Hispec HSSA/PE User Manual

220~240V
C OPERATED
A
NTERCONNECTABLE
I
HOTOELECTRIC SMOKE
P
A
ODEL: HSSA/PE
M (
With 9V Battery Back-up)
638573
KM 638574
BS EN14604:2005
M
ain Features :
Photoelectric Sensor For Slow
moldering Fires
S
Power / Alarm Test Button
HUSH FEATURE
Battery Back Up
Low Battery Warning
INTERCONNECTABLE (UP TO 20
HISPEC’S
LARMS)
A
Kitemark Approved –
S EN14604: 2005
B
Supplied with Fixing Kit
Loud 85dB Alarm Signal
Fault signal
This instruction leaflet contains important information on the correct installation and operation of your smoke alarm. Read this leaflet fully before attempting installation and retain for future reference.
HEAT AND/OR SMOKE
CLASS II APPARATUS
SPECIFICATION
Power Source : 220-240Vac~ 50-60Hz with 9V battery
Battery Back-up : 9V DC Carbon Zinc (Golden Power
Battery Back-up Life : In the event of a break in the mains supply
Operation Current : <40mA operation (In Alarm) Sensitivity to smoke : 0.65-1.52 % per foot obscuration Operation Temperature : 0-40 Ambient Humidity : 10%-90% Alarm Sound Level : 85 Decibels at 3 metres Interconnect facility : 20 smoke detector over 80
Approved to : BS EN14604:2005
back-up (battery included)
1604D, Gold Peak 1604P), 9V Alkaline Battery (Gold Peak 1604A, Energizer 522, Duracell MN1604) or Lithium Battery (EVE CR9V/P)
the battery will give detector operation for 1 year minimum
metres maximum
PRODUCT DESCRIPTION
HSSA/PE
is a multiple station photoelectric smoke alarm and can be connected to other alarms of the same make and type. This interconnect feature allow up to 20 units to be connected together over 80 metres maximum, using the single white wire, and thus allowing all alarms to sound when any one is activated.
Note: This smoke alarm cannot be connected to any other device such as a fi
All the Smoke Alarms should be interconnected to ensure the early warning will be heard, particularly by somebody sleeping. A properly designed early warning fire system ensures the alarm is given before the escape routes become blocked with smoke.
re alarm panel.
FIGURE 1 - SINGLE STOREY DWELLING
BEDROOM
BEDROOM
BEDROOM
FIGURE 2 - 2/3 STOREY DWELLING
BATHROOM
HALL
BEDROOM
LANDING
HALL
KITCHEN
KEY
MAXIMUM PROTECTION MINIMUM PROTECTION
BATHROOMBEDROOM
LIVING ROOM
BASEMENT
KITCHEN
LIVING ROOM
LOCATING THE SMOKE ALARM
If your dwelling is on a single storey, for minimum protection you should fit an alarm in a corridor or hallway between the sleeping and
living areas
possible and ensure the audible alarm can be heard when the bedrooms are occupied. See Figure 1 for examples.
If your dwelling is multi-storey, for minimum protection should be fitted at the bottom of the staircase with further alarms fitted on each upstairs landing. This includes basements but excludes crawl spaces and unfinished attics. See Figure 2 for examples.
NOTE: For maximum protection an alarm should be fitted in every room (except kitchen, bathroom and garage).
DO NOT FIT AN ALARM IN THE KITCHEN OR BATHROOM, as cooking fumes or steam may DO NOT FIT ALARM IN GARAGE, as exhaust fumes are likely to set it off.
(incl. Kitchens). Place it as near to the living areas as
trigger the alarm.
POSITIONING THE SMOKE ALARM
Ceiling Mounting
As smoke rises and spreads out, it is advisable to mount on a ceiling in a central position. Avoid areas where there is no air circulation. E.g. Corners of rooms and keep away from items which may prevent the free flow of air. Place the unit at least 300 mm from light fitting or decorative object which might obstruct smoke entering the alarm from walls. See Figure 3i.
. Keep at least 300 mm away
Wall Mounting
Do not mount tight into the corners. Put the top edge of your smoke alarm between 150 and 300mm below the ceiling. Keep at least 300mm from room corners. See Figure 3i
On a Sloping Ceiling
In areas with sloping or peaked ceilings install your Smoke Alarm 900mm from the highest point measured horizontally because “dead air” at t reaching the unit. See Figure 3ii.
he apex may prevent smoke from
Areas to be avoided include the following :-
Situations where the temperature may fall below 0or
rise above 40
Humid areas such as bathrooms, kitchens, shower rooms
where the relative humidity may exceed 90%
Near a decorative object, door, light fitting, window
moulding etc., that may prevent smoke from entering the ala
rm.
Fume filled environments such as garages. Exhaust gases
may cause false alarms.
one alarm
Adjacent to or directly above hot components such as radiators or
wall vents that can effect the direction of air currents.
