Hitachi RAS-13CE9, RAC-13CE9 Installation Manual

above 50mm
above 100mm
about 400mm
about 300mm
must not bend
above 100mm
2,300mm or more
1
2
4
5
3
Minimum pipe length 5m
above 200mm
above 700mm
above 200mm
above 50mm when installed on the ceiling of balcony
(
)
above 100mm
above 100mm
give clearance as wide as possible
Plug
6
HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit Outdoor Unit
RAS-13CE9 RAC-13CE9
+ – Screwdriver●Measuring Tape●Knife
Saw●ø 65mm Power Drill●Hexagonal Wrench
Key ( 4mm)
Wrench (14, 17, 19, 22mm)
Gas Leakage Detector●Pipe Cutter
Vinyl Tape●Pliers●Flare Tool
Carefully read through the procedures of proper installation before starting installation work.
The sales agent should inform customers regarding the correct operation of installation.
Tools Needed For Installation Work
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating the unit as described in the user’s guide.
!
!
WARNING
!
CAUTION
!
A circuit breaker should be installed depending on the mounting size of the unit. Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas. The condensing unit may catch fire if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose.
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use wire which is specified for the air conditioner. A short circuit and fire may occur due to the use of low quality wire or improper work.
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock and fire may occur.
Do not mix any coolant other than R-22 into the cooling circulation path when mounting or shifting the unit. If it is mixed with air, the high pressure in the circulation path will rise and this may result in broken copper pipes or faults.
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation).
WARNING
!
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
WARNING
!
The outdoor unit must be mounted at a location which can sup­port heavy weight. Otherwise, noise and vibration will increase.
CAUTION
!
No nearby heat source and no obstruction near the air outlet is allowed.
The clearance distances from top, right and left are specified in figure below.
The location must be convenient for water drainage and pipe connection with the outdoor unit.
To avoid interference from noise please place the unit and its remote controller at least 1m from the radio, television and inverter type fluorescent lamp.
To avoid any error in signal transmission from the remote controller, please put the controller far away from high-frequency machines and high-power wireless systems.
The installation height of indoor unit must be 2.3m or more in a non public area.
CAUTION
!
Do not expose the unit under direct sunshine or rain. Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right and front are specified in figure below. At least three of the above sides must be open air.
Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
Do not install at a location where there is flammable gas, steam, oil and smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connection wire at least 1m away from the antenna or signal line of television, radio or telephone. This is to avoid noise interference.
Do not install outdoor unit facing strong wind direction. It may damage the fan motor.
INDOOR UNIT
Names of Indoor Components
QtyNo. Item
The Length of Indoor Unit
Connecting Cord
Figure showing the Installation of Indoor and Outdoor Unit.
about 1.6m
about
0.9m
OUTDOOR UNIT
Drain hose
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
1
CAUTION
!
The draining of the water container inside the indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on wall which is slightly tilted towards the outdoor side. Drill the wall at a small angle.
Cut the protection pipe according to the wall thickness.
Empty gap in the sleeve of protection pipe should be completely sealed with putty to avoid dripping of rain water into the room.
Procedures of Installation and Precautions
Procedures to fix the hanger.
1.Drill holes on wall. 2. Push plug into the holes. 3. Fix the hanger on wall (As shown below) (As shown below) with 4.1 x 32 screw
(As shown in figure below)
Procedures to fix the holder of remote controller.
1.Drill holes on wall. 2. Push plug into the holes. (As shown below) (As shown below)
Installation of the Indoor Unit
2
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
The upper part of the indoor unit is hanged on the hanger.
The projection at the lower part of the indoor unit is hooked onto the hanger.
Please pull the lower part of the indoor unit outwards to check if the unit is hooked onto the hanger. Improper installation may cause vibration and noise.
!
CAUTION
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown in figure below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap. (This is an easier way to remove the drain cap).
Drain hose
Drain cap
Drain cap
Remove the cap for drain hose installation
Drain cap
Please insert until here
Drain hose
Please insert until here
!
CAUTION
Condensed water may leak out if not inserted properly.
HORIZONTAL & DOWNWARD PIPING – MAKING OPENINGS
During horizontal or downward piping, use a knife to cut openings as shown in figure. Then smoothen the edges of openings with a file.
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fit into the hole on the wall and then ready for further connection.
