Hitachi L100 IP Instruction Manual

HITACHI
Series Inverter
Instruction Manual
Three-phase input 400V class
After reading this manual, keep it handy for future reference
Manual Number: NUL100IPV6
MADE IN SLOVENIA
P
lease read this manual carefully before you install and operate an L100IP series inverter and observe all of
the instructions given in there. This manual may also serve as a reference guide und therefore should always be kept at hand.
Symbols used
There are several safety instructions in this manual which are marked with a special hazard alert symbol (flash or exclamation mark in the center of a triangle). Additionally, either the word CAUTION or WARNING is added following the triangle with the exclamation mark.
This symbol means hazardous high voltage. It is used to call your attention to items or operations that could be dangerous to your or other persons life. Please read the safety message carefully and follow all the instructions given.
This symbol is used to call your attention to situations which are potentially dangerous to persons. Please read the safety message carefully and follow all the instructions given.
The safety messages given following this symbol are further divided into two categories:
WARNING This message indicates a situation which may lead to serious injury or even
death if the instruction is not observed.
CAUTION This message indicates a situation which may lead to minor or moderate
injury, or damage of product.
HAZARDOUS HIGH VOLTAGE
Motor control equipment or electronic controllers are connected to hazardous line
voltages. When servicing drives and electronic controllers there migh exist exposed components with cases or protrusions at or above line potential. Extreme care should
be taken to protect against shock. For these reasons, the following safety guidelines should be observed: Stand on an insulating pad and make it a habit to use only one hand when checking
components. Disconnect power before checking controllers or performing
maintenance. Be sure that equipment is grounded properly. Wear safety glasses
whenever working on an electronic controller or rotating electrical equipment.
WARNING This equipment should be installed, adjusted and serviced only by qualified electrical
maintenace personnel familiar with the construction and operation of the equipment
and the hazards involved. Failure to observe this precaution could result in bodily
injury.
WARNING The user is responsible that all driven machinery, drive train mechanism not supplied
by Hitachi, Ltd., and process line material are capable of safe operation at an applied
frequency of 150% of the maximum selected frequency range to the AC motor. Failure
to do so can result in destruction of equipment and injury to personnel should a single
point failure occur.
WARNING HAZARD OF ELECTRICAL SHOCK. DISCONNECT INCOMING POWER
BEFORE WORKING ON THIS CONTROL.
WARNING SEPARATE MOTOR OVERLOAD AND OVERCURRENT PROTECTION
DEVICES ARE REQUIRED TO BE PROVIDED IN ACCORDANCE WITH THE
SAFETY CODES REQUIRED BY JURISDICTIONAL AUTHORITIES.
CAUTION These instructions should be read and clearly understood before working on L100IP
series equipment.
CAUTION Proper grounds, disconnecting devices (e.g. fuses) and other safety devices and their
location are the responsibility of the user and are not provided by Hitachi, Ltd.
CAUTION DANGEROUS VOLTAGE EXISTS UNTIL THE POWER LIGHT ON THE
DIGITAL OPERATOR IS OFF.
CAUTION Rotating shafts and electrical potentials above ground level can be hazardous.
Therefore it is strongly recommended that all electrical work conform to the national
electrical codes and local regulations. Installation, maintenance and alignment should
be performed by qualified personnell only.
Factory recommended test procedures included in this instruction manual should be
followed. Always disconnect electrical power before working on the unit.
WARNING a) Any motor used must be of suitable rating.
b) Motors may have hazardous moving parts so that suitable protection must be
provided in order to avoid injury.
CAUTION Alarm connections may have hazardous live voltages even when the inverter is
disconnected. In case of removing the front cover for maintenance or inspection,
confirm that incoming power for alarm connections is surely disconnected.
CAUTION Main terminals or other hazardous terminals for any interconnection (terminals for
connecting the motor, contact breaker, filter etc.) must be inaccessible in end
installation.
CAUTION If the unit is used in a manner not specified by the manufacturer the protection
provided by the unit may be impaired..
All of the above instructions, together with any other requirements, reccommendations,
and safety messages highlighted in this manual must be strictly complied with for continued LVD
compliance.
NOTES ON EMC (ELECTRO MAGNETICAL COMPATIBILITY)
WARNING This equipment should be installed, adjusted and serviced by qualified personnel
familiar with construction and operation of the equipment and the hazards
involved. Failure to observe this precaution could result in bodily injury.
When using L100IP series inverters in EU countries, the EMC directive 89/336/EEC must be observed. To satisfy the EMC directive and to comply with the standard, the following provisions should be obeyed:
A) Environmental conditions for the inverter:
Ambient temperature: -10°C to 40°C.
Relative Humidity: 20% to 90% (no dew condensation)
Vibrations: max. 5,9m/s
2
(0.6 g) at 10–55Hz.
Location: 1000 meter or less altitude, indoors (no corrosive gas or dust).
B) The power supply to the L100IP inverter must conform to the conditions stated below. If one of the
conditions mentioned is not satisfied then an appropriate L100IP AC reactor will have to be installed.
Voltage fluctuation +/-10% or less
Voltage unbalance +/-3% or less
Frequency variation +/-4% or less
C) Wiring
Shielded wiring (screened cable) is required for motor wiring, and total length has to be kept to less
than 50m. When using motor cables longer than 50m L100IP motor filters should be installed. Directions for installing filters can be found in the L100IP installation manual.
The carrier frequency setting must be less than 5 kHz to satisfy EMC requirements.
Separate the mains circuit wiring from the wiring used for signals or process circuit. Please refer to
the L100IP installation manual.
D) Installation
For L100IP series inverters, the filters described hereafter have to be used and the installation notes
have to be observed.
If installed according to the following directions, the frequency inverters comply with the following standards: Emmissions: EN 61800-3 (EN 55011 group 1, class B) Immunity: EN 61800-3, industrial environments
For the best possible damping of interference, special line filters have been developed which guarantee you easy assembly and installation along with the necessary electrical reliability. However, effective EMC is only ensured if the suitable filter is selected for the particular drive and installed in accordance with these EMC recommendations. Please order the appropriate filter when ordering L100IP inverter.
