Hitachi RAC-35FXA, RAF-25PXA, RAF-35PXA, RAF-50PXA, RAC-50FXA Installation Manual

...
< S818 : A >
3
1 2 5 6
4 8
No. Item Qty
7
Remote Controller
1
8
Insulator
1
(t3 x 160 x 600)
9
Screw for Overturn Prevention
2
(4.0 × 34)
0
Insulator
1
(20 × 30 × 300)
-
Bush
3
2.3 Connecting the pipe to indoor unit
Draw in the pipes through the hole of the wall or the floor to indoor.
Arrange the pipe shown below. In the case that large pipe and small pipe arrange to make in front and behind.
The indoor piping should be insulated with the enclosed insulation pipe.
The pipe should first be cut longer than the length shown below.
The excess section of the pipe should be cut off during pipe connection.
1. Installation of wall penetration and installation of protection pipe
1.1 Hole position
Make a hole on the wall such the position as shown below, in order to keep the flow for condensed water smooth.
Carefully read through the procedures of proper installation before starting installation work.
The sales agent should inform customers regarding the correct operation of installation.
Tools Needed For Installation Work
(Mark is exclusive use tool for R410A) • ª· Screwdriver
Measuring Tape • Knife • Saw • ø65mm Power Drill
Hexagonal Wrench Key ( 4mm) • Wrench (14,17,19,
22mm) Gas leakage Detector
Pipe Cutter • Putty
Vinyl Tape • Pliers • Flare Tool Vacuum Pump Adapter
Manifold Valve Charge Hose Vacuum Pump
FOR SERVICE PERSONNEL ONLY
7
INDOOR UNIT / OUTDOOR UNIT
RAF-2508! / RAC-25&8! RAF-3508! / RAC-35&8! RAF-5008! / RAC-50&8!
HITACHI SPLIT UNIT AIR CONDITIONER
INSTALLATION MANUAL
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING............. Incorrect methods of installation may cause death or serious injury.
CAUTION.............. Improper installation may result in serious consequence.
Make sure to connect earth line. This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit as described in the user’s guide. Ask customers to keep this installation manual together with the instruction manual.
WARNING
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and fire may occur due to the use of low quality wire or improper work.
Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the terminal base. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or stronger vibration may occur.
Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A) does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause electric shocks.
When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
When installing the unit, be sure to install the refrigerant pipe before starting the compressor. If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
CAUTION
A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your furniture.
An IEC approved power cord should be used. Power cord type: NYM.
Names of Indoor Components
INDOOR UNIT
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation.)
WARNING
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specified in figure below.
The location must be convenient for water drainage and pipe connection with the outdoor unit.
To avoid interference from noise, please place the unit and its remote controller at least 1m from the radio and television.
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency machines and high-power wireless systems.
OUTDOOR UNIT
WARNING
The outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.
CAUTION
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right and front are specified in figure below. At least two of the above sides must be open air.
The installation height should be at least 2,300mm or more from the floor.
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
Do not install at a location where there is flammable gas, steam, oil and smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connecting cord at least 1m away from the antenna or signal line of television, radio or telephone. This is to avoid noise interference.
1.2 Wall penetration and installation of protection pipe
Drill a ø65mm hole on wall which is slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe according to the wall thickness.
Empty gap in the sleeve of protection pipe should be completely sealed with putty to avoid dripping of rain water into the room.
CAUTION
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse.
Indoor
Outdoor
Seal with putty
2~5mm
WALL
Seal with putty
Sleeve of protection pipe
Protection pipe
2. Installation of the indoor unit
2.1 How to remove the front cover
Please refer to section for details.
Front cover bushing
Bushing (2 pieces on each side)
2.2 Drain pipe
Make sure drain pipe slopes downward so that drain flows smoothly without being trapped in the middle.
The drain hose (connecting port outer diameter: 16mm or 20mm, length: 500mm) is included in the indoor unit. Prepare a drain pipe as shown in the following figure.
To prevent condensation, the indoor drain pipe should be covered with heat insulation material with a thickness of more than 10mm.
After piping is completed, check to make sure that drain discharges smoothly. Seal the drain pipe tightly with tape to keep dirt out.
Front view Right side view
88
210
96
500
Drain hose
Make sure the drain hose slopes downward.
