Hirschmann RSPE30, RSPE35, RSPE32, RSPE37 User Manual

Installation RSPE30/32/35/37
Release 16 04/2019
Technical support
https://hirschmann-support.belden.com
Installation Industrial Ethernet Rail Switch Power
RSPE30/32/35/37
26.04.2019
Installation RSPE30/32/35/37
Release 16 04/2019
The naming of copyrighted trademarks in this manual, even when not specially indicated, should not be taken to mean that these names may be considered as free in the sense of the trademark and tradename protection law and hence that they may be freely used by anyone.
© 2019 Hirschmann Automation and Control GmbH
Manuals and software are protected by copyright. All rights reserved. The copying, reproduction, translation, conversion into any electronic medium or machine scannable form is not permitted, either in whole or in part. An exception is the preparation of a backup copy of the software for your own use.
The performance features described here are binding only if they have been expressly agreed when the contract was made. This document was produced by Hirschmann Automation and Control GmbH according to the best of the company's knowledge. Hirschmann reserves the right to change the contents of this document without prior notice. Hirschmann can give no guarantee in respect of the correctness or accuracy of the information in this document.
Hirschmann can accept no responsibility for damages, resulting from the use of the network components or the associated operating software. In addition, we refer to the conditions of use specified in the license contract.
You can get the latest version of this manual on the Internet at the Hirschmann product site (www.hirschmann.com).
Hirschmann Automation and Control GmbH Stuttgarter Str. 45-51 72654 Neckartenzlingen Germany
Installation RSPE30/32/35/37
Release 16 04/2019
3
Contents
Safety instructions 6
About this manual 18
Key 19
1 Description 20
1.1 General description 20
1.2 Device name and product code 21
1.3 Device views 25
1.3.1 Front view 25
1.3.2 Rear view 26
1.4 Power supply 27
1.4.1 Supply voltage with the characteristic value K9 27
1.4.2 Supply voltage with the characteristic value KK 27
1.4.3 Supply voltage with the characteristic value CC 27
1.4.4 Supply voltage with the characteristic value PP 27
1.5 Ethernet ports 28
1.5.1 10/100 Mbit/s twisted pair port 29
1.5.2 Gigabit combo port 29
1.5.3 100 Mbit/s F/O port (optional) 30
1.5.4 Support of PoE(+) 31
1.6 Display elements 32
1.6.1 Device state 32
1.6.2 Media module status 33
1.6.3 Port status 34
1.7 Management interfaces 36
1.7.1 V.24 interface (external management) 36
1.7.2 SD card interface 36
1.7.3 USB interface 37
1.8 Signal contact 37
2 Installation 38
2.1 Checking the package contents 38
2.2 Installing the SD card (optional) 38
4
Installation RSPE30/32/35/37
Release 16 04/2019
2.3 Mounting a cover panel or a media module 39
2.3.1 Mounting a cover panel 39
2.3.2 Mounting a media module 39
2.4 Installing and grounding the device 39
2.4.1 Installing the device onto the DIN rail 40
2.4.2 Grounding the device 41
2.5 Installing an SFP transceiver (optional) 41
2.6 Connecting the terminal blocks 42
2.6.1 Supply voltage with the characteristic value K9 42
2.6.2 Supply voltage with the characteristic value KK 43
2.6.3 Supply voltage with the characteristic value CC 45
2.6.4 Supply voltage with the characteristic value PP 46
2.6.5 Signal contact 47
2.7 Operating the device 48
2.8 Connecting data cables 48
2.9 Filling out the inscription label 49
3 Making basic settings 50
4 Monitoring the ambient air temperature 51
5 Maintenance and service 52
6Disassembly 53
6.1 Removing the device 53
6.2 Removing an SFP transceiver (optional) 54
6.3 Removing a media module (optional) 54
7 Technical data 55
7.1 General technical data 55
7.2 Dimension drawings 59
7.3 EMC and immunity 61
7.4 Network range 64
7.5 Power consumption/power output 68
7.6 Scope of delivery, order numbers and accessories 68
Installation RSPE30/32/35/37
Release 16 04/2019
5
8 Underlying technical standards 71
A Further support 72
6
Installation RSPE30/32/35/37
Release 16 04/2019
Safety instructions
General safety instructions
You operate this device with electricity. Improper usage of the device entails the risk of physical injury or significant property damage. The proper and safe operation of this device depends on proper handling during transportation, proper storage and installation, and careful operation and maintenance procedures. Before connecting any cable, read this document, and the safety
instructions and warnings.