In very dusty or dirty environments such as workshops. Locate unit at least 1.5m and route wiring at least 1m away for
fluorescent light fittings as electrical “noise” and/or flickering may affect the unit. Do not wire into the same circuit as fluorescent
dimmers.
lights or
Do not locate in insect infested areas. Insects and contamination
on the alarm sensor can increase its response time.
INSTALLING THE SMOKE ALARM
WARNING – This smoke alarm is mains powered and requires wiring by a qualified electrician in accordance with the current IEE Regulations for Electrical Installations (BS7671).
The circuit used to power the smoke alarm must be a dedicated permanent supply that cannot be switched off accidentally by the normal user. Before installing ensure the electrical supply is isolate
d.
WARNING : To prevent injury, this smoke alarm must be securely attached to the ceiling/wall in accordance with the installation instructions.
The Smoke Alarm will function correctly either as a stand-alone alarm or inter-connected. All interconnected Smoke Alarms must be supplied from a single power circuit. A common neutral must be used for the interconnect to function.
Do not connect the Inter-conne
Disconnect the AC main power from the circuit that is going to be
used.
Having established the mounting location install a junction box
suitable for locating the termination point. Ensure that there is no other electrical wiring or pipe work in the area adjacent to the mounting surface.
Unlock the detector unit from the base by push back the snap
lock with a screw driver release it. See Figure 5 and Figure 6
Fix mounting plate in position. Strip the Live / Neutral and Inter-connect (if used) wires. Connect the wires correctly. If the smoke alarms are to be
interconnected, connect the wire. For Alarm that are used as singl e station, DO NOT CONNECT THE WHITE WIRE TO ANYTHING. Ensure the screws are fully tightened. See Figure 6.
The alarm must
codes.
ct wire to Live or Neutral.
and turn the alarm unit anti-clockwise to
be wired in accordance with National wiring
LIVE - connect to house wires coloured Brown, or marked with L.
NEUTRAL - connect to house wires coloured Blue, marked with N.
INTERCONNECT - connect to the white third wire.If you are not interconnecting to other units, do not connect any wire to this terminal.
Insert a 9V battery firmly into battery compartment on the rear
of the alarm. NOTE POLARITY Ensure the metal tab is fully depressed when the battery has been fitted.
OF CONNECTIONS.
or
NOTE – For the safety of the end user, the smoke alarm cannot be fitted without its battery.
Before assembly to base plate test the correct operation
of the smoke alarm (operating from the battery only) by depressing the test button on the front of the alarm. The unit should emit a loud pulsating alarm.
Assemble alarm unit onto the mounting plate by turning
the alarm unit counter-clockwise. Se
Restore the AC supply by plugging the AC QUICK
CONNECTOR into the back of the alarm (see Figure 4). Make sure that the locks on the connector snap into place.
Test the correct
operation of the smoke alarm by depressing the test button on the front of the detector. The unit should emit a loud pulsating alarm.
Should use 2.1mm wire
for connection.
Figure 5 Turn the alarm units clockwise until the snap lock engages.
Figure 6 – Push Back the snap lock and turn the Alarm anti-clockwise
e Figure 4
Figure 4 Plug the AC QUICK CONNECTOR into the back of the alarm.
OPERATING YOUR SMOKE ALARM
Once the smoke alarm has been installed a small GREEN indicator light (LED) should be visible through the alarm grill indicating that AC supply is healthy. A RED indicator light (LED) should also flash approximately once a minute to indicate the battery is healthy and the unit is operating properly.
If smoke is detected, the unit will emit a load pulsating alarm and a RED indicator light (LED) will be flashing quickly at the same time until the air is clear.
TESTING YOUR SMOKE ALARM
It is recommended that you test your smoke alarm once a week to ensure the detector is working correctly. Push and hold the test button for approximately 3 seconds. A loud pulsating alarm should sound and a RED indicator light (LED) will flash at the same time. NOTE – for multiple interconnected smoke alarms, only the RED indicator light (LED) of the originating unit will units in the interconnect system will sound an alarm but their RED indicator light (LED) will the alarm is triggered on all other alarms installed.
2
NOT
flash. Test each alarm checking that
flash rapidly. All other
HUSH OR SILENCE FEATURE
This Smoke Alarm has a built-in Hush or Silence feature incorporated into the Test button. If cooking or other non­hazardous sources cause the unwanted alarm, it can be temporarily silenced by depressing the test button and holding for approximately 3 seconds. The alarm will enter a dormant period for 10 minutes. The red LED will flash every 10 seconds to indicate the se reduced. At the end of the hush period the alarm will reset to normal sensitivity. NOTE – If the smoke density increase during this period (i.e. from a fire) the unit will go into alarm mode.
LOW BATTERY WARNING
If the smoke alarm emits a short ‘beep’ once a minute the battery is at the end of its life and should be replaced immediately. This low voltage warning will be given for at least 30 days. In this case, the other interconnected units in the system which are not in low battery condition will chirps for a few seconds once an hour as long as the detector with the “dead” battery be
If the red indicator light (LED) does not flash every minute then replace the battery.
eps.
nsitivity is
MAINTAINING YOUR SMOKE ALARM
Clean your smoke alarm at least once every six months to prevent dust build up. This can be done using a vacuum cleaner with the brush attachment. Clean gently around the front grilled section and sides.