Note: All filters are designed for 50Hz/60Hz +/-5%.
The amount of line-conducted interference also increases as motor cable length increases. Adherence to the interference limits for line-conducted interference is guaranteed on following way:
If maximum motor cable length is 10 m at maximum elementary frequency:
Class „B“.
If maximum motor cable length is 20 m at elementary frequency 5 kHz:
Class „B“.
If maximum motor cable length is 50 m at maximum elementary frequency:
Class „A“.
Observe the following provisions for an electromagnetically compatible setup of your drive system:
1. As user you must ensure that the HF impedance between frequency inverter, filter and ground is as small as possible.
See to it that the connections are metallic and have the largest possible areas (zink-plated mounting
plates)
2. Conductor loops act like antennas, especially when they encompass large areas. Consequently:
Avoid unnecessary conductor loops
Avoid parallel arrangement of „clean“ and interference-prone conductors
3. Lay the motor cable and all analog and digital contol lines shielded.
You should allow the effective shield area of these lines to remain as large as possible; i.e., do not
move the shield further away than absolutely necessary.
With compact systems, if for example the frequency inverter is communicating with the steering unit,
in the same control cabinet connected at the same PE-potential, the screen of control lines should be put on, on both sides with PE. With branch systems, if for example the communicating steering unit is not in the same control cabinet and there is a distance between the systems, we recommend to put on the screen of control lines only on the side of the frequency inverter. If it is possible, direct in the cable entry section of the steering unit. The screen of motor cables always must be put on, on both sides with PE.
The large area contact between shield and PE-potential you can realise with a metal PG screw
connection or a metallic mounting clip.
Use only copper mesh cable (CY) with 85% coverage
The shielding should not be interrupted at any point in the cable. If the use of reactors, contactors,
terminals or safety switches in the motor output is necessary, the unshielded section should be kept as small as possible.
Some motors have a rubber gasket between terminal box and motor housing. Very often, the terminal
boxes, and particularly the threads for the metal PG screw connections, are painted. Make sure there is always a good metallic connection between the shielding of the motor cable, the metal PG screw connection, the terminal box and the motor housing, and carefully remove this paint if necessary.
4. Very frequently, interference is coupled in through installation cables. This influence you can minimize:
Lay interfering cables separately, a minimum of 0.25 m from cables susceptible to interference.
A particularly critical point is laying cables parallel over larger distances. If two cables intersect, the
interference is smallest if they intersect at an angle of 90°. Cables susceptible to interference should therefore only intersect motor cables, intermediate circuit cables, or the wiring of a rheostat at right angles and never be laid parallel to them over larger distances.
5. The distance between an interference source and an interference sink (interference-threatened device) essentially determines the effects of the emitted interference on the interference sink.
You should use only interference-free devices and maintain a minimum distance of 0.25 m from the
drive.
6. Safety measures
Ensure that the protective conductor terminal (PE) of the filter is properly connected with the protective
conductor terminal of the frequency inverter. An HF ground connection via metal contact between the housings of the filter and the frequency inverter, or solely via cable shield, is not permitted as protective conductor connection. The filter must be solidly and permanently connected with the ground potential so as to preclude the danger of electric shock upon touching the filter if a fault occurs. You can achieve this by connecting it with a grounding conductor of at least 10 mm² or connecting a second grounding conductor, connected with a separate grounding terminal, parallel to the protective conductor (the cross section of each single protective conductor terminal must be designed for the required nominal load).
Revision history table:
Revision contents Date of issue Manual no.
1 2 3
CONTENTS
CHAPTER 1 – SAFETY PRECAUTIONS
I
NSTALLATION ...................................................................................................................................1-1
WIRING..............................................................................................................................................1-1
C
ONTROL AND OPERATION ................................................................................................................1-2
M
AINTENANCE AND INSPECTION .......................................................................................................1-3
O
THERS .............................................................................................................................................1-3
CHAPTER 2 – INSPECTION UPON UNPACKING .....................................................................2-1
CHAPTER 3 – APPEARANCE AND NAMES OF PARTS...........................................................3-1
CHAPTER 4 – INSTALLATION .....................................................................................................4-1
CHAPTER 5 – WIRING
W
IRING THE POWER SUPPLY AND MOTOR..........................................................................................5-1
W
IRING THE CONTROL TERMINALS....................................................................................................5-2
G
ENERAL REMARKS...........................................................................................................................5-3
W
IRING EQUIPMENT AND OPTIONS ....................................................................................................5-5
TERMINALS........................................................................................................................................5-6
CHAPTER 6 – GENERAL OPERATION NOTES
B
EFORE STARTING OPERATION..........................................................................................................6-1
T
EST RUN...........................................................................................................................................6-1
CHAPTER 7 – CONTROL CIRCUIT TERMINAL FUNCTIONS
O
VERVIEW.........................................................................................................................................7-1
FM
TERMINAL ...................................................................................................................................7-3
T
ERMINALS 1 - 5 (PROGRAMMABLE DIGITAL INPUTS)
General notes ................................................................................................................................7-4
FW: Start/stop forward run...........................................................................................................7-5
RV: Start/stop reverse run.............................................................................................................7-5
CF1 – CF4: Multistage speed settings..........................................................................................7-6
AT: Analog set value using current 4-20mA .................................................................................7-7
2CH: Second stage acceleration/deceleration..............................................................................7-7
FRS: Free run stop........................................................................................................................7-8
EXT: External trip.........................................................................................................................7-8
USP: Prevention of restart upon power recovery.........................................................................7-9
RS: Reset .....................................................................................................................................7-10
JG: Jogging run ..........................................................................................................................7-11
PTC: Thermistor input ................................................................................................................7-12