Operate the device with undamaged components exclusively.The device is free of any service components. In case of a damaged
or malfunctioning device, turn off the supply voltage and return the device to Hirschmann for inspection.
Certified usage
Use the product only for the application cases described in the
Hirschmann product information, including this manual.
Operate the product only according to the technical specifications.
See “Technical data” on page 55.
Connect to the product only components suitable for the requirements
of the specific application case.
Installation site requirements
Install the device in a fire enclosure according to EN 60950-1.Only for device variants featuring supply voltage with characteristic
value K9 or KK: Install this device solely in a switch cabinet or in an operating site with restricted access, to which maintenance staff have exclusive access.
Install the device at ambient temperatures greater than +113 °F
(+45 °C) in “restricted access locations” based on EN 60950-1 exclusively.
WARNING
UNCONTROLLED MACHINE ACTIONS
To avoid uncontrolled machine actions caused by data loss, configure all the data transmission devices individually. Before you start any machine which is controlled via data transmission, be sure to complete the configuration of all data transmission devices.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Installation RSPE30/32/35/37
Release 16 04/2019
7
Device casing
Only technicians authorized by the manufacturer are permitted to open the casing. Never insert pointed objects (narrow screwdrivers, wires, etc.) into the
device or into the connection terminals for electric conductors. Do not touch the connection terminals.
Keep the ventilation slits free to ensure good air circulation.Mount the device in the vertical position.At ambient air temperatures > 140 °F (+60 °C):
The surfaces of the device housing may become hot. Avoid touching the device while it is operating.
Qualification requirements for personnel
Only allow qualified personnel to work on the device.
Qualified personnel have the following characteristics:
Qualified personnel are properly trained. Training as well as practical
knowledge and experience make up their qualifications. This is the prerequisite for grounding and labeling circuits, devices, and systems in accordance with current standards in safety technology.
Qualified personnel are aware of the dangers that exist in their work.Qualified personnel are familiar with appropriate measures against
these hazards in order to reduce the risk for themselves and others.
Qualified personnel receive training on a regular basis.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the device.
Ground the device before connecting any other cables.Disconnect the grounding only after disconnecting all other cables.Always ground the device via the grounding screw.
Shielding ground
The overall shield of a connected shielded twisted pair cable is connected to the grounding connector on the front panel as a conductor. Beware of possible short circuits when connecting a cable section with
conductive shielding braiding.
Requirements for connecting electrical wires
Before connecting the electrical wires, always verify that the
requirements listed are complied with.
8
Installation RSPE30/32/35/37
Release 16 04/2019
Requirements for connecting the signal contact
Requirements for connecting the supply voltage
All of the following requirements are complied with:
The electrical wires are voltage-free.The cables used are permitted for the temperature range of the application case.
Table 1: Requirements for connecting electrical wires
All of the following requirements are complied with:
The voltage connected complies with the requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See “General technical data” on page 55.
Table 2: Requirements for connecting the signal contact
Device variant Requirements All variants All of the following requirements are complied with:
The supply voltage corresponds to the voltage specified on the type
plate of the device.
The power supply conforms to overvoltage category I or II.The power supply has an easily accessible disconnecting device (for
example a switch or a plug). This disconnecting device is clearly identified. So in the case of an emergency, it is clear which disconnecting device belongs to which power supply cable.
The cross-section of the ground conductor is the same size as or
bigger than the cross-section of the power supply cables.
Relevant for North America:
The power supply cables are suitable for ambient air temperatures of at least 167 °F (75 °C). The power supply cable wires are made of copper.
