connecting cord after removing electrical cover. (Refer to Connection of Power Cord”)
After adjustment, the connecting cord and refrigerating pipes are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.
CAUTION
Please fix in the plastic core after flaring to avoid plastic chips entering the pipes.
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on wall which is slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe according to the wall thickness.
Empty gap in the sleeve of protection pipe should be completely sealed with putty to avoid dripping of rain water into the room.
<
I477: A
>
WARNING
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse. Unless it seals completely, any air with high humidity flows from outdoor and any dew may drop.
CAUTION
Condensed water may leak out if not inserted properly.
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
During horizontal or downward piping, use a knife to cut openings as shown in figure. Then smoothen the edges of openings with a file.
Turn the piping while holding down the lower portion of pipe-support by hand.
Heat insulation pipe
Connecting cord
Refrigerating pipe
3
Installation of Drain Hose
Pull this to the front during the connection of refrigerating pipes to ease task.
You are free to choose the side (left or right) for the installation of drain
CAUTION
hose. Please ensure the smooth flow of condensed water of the Indoor unit during installation. (Carelessness may result in water leakage.)
CAUTION
Be sure that the drain hose is not loosely connected or bend.
1
!
!
Copper pipe
Trimming tool
A
Die
Die
Copper pipe
Wrench
Torque wrench
Flare nut
!
Lo Hi
The body of service valve
Cap of
valve core Hexagonal Wrench Key
Cap of valve head
Cap of valve head
30mm
10mm
10mm
70mm
!
CD
AUTO RESTART SWITCH
Preparation of Pipe
Use a pipe cutter to cut the copper pipe.
CAUTION
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
Before flaring, please put on the flare nut.
Recommend to use R410A flaring tool.
Outer Diameter (mm)
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
6.35
9.52
12.7
For R410A tool
0.0
0.5mm
~
0.0
0.5mm
~
0.0
0.5mm
~
A (mm)
For R22 tool
1.0mm
1.0mm
1.0mm
2
Pipe Connection
CAUTION
Small dia. side Large dia. side
Small dia. side
Valve
head cap
Valve core cap
Large dia. side
In case of removing flare nut of an Indoor unit, first remove a nut of small diameter side, or a seal cap of big diameter side will fly out. Prevent water from entering into the piping when working.
Outer
dia.of pipe
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Torque N·m
(kgf · cm)
13.7 – 18.6 (140 – 190)
34.3 – 44.1 (350 – 450)
44.1 – 53.9 (450 – 550)
19.6 – 24.5 (200 ~ 250)
19.6 – 24.5 (200 ~ 250)
29.4 – 34.3 (300 – 350)
12.3 – 15.7 (125 ~ 160)
3
Removal Of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap of valve core. Then, connect the charge hose. Remove the cap of valve head. Connect the vacuum pump adapter to the
1
vacuum pump and connect the charge hose to the adapter.
Fully tighten the “Hi” shuttle of the manifold valve and completely unscrew the “Lo” shuttle. Run the vacuum pump for about 10–15 minutes, then completely
2
tighten the “Lo” shuttle and switch off the vacuum pump.
Completely unscrew the spindle of the service valve (at 2 places) in anti-clockwise
3
AIR REMOVAL
direction to allow the flow of coolant (using Hexagonal Wrench key).
Remove the charge hose and tighten the cap of valve head. Check the cap’s
4
periphery if there is any gas leakage. The task is then completed.
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage. (Use the detector provided for R410A).
When the meter reaches - 101KPa (-76cmHg) during pumping, fully tighten the shuttle.
Valve
When pumping starts, slightly loosen the flare nut to check of air sucked in. Then tighten the flare nut.
Meter showing pressure
Charge hose
Vacuum pump adapter
Valve
Closed R410A
Manifold valve
Vacuum pump
WARNING
THIS APPLIANCE MUST BE EARTHED.
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the specified capacity.
Procedures of Wiring
In case that power is supplied from Indoor Unit
Indoor Unit
GRN + YEL
Strip wires
WARNING
The naked part of the wire core should be 10 mm and fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is tight. Improper insertion may burn the terminal.
Be sure to use only power cables approved from the authorities in your country. For example in Germany: Cable type: NYM 3x1.5mm
CONNECTION OF POWER CORD
Please refer to the installation manual for wire connection to the terminals of the units. The cabling must meet the standards of electrical installation.
There is a AC voltage of 230V between the L and N terminals. Therefore, before servicing, be sure to remove the plug from the AC outlet or switch off the main switch.
2
.
Wiring Of The Indoor Unit
For wire connection of the Indoor unit, you need to remove front panel and electrical cover.
Method to remove front panel
Refer to FINAL STAGE OF INSTALLATION – How to Remove The Front Cover”.