SFT: Software lock......................................................................................................................7-12
T
ERMINALS 11, 12 (PROGRAMMABLE DIGITAL OUTPUTS)
General notes ..............................................................................................................................7-13
FA1, FA2: Frequency arrival signals .........................................................................................7-14
RUN: Motor running...................................................................................................................7-14
OL: Overload signal....................................................................................................................7-15
OD: PID deviation ......................................................................................................................7-15
AL: Alarm signal .........................................................................................................................7-16
T
ERMINALS AL0, AL1, AL2 (ALARM RELAY).................................................................................7-17
CHAPTER 8 – USING THE DIGITAL OPERATOR
THE DIGITAL OPERATOR CONTROL PANEL .........................................................................................8-1
O
PERATING PROCEDURE EXAMPLE....................................................................................................8-1
D
IGITAL OPERATOR KEYS..................................................................................................................8-2
OVERVIEW OF PARAMETER SETTINGS
Display functions...........................................................................................................................8-3
Basic functions ..............................................................................................................................8-4
Extended functions of group A ......................................................................................................8-4
Extended functions of group B ....................................................................................................8-10
Extended functions of group C ....................................................................................................8-13
CHAPTER 9 – MESSAGES
T
RIP MESSAGES .................................................................................................................................9-1
O
THER MESSAGES..............................................................................................................................9-2
CHAPTER 10 – TROUBLE SHOOTING...................................................................................... 10-1
CHAPTER 11 – TECHNICAL SPECIFICATIONS ..................................................................... 11-1
CHAPTER 12 – WIRING EXAMPLES
S
ET VALUE SUPPLIED BY EXTERNAL POTENTIOMETER ....................................................................12-1
I
NVERTER OPERATION USING ANALOG SET VALUE ..........................................................................12-2
I
NVERTER OPERATION USING FIXED SET VALUES ............................................................................ 12-3
CHAPTER 13 – THE OPTIONAL REMOTE OPERATORS
C
ONNECTION OF THE REMOTE OPERATOR .......................................................................................13-1
T
HE MONITOR MODE........................................................................................................................13-2
THE FUNCTION MODE ......................................................................................................................13-3
P
ROTECTIVE FUNCTIONS..................................................................................................................13-6
D
IMENSIONS OF ACCESSORIES.........................................................................................................13-7
U
SING THE COPY UNIT .....................................................................................................................13-8
CHAPTER 14 – SERVICE AND WARRANTY............................................................................ 14-1
APPENDIX A – PRINTED FORM FOR USER DEFINED PARAMETER SETTINGS ..........A-1
APPENDIX B – PRINTED FORM FOR USER DEFINED PARAMETER SETTINGS
(REMOTE OPERATOR) ................................................................................................................. B-1
APPENDIX C – INITIALIZING THE INVERTER ......................................................................C-1
APPENDIX D – PERIODICAL MAINTENANCE ........................................................................ D-1
Chapter 1 – Safety precautions
1-1
Chapter 1 – Safety precautions
Installation
The following safety precautions are to be observed when installing the frequency inverter:
CAUTION Be sure to install the inverter on flame resistant material such as metal. Otherwise,
there is a danger of fire.
CAUTION Be shure not to place anything inflammable in the vicinity. Otherwise, there is a
danger of fire.
CAUTION Be sure not to let foreign matter (such as cut wire refuse, spatter from welding, iron
refuse, wires, dust etc.) enter the inverter. Otherwise, there is a danger of fire.
CAUTION Install the inverter in a room which is not exposed to direct sunlight and is well
ventilated. Avoid environments which tend to be high in temperature, high in humidity or which have dew condensation, as well as places with dust, corrosive gas, explosive or inflammable gas, grinding-fluid mist, salt damage etc. Otherwise, there is a danger of fire.
CAUTION The wall surface on which the inverter is mounted must be of a nonflammable
material, such as a steel plate.
Wiring
WARNING The inverter has to be grounded properly. Otherwise, there is a danger of fire.
WARNING Wiring work must only be carried out when the power supply is off. Otherwise,
there is a danger of electric shock and/or fire.
WARNING Before carrying out the wiring work, the inverter has to be mounted properly.
Otherwise, there is a danger of electric shock or injury.
CAUTION Make shure that the input voltage is as follows (please also refer to chapter 11): Single/three phase: 200~240V, 50/60Hz (models up to 2,2kW) Three phase: 380~460V, 50/60Hz
CAUTION Don´t connect AC power supply to the inverter output terminals U, V, and W or fan
supply terminals F, F. Otherwise, there is a danger of injury and/or fire.
INPUTS
(L1) (N)
L1 L2 L3
OUTPUTS
U V W
Note)
Power su
pply
Note) Terminals L1, N: single phase power supply
Terminals L1, L2, L3: three phase power supply
Not allowed
F F
CAUTION Remarks for using earth leakage circuit breakers in the mains supply:
Frequency inverters with CE-filters (RFI-filter) and screened motor cables have a
higher leakage current against earth. Especially in the moment of switching this can cause unintentional triggering of earth leakage circuit breakers. Because of the rectifier
Chapter 1 – Safety precautions
1-2
on the input side of the inverter there is the possibility to stall the switch-off function through amounts of DC current. For these reasons, the following items should be observed:
Only pulse current sensitive earth leakage circuit breakers which have a short term
delay and a higher trigger current (500mA) should be used. Other components should be secured with separate earth leakage circuit breakers. Earth leakage circuit breakers in front of an inverter´s rectifier are not an absolute protection against direct touching.
CAUTION Each phase of the power supply has to be provided with a fuse. Otherwise, there is a
danger of fire.
Control and operation
WARNING Be sure to turn on the input power supply only after closing the front case. While
being energized, don´t open the front case. Otherwise, there is a danger of electric shock.
WARNING Never operate the switches with wet hands. Otherwise, there is a danger of electric
shock.
WARNING If the retry mode is selected, the inverter may suddenly restart during a stop which
was caused by a trip. In such a case, be sure not to approach the machine. Provisions have to be taken that the driven motor or machine does not endanger personnell even in the case of a sudden restart. Otherwise, there is a danger of injury.
WARNING Even if the power supply is cut off for a short period of time, the inverter may restart
operation after the power supply has recovered if the operation command is given. If this may incur danger to personnell, provisions have to be made in order to prevent a restart after power recovery. Otherwise, there is a danger of injury.
WARNING The STOP key is effective only if the corresponding parameters have been set.
