Caution: Be s ure to read the L2002 Inverter Manual and follow
its Cautions and Warnings for the initial product installation.
This Quick Reference Guide is intended for reference use by
experienced users in servicing existing installations.
UL® Cautions, Warnings, and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The Cautions, Warnings, and instructions in this section summarize the
procedures necessary to ensure an inverter installation complies with
Underwriters Laboratories
Wa rn in g: “Use 60/75°C Cu wire only” or equivalent.
Wa rn in g: “Open Type Equipment.”
Wa rn in g: “Suitable for use on a circuit capable of delivering
not more than 100,000 rms symmetrical amperes, 240 V
maximum.” For models with suffix N or L.
Wa rn in g: “Suitable for use on a circuit capable of delivering
not more than 100,000 rms symmetrical amperes, 480 V
maximum.” For models with suffix H.
Wa rn in g: “Hot surface—risk of burn.”
Wa rn in g: “Install device in pollution degree 2 environment.”
Wa rn in g: “Maximum Surrounding Air Temperature 50°C.”
Wa rn in g: “Risk of electric shock—capacitor discharge time is at
least 5 minutes.”
Wa rn in g: “Solid state motor overload protection is provided in
each model.”
Wa rn in g: “Tightening torque and wire range for field wiring
terminals are marked adjacent to the terminal or on the wiring
diagram.”
®
guidelines.
1
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are
presented in the tables below.
200V Models
Motor output
Inverter Model
kWHPft-lbs (N-m)
0.21/4–002NFE(F)2/NFU2
0.553/4–005NFE(F)2
0.751–007NFE(F)2/NFU2
1.11 1/2–011NFE(F)2
1.52–015NFE(F)2/NFU212
2.23–022NFE(F)2/NFU210
3.75–037LFU212
5.57 1/2–055LFU210
7.510–075LFU28
400V Models
Motor output
Inverter Model
kWHPft-lbs (N-m)
0.41/2–004HFE(F)2/HFU2
0.751–007HFE(F)2/HFU2
1.52–015HFE(F)2/HFU2
2.23–022HFE(F)2/HFU2
3.04–030HFE(F)214
4.05–040HFE(F)2/HFU2
5.57 1/2–055HFE(F)2/HFU2121.52.0
7.510–075HFE(F)2/HFU2
Wire Size
(AWG)
160.60.80.41/2–004NFE(F)2/NFU2
14
Wire Size
(AWG)
16
Torque
0.91.2
1.52.0
Torque
0.91.2
2
Wire Size
Terminal Connector
Logic/Analog connector30—160.16—0.190.22—0.25
Relay connector30—140.37—0.440.5—0.6
Range
(AWG)
Torque Range
ft-lbs(N-m)
Wire Connectors
Wa rn in g: Field wiring connections
must be made by a UL Listed and CSA
Certified ring lug terminal connector
sized for the wire gauge being used.
The connector must be fixed using the
crimping tool specified by the connector manufacturer.
Terminal (ring lug)
Cable support
Cable
Fuse and Circuit Breaker Sizes
The inverter’s input power wiring must include UL Listed, dual-element,
600V fuses, or UL Listed, inverse-time, 600V circuit breakers.
200V Models
Motor output
Inverter Model
kWHP
0.21/4–002NFE(F)2/NFU210
0.41/2–004NFE(F)2/NFU210
0.553/4–005NFE(F)210
0.751–007NFE(F)2/NFU215
1.11 1/2–011NFE(F)215
1.52–015NFE(F)2/NFU220 (single ph.)
2.23–022NFE(F)2/NFU230 (single ph.)
3.75–037LFU230
5.57 1/2–055LFU240
7.510–075LFU250
Ampere Rating for
Fuse or Breaker
15 (three ph.)
20 (three ph.)
3
400V Models
Motor output
Inverter Model
kWHP
0.41/2–004HFE(F)2/HFU23
0.751–007HFE(F)2/HFU26
1.52–015HFE(F)2/HFU210
2.23–022HFE(F)2/HFU210
3.04–030HFE(F)215
4.05–040HFE(F)2/HFU215
5.57 1/2–055HFE(F)2/HFU220
7.510–075HFE(F)2/HFU225
Ampere Rating for
Fuse or Breaker
Motor Overload Protection
Hitachi L2002 inverters provide solid state motor overload protection,
which depends on the proper setting of the following parameters:
Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is 0.2 * rated current to 1.2 * rated current.
War n in g: When two or more motors are connected to the
inverter, they cannot be protected by the electronic overload protection. Install an external thermal relay on each motor.
The following wiring diagram shows the power and motor connections
for basic operation. The optional signal input wiring supports external
Fwd and Rev Run command, and a speed potentiometer.
L200
From 3-phase
power input
source (See
specifications
label on inverter
for details)
Inputs:
Forward
Reverse
GND for logic inputs
Analog reference
External
speed
reference
pot.
GND for analog signals
R
(L1)
S
(L2)
T
(N/L3)
PCS
1
2
L
H
O
L
U
(T1)
V
(T2)
W
(T3)
AL1
Relay contacts,
AL0
AL2
Open collector
outputs:
Run signal
12
arrival signal
11
GND for logic
CM2
Motor
1 Form C
Load
Load
Frequency
outputs
8
Inverter Keypad Operation
STOP
RESET
1
2
Parameter Display
POWER
Hz
A
RUN
PRG
ALARM
STR
Store Key
Serial Port
Powe r L ED
Alarm LED
Display Units LEDs
Hertz
Amperes
Pot entio mete r
Enable LED
Pot entio mete r
Stop/Reset Key
Run Key Enable LED
Program/Monitor LED
Run/Stop LED
HITACHI
50.0
RUN
FUNC.
Run Key
Up/Down Keys
Function Key
• Run/Stop LED – ON when the inverter output is ON and the motor is
developing torque, and OFF when the inverter output is OFF (Stop
Mode).
• Program/Monitor LED – ON when the inverter is ready for parame-
ter editing (Program Mode). It is OFF when the parameter display is
monitoring data (Monitor Mode).
• Run Key Enable LED – ON when the inverter is ready to respond to
the Run key, OFF when the Run key is disabled.
• Run Key – Press this key to run the motor (the Run Enable LED must
be ON first). Parameter F004, Keypad Run Key Routing, determines
whether the Run key generates a Run FWD or Run REV command.
• Stop/Reset Key – Press this key to stop the motor when it is running
(uses the programmed deceleration rate). This key will also reset an
alarm which has tripped.
• Potentiometer – Allows an operator to directly set the motor speed
when the potentiometer is enabled for output frequency control.
• Potentiometer Enable LED – ON when the potentiometer is enabled
for value entry.
(continued, next page...)
9