Method to remove electrical cover
Remove the screw and electrical cover.
Insert the connecting cord (C, D) from the bottom of unit.
Fixed the wire to terminal wires firmly as shown in figure at right side.
Electrical cover
Screw
Connect the earth cord
After remove the screw and band, put the connecting cords and fix the band with screw.
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the main switch and outdoor unit in consideration of the locked rotor current.
IMPORTANT
Cable length
up to 16m up to 15m up to 25m
Wire cross-section
2
1.5mm
2
2.5mm
2
4.0mm
1
!
!
!
Copper pipe
Trimming tool
A
Die
Die
Copper pipe
Wrench
Torque wrench
Flare nut
Sleeve of protection pipe
Putty
Putty
Insulation material for pipe connection
Remote
Controller
Holder for Remote Controller
Screw (2 pieces)
1
2
!
Lo Hi
The body of service valve
Cap of
valve core Hexagonal Wrench Key
Cap of valve head
Cap of valve head
30mm
10mm
10mm
70mm
!
CD
AUTO RESTART SWITCH
Insulation And Maintenance Of Pipe Connection
The connected terminals should be completely sealed with heat insulator and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown in the figure showing the installation of Indoor and Outdoor units. Then fix their position with holders.
To enchance the heat insulation and to prevent water condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
3
Power Source And Operation Test
Power Source
FINAL STAGE OF INSTALLATION
Please use a new socket. Accident may occur due to the use of old socket because of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
CAUTION
2
Installation Of Remote Controller
The remote controller can be placed in its holder which is fixed on wall or beam.
To operate the remote controller at its holder, please ensure that the unit can receive signal transmitted from the controller at the place where the holder is to be fixed. The unit will beep when signal is received from the remote controller. The signal transmission is weaken by the fluorescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting location of the holder.
The controller must be hooked onto the hook at the lower part of the holder. Push in the remote controller in the direction as shown in figure below.
Operation Test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the user’s manual.
How to Remove The Front Cover
1 Remove the front panel.
Please remove and attach the front panel by both hands.
After opening the front panel by both hands.
11
Undo the right arm while pushing it inside.
1
11 22
2
Slide the front panel to right as shown in figure. Then
22
remove while pulling it to front. 2 Remove the filters. 3 Remove the caps and screws at the lower portion of the
front cover.
Cap
Screw
4 Pull the front cover upward as far as the location where
the lower portion of the front cover is on the deflector.
Lower portion of front cover
5 Remove while pulling the front cover in direction to arrow
as shown in figure to hold the both sides of front cover.
Deflector
How to Attach the Front Cover
11
1
After covering the front cover to the unit, certainly hook at
11
the upper portion (three places). Then, check that the drain pan is certainly attached. Push the center of front cover in the direction of arrow.
22
2
Fix the front cover at lower portion by screws and attach
22
the caps.
33
3
Attach the front panel.
33
Certainly insert the left shaft of the front panel to the hole of the front cover. Next insert the right shaft as same as the left.
44
4
Attach the filters which are placed the surface written
44
“FRONT” up.
After attaching the filters, push the front panel at three arrow portion as shown in figure and close it.
Hole
Shaft
Guide
<
I477: A
>
SAFETY DURING REPAIR WORK
1. In order to disassemble and repair the unit in question, be sure to disconnect the power cord plug from the power outlet before starting the work.
2. If it is necessary to replace any parts, they should be replaced with respective genuine parts for the unit, and the replacement must be effected in correct manner according to the instructions in the Service Manual of the unit.
If the contacts of electrical parts are defective, replace the electrical parts without trying to repair them.
First, I must disconnect the power cord plug
from the power outlet.
3. After completion of repairs, the initial state should be restored.
4. Lead wires should be connected and laid as in the initial state.
5. Modification of the unit by user himself should absolutely be prohibited.
6. Tools and measuring instruments for use in repairs or inspection should be accurately calibrated in advance.
7. In installing the unit having been repaired, be careful to prevent the occurence of any accident such as electrical shock, leak of current, or bodily injury due to the drop of any part.
8. To check the insulation of the unit, measure the insulation resistance between the power cord plug and grounding terminal of the unit. The insulation resistance should be 1M or more as measured by a 500V DC megger.
9. The initial location of installation such as window, floor or the other should be checked for being and safe enough to support the repaired unit again. If it is found not so strong and safe, the unit should be installed at the initial location reinforced or at a new location.
10. Any inflammable thing should never be placed about the location of installation.
DANGER
11. Check the grounding to see whether it is proper or not, and if it is found improper, connect the grounding terminal to the earth.