Otherwise, there is a danger of injury.
WARNING If a reset is carried out following a trip condition the motor will restart if the
operation command has been given. Be sure to acknowledge this trip condition with a reset only after confirming that no operation command is active. Otherwise, there is a danger of injury.
WARNING When the power to the inverter is turned on while the operation command is active
the motor starts immediately. So before turning power supply on be sure to confirm that no operation command is active.
WARNING If the inverter has been configured for the stop command not to be given using the
STOP key, pressing the STOP key does not stop the motor. In this case a separate emergency stop switch is necessary.
CAUTION Operate the motor and machine connected to the inverter only within the
manufacturer´s speed specifications. Otherwise, there is a danger of injury.
CAUTION If a motor is to be operated at a frequency higher than the standard setting value of
50 or 60Hz, be sure to check the allowable speed of the motor and the machine with each manufacturer, and operate them only after getting their consent.
CAUTION Check the following during and after the test run. Otherwise, there is a danger of
machine breakage:
Was the short cut bar between terminals +1 and + removed by mistake?
Was the running direction of the motor correct?
Was the inverter tripped during acceleration or deceleration?
Were the indications of the rpm and the frequency meter correct?
Were there any abnormal motor vibrations or noise?
Chapter 1 – Safety precautions
1-3
Maintenance and inspection
WARNING Before carrying out maintenance and inspection wait for at least five minutes after
having turned off the input power supply. Otherwise, there is a danger of electric shock.
WARNING When removing connectors (e.g. from fans and printed circuit boards) never pull the
attached wires. Otherwise, there is a danger of fire due to wire breakage and/or injury.
Others
CAUTION Withstand voltage tests and insulation resistance tests (megger tests) are executed
before the units are shipped, so that there is no need to conduct these tests before operation.
CAUTION Do not attach or remove wiring or connectors when power is applied. Also, do not
check signals (e.g. using a multimeter) during operation.
CAUTION Never stop motor operation by switching off the electromagnetic contactors on the
primary or secondary side of the inverter.
Motor
Inverte
r
Earth leakage
circuit breaker
L1(L1) L2 L3(N)
T1(U) T2(V)
T3(W)
Powe
r
supply
S2
FW
P24
CORRECT: Start and stop using FW terminal
S1
WRONG: Start and stop using
secondary side contactor
WRONG: Start and stop using
primary side contactor
When there has been an instantaneous power failure, and if an operation instruction
has been given, then the inverter may restart operation after the power failure has ended. If there is a possibibility that such an occurrence may harm humans, then install an electromagnetic contactor on the primary (power supply) side of the inverter, so that the circuit does not allow automatic restarting after the power supply has recoverd. If the optional remote operator is used and the retry function has been selected, this will also cause automatic restarting when an operation instruction has been input, so please be careful.
CAUTION Do not insert leading power factor capacitors or surge absorbers between the output
terminals of the inverter and the motor.
Motor
Inverte
r
Earth leakage
circuit breaker
L1(L1) L2 L3(N)
T1(U) T2(V)
T3(W)
Powe
r
supply
WRONG: Capacitor
WRONG:
Surge absorber
CAUTION Be sure to ground the grounding terminal properly.
CAUTION Before inspecting the unit wait at least five minutes before opening the inverter .
CAUTION PROTECTION AGAINST NOISE INTERFERENCE FROM THE INVERTER
L100IP series inverters use many semiconductor switching elements such as
transistors and IGBTs. For this reason, a radio set or measuring instrument located near the inverter is susceptible to noise interference. To protect the instruments from erreneous operation due to noise interference produced by the inverter, they should be
Chapter 1 – Safety precautions
1-4
installed well apart from the inverter. It is also effective to shield the whole inverter structure (refer to figure below, left part).
Motor
Inverte
r
L1(L1)
L2
L3(N)
T1(U)
T2(V)
T3(W)
R2
S2
T2
Power
supply
R1
S1
T1
EMI filter +
Grounding
Inverter
EMI
filter
Motor
Power
supply
Noise
Noise
Grounded
frame
Completely ground the frame
with as short a wire as possible.
Grounded piping
or shielded wire
Added EMI filter on the input side of the inverter also reduces the effect of noise from
commercial power lines on external devices (refer to figure above).
CAUTION EFFECTS OF DISTRIBUTER LINES ON INVERTERS
In the cases mentioned below involving a general purpose inverter, a large peak
current flows on the power supply side, sometimes destroying the converter module: A) The unbalance factor of the power supply is 3% or higher. B) The power supply capacity is set at least ten times greater than the inverter
capacity (i.e. 500kVA or more)
C) When abrupt power supply changes are to be expected. Some examples:
1) Several inverters are interconnected using a short bus to the same power
supply.
2) A thyristor converter and an inverter are interconnected using a short bus.
3) An installed power factor compensating device is connected or disconnected.
In the cases mentioned above we recommend installing an AC reactor of 3% voltage drop at rated current with respect to the supply voltage on the power supply side.
CAUTION When an EEPROM error occurs (trip E 08) all parameter values have to be checked
for correctness (especially the RS input).
CAUTION When the intelligent digital inputs FW or RV are configured as normally closed
contact (standard setting is normally open), then the inverter starts automatically. Do not configure these inputs as normally closed inputs unless absolutely necessary.
CAUTION Factory setting of the carrier frequency is different for diferent types of the inverter.
This setting is at the same time also highest allowable carrier frequency without derating output power. See bottom of the terminal cover for reference.
GENERAL NOTICE
In all the illustrations and figures in this manual, covers and safety devices are
occasionally omitted in order to better describe the details. When the inverter is operated make shure that all the covers and safety devices are placed in their correct positions.
Chapter 2 – Inspection upon unpacking
2-1
Chapter 2 – Inspection upon unpacking
Please check the shipment by the time of delivery for damages and completeness. Check that the inverter and the accompanying instruction manual has been provided. Using the specification label attached to the side of inverter make sure that the inverter model delivered is the one you ordered.