Table 3: Requirements for connecting the supply voltage
Installation RSPE30/32/35/37
Release 16 04/2019
9
Only for device variants featuring supply voltage with the characteristic value CC:
If you connect 2 independent power sources, verify that the minus terminal is grounded. Failure to follow this instruction can result in equipment damage.
The wire diameter of the power supply cable is at least 1 mm² (North America: AWG16) on the supply voltage input.
The following requirements are alternatively complied with: Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) as per EN 60950-1.
Alternative 2 Relevant for North America:
The power supply complies with the requirements according to NEC Class 2.
Alternative 3 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage (SELV) as per IEC/EN 60950-1.
A fuse suitable for DC voltage is located in the
plus conductor of the power supply. The minus conductor is on ground potential. Otherwise, a fuse is also located in the minus conductor. Regarding the properties of this fuse:
See “General technical data” on page 55.
Device variant Requirements
Table 3: Requirements for connecting the supply voltage
10
Installation RSPE30/32/35/37
Release 16 04/2019
Supply voltage
The supply voltage is connected to the device casing through protective elements exclusively. For supply voltage connections with protective conductor connection:
First connect the protective conductor before connecting the wires for the supply voltage.
Exclusively for device variants featuring supply voltage with characteristic value PP:
If you connect 2 independent power sources, verify that the plus terminal of the power sources is not connected to each other. Failure to follow these instructions can result in equipment damage.
The wire diameter of the power supply cable is at least 1 mm² (North America: AWG16) on the supply voltage input.
The following requirements are alternatively complied with: Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) as per EN 60950-1.
Alternative 2 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage (SELV) as per IEC/EN 60950-1.
A fuse suitable for DC voltage is located in the
plus conductor of the power supply. The minus conductor is on ground potential. Otherwise, a fuse is also located in the minus conductor. Regarding the properties of this fuse:
See “General technical data” on page 55.
Only for device variants featuring supply voltage with characteristic value K9 or KK:
All of the following requirements are complied with:
Supply with DC voltage:
A fuse suitable for DC voltage is located in the plus conductor of the power supply. The minus conductor is on ground potential. Otherwise, a fuse is also located in the minus conductor. Regarding the properties of this fuse:
See “General technical data” on page 55.
The wire diameter of the power supply cable is at least 1 mm² (North America: AWG16) on the supply voltage input.
Supply with AC voltage:
A fuse is located in the outer conductor of the power supply. The neutral conductor is on ground potential at both voltage inputs. Otherwise, a fuse is also located in the neutral conductor. Regarding the properties of this fuse:
See “General technical data” on page 55.
The wire diameter of the power supply cable is at least 0.75 mm² (North America: AWG18) on the supply voltage input.
Device variant Requirements
Table 3: Requirements for connecting the supply voltage
Installation RSPE30/32/35/37
Release 16 04/2019
11
ATEX directive 2014/34/EU – specific regulations for safe
operation
Relevant for RSPE devices when operating in explosive gas atmospheres according to ATEX directive 2014/34/EU, the following applies:
List of standards:
EN 60079-0:2012, A11:2013 EN 60079-15:2010 Certificate No.: DEKRA 15ATEX0016X
Use only device variants featuring supply voltage with characteristic
value CC.
Make sure that the device has the following label:
II 3G Ex nA IIC T4 Gc DEKRA 15ATEX0016X
for RSPE types
Ambient rating and temperature code for RSPE types:
T4: 0 °C Ta +60 °C for “S” types or T4: 40 °C Ta +70 °C for “T” or “E” types
The modules shall be installed in a suitable enclosure in accordance
with IEC 60079-15 providing a degree of protection of at least IP54 according to IEC 60529, taking into account the environmental conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching point of the conductors, the temperature specification of the selected cable and cable entries shall be in compliance with the actual measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
DIP switches shall be switched exclusively in dead-voltage state.
The USB port shall remain disconnected.