– 1 –
WORKING STANDARDS FOR PREVENTING BREAKAGE OF SEMICONDUCTORS
1. Scope The standards provide for items to be generally observed in carrying and handling semiconductors in relative manufacturers during maintenance and handling thereof. (They apply the same to handling of abnormal goods such as rejected goods being returned).
2. Object parts (1) Micro computer
(2) Integrated circuits (IC) (3) Field-effect transistors (FET) (4) P.C. boards or the like on which the parts mentioned in (1) and (2) of this paragraph are equipped.
3. Items to be observed in handling (1) Use a conductive container for carrying and storing of parts. (Even rejected goods should be handled in
the same way).
A conductive polyvinyl bag
IC
Fig. 1. Conductive Container
(2) When any part is handled uncovered (in counting, packing and the like), the handling person must always
use himself as a body earth. (Make yourself a body earth by passing one M ohm earth resistance through a ring or bracelet).
(3) Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being
taken. (4) Be sure to place a part on a metal plate with grounding. (5) Be careful not to fail to turn off power when you repair the printed circuit board. At the same time, try
to repair the printed circuit board on a grounded metal plate.
IC
Conductive sponge
Body earth (Elimik conductive band)
1M
Fig. 2. Body Earth
Clip for connection with a grounding wire
– 2 –
(6) Use a three wire type soldering iron including a grounding wire.
Metal plate (of aluminium, stainless steel, etc.)
Staple
Bare copper wire (for body earth)
Fig. 3. Grounding of the working table
Working table
Resistor of 1 M (1/2W)
Earth wire
Soldering iron
2
Screw stop at the screwed part using a rag plate
Fig. 4. Grounding a soldering iron
Use a high insulation mode (100V, 10M or higher) when ordinary iron is to be used.
(7) In checking circuits for maintenance, inspection or some others, be careful not to have the test probes of the
measuring instrument shortcircuit a load circuit or the like.
Grounding wire
– 3 –
CAUTION
!
1. In quiet operation or stopping the running, slight flowing noise of refrigerant in the refrigerating cycle is heard occasionally, but this noise is not abnormal for the operation.
2. When it thunders near by, it is recommend to stop the operation and to disconnect the power cord plug from the power outlet for safety.
3. The room air conditioner does not start automatically after recovery of the electric power failure for preventing fuse blowing. Re-press START/STOP button after 3 minutes from when unit stopped.
4. If the room air conditioner is stopped by adjusting thermostat, or missoperation, and re-start in a moment, there is occasion that the cooling and heating operation does not start for 3 minutes, it is not abnormal and this is the result of the operation of IC delay circuit. This IC delay circuit ensures that there is no danger of blowing fuse or damaging parts even if operation is restarted accidentally.
5. This room air conditioner should not be used at the cooling operation when the outside temperature is below 10°C (50°F).
6. This room air conditioner (the reverse cycle) should not be used when the outside temperature is below –10°C (14°F). If the reverse cycle is used under this condition, the outside heat exchanger is frosted and efficiency falls.
7. When the outside heat exchanger is frosted, the frost is melted by operating the hot gas system, it is not trouble that at this time fan stops and the vapour may rise from the outside heat exchanger.
– 4 –
SPECIFICATIONS
MODEL
RAK-25NH4 RAK-35NH4 RAK-50NH4
RAC-25NH4 RAC-50NH4RAC-35NH4
FAN MOTOR
FAN MOTOR CAPACITOR
FAN MOTOR PROTECTOR
COMPRESSOR
COMPRESSOR MOTOR CAPACITOR
OVERLOAD PROTECTOR
OVERHEAT PROTECTOR
FUSE (for MICROPROCESSOR)
POWER RELAY
POWER SWITCH
TEMPORARY SWITCH
PWM DC35V
NO
NO
NO
NO
NO
NO
NO
NO
YES
40 W
NO
NO
JU1012D JU1013D
NO
YES
YES
3.0A
G4A
NO
NO
SERVICE SWITCH
TRANSFORMER
VARISTOR
NOISE SUPPRESSOR
THERMOSTAT
REMOTE CONTROL SWITCH (LIQUID CRYSTAL)
REFRIGERANT CHARGING VOLUME (Refrigerant 410A)
UNIT
PIPES (MAX. 20m)
NO
NO
NO
NO
YES(IC)
YES
----------
WITHOUT REFRIGERANT BECAUSE
COUPLING IS FLARE TYPE.