The specifications included on the specification label are described below:
Model : L100IP – 007NFE 510
kW/HP: 0.75 / 1
Input : 50,60Hz 200-240V 1 Ph 9.0A
Hitachi Industrial Equipemnt Systems Co,. Ltd.
MADE IN SLOVENIA
Output : 1-360Hz 200-240V 3 Ph 4.0A
Serial No. : 030300067 Date: 0403
HITACHI
Model designation:
(example for L100IP-007NFE 510)
Applicable motor capacity
(example: 0.75kW/1HP)
Inverter input specifications:
Frequency, voltage, numbe r of phases, current
Inverte r outp ut specifications :
Frequency, voltage, rated current
Manufac turing number,
date (example: April 2003)
8310793 298046
030300067
EAN code
www.hitachi-ds.com (Hitachi Europe GmbH)
In the illustration below, the contents of the model designation used for L100 series inverters is explained:
L100IP - 007 H F E 5
Inverter series
Distribution for (E: Europa U: USA)
Type of inverter (F: with digital operator)
Input voltage (N: 200V single phase) (H: 400V three phase)
Motor capacit
y
004: 0.40kW 040: 4.00kW 007: 0.75kW 055: 5.50kW 015: 1.50kW 075: 7.50kW 022: 2.20kW
1
0
Option
Input side 1: EMI filter 2: AC reactor 3: EMI filter & AC reactor
Protection class 0: IP00 5: IP54 2: IP20 6: IP65
Chapter 2 – Inspection upon unpacking
2-2
Chapter 3 – Appearance and names of parts
3-1
Chapter 3 – Appearance and names of parts
Terminal cover revealed:
Specification label
Terminal cover
Digital operator
Casing – plastic part
Casing – metal part
Fan inside (air inlet)
Cable glands
Grounding terminal (PE)
Mains circuit terminals
Fan cable
Control terminals
Serial interface
Alarm terminals
Chapter 3 – Appearance and names of parts
3-2
Chapter 4 – Installation
4-1
Chapter 4 – Installation
Explanation of IP54 protection provided by enclosure
Generally, the enclosure must provide sufficient protection for persons who use them and for equipment itself. IP54 enclosure provides protection to some extent and it is not foreseen for very severe environmental conditions. Here is the explanation of the two digits:
Protection of persons against access to hazardous parts inside the enclosure indicated by the first characteristic numeral 5:
Protected against access to hazardous parts with wire.
Protection of the equipment inside the enclosure against ingress of solid foreign objects indicated by the first characteristic numeral 5:
Dust-protected: Ingress of dust is not totally prevented, but dust shall not penetrate in a quantity to interfere with satisfactory operation of the apparatus or to impair safety.
The inverter shall not be exposed to severe environmental conditions for more than 8 h (test condition).
Protection of the equipment inside the enclosure against harmful effects due to the ingress of water indicated by the second characteristic numeral 4:
Protected against splashing water: Water splashed against the enclosure from any direction shall have no harmful effects.
The inverter shall not be exposed to splashing water for more than 10 minutes (test condition).
The unit is not intended for outdoor usage.
Other than in the time specified above, inverter must be operated in the condition of 90% humidity or less.
WARNING the above explanation is intended as an indication. Refer always to the a.m.
standard in the case of any doubt.
Chapter 4 – Installation
4-2
The inverter must be mounted vertically on a non-flammable wall in order to prevent from overheating and fire. The minimum clearances to the surrounding walls shown in the figure below must be complied with to ensure a good ventilation. Foreign matter (especially conductive objects) must nut be dropped into the inverter since they not only cause malfunction and damage but may also lead to electrical and fire hazards.
Cover all ventilation holes on the inverter during installation so that no foreign objects can enter the inverter. Be sure to remove those covers from the inverter before you put the inverter to work.
approx. 10cm
approx. 1c
m
approx.
1cm
Inverter
Air flow
The inverter must be installed vertically
(do not install it on the floor or horizontally)
Wall or mounting surface
The mounting base must be a non-
flammable material (e.g. metal)
approx. 10cm
The minimum clearances to the surrounding walls shown in the figure are only meant for reference. A more compact installation (back to back or side by side) may well be possible and should be discussed with Hitachi. Please always leave enough room for the teminal cover to be opened without problems in order to connect wires to the control terminals.
The ambient temperature should be in the range of -10°C to 40°C. Higher ambient temperature causes shorter inverter life. So if there is hot equipment in the vicinity of the inverter, keep it away from the inverter as far as possible.
The end application must be in accordance with the BS EN 60204-1 standard.
Chapter 5 – Wiring
5-1
Chapter 5 – Wiring
CAUTION Fasten the screws with the specified fastening torque so that they will not loosen
unintentionally. Check all terminals for loose screws. Otherwise there is a danger of fire.
CAUTION Remarks for using earth leakage circuit breakers in the mains supply
Frequency inverters with CE-filters (RFI-filter) and screened motor cables have a
higher leakage current against earth. Especially in the moment of switching this can cause unintentional triggering of earth leakage circuit breakers. Because of the rectifier on the input side of the inverter there is the possibility to stall the switch-off function through amounts of DC current. For these reasons, the following items should be observed:
Only pulse current sensitive earth leakage circuit breakers which have a short term
delay and a higher trigger current (500mA) should be used. Other components should be secured with separate earth leakage circuit breakers. Earth leakage circuit breakers in front of an inverter´s rectifier are not an absolute protection against direct touching.
CAUTION Each phase of the power supply has to be provided with a fuse. Otherwise, there is a
danger of fire.
CAUTION As for motor leads, earth leakage breakers, and electromagnetic contactors, be sure to
use the ones that have the correct rating. Otherwise, there is a danger of fire.
CAUTION Make sure that the mains supply leads are reliably fixed.
Wiring the power supply and motor
In order to connect cables to the power supply and other terminals the terminal cover has to be opened. For this, first of all the four corresponding screw has to be loosened. The location of the terminals is depicted in the figure below:
CAUTION Don’t disconnect wires attached to F terminals (fan power supply), otherwise
inverter may overheat. In case the wires are exchanged, the fan doesn’t work. This terminals cannot be used for the power supply for external device.