Drain pipe (procure locally)
(Unit: mm)
Cabinet
For floor piping
For floor piping, cut the front cover bushing with a plastic cutter or similar tool and use a file for an attractive finish.
For sideways piping
For right sideways piping, cut the stand’s bushing with a plastic cutter or similar tool and use a file for an attractive finish.
If there is a baseboard
If the baseboard is 5~15mm in thickness and 115mm or less in height, cut the pipe bushing to conform to the baseboard.
115
70
5
15
Baseboard
Cabinet
Removal and installation of front cover
Screw (3 pieces)
Connecting section
Screw (3 pieces)
80~100mm
65mm
Drain hose make lower than center of the hole.
55mm
184mm or less
Hole Position
In the case of making a hole on the wall.
In the case of making a hole on the floor.
INDOOR UNIT
40180
R80
130
170
R60
40180
R80
170
40340
40
WARNING
For sideways piping, do not install the drain hose sideways. Connect the drain hose so that it comes out directly.
Sideways installation of the drain hose will prevent it from sloping downward, causing water leakage. To avoid dripping, make sure to pass the drain hose under the pipe.
PIPE SUPPORT
PIPE SUPPORT
Screws
Mount PIPE SUPPORT so that the cylindrical portion of the drain pan passes through its hole and secure it with screws located at the right back corner.
Hook the PIPE SUPPORT tab in the square hole.
Since there is some space between PIPE SUPPORT and the pipe, affix the insulator 0 to the PIPE SUPPORT. As shown in the figure on the right, affix the insulator 0 to the PIPE SUPPORT to sandwich it.
After connecting the pipes and connecting cord, be sure to screw PIPE SUPPORT tightly and fix the pipes and connecting cord.
Position the easy-to-attach side of PIPE SUPPORT (after aligning it with the pipe) to face the front and secure it with a screw. (Be sure to install PIPE SUPPORT to prevent rodents from entering the indoor unit.)
To prevent the pipe connector from contacting the front cover, push the connector as far as it goes.
Arrange the connecting cord, pipes and drain hose neatly and store them in the bottom section of the rear surface of the indoor unit.
Indoor unit rear surface
Pipe layout of the unit rear surface
Connecting cord
8 Insulator
Connecting cord
Pipe
Drain hose
Pipe/drain hose layout when passing through the file in a wall
Pipe
8 Insulator
Sideways piping.
Top view Front view Right side view
Wall
Wall
160mm or less
Floor
160mm or less
Large pipe
Small pipe
In the case of make a hole on the wall.
Before piping After piping
In the case of make a hole on the floor.
Floor
Wall
Wall
CAUTION
When mounting the flare insulator 1, make sure there is a space between the insulator and left of resin part. Otherwise, may cause water dripping.
(Unit: mm)
above 350
0Insulator
PIPE SUPPORT
2 Binder
1Flare
insulator
Wrap flare insulation, bind top and bottom flare insulation by binder. Wrap tape on flare insulation closely.
2 Binder
Pipe
Floor
32mm
3. Fixing the indoor unit
3.1 Floor installation
438
440 155
55
ø9 rear fixing hole for anchor bolt or screw of accessory.
Fixing on the wall
Case
Fixing the base of indoor unit
Fix the base of indoor unit on the floor with 4.1 × 32mm screws (right and left).
When fixing the indoor unit above the ground, be sure to fix an L-angle at the bottom to support it.
2. Push plug into the holes.
1. Drill holes on floor.
(The plug can be secured diagonally with a screw as shown above.)
WARNING
Be sure to attach screw 3 to prevent the indoor unit from overturn.
3 Screw (4.1x32)
Indoor unit
Plug (Procure locally)
Screw
Screw
3 Screw (4.1x32)
3 Screw (4.1x32)
3 Screw
(4.1x32)
3 Screw (4.1x32)
Fixing on the hanger
3.2 Wall installation
Direct mounting on the wall
184mm o
r less
Procedures of installation and precautions
Procedures to fix the hanger and indoor unit.
1. Drill holes on wall. (As shown below)
2. Push plug into the holes. (As shown below)
3. Fix the hanger on wall with
4.1 X 32 and 4.0 X 34 screw. (As shown in figure below)
Wall
ø4.8mm
32mm
Wall
Plug
Hanger
3 Screw (4.1 x 32)
Horizontal air deflector (Air intake)
Above 100mm
Above 200mm
Above 150mm
Lattice door
Horizontal air deflector (Air outlet)
3.3 Built-in installation
If outlet is covered with the lattice door, room temperature may not be controlled properly. Therefore, air outlet must be open as much as possible.