450NR
YES(IC)
1150g1150g
YES
NO
YES
NO
1400g
– 5 –
CONSTRUCTION AND DIMENSIONAL DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
Air suction grill
Mounting plate
183
860
Top air suction grill
Front panel
Cabinet
285
About
380
350
About
View from back
(Pipe lead-out)
6.5 60
47
47
31 120.5
Drain outlet
60 60
240 170450
Horizontal deflectorDischarge grill
Drain hose
Hole on the wall for ø 65mm pipe
P
47
Drain
Narrow pipe
Vertical deflector
7070140
Drain cap connection port
147
56 17.5
28
47
When piping is drawn horizontally, exchange the drain hose for the drain cap
6.5 60
Connecting cable
– 6 –
Wide pipe
CONSTRUCTION AND DIMENSIONAL DIAGRAM FOR OUTDOOR
MODEL RAC-25NH4, RAC-35NH4
852
28 750
16556
76
559
570
195
95
2616 280
166
MODEL RAC-50NH4
10464
Handle
Air suction grille
955
26 850
Air outlet
79
638
650
340
201
280
2022 298
Handle
96
340
169.5
Fixing hole
Holes for anchor bolt (2-ø12)
507 198
Notch for anchor bolt (2-ø12 Notchs)
12 37
57
10
1010
320
340
– 7 –
More than
100
700
More than
100
More than
Service space
More than
100
MAIN PARTS COMPONENT
RED
360V
BLK
0V
WHT
15V
M
YEL
0~6V
BLU
0~15V
THERMOSTAT
Thermostat Specifications
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4 THERMOSTAT MODEL IC OPERATION MODE COOL HEAT
ON 15.6 (60.1) 20.0 (68.0) OFF 15.3 (59.5) 20.7 (69.3) ON 23.6 (74.5) 28.0 (82.4) OFF 23.3 (73.9) 28.7 83.7) ON 31.6 (88.9) 36.0 (96.8) OFF 31.3 (88.3) 36.7 (98.1)
TEMPERATURE °C (°F)
INDICATION
16
INDICATION
24
INDICATION
32
FAN MOTOR
Fan Motor Specifications
MODEL
RAK-25NH4, RAK-35NH4,
RAK-50NH4
POWER SOURCE DC: 0 ~ 35V OUTPUT 23W
RED BLK
WHT
YEL BLU
CONNECTION
35V
0V 5V
0 ~ 5V
FG
RAC-25NH4, RAC-35NH4,
RAK-50NH4
DC360V
40W
M
(Control circuit built in)
BLU : BLUE YEL : YELLOW BRN : BROWN WHT : WHITE GRY : GRAY ORN : ORANGE GRN : GREEN RED : RED BLK : BLACK PNK : PINK VIO : VIOLET
– 8 –
COMPRESSOR MOTOR
Compressor Motor Specifications
MODEL COMPRESSOR MODEL
RAC-25NH4 RAC-50NH4RAC-35NH4
JU1012D JU1013D PHASE SINGLE RATED VOLTAGE AC 220 ~ 230 V RATED FREQUENCY 50 Hz POLE NUMBER 4
(U)
WHITE
CONNECTION
M
M
M
(W)
(V)
YELLOW
RESISTANCE VALUE
20°C
(68°F)
2M = 1.05
RED
75°C
(167°F)
YELLOW
2M = 1.28
WHITE
RED
!
CAUTION
( )
When the refrigerating cycle has been operated for a long time with the capillary tubes clogged or crushed or with too little refrigerant, check the color of the refrigerating machine oil inside the compressor. If the color has been changed conspicuously, replace the compressor.
– 9 –
WIRING DIAGRAM
BLU
POWER RELAY
COIL
NF COIL 1
C003
C001
C002
VARISTOR1
L001
CT1
VARISTOR3
SURGE
ABSORBER
DIODE STACK
R010
L002
R011
C011
C010
FAN
MOTOR
VARISTOR2
CN6 WHT
C008 C013 C015
M
WHT YEL
RED
WHT YEL
YEL
YEL
YEL
DIODE STACK
RED
UVW
REACTOR
SYSTEM POWER
MODULE 2
L2 L1
CN14
CN13
CN11
C503
C502C501
10
CN14
CN10 RED
CN9 BLU
CN8 WHT
CN15 WHT
CN13
CN11
5
5
CN12
CN12
RED
GRY
2A FUSE
ICP RELAY
R008R007
3A FUSE
25A FUSE
C006
R001
BLK GRN WHT
(WHT) (BRN) (RED)(BLK)
CONNECTING
CORD
BRN RED
BLK
BLK
GRN
RED BLK
WHT
YEL
BLU
POWER CIRCUIT
TERMINAL BOARD
(GRN+YEL)
LNCD
SINGLE PHASE
AC220~230V
50Hz
(GRN+YEL)
THERE ARE SOME LEAD WIRES WHICH HAVE SPIRAL STRIPES WITH WHITE IN ADDITION TO THE ORIGINAL COLOR
CN2 RED
MAIN P.W.B.