12
Installation RSPE30/32/35/37
Release 16 04/2019
Relevant for use in explosion hazard areas (Hazardous
Locations, Class I, Division 2):
The relay connections are to be installed and used within their Entity Parameters as per Control Drawing 000182303DNR.
Avertissement - Risque d'explosion - Ne pas débrancher tant que le circuit est sous tension à moins que l'emplacement soit connu pour ne contenir aucune concentration de gaz inflammable.
Avertissement - Risque d'explosion - La substitution de tout composant peut rendre ce matériel incompatible pour une utilisation en classe I, division 2.
Installation RSPE30/32/35/37
Release 16 04/2019
13
Control Drawing for RSPE devices according to Class , Division 2 Hazardous Locations Rev.: 1 Document No.: 000182303DNR Page 1/2
For Use in Hazardous Locations Class I Division 2 Groups A, B, C, D:
Only allowed for RSPE/RSPM model No´s. which are individually labeled “FOR USE IN HAZARDOUS LOCATIONS”.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, and D OR non-hazardous locations only.
Nonincendive  eld wiring circuits must be wired in accordance with the National Electrical Code (NEC), NFPA 70, article 501.
WARNING – EXPLOSION HAZARD Substitution of any components may impair suitability for hazardous locations or explosive atmospheres.
WARNING – EXPLOSION HAZARD Do not disconnect equipment unless power has been switched off or the area is known to be known to be non-hazardous.
14
Installation RSPE30/32/35/37
Release 16 04/2019
Control Drawing for RSPE devices according to Class , Division 2 Hazardous Locations Rev.: 1 Document No.: 000182303DNR Page 2/2
Ordinary Location,
Non-Hazardous Area,
Non-Explosive Atmosphere
Explosive Atmosphere Class , Division 2 Groups A, B, C, D Hazardous Location
RSPE - Industrial Ethernet
Rail Switch Power Enhanced
Relay
USB
P1
P2
The earth conductor must
be at least of the same wire size (mm² or
AWG)
as the supply conductors.
Temperature Code: T4 Ambient Temperature rating: Ta: 0 °C to +60 °C for “S” temperature types Ta: í40 °C to +70 °C for “T” or “E” temperature types
(Refer to the temperature code of the type designation on the device.)
Power Supply connectors
*) Notes:
The nonincendive  eld wiring circuit concept allows interconnection
of nonincendive  eld wiring apparatus and associated nonincendive  eld wiring apparatus using any of the wiring methods permitted for unclassi ed locations when certain parametric conditions are met.
Capacity: Ca Ci + C
Cable
; Inductivity: La Li + L
Cable
WARNING!
The USB is for temporary connection only, for maintenance
use. Do not use, connect or disconnect unless the area is known to be non-hazardous. Connection or disconnection in an explosive atmosphere could result in an explosion.
The maximum cable length has to be determined as follows:
(a) max. Cable Length < (La í Li) / Cable
L
(”CableL” denotes the inductance per unit length of used cable) and
(b) max. Cable Length < (Ca í Ci) / Cable
C
(“CableC” denotes the capacitance per unit length of used cable)
The lower value of (a) and (b) is to apply.
Relay contacts: Equipment with nonincendive  eld wiring parameters. Polarity is not relevant.
The relay terminals are dependent upon the following
Entity parameters:
U
i
I
i
C
i
L
i
30 V 90 mA 2 nF 1 H
Installation RSPE30/32/35/37
Release 16 04/2019
15
IECEx – Certification Scheme for Explosive Atmospheres
For RSPE devices labeled with an IECEx certificate number, the following applies:
List of standards: IEC 60079-0:2011 + Cor.2012 + Cor.2013 IEC 60079-15:2010
The equipment is suitable for use in an area with maximum pollution
degree 2, as defined in IEC 60664-1.
