Hitachi RAs-R10ex, RAC-R10EX Installation Manual

FOR SERVICE PERSONNEL ONLY
above 100mm
above 200mm
above 200mm
above 100mm
give clearance
as wide as possible
above 50mm
above 100mm
about 0.45m
above 300mm
must not bend
above 50mm when installed on the ceiling of balcony
above 200mm
2,300mm or more
4
5
3
6
Maximum pipe length 15m
Minimum pipe length 5m
above 100mm
1
2
!
!
Carefully read through the procedures of proper installation before starting installation work.
The sales agent should inform customers regarding the correct operation of installation.
HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit Outdoor Unit
RAS-R10EX RAC-R10EX
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
!
!
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as described in the user’s guide.
!
WARNING
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use wire which is specified for the air conditioner. A short circuit and fire may occur due to the use of low quality wire or improper work.
Be sure to use the specified wire for connecting the indoor/outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock and fire may occur.
Do not mix any coolant other than R-22 into the cooling circulation path when mounting or shifting the unit. If it is mixed with air, the high pressure in the circulation path will rise and this may result in broken copper pipes or faults.
!
CAUTION
Be sure to use the earth line. Do not place earth line near gas or water pipes, lightning conductor and the earth line of telephone. Improper earthing may cause electric shocks.
A circuit breaker should be installed depending on the mounting size of the unit. Without a circuit breaker, the danger of electric shocks exists.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
Tools Needed For Installation Work
+ – Screwdriver ● Measuring Tape ● Knife
Detector ● Pipe Cutter ● Plastic Tape ● Pliers
ø 65mm Power ● Drill Allen Key ( 4mm)
Wrench (14, 17, 19, 22mm)
Gas Leakage
Flare Tool
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
WARNING
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specified in figure below.
The location must be convenient for water drainage and pipe connection with the outdoor unit.
To avoid interference from noise please place the unit and its
INDOOR UNIT
remote controller at least 1m from the radio, television and inverter type fluorescent lamp.
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency machines and high-power wireless systems.
The installation height of indoor unit must be 2.3m or more.
Names of Indoor Components
QtyNo. Item
Mounting Plate
1
Screw for Mounting Plate
2
Holder for Remote Controller
3
AAA Size Battery
4
Screw for holder of Remote Controller
5
Remote Controller
6
Purifying Filter
7
Holder
8
Air Exchanger Filter
9
Air Duct Filter
0
Insulation Sheet
!
Anti Insect Ventilate Net
@
Rain Proof Ventilate Protection Cap
#
(3.1x16)
$
1
%
5
^
1
&
2
2
*
1
(
1
)
1
1
q
1
w
1
e
1
r
1
Binder
Right Downward Pipe Connector
Right Horizontal Pipe Connector
Right Connector
Left Backward Pipe Connector
Left Downward Pipe Connector
Left Horizontal Pipe Connector
Right Horizontal Pipe Connector
Ventilation pipe
Extension Ventilation Pipe
Outdoor Thermistor Extension Wire
The outdoor unit must be mounted at a location which can sup­port heavy weight. Otherwise, noise and vibration will increase.
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right and front are specified in figure below. At least 2 of the above sides must be open air.
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
OUTDOOR UNIT
Do not install at a location where there is flammable gas, steam, oil and smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connection wire at least 1m away from the antenna or signal line of television, radio or telephone. This is to avoid noise interference.
QtyNo. Item
Figure showing the Installation of Indoor and Outdoor Unit.
!
1
CAUTION
In case the pipe length is more than 8m, add refrigerant R22 at 10 gram per every meter exceeds. However, pipe length shall not exceed 15m.
1
The Length of Indoor
Unit Power Cord
Horizontally perpendicular to the unit
Be sure to completely seal any gap with putty.
about
0.9m
1
Do not alter the power cord.
1
1
1
Direction of Piping
Connection
There are 4 directions allowed, namely, horizontally perpendicular to the unit, vertically down from right, horizontally out from right and horizontally out to left. Dont form the piping downward at the left of the unit.
about 1.6m
1
1
1
1
Cut away shaded portion, and finish the edge of the
1
opening so that there is no burr.
20
!
WARNING
!
CAUTION
Dimension of Mounting
Stand of the outdoor unit
(unit : mm)
mounting stand
35
12
8
225
35
500
100
The difference in
height between the indoor and outdoor unit should be kept below 5m.
The connecting
pipe, no matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).
The connection of in­sulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
1
Air Exchanger And Exhaust Hose Installation
The air exchanger and exhaust function is included in this model. Please follow the installation instructions when mounting.
Please install only with the customer’s consent
The air exchanger should not be operated under the following conditions: (A) When the air exchanger hose cannot be vented directly outside the room (mounting work specified for
the embedded ducting).
(B) When there is a source of a questionable odor, smoke, or oily smoke in the vicinity of the opening of
the air exchanger hose, even if the mounting work directly vents the air exchanger hose outside the room.
The fresh air in should not be operated (only exhaust can be operated) under the following conditions: (C) When there is space to vent the air exchanger hose between the internal and external walls, which leads
outside the room, even if the mounting work cannot directly vent the air exchanger hose outside the room (conventional construction methods).