REVERSING VALVE
R002
C007 C012 C014
ELECTRIC EXPANSION VALVE
OH THERMISTOR
DEFROST THERMISTOR
OUTDOOR TEMPERATURE THERMISTOR
GRY GRY
GRY GRY
RED RED
COMPRESSOR
MODEL RAK-25NH4 / RAC-25NH4
RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
INDOOR UNIT
CONNECTING CORD
FROM OUTDOOR UNIT
(BROWN) (RED)
GREEN & YELLOW
INDOOR ROOM TEMPERATURE THERMISTOR
HEAT EXCHANGER THERMISTOR
TERMINAL
BOARD
C D
BLACK BLACK
GRAY GRAY
BROWN RED
CN1
CN5 CN9
EEPROM / TEST HA
1234 1 2 3 4
5678
CN12
MAIN P. W. B.
C1 C2 M1 M2
CN4 CN11
4 LINES 5 LINES
CN8
CN10
9 LINES
STEPPING
MOTOR
M
M
INDOOR
FAN MOTOR
WIRELESS
REMOTE CONTROLLER
RECEIVER
P. C. B.
CN3A
CN2A
OUTDOOR UNIT
CN2
LED
P. C. B.
– 10 –
CIRCUIT DIAGRAM
Remote Control
Key matrix table
1
SEG5
2
SEG0
3
SEG1
4
SEG2
5
SEG3 SEG4
6 7
SEG5
8
SEG6
9
SEG7
10
COM3
11
COM2
12
COM1
13
COM0
14
SEG14
15
SEG13
16
SEG12
17
SEG11
18
SEG13
19
SEG9
20
SEG8
D3 RB425D(1/2)
C8
50v/1u
LCD 1
K 1
K2K3
K4
K5
P10
P11
K6
K7 K8
K9 K10
K11K12
SEG20 SEG19 SEG18 SEG17 SEG16 SEG21
SEG27 SEG28
P12
SEG24 SEG25 SEG26
NC NC NC NC NC NC NC
NC
NC
K13 K14
K15 K16
K17
K18
40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21
D0
D1
D2
D3
65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80
64
SEG20 SEG21 SEG22 SEG23 SEG24 SEG25 SEG26 SEG27 SEG28 SEG29 SEG30 SEG31 SEG32 SEG33 SEG34 SEG35
1
62
63
SEG19
SEG18
P41
P40
3
2
R1
100k
60
61
SEG17
SEG16
P42
P43
5
4
59
58
57
54
SEG14
SEG15
IC 1
56
SEG13
SEG12
55
SEG11
SEG10
SEG9
53
52
51
SEG8
SEG7
50
49
SEG5
SEG6
M3455OM6A-504FP
D2
P00
6
P01
7
P02
8
P03
9
P10
10
P11
11
P12
12
P13
13
D0
14
D1
15
16
48 47
SEG4
D3
17 18
SEG3
D5
D4
45
46
SEG1
SEG2
D6
20
19
Input
P10
P11
P12
43
44
42
SEG0
SEG42
SEG43
NCVL C1
XC OUT
D7
D9
D8
BEEP
22
21
23
SW1
SW-187-2P
Output
D0
Door open Automatic swingFan speed selectionOperation selectionStart/Stop
Door shut Automatic swingStart/Stop
Door open Day
Door shut Fan speedRoom temperature downRoom temperature up
Door open CancelReservationOff timer
Door shut Sleep
41
SEG41
SEG40
40
P30 P31
39 38 37
VL C2 VL C3
36 35
XC IN
34 33
VDD
32
VSS
X OUT
31
X IN
30 29
RESET
28
CARR
27
P23
26
P22
25
24
P21
P20
R2
100k
R3
100k
R5
330
P
R4
100k
R6
D1 D2
EL-1L7
D2D1
R8
R7
R6 R9
24(1/8W)
Q1
2SC3443
or 2SC2982
R9
R10 12M
D3
RB425D
(1/2)
K19
X1
910kHz
C9
105
R11
150k
X2
32.768
kHz
C6
104
present timeHour downHour upOn timer
D3D2D1
R14 220k
220K
R13
C7
104
R15
100k
R16 100k
C1
334
C2
220p
C3
220p
C4
18p
C5 22p
R12
220k
11
CIRCUIT DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
12
CIRCUIT DIAGRAM
MODEL RAC-25NH4/RAC-35NH4/RAC-50NH4
13
PRINTED WIRING BOARD LOCATION DIAGRAM
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
MAIN P.W.B.
Marking on P.W.B.