Make sure that the device has the following label:
Ex nA IIC T4 Gc IECEx DEK 15.0013X
for RSPE types
Environmental class and temperature code for RSPE types:
T4: 0 °C Ta +60 °C for “S“ types or T4: 40 °C Ta +70 °C for “T“ or “E“ types
The modules shall be installed in a suitable enclosure in accordance
with IEC 60079-15 providing a degree of protection of at least IP54 according to IEC 60529, taking into account the environmental conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching point of the conductors, the temperature specification of the selected cable and cable entries shall be in compliance with the actual measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.
16
Installation RSPE30/32/35/37
Release 16 04/2019
CE marking
The labeled devices comply with the regulations contained in the following European directive(s):
In accordance with the above-named EU directive(s), the EU conformity declaration will be at the disposal of the relevant authorities at the following address:
Hirschmann Automation and Control GmbH Stuttgarter Str. 45-51 72654 Neckartenzlingen Germany www.hirschmann.com
The product can be used in the industrial sector.
Interference immunity: EN 61000-6-2Emitted interference: EN 55032Reliability: EN 60950-1
You find more information on technical standards here:
“Technical data” on page 55
Warning! This is a class A device. This device can cause interference in living areas, and in this case the operator may be required to take appropriate measures.
Note: The assembly guidelines provided in these instructions must be strictly adhered to in order to observe the EMC threshold values.
LED or laser components
LED or LASER components according to IEC 60825-1 (2014): CLASS 1 LASER PRODUCT CLASS 1 LED PRODUCT
Device variant Directive All variants 2014/30/EU (EMC)
Directive of the European Parliament and the council for standardizing the regulations of member states with regard to electromagnetic compatibility.
2011/65/EU (RoHS) Directive of the European Parliament and of the Council on the restriction of the use of certain hazardous substances in electrical and electronic equipment.
Only for device variants featuring supply voltage with characteristic value K9 or KK:
2014/35/EU Directive of the European Parliament and of the Council on the harmonisation of the laws of the Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits.
Installation RSPE30/32/35/37
Release 16 04/2019
17
FCC note:
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference; (2) this device must accept any interference received, including interference that may cause undesired operation. Appropriate testing has established that this device fulfills the requirements of a class A digital device in line with part 15 of the FCC regulations. These requirements are designed to provide sufficient protection against interference when the device is being used in a business environment. The device creates and uses high frequencies and can also radiate these frequencies. If it is not installed and used in accordance with this operating manual, it can cause radio transmission interference. The use of this device in a residential area can also cause interference, and in this case the user is obliged to cover the costs of removing the interference.
Recycling note
After usage, this device must be disposed of properly as electronic waste, in accordance with the current disposal regulations of your county, state, and country.
18
Installation RSPE30/32/35/37
Release 16 04/2019
About this manual
The “Installation” user manual contains a device description, safety instructions, a description of the display, and the other information that you need to install the device.
Documentation mentioned in the “User Manual Installation” that is not supplied with your device as a printout can be found as PDF files for downloading on the Internet at https://www.doc.hirschmann.com
Installation RSPE30/32/35/37
Release 16 04/2019
19
Key
The symbols used in this manual have the following meanings:
Listing
Work step
Subheading
20
Installation RSPE30/32/35/37
Release 16 04/2019
1 Description
1.1 General description
The RSPE30/32/35/37 devices are designed for the special requirements of industrial automation. They meet the relevant industry standards, provide very high operational reliability, even under extreme conditions, and also long-term reliability and flexibility.
You can choose from between a wide range of variants. You have the option to set up your device individually based on different criteria:
Support of PoE(+)Temperature rangeSupply voltage rangeCertificationsRedundancy functions
You have the option of choosing various media to connect to the end devices and other network components:
Multimode optical fiberSinglemode optical fiberTwisted pair cable
The device is mounted by latching in place on a DIN rail. The devices work without a fan. By using media modules, you obtain up to 16 additional Fast Ethernet ports. You will find more information on the media modules in the “User Manual for Installation of RSPM”. You find these manuals as PDF files on the Internet at http://
www.doc.hirschmann.com
The redundancy concept allows the network to be reconfigured quickly.