If air deflector of air outlet is adjusted too much upward, room temperature may not be controlled properly due to the heat inside the lattice door. Therefore, the deflector must be adjusted to nearly horizontal angle.
If signal receiver is covered with the lattice door, signal receiving distance or range (angle) becomes smaller. Therefore, signal receiver must not be covered with the lattice door.
Only the vertical lattice door may be used. Be sure to use a lattice door with an open area ratio of 75% or more. If another lattice door or one with an open area ratio of less than 75% is used, maximum performance may not be obtained.
With a built-in installation, it may take more time to reach the set temperature after the unit is switched on.
30mm
Air conditioner
4. Checking of drawing drain hose
• Connect the separate drain hose to the drain hose that is attached to the indoor unit.
• For keeping the smooth flowing of condensed water the drain hose should be inclined as shown in figure below.
Bending upwards
Bad
Condensed water pond
Bad Bad
Condensed water pond
Bad
Ditch
CAUTION
Please ensure the smooth flow of condensed water of the Indoor unit during installation. (Carelessness may result in water leakage.)
WARNING
Be sure that the hose is not loosely connected or bent.
OUTDOOR UNIT
Condensed water disposal of outdoor unit
• There is holes on the base of outdoor unit for condensed water to exhaust.
• In order to flow condensed water to the drain, the unit is installed on a stand or a block so that the unit is 100mm above the ground as shown figure. Join the drain pipe to one hole.
• Cover the drain hole with a bush. To install the bush, put it on the drain hole as shown in the figure and press the both sides of the bush to fit into the hole. After installation, check whether the drain pipe and bush cling to the base firmly.
Please mount the outdoor unit on stable ground to prevent vibration and increase of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side cover, please pull the handle after undoing the hook by pulling it downward. Reinstall the side cover in reverse order of the removal.
Pull downward
Please face this side (suction side) of the unit to the wall.
Please remove side cover when connecting the piping and connecting cord.
= Bush
~ Drain pipe
Outer diameter: 16mm
Above 100mm
Base
Drain hole
RAC-25FX8 • RAC-35FX8RAC-50FX8
~ Drain pipe
Outer diameter: 16mm
Above 100mm
Base
Drain hole
= Bush
Do not touch the suction port, bottom surface, or aluminium fin of the outdoor unit.
Failure to do so may cause an injury.
CAUTION
• Install the outdoor unit horizontally and make sure that condensate drains away.
• In case of using in cold weather area Especially when there are heavy snows in cold weather area, condensed water freezes on the base and may not drain. In this case, please remove the bush and the drain pipe at the bottom of the unit (left and centre near discharge portion of air, each 1 place) to restore smooth drainage. Ensure that the distance from the drain hole to the ground is 250mm or more.
Remove PIPE SUPPORT.
Insert the drain hose into the hole in the wall.
Winding insulation pipe for drain hose and taping 4 or 5 places to fix.
Connect the pipe to the Indoor unit.
After completing the piping connection, cover the connector with the insulator.
Connect the cord (follow instructions in the section “Connection of the connecting cord” on the reverse of this sheet).
ø4.8mm
Direction of Piping
Piping configuration may be in three different directions: direct rear piping, right downward piping and right sideways piping.
Figure showing the installation of Indoor and Outdoor Unit.
(For example: Wall installation)
• The refrigerating machine oil is easily affected by moisture. Use caution to prevent water from entering the cycle.
• The difference in height between the indoor and outdoor unit should be kept below 10m.
• The connecting pipe, no matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape.)
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
above 200mm
above 50mm
give clearance as
wide as possible
above 200mm
above 100mm
above 200mm
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commercial products.)
Above 100mm
Above 150mm
Above
200mm
- Bush
When mounting on a wall (up to 150~500mm from the floor surface)
Be sure to completely seal any gap with putty.
The space indicated by an arrow  is to guarantee the performance of the air conditioner. install the apparatus at the ample space in order to carry out the maintenance and repair works.
Maximum pipe length 30m
RAF-50FX8/RAC-50FX8
Above 100mm
Above 150mm Above 200mm
The space indicated by an arrow  is to guarantee the performance of the air conditioner. install the apparatus at the ample space in order to carry out the maintenance and repair works.