The terminals of 2 connected pipes must be covered with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
Connect the connecting cord.
After adjustment, fit the connecting cord and pipes into the space available under the indoor unit.
!
CAUTION
The rubber strap used for fixing the insulator should not be tied with great force. Otherwise, this will damage heat insulation and causes water condensation.
Pipe
Rubber strap tied with great force
Insulation pipe (must be wrapped with vinyl tape at every 120mm).
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
!
CAUTION
Please fix in the plastic core after flaring to avoid plastic chips entering the pipes.
below
5mm Please bend at a small radius to form an arc
CAUTION
!
You are free to choose the side (left or right) for the installation of drain hose. Please ensure the smooth flow of condensed water of the indoor unit during installation. (Carelessness may result in water leakage.)
!
CAUTION
Be sure that the drain hose is not loosely connected or bent.
Be sure that the wire is not in contact with any metal in the wall. Please use the protection pipe as wire passing through the hollow part of the wall so as to prevent the possibility of damaged by mouse.
!
CAUTION
Refrigerating pipes and connecting cord must be tied together.
The front part of the refrigerating pipes are at locations marked with
symbol.
Installation of Drain Hose
3
Installation
Hang the indoor unit onto the hanger. Use the temporary stand at the back of the indoor unit to push its lower part 15cm forwards.
Place the drain hose through the hole on the wall.
Insulate the connecting portion of refrigerating pipe with insulator.
Wrap the refrigerating pipes with insulation pipe.
Connect the connecting cord.
After adjustment, the connecting cord and refrigerating pipes are placed into the space available under the cooling unit.
The projection of indoor unit must hook to the hanger.
2~5mm
Protection pipe
Outdoor
Indoor
Seal with putty
Sleeve of protection pipe
WALL
INDOOR UNIT
about 15cm
Projection
Temporary stand
Hook
Openings
FOR SERVICE PERSONNEL ONL Y
The difference in height
between the indoor and outdoor unit should be kept below 5m.
The connecting pipe, no
matter big or small, should all be insulated with insulation pipe and then wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped with tape).
The connection of insulated drain hose.
Please use insulated drain hose for the indoor piping (commercial product).
inner diameter ø 16mm
The indoor piping should be insulated with the enclosed insulation pipe. (If the insulator is insufficient, please use commersial products).
Be sure to completely seal any gap with putty.
Direction of Piping
Dimension of Mounting Stand
of the outdoor unit
(unit : mm)
There are 4 directions allowed, namely, horizontally perpendicular to the unit, vertically down from right, horizontally out from right and horizontally out to left. Don't form the piping downward at the left of the unit.
External dimension of
indoor unit
160mm
160mm
80mm
860mm
40mm
45mm
30mm
Drain Hose
45mm
298mm
Level
Line
Hole for pipe
Mark
Screw for Mounting plate
Please use more than 4 screws.
Mounting Plate
32mm
19mm
Wall
1 Hanger
2 Screw
Plug
Wall
above 50mm
Ceiling
4.1 x 32 Screw
Wall
Remote Control Holder
5 Screw
Plug
3
Connecting cords, pipe and drain hose must be tied together with Vinyl tape.
Hanger
Hook
Refrigerating Pipe
Connecting Cord
Drain Hose
Protection Pipe
Lift the body of the unit upwards and then force it downwards.
Hanger
Projection
Pipe
Connecting cord
Drain hose
Pipe
Insulation pipe
0.70m
Bending upwards
Condensed water pond
Ditch
Condensed water pond
20
Cut away shaded portion, and finish the edge of the opening so that there is no burr.
Connection
Horizontally perpendicular to the unit
Connected section
Connecting cord
Drain hose
Protection
pipe
Refrigerating pipes
Connecting cord
Heat insulation pipe
Pull this to the front during the connection of refrigerating pipes to ease task.
<
I699: A
>
Pipe support
Pull up the pipe after bending downward
Transform the piping while holding down the lower portion of pipe-support by hand.
Hanger
1
Screw for holder of Remote Controller
(3.1x16)
AAA Size Battery
Screw for Hanger
Holder for Remote Controller
(4.1x32)
Remote Controller
Purifying Filter
6
1
2
2
1
1
57
12 35
120
500
320
10
35
(10)
340
mounting stand
!