There are convenient options for managing the device. Manage your devices via:
Web browserSSHTelnet
Installation RSPE30/32/35/37
Release 16 04/2019
21
V.24 interface (locally on the device)Network management software (for example Industrial HiVision)
The Network Management Software Industrial HiVision provides you with options for smooth configuration and monitoring. You find further information on the Internet at the Hirschmann product pages: http://
www.hirschmann.com/en/QR/INET-Industrial-HiVision
The devices provide you with a large range of functions, which the manuals for the operating software inform you about. You find these manuals as PDF files on the Internet at http://www.doc.hirschmann.com The Hirschmann network components help you ensure continuous communication across all levels of the company.
1.2 Device name and product code
The device name corresponds to the product code. The product code is made up of characteristics with defined positions. The characteristic values stand for specific product properties. You have numerous options of combining the device characteristics. You can determine the possible combinations using the Configurator which is available in the Belden E-Catalog (www.e-catalog.beldensolutions.com) on the web page of the device.
Item Characteristic Character
istic value
Description
1 ... 4 Product RSPE Rail Switch Power Enhanced 5 Data rate 3 10/100 Mbit/s
and 10/100/1000 Mbit/s
6 Hardware type 0 Standard
2 Standard with PoE(+) 5 Extended redundancy
7 Extended redundancy with PoE and PoE+ 7 (hyphen) – 8 ... 9 Number
Fast Ethernet ports
24 24 ×
10 ... 11 Number
Gigabit Ethernet ports
04 4 ×
12 ... 14 Configuration of the
uplink ports
4O7 4 × Combo port for 10/100/1000 Mbit/s
connections
15 ... 17 Configuration of the
other ports
T 8 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
99 2 × free slot for media module 18 (hyphen)
Table 4: Device name and product code
22
Installation RSPE30/32/35/37
Release 16 04/2019
19 Temperature range S Standard +32 °F ... +140 °F (0 °C ...
+60 °C)
T Extended 40 °F ... +158 °F
(40 °C ... +70 °C)
E Extended with
Conformal Coating
40 °F ... +158 °F (40 °C ... +70 °C)
20 ... 21 Supply voltage CC 2 voltage inputs for redundant power supply
Rated voltage range DC: 24 V DC ... 48 V DC
K9 1 voltage input
Rated voltage range AC: 110 V AC ... 230 V AC, 50 Hz ... 60 Hz
Rated voltage range DC: 60 V DC ... 250 V DC
KK 2 voltage inputs for redundant power supply
Rated voltage range AC: 110 V AC ... 230 V AC, 50 Hz ... 60 Hz
Rated voltage range DC: 60 V DC ... 250 V DC
PP PoE 2 voltage inputs for redundant power
supply Rated voltage range
47 V DC ... 57 V DC
PoE+ 2 voltage inputs for redundant power
supply Rated voltage range DC:
53 V DC ... 57 V DC
22 ... 23 Certificates and
declarations
You will find detailed information on the certificates and declarations applying to your device in a separate overview.
See table 5 on page 24.
24 ... 25 Software packages 99 Reserved 26 ... 27 Customer-specific
version
HH Hirschmann Standard
28 Hardware
configuration
S Standard
MFast MRP
PPRP
HHSR
D From software version 05.0 onward:
Hirschmann DLR
Note: You can exchange software with each other on the
following device variants:
M
P
H
R
Item Characteristic Character
istic value
Description
Table 4: Device name and product code
P
++
Installation RSPE30/32/35/37
Release 16 04/2019
23
29 Software configuration E Entry (without configuration)
B Diagnostic User (BDEW) PProfinet I Ethernet/IP D DLR (pre-configuration)
30 ... 31 Software level 2S HiOS Layer 2 Standard
2A HiOS Layer 2 Advanced 3S HiOS Layer 3 Standard
32 ... 36 Software version 03.1. Software version 03.1
XX.X. Current software version
37 ... 38 Maintenance 00 Bugfix version 00
XX Current bugfix version
Item Characteristic Character
istic value
Description
Table 4: Device name and product code
Loading...