COMPONENT SIDE
SOLDERING SIDE
1
IVORY
CN5
8 4
1
CN1
WHT
C621
C751
C132
C131 R111
ICP2
1
1
IC402
J29
J30
J17
R631 L751
R751
R114
Q113
R121 ICP1
WHT
CN4
CN8 WHT
J31
J18
J19
J10
5
IVORY
ZD131
Q111
R122
IC111
R112 C112
C111
ZD111
R125
R126
J20
CN6
4
5
BZ
J39
RES1
J33
J32
J34
J11
J12
1
1
HB-098-101A
Q131
C133
R132
Q112
D111
R115
Q115
C103
D821
C823 R825 R823 C822
IVORY
1
CN14
1
J52 J46 J44
J51 J50
J45
J42
J43
J49 J48
J40
J41
J21 J22
J14 J13
J15
CN9
4
BLK
ZD211
R201
R131
ZD121
C123
Q114
C113 R117
R828
R829
R826
R824
R822
1
IC801
4 Q801
R812 J72
Q821
C763
R612
R764
R609
R830
C115
J78
C651
C825
R118
R651
Q803
R119
R761
R120
R658
ID
8
C801
R804
C121
C116
R116 R124
Q116
R123
J79
R827
R821
C803 C804
J801
L801
R806 R805 R803
J16
J23
R811
4
J35
J24
R701
REG2
J37
J36
R606
32
33
R657
R610
C507
R807
R810
C631
R656
R503
J76
R403
J47
R605
R404
Q802
J53
J38
IC501
R500
R654
5
R763
R504
R813
J54
J25
C821
ICP3C762
R219
R653
WHT
CN11
J55
R743
R604
R603
17
C601
R505
1
C114
C122
J26
J27
C802
J83
Q722
R745
R742
R744R741
R611
C506
16
R501
R602
C824
R641
R601
J75
R652
J71
AUTO RESTART CANCEL
L111
R506
R508 L501
R502
C501
C611
R514
R507
R655
IC711
C524
R746
C521
R509
J82
1
R515
R510
HB–098–101A
J56
L101
C101
D101
13
L743 L742 L741
16
J81
1
C522
IC521
R521
R522
C505 C304 R307
C302
R511
R512
R513
J74
R308
C104 R127
C502
Q521
D402
R650
C102
CN12
WHT
C711
R305
C523
C401
R128
F
No. Lot
J28
J80
R301
1
CN10
IVORY
6
9
R749
8
R748 R747
IC401
R401
R402
J77
D403
D401
R306 C303 R303
J73
R302
J70
RECEIVING P.W.B.
Marking on P.W.B.
Lot No.
IR1
1 14
J57
C1
IVORY
CN2A
IVORY CN3A
COMPONENT SIDE
F
SW1
9
HB-098-102A
– 14 –
R1
R2
SOLDERING SIDE
MODEL RAC-25NH4, RAC-35NH4, RAC-50NH4 MAIN P.W.B. Marking on P.W.B
COMPONENT SIDE
– 15 –
RAK-25NH4 / RAC-25NH4 RAK-35NH4 / RAC-35NH4 RAK-50NH4 / RAC-50NH4
LCD wireless
Room temperature thermistor
Wireless receive circuit
Filter. Operation. Timer.
Power source 1ø, 50Hz, 220~230V
L N
Outdoor unit Terminal board
SPM2
Trip signal synthesis circuit
Heat exchanger thermistor
Temporary switch
Initial setting circuit
Reset circuit
Auto sweep motor for Air deflector
Indoor microcomputer (AX-7R11)
Outdoor microcomputer / HIC (AX-8N00)
Electric Expansion valve drive circuit
Electric
Expansion
valve
– 16 –
BASIC MODE
MODEL RAK-25NH4, RAK-35NH4, RAK-50NH4
Operation mode
Basic operation of start/stop switch
Off-timer
On-timer
Timer functions
Off -> On On -> Off timer
Auto
Hi
Med
Fan speed mode (indoor fan)
Lo
Basic operation of temperature controller
Sleep operation (with sleep button ON)
Operates at Hi regardless of the room temperature.
Operates at Med regardless of the room temperature.
Operates at Lo regardless of the room temperature.
Performs only fan operation at the set speed regardless of the room temperature.
Enters sleep operation after set as on the left.
Action during sleep operation Lo (sleep) operation
Fan
Start/stop switch Operation lamp
Hi Med
Fan
Speed
Lo
Hi Med Lo
Changes from Hi to Med or Lo depending on room temperature.
Temperature set for cooling
Thermo iudgment Compressor
Hi Med Lo
1. Runs at Hi until first thermo off after operation is started.
2. Runs at Lo when thermo is off.
Set to ultra-Hi when the compressor runs at maximum speed, and to Hi in other modes.
Same as at left.
Same as at left.
See page 49.
Same as at left
See page 51.