Please set the Air Exchanger Selection Switch according to the mounting configuration.
[Dimensions when Installing included Fittings]
Under the following conditions, the device can be installed with these fittings alone.
ø20 two way air exchange hose
Vented within 0.9m to the left and down or within 1.4m to the right and down.
Diagram Describing Backward Piping From Left
Air Exchanger Hose
Drain Hose
Connecting Cable
Refrigerating Pipe
Diagram Describing Horizontally Piping From Right
Within 0.9m
Within 0.9m
Dimensions when installing the fitting for ø20 air exchanger hose
Part Name Cap
Backward piping
Vertically down from right Horizontally piping from right
Backward piping from left Vertically down from left
Horizontally piping from left
Remark
ø20 Air
Exchanger Hose
Net
When Air Exchanger cover (HC-D55) is not using.
Within 1.4m
Within 1.4m
Extension Pipe Connector
Air Exchanger Hose
Drain Hose
Refrigerating Pipe
Diagram Describing Vertically Down From Left
Air Exchanger Hose
Drain Hose
<
I719: A
>
Connecting Cable
Refrigerating Pipe
Drain hose
1
Installation of Mounting Plate, Wall Penetration And Protection Pipe
2
Installation of the Indoor Unit
!
CAUTION
The draining of the water container inside the indoor unit can be done from the left. Therefore the mountting plate must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the mounting plate.
Visible Outline Of The Indoor Unit
Level
The end of big refrigerant pipes.
Center line for mounting plate
The end of small refrigerant pipes.
level adjustment.
Drain Hose
Stamp
Line
500 mm500 mm500 mm500 mm500 mm
Weight
Wall Hole
Screw For Hanger
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, power cord and drain hose.
Installation
The upper part of the indoor unit is hanged on the mounting plate.
The projection at the lower part of the indoor unit is hooked onto the mounting plate.
Hanger
Refrigerating Pipe
Projection Pipe
HORIZONTAL PIPING
Drain Hose
Two Way Air Exchange Hose
Connecting Cord
Wrap With The Tape
Hanger
Projection
Procedures of Installation and Precautions
Procedures to fix the mounting plate.
1.Drill holes on wall. 2. Fix the mounting plate on wall (As shown below) with 4.1 x 32 screw
(As shown in figure below)
INDOOR UNIT
Procedures to fix the holder of remote control.
1.Drill holes on wall. (As shown below)
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown in figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap. (This is an easier way to remove the drain cap).
Drain Cap
Drain Hose
!
CAUTION
Please pull the lower part of the indoor unit outwards to check if the unit is hooked onto the mounting plate. Improper installation may cause vibration and noise.
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on wall which is slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe according to the wall thickness.
Empty gap in the sleeve of protection pipe should be
Indoor
completely sealed with putty to avoid dripping of rain water into the room.
WALL
Protection pipe
Sleeve of protection pipe
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
During horizontal or downward piping, use a knife to cut openings as shown in figure. Then smoothen the edges of openings with a file.
Pipe support
Outdoor
2~5mm
Seal with putty
!
CAUTION
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse.
Openings
Drain cap
Drain cap
Please insert until here
Drain hose
Please insert until here
!
CAUTION
Condensed water may leak out if not inserted properly.
THE CONNECTION OF COOLANT PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Coolant Pipes
Coolant pipes and power cord must be tied together.
Openings
Pull Up The pipe After Bending Downward
Transform the piping while holding down the lower portion of pipe-support by hand.
INSTALLATION OF COOLANT PIPES AFTER CONNECTION
The coolant pipes should be adjusted to fit into the hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered with insulator used for terminal connection.
Connect the power cord.
After adjustment, fit the power cord and pipes into the space available under the indoor unit.
Drain layout of backward piping
Cross section view for pipes
from left ¿65 area
arrangement at backward ø65 wall diameter.
Please Bend At A Small Radius To Form An Arc
Below 5mm
Projection
!
CAUTION
Please fix in the plastic core after flaring to avoid plastic chips entering the pipes.
Hook
Temporary Support
About 15cm
Wall Hole
Insulation Pipe (must be wrapped with vinyl tape at every 120mm).
Coolant Pipe
Bend Coolant Pipe Until Touching Air Exchanger Hose As Shown in Figure
!
The rubber strap used for fixing the insulator should not be tied with great force. Otherwise, this will damage heat insulation and causes water condensation.
Pipe
Air Exchanger Hose
CAUTION
Rubber strap tied with great force
Installation
Hang the indoor unit onto the mounting plate. Use the temporary stand at the back of the indoor unit to push its lower part 15cm forwards.
Place the drain hose through the hole on the wall.
Insulate the connecting portion of coolant pipe with insulator.
Connect the power cord.
After adjustment, the power cord and coolant pipes are placed into the space available under the indoor unit.
The projection of indoor unit must hook to the mounting plate.
Air Exchange Hose
Protection Pipe
Drain Hose
Holder
Connecting
Connected Section
Cord
Insulation Material For Pipe Connection
Connecting Cord
Sub Insulation Sheet
Refrigerating Pipe
Heat Insulation Pipe