When connecting cables, the following details have to be considered:
1) Power supply cables must only be connected to the terminals L1, L2, L3 or L, N.
2) Refer the page 5-5 for wiring equipment and options.
L1 L3L2 +VUFF-W
Motor
To the power supply
Mains circuit terminals
LN +VUFF-W
NFE:
HFE:
Grounding terminal (PE)
Chapter 5 – Wiring
5-2
3) If more than one motor is to be driven by a single inverter, thermal relays have to be provided for each
motor.
Therma l relay
L100IP
4) The leads from the power supply must be connected to the mains circuit terminals as follows:
Connect single phase power supply (50/60Hz) to terminals L1, N.
Connect three phase power supply (50/60Hz) to terminals L1, L2, L3.
Wiring the control terminals
The following figure shows the location of the control terminals. The exact use of each of the control terminals is described later in this chapter.
The figure below contains an example for control terminal wiring:
Reset (RS)
FA1
Prevention of
restart (USP)
Jogging run (JG)
Reverse run (RV)
Forward run (FW)
24VDC
(Common fo
r
inputs)
RUN
Potentiometer
(1k-2kOhm)
for frequency
set value
Frequenc
y
meter
24V DC,
max. 50 mA
L 3 4 5 2 1 H O OI FML 12 11
NOTE: Function of digital inputs and outputs can be changed
Control terminals
Alarm circuit terminal REMOVABLE CONNECTOR
Control circuit terminal REMOVABLE CONNECTOR
L
3
4
5
2 1 H
O OI
FM L 12 11
Chapter 5 – Wiring
5-3
General remarks
When connecting cables, the following items must be observed:
- When changing the power supply of the motor between the inverter and commercial power line, be sure
to install mechanically interlocked switches (S1 and S2) as shown in the figure below:
Motor
Inverter
Earth leakage
circuit breakers
L1 (L) L2 L3 (N)
U V
W
Power
supply
S1
S2
- Install an earth leakage breaker at the input of the inverter. Select an earth leakage breaker which has a
short term delay and a higher trigger current.
When the cable between the inverter and the motor is more than 10 meters long, the thermal relay may malfunction due to high-frequency waves. To prevent this, install an AC reactor on the output side of the inverter or use a current sensor rather than a thermal relay.
- In case a relay is connected to the digital output terminals 11 or 12 be sure to install a surge absorbing
diode in parallel to the relay. Otherwise the surge voltage created when the relay goes on or off may damage the output circuit.
- Be sure that the specified grounding is carried out. Separate the inverter´s grounding pole from those of
other heavy electric machinery and avoid using common grounding poles when multiple inverters are employed.
Inverter 1
Inverter 2
Inverter 3
Ground ing poi nt Ground ing poi nt
WRONG CORRECT
Inverter 1
Inverter 2
Inverter 3
- Use a twisted and shielded wire when connecting signal lines to the control terminals and cut the
shielded covering as shown in the figure below. Make sure that the length of the signal line is 20 m or less. If the line must be longer than 20 m then an appropriate signal amplifier should be used.
Frame ground
Isolate here
No grou nding
necessary here
- Use relays which are capable of reliably switching at a voltage of 24VDC and a current of 3mA.
- Install the mains circuit cables at a safe distance from the control circuit cables. If the mains circuit
cables and the control circuit cables have to cross each other, this should be done at an angle of 90 degrees because interference can be minimized in this case.
Chapter 5 – Wiring
5-4
90°-angle
Mains circuit power cable (L1, L2, L3 (L, N), U, V, W, +1, +, - )
Signal line (H, O, OI, L, FM, 1,
2, 3, 4, 5, 11, 12, CM2, P24)
Separate by 10cm or more
- Do not short circuit the terminals P24 and L, H, OI, or FM by mistake, because this may cause a
malfunction.
- Do not short circuit the terminals H and L because this may cause a malfunction.
The following figure shows an example for connecting a driver-IC to the digital inputs when using the inverter´s internal 24VDC power supply terminal (left half of figure below) and when using a separate external 24VDC power supply (right half of figure below).
L100IP series
frequency inverter
L1 (L)
L2
L3 (N)
U
V
W
1
2
3
4
5
L
P24
AL0
AL1
AL2
Motor
+
Alarm
terminals
1
2
3
4
5
S
COM
Transistor output driver
YTS48 or similar
24VDC
(
Note)
Note: Do not short circuit the terminals P24 and L by mistake because this may lead to a malfunction.
-
Terminals for
braking unit
1
2
3
4
5
L
P24
1
2
3
4
5
S
COM
24VDC
(
Note)
24V
b
attery
L100IP series
frequency inverter
(terminals not shown here
are exactly like those of
the inverter shown in the
left part of this figure).
Transistor output driver
YTS48 or similar
Chapter 5 – Wiring
5-5
Wiring equipment and options
CAUTION A switch or circuit breaker shall be included in the building installation. It shall be
marked as the disconnecting device for the equipment and should meet the requirements of the IEC947-1 and IEC947-3 standard. Ratings should be in accordance with table below. For single phase there should be a double pole and for three phase there should be a three pole disconnecting device. The switch or circuit breaker should be near the equipment (close proximitly to the equipment and in easy reach to the operator).
CAUTION Provide the wiring equipment in accordance with the safety codes required by
jurisdictional authorities (IEC example: supply wires should meet the requirements of the IEC 60227 or IEC 60245... They should be made of suitable heat-resistant material). If specified in standards or laws and regulations, follow their istructions. In the following table some guidelines for choosing an appropriate wire gauge are presented:
Cable specifications
600V fuse to be
used
(rated current / A)
Input
voltage
Motor
output
(kW)
Inverter
model
Power lines
Cable
diameter
Signal
lines
0.4
L100IP-004NFE
L100IP-004NFU
1.5 mm
2
(AWG 15)
10 A
0.75
L100IP-007NFE
L100IP-007NFU
2.5 mm
2
(AWG 13)
16A
1.5
L100IP-015NFE
L100IP-015NFU
4.0 mm
2
(AWG 11)
25 A
200V single phase
2.2
L100IP-022NFE
L100IP-022NFU
4.0 mm
2
(AWG 11)
40 A
0.75
L100IP-007HFE
L100IP-007HFU
1.5
L100IP-015HFE
L100IP-015HFU
2.2
L100IP-022HFE
L100IP-022HFU
1.5 mm
2
(AWG 15)
10A
4.0
L100IP-040HFE
L100IP-040HFU
2.5 mm
2
(AWG 13)
16A
5.5
L100IP-055HFE
L100IP-055HFU
400V three phase
7.5
L100IP-075HFE
L100IP-075HFU
4.0 mm
2
(AWG 11)
10-17mm
Shielded wire (max. 1.5mm
2
)
*)
cable diameter 5-10 mm.