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commercial products.)
- Bush
When mounting on a wall (up to 150~500mm from the floor surface)
Be sure to com­pletely seal any gap with putty.
Maximum pipe length 20m
above 200mm
()
above 50 mm when installed on the ceiling of balcony
above 100mm
above 200mm
above 50mm
give clearance as
wide as possible
RAF-25FX8/RAC-25FX8 RAF-35FX8/RAC-35FX8
above 300mm
Inner diameter ø16mm
()
above 50 mm when installed on the ceiling of balcony
• The refrigerating machine oil is easily affected by moisture. Use caution to prevent water from entering the cycle.
• The difference in height between the indoor and outdoor unit should be kept below 10m.
• The connecting pipe, no matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape.)
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
Inner diameter ø16mm
No. Item Qty
1
Flare Insulator
1
2
Binder
2
3
Screw for Overturn Prevention
8
(4.1 × 32)
4
Holder for Remote Controller
1
5
Screw for Holder of Remote Controller
2
(3.1 × 16)
6
AAA size Battery
2
Dimension of Mounting Stand of
the Outdoor Unit
(unit : mm)
Mounting Stand
Signal receiver
Hanger
Hole for pipe
Level
Line
Weight
Screw for Hanger
Please use more than 6 screws
Mark
External dimension of
indoor unit
20mm
750mm
50mm
470mm
Drain Hose
20mm
55mm
Please remove 3 screws and clip which fix to the stand and cabinet. (As shown in the figure below)
P
lease remove the screws which fix the cabinet and hanger
.
Ple
ase use hidden beams in the wall to hold the
hanger.
@ Sheet
@ Sheet
1. Drill holes on wall. (As shown below)
2. Push plug into the holes. (As shown below)
Wall
ø4.8mm
32mm
Wall
Plug
3 Screw
(4.1 x 32)
For outdoor unit installation, allow at least 2 sides of space around the unit to ensure ventilation flue.
For outdoor unit installation, allow at least 2 sides of space around the unit to ensure ventilation flue.
Screw (2 pieces)
9 Screw
(4.0 x 34)
9 Screw
(4.0 x 34)
3 Screw (4.1 x 32)
3 Screw (4.1 x 32)
4. Fix the indoor unit on the wall with 4.1 X 32 screw.
Cabinet
3 Screw
(4.1x32)
CAUTION
The draining of the water container inside the Indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
No. Item Qty
=
Bush
1
(2 pcs for RAC-50FX8 )
~
Drain Pipe
1
!
Purifying Filter
1
@
Sheet
3
The components of = & ~ are included in the package of the outdoor unit.
330
310
(10)10
500
35
50
12
125
(2 pcs for RAC-50FXA )
Plug (Procure locally)
RAF-50PXA/RAC-50FXA
RAF-25PXA/RAC-25FXA RAF-35PXA/RAC-35FXA
RAC-25FXA s RAC-35FXARAC-50FXA
Plug (Procure locally)
7
4
6
5
< S885 : >
1
Hanger
16
7
4
6
5
Minimum pipe length 3m
Minimum pipe length 3m
B
< S818 : A >
9 10
11 12
13 14
10mm
10mm
50mm
25mm
20mm
100mm
10mm
160mm
20mm
100mm
10mm
160mm
L N C D
Cover
RAC-50FX8
L(A)
N(B)
CD
Cover
Earth terminal
RAC-25FX8 RAC-35FX8
AIR REMOVAL
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
Procedures of using vacuum pump for air removal
A
1. Preparation of pipe
Use a pipe cutter to cut the copper pipe and remove burr.
CAUTION
Remove burr and jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
Die
Copper pipe
Die
Trimming tool
Copper pipe
2. Pipe connection
Flare nut
Wrench
Torque wrench
Remove the cap of valve core. Then, connect the charge hose. Remove the cap of valve head. Connect the vacuum pump adapter to the vacuum pump and connect the charge hose to the adapter.
Fully tighter the “Hi” shuttle of the manifold valve and completely unscrew the “Lo” shuttle. Run the vacuum pump for about 10-15 minutes, then completely tighten the “Lo” shuttle and switch off the vacuum pump.
• Loosen the spindle of the service valve with small diameter by 1/4 turn and tighten the spindle immediately after 5 to 6 seconds.
• Remove the charging hose from the service valve.