(Compressor stopped forcibly for 3 minutes)
Dehumidifying
(dehumidifying operation by the function select button only, not including that engaged by the dehumidify button)
Start/stop switch Operation tamp
Start/stop switch Operation tamp
Cancel switch Operation temp Timer tamp
Timer memory
Srart/stop switch Reserve switch Cancel switch Operation temp Timer tamp
Timer memory
Start/stop switch Reserve switch Cancel switch Operation lamp Timer lamp
Timer memory
Start
(Change in reserved time)
Changes between Lo and “Med” depending on the room temperature.
Fan speedTemperature division Division 1 Division 2 Division 3 Division 4
Lo
Lo Med Med
1. The indoor fan also stops when the compressor is in stop status.
Set to Hi in modes other than when the compressor stops.
Set to Med in modes other than when the compressor stops.
Set to Lo in modes other than when the compressor stops.
See page 53.
Same as at left
See page 53.
Stop
Start Stop
(Off-timer during stop)
(On-timer during operation)
ON ONONOFF OFF OFF ONOFF
(Off->On timer) (On->Off timer) (On->Off timer)
(Change in reserved time)
during operation)
(Off->On timer)
during stop)
Set to ultra-Lo, Lo, Med, “Hi”, “ultra-Hi” or “stop” depending on the room temperature, time and heat exchange temperature. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preheating (cooling is recovered at 18.33˚C).
When the compressor is running at maximum speed during hot dash or when recovered from defrosting.
˚C
42. 66
37. 66
32. 66
29. 66
Hi or ultra-HI (fan speed set to auto”)
Med Lo
In modes other than left
Heat exchanger temperature
Set to ultra-Lo, Lo, Med, “Hi”, “ultra-Hi” or “stop” depending on the room temperature, and time. Set to “stop” if the room temperature is 18˚C in the “ultra-Lo” mode other than during preheating (cooling is recovered at 18.33˚C). Set to ultra-Hi when the compressor is running at maximum speed during hot dash or when recovered from defrosting.
Set to ultra-Lo, Lo, Med” or stop depending on the room temperature and time. Set to stop if the room temperature is 18˚C in the ultra-Lo mode other than during preseating (cooling is recovered at 18.33˚C).
Set to ultra-Lo, Lo, or stop” depending on the room temperature and time. Set to stop” if the room temperature is 18˚C in the ultra-Lo mode other than during preseating (cooling is recovered at 18.33˚C). The fan speed is controlled by the heat exchanger temperature; the overload control is executed as in the following diagram:
KAFON KAFOF
Med with overload
Lo
Heat exchanger temperature
See page 55.
Same as at left
See page 57.
N&F autoHeatingCooling
The neuro & fuzzy control allows device to determine optimum operation mode and set temperature. However, during auto cooling, the new cool rhythm starts when the room temperature is less than the set temperature plus 0.66˚C, after dash is finished.
Room temperature
Outdoor temperature
Calendar
Humidity
Neuro pattern recognition
Fuzzy control
Operation mode
Set temperature
Notes: (1) The set temperature can be varied ±3˚C using the
temperature setting buttons and .
v
v
(2) If operation is started by tele-control or by temporary switch
in status where remote control has not been used after power was supplied, the operation mode will be as follows (since there is no stored calendar data):
Room temparature at
operation start (˚C)
Cooling Dehumidifying
Heating
Set temperature: 28˚C Fan mode: Auto
Set temperature: Room temperature at operation Fan mode: Auto
Set temperature: 22˚C Fan mode: Auto
start
Same as at left.
Performs the sleep operation of each operation mode.
Special auto (not normally used)
The special auto mode is based on N&F auto, but the following is different:
Operation mode
N&F auto
Special auto
Mode change during operation
Does not change as long as outdoor temperature or calendar data does not change greatly.
The operation mode will be judged the same as at operation start every hour.
The special auto operation mode is entered when operation is started in the following status:
<Start condition> Power is supplied white the tele-control signal is being input. (Operation starts automatically.)
<End condition> The remote control restores the normal operation mode.
Note (1) Since there is no stored calendar
data, N&F control is not determined. See Note (2) of N&F auto.