25A
Notes:
- Field wiring connections for PE wire must be made by a certified closed-loop terminal connector sized
for the wire gauge involved. The connector must be fixed using the crimp tool specified by the connector manufacturer.
- Only use a fuse that has the appropriate rated current.
- Be sure to use bigger wires for mains circuit cables and motor cables if the distance exceeds 20m.
- Tighten firmly the cable gland nuts after pulling through the cable. The round rubber protection is to be
removed before wiring. Leave rubber protectection in unused glads in order to keep IP54 protection.
*)
Use max. 1,5mm2 for the alarm signal wire. The wire stripping length should be approximately 6–7 mm.
Chapter 5 – Wiring
5-6
Part description Function
AC reactor
This part is used when the unbalance ratio is 3% or
more and the power supply is 500kVA or more, and
there are rapid changes in the power supply. This part
also improves the power factor.
EMI filter
(Note)
This part is used to conform with the applicable
EMC standards.
Radio noise filter
This part reduces noise generated at the output of the inverter (this type of filter supplies an almost perfect sine shaped output voltage between phase-phase and
phase-PE).
Motor filter
Motors that are driven by an inverter are to a larger
extent subject to voltage fluctuations than motors directly
driven (without inverter) by power lines. An AC reactor
installed between inverter output and motor smoothens motor run and so reduces torque ripple. When the cable between the inverter and the motor is too long, this part
also forces the voltage dv/dt to be limited and so protects
the isolation of the motor.
Note: Usage of an EMI filter is necessary for the European EMC directive, for the Australian C-TICK and others. In comparison, the other parts mentioned in the table above are not intended for this special use.
Terminals
In the table below the location and dimensions of the power terminals (terminals for power supply and motor) are listed:
Location of power terminals Inverter model
Screw size
(Screwdriver type)
Cross section
of cable
Tightening
torque range
LN +VUF-W
All NF models
M3
(0.6x3.5mm)
0.5…6mm
2
(AWG 22...10)
0.5…1.0 Nm
L1 L3L2 +VUF-W
All HF models
M3
(0.6x3.5mm)
0.5…6mm
2
(AWG 22..10)
0.5…1.0 Nm
View of grounding terminal
All
M4
(PH2)
Ring or fork type
cable terminal
diameter: 4mm
1.2…1.3 Nm
L1
(L1)
L2
L3 (N)
(T1) U (T2) V (T3)
W
Motor
Thermal
relays
Chapter 5 – Wiring
5-7
The following table shows the location and dimensions of control and alarm terminals:
Location of terminals
(REMOVABLE CONNECTOR)
Screw size
(Screwdriver type)
Cross section
of cable
Tightening
torque range
M2
(0.4x2.5mm)
0.5…1.5mm
2
(AWG 22...14)
0.2...0.25 Nm
M2.5
(0,6x3,5mm)
0,5-2.5mm
2
(AWG 22..12)
0.4…0.5 Nm
In the following table the purpose of the power terminals is shown:
Terminal symbol Purpose Description
L1, L2, L3
(L, N)
Mains supply
Single phase supply: connect to L, N
Three phase supply: connect to: L1, L2, L3
U, V, W
Inverter output Connect a three phase motor
+, - Braking unit
Connect the optional braking unit (when high
braking torque is required).
Grounding
Ground must be connected to prevent electric shock
should the inverter case carry dangerous voltages
due to a malfunction. Also to connect cable shield.
L1
(L)
L
2
L3
(N)
U
V W
Motor
The following table lists the tightening torque values for tightening the screws:
Screw Torque in Nm
M2 Typ. 0.20 Max. 0.25
M3 Typ. 0.50 Max. 0.60
M3.5 Typ. 0.80 Max. 0.90
M4 Typ. 1.20 Max. 1.30
M5 Typ. 2.00 Max. 2.20
The next table describes the purpose of each control terminal: (To be continued on next page)
Terminal category
Sym
bol
Purpose Initial setting Remarks
5 Reset input
4
Multistage frequency
input / USP function
3
Multistage frequency
input / use 4-20mA input
2 Reverse run
1
These inputs have different purposes depending on the user programmed configuration:
Forward and reverse running command, up to 4 multistage speed settings, jogging run, 2nd stage acceleration/decel., free run stop, external trip, USP function, terminal software lock, reset, PTC, input for choosing current as analogue set value
Forward run
Input closed (ON):
Function active
Input opened (OFF):
Function not active
Input must be ON for a
minimum of 12ms
Digital
Inputs
P24 Common for input signals 24V DC; max. 30mA
FM
Connection of an analogue or digital meter
for measuring frequency;
connection of an analogue meter for
current measurement
Frequency monitor
(analogue)
Monitor
signal
L Common for monitor signal
L 3 4 5 2 1 H
O OI
FM L 12 11
Chapter 5 – Wiring
5-8
Terminal category
Sym
bol
Purpose Initial setting Remarks
H Reference for frequency command input 10V DC; max. 10mA
O Voltage frequency command
Set value 0-10V;
Input impedance 10k
Ohm
OI Current frequency command
Set value 4-20mA;
Input impedance 250
Ohm
Frequency
command
input
L Common for frequency command input
11
Frequency arrival signal
(signal when reaching
set value)
12
The digital outputs can be user programmed to provide different signals for the following situations:
Signal when reaching set value or passing a configurable frequency; signal during motor run; overload signal; PID deviation signal; alarm signal
Signal during
motor run
Outputs of
open collector type for
connection to a relay
(max. 27V DC and
max. 50mA)
Digital
output
CM2 Common for digital outputs
AL0
AL1
Fault
alarm
output
AL2
AL0 AL1 AL2
Initial setting: During normal operation AL0-AL1 is closed; during a trip condition or cut off power supply AL0-AL1 is opened (i.e. AL0-AL2 is closed).