The apparatus shall not be exposed to dripping or splashing and no objects filled with liquids, such as vases, shall be placed on the app
aratus.
BATTERY REPLACEMENT
Always TURN OFF the A.C. supply to the Smoke Alarm before replacing the battery. Replace the battery at least once annually, or immediately when the low battery signal sounds once a minute, even though the Smoke Alarm is receiving A.C. power.
Test the alarm for correct operation using the test facility whenever the battery is replaced.
WARNING: DANGER OF EXPLOSION IF BATTERY IS
INCORRECTLY REPLACED. THE USE OF BATTERIES OTHER THAN THOSE RECOMMENDED ON THE BACK OF THE SMOKE ALARM MAYBE DETRIMENTAL TO ITS OPERATION
The battery should only be replaced by a qualified electrician or similarly qualified person.
Turn off the A C power supply to the Smoke Alarm. Gently unlock the detector unit from the base by
push back the snap lock with a screw driver and turn the alarm unit and Figure 6
Remove the battery from the compartment. Insert a new, healthy 9V battery. NOTE POLARITY OF
CONNECTIONS. Ensure the metal tab is fully depressed when the battery has been fitted
Using the Push-to-Test button, test the smoke alarm to
verify 9V DC battery back-up. See “TESTING YOUR SMOKE ALARM”
Reattached the Smoke alarm to the mounting plate
rotating the alarm unit counter-clockwise until the it snaps into place. (see Figure 4)
Turn on the AC power and test the Smoke Alarm using
the Push-to-Test button. See “TESTING YOUR SMOKE ALARM”
clockwise to release it. See Figure 5
by
IMPORTANT SAFEGUARDS
Installation of your smoke alarm is only one step in your safety plan. Other important steps should be taken to further improve your safety:-
Install the smoke alarm properly, following this instruction
leaflet
Test your smoke alarm weekly Replace the battery immediately once depleted Do not smoke in bed Keep matches & lighters away from children Store flammable ma
use them near naked flames or sparks
Maintain emergency equipment such as Fire
Extinguishers, escape ladders etc and ensure all occupants know how to use them correctly.
terials in a proper manner and never
Plan an escape route/s from your building in advance and ensure
all occupants are aware of them. Re-enforce this awareness periodically through-out the year.
Make sure escape routes remai
WARNING: IF THERE IS ANY QUESTION AS TO THE CAUSE OF AN ALARM IT SHOULD BE ASSUMED THAT THE ALARM IS DUE TO AN ACTUAL FIRE AND THE DWELLING SHOULD BE EVACUATED IMMEDIATELY.
THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE WARRANTY. IF THE UNIT IS FAULTY PLEASE RETURN IT TO YOUR ORIGINAL SUPPLIER WITH YOUR PROOF O
n free of any obstructions.
F PURCHASE.
YOUR SMOKE ALARM WARRANTY
These smoke alarms are warranty to be free from defects in materials and workmanships under normal use and service for a period of five years from date of purchase. The company will not be obligated to repair or replace parts which are found to be in need of repair because of misuse, damage or alterations occur after the date of purchase. Send the Smoke Alarm with proof postage prepaid, to local distributor. The liability of the company arising from the sale of this smoke alarm shall not in any case exceed the cost of replacement of smoke alarm and in no case shall the company be liable for consequential loss or damages resulting from the failure of the smoke alarm.
HISPEC ELECTRICAL PRODUCTS LTD SHALL HAVE NO LIABILITY FOR ANY
PERSONAL INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL DAMAGE OF REMEDY HEREIN PRODUCT LTD BE LIABILITY UNDER ANY OTHER LAW EXCEED THE PURCHASE PRICE. NOT A SUBSTITUTE FOR PROPERTY, INSURANCE OF ANY KIND. RESPONSIBILITY. CONSULT
This does not affect your statutory ri
This alarm is only suitable for residential dwellings and is not suitable for commercial or industrial use.
Waste electrical products should not be disposed of with normal household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice. New regulation will encourage the recycling of Waste from Electrical and Electronic Equipment (European "WEEE Directive" effective August 2005).
Manufactured for: Hispec Electrical Products Ltd
INCIDENTAL, CONTINGENT OR CONSEQUENTIAL
ANY KIND RESULTING FROM A FIRE. THE EXCLUSIVE
FOR BREACH OF THE LIMITED WARRANTY CONTAINED
IS THE REPAIR OR REPLACEMENT OF THE DEFECTIVE
. IN NO CASE SHALL
www.hispec.co.uk
of purchase, postage and return
HISPEC ELECTRICAL PRODUCTS
REMEDY PRESCRIBED BY
YOUR SMOKE ALARMS IS
DISABILITY, LIFE OR OTHER
APPROPRIATE COVERAGE IS YOUR
YOUR INSURANCE AGENT.
ghts.
Ver: September -2017
Loading...