CAUTION
The installation height
of indoor unit must be
2.3m or more in a non public area.
1
2
3
4
5
6
7
!
CAUTION
In case the pipe length is more than 8m, add refrigerant R22 at 20 grams per every meter exceeds. However, pipe length shall not exceed 15m.
RAS-13CE9/RAC-13CE9 (1) EN 24/3/05, 12:56 PM1
OUTDOOR UNIT
Please mount the outdoor unit on stable ground to prevent vibration and increase of noise level.
Decide the location for piping after sorting out the different types of pipe available.
Open the side plate by unscrewing the screws as shown below.
Removal Of Air From The Pipe And Gas Leakage Inspection
Gas Leakage Inspection
Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage.
FINAL ST AGE OF INST ALLA TION
Insulation And Maintenance Of Pipe Connection
1
The connected terminals should be completed sealed with heat insulator and then tied up with rubber strap.
Please tie the pipe and power line together with vinyl tape as shown in the figure showing the installation of indoor and outdoor units. Then fix their position with holders.
To enchance the heat insulation and to prevent water condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
Installation Of Remote Controller
2
Power Source And Operation Test
3
The remote controller can be placed in its holder which is fixed on wall or beam.
To operate the remote controller at its holder, please ensure that the unit can receive signal transmitted from the controller at the place where the holder is to be fixed. The unit will beep when signal is received from the remote controller. The signal transmission is weaken by the florescent light. Therefore, during the installation of the remote control holder, please switch on the light, even during day time, to determine the mounting location of the holder.
Power Source
CAUTION
!
Please use a new socket. Accident may occur due to the use of old socket because of poor contact.
Please plug in and then remove the plug for 2 – 3 times. This is to ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
Operation Test
Please ensure that the air conditioner is in normal operating condition during the operation test.
Explain to your customer the proper operation procedures as described in the user’s manual.
Insulation material for pipe connection
Sleeve of protection pipe
Putty
<
I699: A
>
The controller must be hooked onto the hook at the lower part of the holder. Push in the remote controller in the direction as shown in figure below.
3
Procedures of using Vacuum Pump for Air Removal
As shown in figure on the right, remove the cap of valve head and valve core and then connect them to the vacuum pump and manifold valve.
Fully tighten the Hi shuttle of the manifold valve and completely unscrew the Lo shuttle. Run the vacuum pump for about 10–15 minutes, then completely tighten the “Lo” shuttle and switch off the vacuum pump.
2
Completely unscrew the spindle of the service valve (at 2 places) in anti­clockwise direction to allow the flow of coolant (using Hexagonal Wrench key).
3
Remove the Charge hose and tighten the cap of valve head. The task is then completed.
4
1
Preparation of Pipe
1
Use a pipe cutter to cut the copper pipe.
Jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
Before flaring, please put on the flare nut.
Pipe Connection
2
INSTALLA TION OF REFRIGERA TING PIPES AND AIR REMO VAL
CAUTION
!
Outer
diameter
of pipe
6.35 (1/4")
12.7 (1/2")
Valve head cap
Valve core cap
Torque N.m
(kgf
cm)
13.7 – 18.6 (140 – 190)
44.1 – 53.8 (450 – 550)
19.6 – 24.5 (200 – 250)
12.3 – 15.7 (125 – 160)
Copper pipe
Trimming tool
Outer
Diameter (ø)
6.35 (1/4")
12.7 (1/2")
Imperial flaring tool
0.8 – 1.5
1.0 – 2.0
Rigid flaring tool
0 – 0.5
0 – 1.0
A (mm)
Small diameter
side
Big diameter
side
AIR REMOVAL
Remote
Controller
Holder for Remote Controller
Screw (2 pieces)
WARNING
You may not be able to close the side cover due to the connecting cord, under such situation, please press against the wall of side cover to fix it.
Be sure that the hooks (2 places) are plugged in. Otherwise, water leakage may occur and this causes short circuit or faults.
The naked part of the wire core should be 10 mm and the insulated part of the wire must be push into the terminal for 3 – 4 mm. Then try to pull the individual wire to check if the contact is tight. Improper insertion may burn the terminal.
Be sure to use only wire specified for the use of air-conditioner.
Please refer to the installation manual for wire connection and the wiring technique should meet the standards of electrical installation.