Ratings of relay contacts:
Max. 250VAC / 2.5A (resistive) or 0.2A (cos phi = 0.4);
Min. 100VAC / 10mA
Max. 30VDC / 3.0A (resistive) or 0.7A (cos phi = 0.4); Min. 5VDC / 100mA
Chapter 6 – General operation notes
6-1
Chapter 6 – General operation notes
Before starting operation
Prior to the test run, the following items should be checked:
1) Make sure that the power lines (input power supply terminals L1, L2, L3 or L, N) and output terminals
(U, V and W) are connected correctly.
2) Make sure that there are no mistakes in the signal line connections.
3) The grounding terminal must be grounded.
4) Terminals other than those marked as grounding terminals must not be grounded.
5) The inverter must be installed vertically on a non-flammable mounting surface (e.g. steel).
6) Remove any residue from wiring work like stray pieces of wire and others. Also, make sure that no tolls
are left behind.
7) Make shure that the wires connected to the output terminals are not short-circuited or grounded.
8) All the terminal screws must be sufficiently tightened.
9) The configurable maximum output frequency parameter must be chosen in accordance with the
maximum frequency of the connected motor and machine.
Do not carry out any withstand voltage tests because the inverter has a surge absorber between the mains circuit terminals and the ground.
Test run
Below an example for an inverter connection is shown. For the initial tests, frequency adjustment and forward and reverse running commands should be carried out via the digital operator in order to check the inverter’s correct functioning.
Power supply
(three phase)
50/60 Hz
Fuses
Earth leakage circuit breaker
Inverter
L100IP series
L1 (L)
L2
L3 (N)
U
V
W
1
2
3
4
5
L
P24
H
O
OI
L
FM
AL0
AL1
AL2
11
CM2
12
Motor
Ground
400V class:
Three phase 380~460V
200V class:
Single phase 200~240V
Fault alarm signal Normal state: AL0-AL1
Trip and pow er off: AL0-A L2
Initial setting for maximum frequency (-FE and -FU series) is 50 or 60Hz and initial setting for direction of rotation is “forward run“.
Chapter 6 – General operation notes
6-2
In order to test the inverter, follow the procedure described below:
1) Turn on power supply to the inverter. The power LED on the digital operator will light up.
2) Set function A 02 to 02.
3) Set function A 01 to 02. Set the corresponding frequency using function F 01.
4) After pressing the RUN key the motor starts to run and the the RUN lamp lights up.
5) The actual frequency can be monitored using function d 01.
6) You can stop the test run by pressing the STOP key.
CAUTION After the test run has been completed, check the following items to ensure that the
motor will not be damaged:
Was the direction of the motor run correct? Was there any trip condition during
acceleration or deceleration? Were there any unusual motor sounds or vibrations?
When a trip occured during the test run due to overcurrent or overvoltage, increase
acceleration or deceleration time.
Chapter 7 – Control circuit terminal functions
7-1
Chapter 7 – Control circuit terminal functions
Overview
Terminal
symbol
Terminal function Description
FW
(00)
Forward run
(Start/Stop)
RV
(01)
Reverse run
(Start/Stop)
Freque nc
y
FW ON OFF OFF
RV OFF ON OFF
Forward run
Reverse run
4321P24
RV
FW
Input FW closed: Motor starts with forward running direction. Input FW open: Motor decelerates from forward running. (same for reverse run using input RV) Inputs FW and RV both closed: motor decelerates.
CF1 (02)
1
CF2 (03)
2
CF3 (04)
3
CF4 (05)
4
Frequenc
y
CF1
Frequ. 1
Frequ. 2
Frequ. 3
Set value
ON ON ON ON
ON ON
ON
CF2
FW
RV
Example:
4 multistage speeds
Analog set value
2 multistage inputs (CF1 and CF2) are necessary for 4 different multistage speeds (3 programmable multistage speeds plus 1 set value).
FR
S
CF2
CF1
RV
FW
345 2 1 H O OI L
JG
(06)
Jogging run
The jogging run activated using the terminal JG may serve for setting up a machine
in manual operation mode. When a forward or reverse run command is given, the frequency configured using A 38 is then sent to the motor. For motor stop, one of
three operating modes can be chosen by configuring A 39.
PTC
(19)
Connection of exter-
nal PTC thermistor
Only digital input 5 can be programmed as a PTC thermistor input (using C 05).
The terminal L serves as common for the thermistor input.
AT
(16)
Activate input OI (cur­rent set value 4-20mA)
When the AT input is activated, then the set value will be a 4-20mA current
that has to be supplied at the terminals OI and L.
2CH
(09)
2. stage acceleration / deceleration
Using this input the second stage acceleration and deceleration time
configured using A 92 and A 93 is activated.
FRS (11)
Free run stop
function
When the terminal FRS is turned on, frequency to the motor is
switched off and the motor runs free.
EXT
(12)
External trip
When the terminal EXT is turned on, the inverter enters the trip state, stops output
to the motor, and displays E 12. The trip condition can be acknowledged, among
others, using the RS input.
USP
(13)
Prevention of restart
When the USP input is on, the motor does not restart when power supply recovers
following a power supply failure and a running command is active at the same time.
RS
(18)
Reset
A trip can be acknowledged by activating the RS input. If a reset is given during
normal inverter operation, the motor runs free. The RS input is always a normally
open contact and cannot be configured as normally closed input.
Programmable digital inputs 1 through 5
SFT (15)
Software lock
When the SFT input is turned on, the configured parameters are protected
from being overwritten.
Pro
g
rammable multista
g
e s
p
eeds
Loading...
+ 65 hidden pages