Completely unscrew the spindle of the service valve (at 2 places) in anticlockwise direction to allow the flow of refrigerant (using Hexagonal Wrench key).
Tighten the cap of valve head. Check the cap’s periphery if there is any gas leakage. The task is then completed.
1
2
3
4
Please use gas leakage detector to check if leakage occurs at connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage.
When the meter reaches -101KPa (-76cmHg) during pumping fully tighten the shuttle.
Meter showing pressure
Closed
R410A Manifold valve
Vacuum pump
Vacuum pump adapter
Valve
Charge hose
Valve
When pumping starts, slightly loosen the flare nut to check of air sucked in. Then tighten the flare nut.
The body of service valve
Cap of valve core
Cap of valve head
Hexagonal wrench key
Cap of valve head
3. Remove of air from the pipe and gas leakage inspection
Gas leakage inspection
Outer diameter Torque N·m
of pipe (ø) (kgf·cm)
Small diameter side 6.35 (1/4") 13.7 – 18.6 (140 – 190)
Large diameter side
9.52 (3/8") 34.3 – 44.1 (350 – 450)
12.7 (1/2") 44.1 – 53.9 (450 – 550)
Valve head cap
Small diameter side 6.35 (1/4") 19.6 – 24.5 (200 – 250)
Large diameter side
9.52 (3/8") 19.6 – 24.5 (200 – 250)
12.7 (1/2") 29.4 – 34.3 (300 – 350)
Valve core cap 12.3 – 15.7 (125 – 160)
CAUTION
In case of removing flare nut of a indoor unit, first remove a nut of small diameter side, or a seal cap of big diameter side will fly out. Free from water into the piping when working.
Be sure to tighten the flare nut to the specfied torque with a torque wrench. If the flare nut is overtightened, the nut may be split after a long period has passed, and may cause a refrigerant leak.
Before flaring, please put on the flare nut.
Please use exclusive tool for refrigerant R410.
Outer diameter (ø) A (mm) Rigid Flaring Tool
For R410A tool For R22 tool
6.35 (1/4") 0 – 0.5 1.0
9.52 (3/8") 0 – 0.5 1.0
12.7 (1/2") 0 – 0.5 1.0
• Please be careful when bending the copper pipe.
• Screw in manually while adjusting the center. After that, use a torque wrench to tighten the connection.
CONNECTION OF POWER CORD
Procedures of wiring
Detail of cutting the connecting cord
Connecting cord
ø1.6 or
ø2.0
Outdoor unitIndoor unit
AC 220–230V
1ø 50Hz
WARNING
THIS APPLIANCE MUST BE EARTHED.
WARNING
The naked part of the wire core should be 10mm fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is tight. Improper insertion may burn the terminal.
Be sure to use only wire specified for the use of air-conditioner.
Please refer to the manual for wire connection and the wiring technique should meet the standard of the electrical installation.
Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the cord band.
Secure the connecting cord along the coated part of the wire using the cord band. Do not exert pressure on the wire as this may cause overheating or fire.
C
Connect the earth cord
Connection of the connecting cord
Securely screw in the connecting cord so that it will not get loose or disconnect.
Tightening torque reference value:
1.2 to 1.6 N·m (12 to 16 kgf·cm)
Excessive tightening may damage the interior of the cord requiring replacement.
D
After remove the screw and cover, and put the connecting cords and fix the cover with screw.
Connecting cord
Wiring of the outdoor unit
Please remove the side cover for wire connection.
WARNING
If you cannot attach the side plate due to the connection cord, please press the connecting cord in the direction to the front panel to fix it.
Be sure that the hooks of the side cover fixed in certainly. Otherwise water leakage may occur and this causes short circuit or faults.
The connecting cord should not touch to service valve and pipes. (It becomes high temperature in heating operation.)
Investigate the power supply capacity and other electrical conditions at the installing location.
Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary electrical work etc.
The electrical work includes the wiring work up the outdoor unit. In localities where electrical conditions are poor, use of a voltage regulation is recommended.
Install outdoor for the room air conditioner within the reaching range of the line cord.
Wire length Wire gauge
up to 6m 1.6mm
2
up to 15m 2.5mm
2
up to 25m 4.0mm
2
Fuse Capacity
16A time delay fuse
IMPORTANT
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire gauge list below for the wiring from house distribution fuse box to the outdoor unit in consideration of the blocked rotor current.