– 17 –
Table 1 Mode data file
RAK-25NH4 RAK-35NH4 RAK-50NH4
LABEL NAME VALUE
WMAX 4500 min WMAX2 4600 min WSTD 3250 min WBEMAX 2600 min CMAX 2900 min CMAX2 3000 min CSTD 2500 min CKYMAX 2200 min CJKMAX 2000 min CBEMAX 1800 min WMIN 1200 min CMIN 1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
5500 min 5600 min 4350 min 2800 min 3700 min 3800 min 3550 min 2800 min 2500 min 2200 min 1200 min 1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
6200 min 6250 min 5200 min 2600 min 5700 min 5800 min 5200 min 3550 min 2700 min 2000 min 1200 min 1500 min
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
–1
STARTMC 60 Seconds 60 Seconds 60 Seconds DWNRATEW 80% 80% 80% DWNRATEC 80% 80% 80% SHIFTW 3.33°C 3.33°C 3.33°C SHIFTC 1.00°C 1.00°C 0.33°C CLMXTP 30.00°C 30.00°C 30.00°C YNEOF 22.00°C 22.00°C 28.00°C TEION 5.00°C 5.00°C 2.00°C TEIOF 9.00°C 9.00°C 9.00°C SFTDSW 1.00°C 1.00°C 1.00°C DFTIM1 45 Minutes 45 Minutes 45 Minutes DFTIM2 60 Minutes 60 Minutes 60 Minutes
18
NOTE (9)
Reversing valve (heating “on” mode)
Notes: (1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor rpm (calculated value in Table 7) larger than WMAX.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode. (3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode. (4) Compressor minimum “ON” time and “OFF” time is 3 minutes. (5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor temperature
is higher than CLMXTP. (6) When fan is set to “Hi”, compressor rpm will be limited to CKYMAX. (7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX. (8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX. (9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
Table 2 ∆TCMAX
Temperature Calculated
difference compressor rpm
1.66 2265 min 2 2435 min
2.33 2600 min
2.66 2765 min 3 2935 min
3.33 3100 min
3.66 3265 min 4 3435 min
4.33 3600 min
4.66 3765 min 5 3935 min
5.33 4100 min
5.66 4265 min 6 4435 min
6.33 4600 min
6.66 4765 min 7 4935 min
7.33 5100 min
7.66 5265 min 8 5435 min
8.33 5600 min
8.66 5765 min 9 5935 min
9.33 6100 min
9.66 6265 min
10 6435 min
10.33 6600 min
10.66 6765 min 11 6935 min
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Note:
1. See the data in Table 1 on page 47 for each constant in capital letters in the diagrams.
– 19 –
New Cool Rhythm
Cooling Sleep Operation
Final set temperature
(Cooling/dehumidifying set temperature (temperature set by remote control (+) SHIFTC)
Set temperature during rhythm (temperature set by remote control (+) SFTRZM)
Thermo judgment
Hi
Indoor fan
New cool rhythm
Outdoor fan
Lo
Rhythm Med
Rhythm Lo
Med
Room temperature
See basic operation.
Lo
Minimum 5min.
5 sec. 5 sec.
Minimum 5min. Minimum 5min.
5min.
1 cycle
2.5 sec. 2.5 sec.
4.5 sec.
2.5 sec.
5min.
Minimum
5min.
5min.
Minimum
5min.
Thermo OFF
15 sec.
Minimum
5min.5min.
5min.
Lo
Final set temperature (Cooling/dehumidifying set temperature (+) sleep shift)
(Cooling/dehumidifying set temperature = Remote control set temperature (+) SHIFTC)
Sleep key
Operation lamp
Timer lamp
Indoor fan
Outdoor fan
Horizontal air deflector
Hi
Med
Lo (sleep)
Shut
Horizontal
Facing down
See basic operation
Lo
Set to 7 hours
0.5hr
1.5hr
2.5hr 3.5hr 6hr 7hr
3hr
Maximum speed
P1
Compressor speed
Notes:
(1) New cool rhythm is engaged when the fan speed is “auto” and the room temperature is less than
set one plus 0.66˚C in the “auto” operation mode or cooling mode. (2) The minimum new cool rhythm time is 10 minutes when the temperature falls and rises. (3) Cool rhythm is not engaged during Nice temperature, Sleep operation. (4) Pl control is engaged during new cool rhythm: the speed limit is the same as during normal operation. (5) The new cool rhythm set temperature is also shifted during thermo OFF.
Compressor speed
Notes:
(1) The sleep operation starts when the sleep key is pressed. (2) When the sleep key is set, the maximum compressor speed is limited, and the indoor fan is set to sleep Lo”. (3) 30 minutes after the sleep key is set, the sleep shift of temperature starts, and upper shift is made at least 6 times. If 25˚C
is not reached after 6 shifts, shifts repeat unit 25˚C is reached. (4) The sleep shift upper value of set temperature is 28˚C. (5) After 6 hours, a shift down to the initial set temperature is made at a rate of 0.33˚C/5 min. (6) If the operation mode is changed during sleep operation, the set temperature is cleared, and shift starts from the point when
switching is made. (7) The indoor fan speed does not change even when the fan speed mode is changed. (8) When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue to be
counted. (9) If the set lime is changed during sleep operation, all data including set temperature, time, etc. is cleared and restarted. (10) If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
Reverse cycle period
MAX. 12min.
min–1
3000
fixed
20
Loading...
+ 66 hidden pages