How to Remove the Front Cover
Open the cover and remove the screw.
After open the front panel, remove the screw and open the cover , disconnect the wire connector .
Remove the filter, release the axis by pulling the center portion of front cover in the direction of arrow .
Push vertical air deflector handle to the right or left side.
After raise the front cover from bottom side as , release the front cover by pull the right or left sides as .
How to Install the Front Cover
Insert the two hooks at the upper side certainly.
Open Front Panel, push the center down in the direction of the arrow to insert the axis at the center of the front cover into the hook at the outlet frame.
Connect the wire connetor , fixed the screw and cover
and .
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must be completed. To make the proper wiring capacity, use the wire gauges list below for the lead-in from a pole transformer and for the wiring from a switch board of fuse box to the outlet in consideration of the locked rotor current.
Investigate the power supply capacity and other electrical conditions at the installation location. Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary electrical work etc. The electrical work includes the wiring work up the outlet. In localities where electrical conditions are poor, use of a voltage regulation is recommended.
USE 15A time delay FUSE IMPORTANT
Wire length
up to 16m up to 10m up to 15m up to 25m up to 42m
Wire gauge
1.6mm (B.S. 14)
2.0mm (B.S. 12)
2.6mm (B.S. 10)
3.2mm (B.S. 18) 14mm
2
(B.S. 16)
IMPORTANT
THIS APPLIANCE MUST BE EARTHED.
Procedures of Wiring
Connect the electrical wiring between the indoor and outdoor unit as shown in below Fig. Never connect the wiring by mistake.
The connection cord must be fixed by the band which is located on the electrical box.
Wiring Of The Outdoor Unit
Please remove the side cover for wire connection.
!
WARNING
!
CONNECTION OF POWER CORD
A
Die
Die
Copper pipe
Wrench
Torque wrench
Flare nut
Lo
Hi
Meter showing pressure
Manifold valve
Vacuum pump
Charge hose
When pumping starts, slightly loosen the flare nut to check of air sucked in. Then tighten the flare nut.
When the meter reaches –101KPa (–76cmHg) during pumping, fully tighten the shuttle.
The body of service valve
Cap of
valve core Hexagonal Wrench Key
Cap of valve head
Cap of valve head
CAUTION
!
In case of removing Flare nut of a cooling unit, first remove a nut of small diameter side, or else seal cap of big diameter side will fly out.
Please be careful when bending the copper pipe.
Applied frozen grease to the connection points and then screw in manually. After that, use a torque wrench to tighten the connection.
WARNING
!
Power supply shall be connected at the rated voltage, otherwise the unit will be broken or could not reach the specified capacity.
Detail of cutting the connecting cord
To remove the connecting wires for the indoor unit, please remove the low cover panel in front of the unit.
A
B
A
B
(L) Brown
(N) Blue
Terminal Board
Line Cord
Terminal Board
Green & Yellow
Green &
Yellow
Outdoor UnitIndoor Unit
Indoor
Unit
Outdoor
Unit
GRN + YEL
10mm
30mm
30mm
10mm
GRN + YEL
70mm
35mm
10mm
Please face this side (suction side) of the unit to the wall.
Please remove side cover when connecting the piping and connecting cord.
Pull downward
Connect the earth cord
After remove the screw and band, put the connecting cords and fix the band with screw.
Earth terminal
B
A
AB
Wiring Of The Indoor Unit
For wire connection of the Indoor unit, you need to remove front panel and electrical cover. Method to remove front panel
Refer to How to Remove The Front Cover”.
Method to remove electrical cover
Remove the screw and electrical cover.
Insert the connecting cord (A, B) from the bottom of unit.
Fixed the wire to terminal wires firmly as shown in figure at right side.
AUTO RESTART SWITCH
Electrical cover
Screw
CAUTION
!
Please make sure to remove all spacers inside the unit.
Open the Top, Back and Side cover of the unit.
Pull out the spacers inside. (Spacers are only for transportation purpose). If not remove, vibration and noise will occur.
Top cover
Back cover
Side cover
1
6 7
2
3
4
5
7
1 6
1
2
1
3
4
Screw
Cover
Front panel
Front Cover
Vertical Air Deflector Handle
Screw
7
6
5
5
1
1
2
2
RAS-13CE9/RAC-13CE9 (2) EN 24/3/05, 2:04 PM1