IMPORTANT
When putting two connecting cords through the band.
Screw
Connecting cord
Insulating plate
Indoor unit
Outdoor unit
Green + Yellow (ground)
Connecting cord
C, D
C, DL, N
Green + Yellow
Green + Yellow
Strip wires
Connection of the connection cord
(1) Remove the cover of the electric box. (2) Connect the connecting cords. (3) Assemble the cover of electric box.
Remove the cover from the terminal base and screw the cable.
WARNING
After wiring the indoor unit, make sure to reattach the terminal cover.
Cord band
FINAL STAGE OF INS
TALLATION
1. Operation test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the user’s manual.
If the indoor unit does not operate, check to see that the connections are correct.
Turn on the lamp in the room where the indoor unit is installed and check the remote controller for normal operation.
Insulation and maintenance of pipe connection
The connected terminals should be completed sealed with heat insulator and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown in the figure showing the installation of Indoor and outdoor units. Then fix their position with holders.
To enhance the heat insulation and to prevent water condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
2. Installation of remote controller
The remote controller can be placed in its holder which is fixed on wall or beam.
To operate the remote controller at its holder, please ensure that the unit can receive signal transmitted from the controller at the place where the holder is to be fixed. The unit will beep when signal is received from the remote controller. The signal transmission is weaken by the fluorescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting location of the holder.
Holder for Remote Controller
Remote controller
Screw (2 pieces)
Sleeve of protection pipe
Putty
Putty
OUTSIDE INSIDE
The controller must be hooked onto the hook at the lower part of the holder. Push in the remote controller in the direction as shown in figure below.
CAUTION
Do not operate the unit for more than 5 minutes while the spindle of the service valve is closed.
Using the claws at the top of front cover to remove and install front cover to the cabinet. Too much force on the claws may cause breakage when removing or installing the front cover. Please follow the below procedures for removal and installation of front cover.
CAUTION
Removal and installation of front cover
How to connect the optional parts (RAC Adapter, Weekly Timer Remote Control, Wired Remote Control)
For cable connection to control P.W.B., you need to remove front cover and electrical box cover. Each connecting location is as below.
1 RAC Adapter: CN7 2 Weekly Timer Wired Remote Control: CN9 3 Wired Remote Control: CN9
Please check and confirm manuals attached to each optional parts for more connection details.
You can refer to this installation manual how to remove and re-attach the front cover.
Please be careful not to damage lead wires by edge of plate when connecting the optional parts.
Screw
Cover
Service switch (If the switch is pressed for more than 1 second, the force-cooling operation starts. If the switch is pressed for additional more than 1 second, the operation stops.)
Force-cooling operation
When the service switch of the outdoor unit is pressed for 1 or more seconds, the force-cooling operation starts. Use this mode when performing the failure diagnosis or collecting refrigerant into the outdoor unit.
1 Push the latch at both sides to open the front panel. Pull out the filter and remove 3 screws. 2 Lift up the front panel and latch the claws
firmly at the lower part of rear of the front panel. Then remove 3 screws.
3 Take off 2 screw caps at the lower part of
the horizontal air deflector and remove 2 screws. Then leave the upper louver in open position.
1 Set the upper louver in open position.
2Insert the front cover fixing claws
(4 places) to the insertion groove of the cabinet and put the upper louver through to the front cover frame.
3 Put the horizontal air deflector to the
lower part of front cover frame and insert to the cabinet. After fixed the front cover, fix back all the screws in order.
4 Hold both sides of the lower part of front
cover and pull down towards an oblique direction.
2. Install the front cover
1. Remove the front cover
Latch
Latch
Screw
Screw
Screw
Screw Cap
Upper Louver
Upper Louver
Horizontal Air Deflector
Horizontal Air Deflector
Lower Flame
Front Panel
Front Panel
Front Cover
Front Cover
Front Cover Fixing Claws (4 places)
Front Cover Fixing Claws (4 places)
Claw
Cabinet
Cabinet
Cabinet
Strip wires
Earth terminal
RAC-50FXA
RAC-25FXA RAC-35FXA
Remote Controller
The remote controller must be slide in the remote controller holder, in the direction as shown in the figure, until it hooks at the lower
end of the remote controller holder.
Remote Controller Holder
Screw (2 pieces)
< S885 : A >
< S885 : >
B
Loading...