Hirschmann Electronics, Inc. makes no warranty of any kind with regard to this material, including, but
not limited to, the implied warranties of merchantability and/or its fitness for a particular purpose.
Hirschmann will not be liable for errors contained in this manual or for incidental or consequential
damages in connection with the furnishing, performance, or use of this manual. This document
contains proprietary information, which is protected by copyright, and all rights are reserved.
No part of this document may be photocopied, reproduced, or translated to another language without
the prior written consent of Hirschmann.
Hirschmann reserves proprietary rights to all drawings, photos and the data contained therein. The
drawings, photos and data are confidential and cannot be used or reproduced without the written
consent of Hirschmann. The drawings and/or photos are subject to technical modification without
prior notice.
All information in this document is subject to change without notice.
This service manual is designed to assist a service or maintenance person in identifying system
problem areas or malfunctions. A digital voltmeter with the capability to measure current will be
required, along with standard maintenance and service tools. NOTE: Knowledge of how to use a
voltmeter to measure both voltage and current is assumed.
REFERENCE:
For system operation, refer to the consoles operator’s manual 031-300-190-147.
2 WARNINGS
The LMI is an operational aid that warns a crane operator of approaching overload conditions and
over hoist conditions that could cause damage to equipment and personnel.
The device is not, and shall not be, a substitute for good operator judgment, experience and use of
accepted safe crane operating procedures.
The responsibility for the safe crane operation shall remain with the crane operator who shall ensure
that all warnings and instructions supplied are fully understood and observed.
Prior to operating the crane, the operator must carefully and thoroughly read and understand the
information in this manual to ensure that he knows the operation and limitations of indicator and
crane.
Proper functioning depends upon proper daily inspection and observance of the operating
instructions set forth in this manual. Refer to Section 6. Pre-Operation Inspection and Calibration Verificationof the operator’s manual.
The LMI can only work correctly, if all adjustments have been properly set. For correct
adjustment, the operator has to answer thoroughly and correctly all questions asked during
the setup procedure in accordance with the real rigging state of the crane. To prevent
material damage and serious or even fatal accidents, the correct adjustment of the LMI has
to be ensured before starting the crane operation.
The iFLEX5 system is a CAN bus system made up of a central microprocessor unit, operating
console, length/angle sensor, pressure transducers, and anti-two block switches. All components and
sensors are equipped with CAN bus controllers.
The PAT Load Moment Indicator system operates on the principle of reference/real comparison. The
real value, resulting from the pressure measurement is compared with the reference data, stored in
the central processor memory and evaluated in the microprocessor. When limits are reached, an
overload warning signal is generated at the operator’s console. At the same time, the aggravating
crane movements, such as hoist up, telescope out and boom down, will be stopped.
The fixed data regarding the crane, such as capacity charts, boom weights, centers of gravity and
dimensions are stored in memory chips in the central processor unit. This data is the reference
information used to calculate the operating conditions.
Boom length and boom angle are registered by the length/angle sensor, mounted inside the cable
reel, which is mounted on the boom. The boom length is measured by the cable reel cable, which also
serves as an electrical conductor for the anti two-block switches.
The crane load is measured by pressure transducer block attached to the piston and rod side of the
hoist cylinders.
The interactive user guidance considerably simplifies the input of operating modes as well as the
setting of geometry limit values.
3.2 DESCRIPTION OF A CAN BUS SYSTEM
CAN stands for “Controller Area Network”. Its intended use is as a serial bus system for a network of
controllers. Each controller connected through a CAN chip is called a "node" and is mostly used to
acquire data from a sensor. All nodes are connected to a common bus and all nodes are able to
simultaneously read the data on that bus. Also, all nodes are able to transmit data on that bus
however only one node at a given time has write access to the bus. If the message is relevant, it will
be processed; otherwise it is ignored. The unique identifier also determines the priority of the
message. The lower the numerical value of the identifier, the higher the priority.
The cable bus is a twisted pair of shielded wire. Data can be transmitted in blocks from 0-8
bytes at a maximum transfer rate of 1 Mbit/s for networks up to 40 meters. For longer network
distances the maximum transfer rate must be reduced to 50 Kbit/s for a 1 km network distance.
CAN will operate in extremely harsh environments and the extensive error checking
mechanisms ensure that any transmission errors are detected.
Pressure Transducer: The pressure transducer converts hydraulic pressure into an electric signal.
A pressure transducer block houses two transducers, CAN bus converter board, and two bus
connectors. One pressure transducer is connected to the piston side of the lift cylinder and the other
to the rod side.
The Length-Angle Transducer: The length-angle sensor (LWG), often referred to as the “cable reel”,
is a combination of two transducers in one box, installed on the base section of the boom. It
measures the length and the angle of the boom.
A reeling drum drives a potentiometer, which is the length transducer. Part of the length transducer
circuit is the length cable on the drum, which is a multi-conductor cable. It is connected to the antitwo-block switch at the boom head and to a slip ring body in the LWG.
The angle transducer is a potentiometer driven by a weighted pendulum that is oil damped. Both
length and angle transducer are connected to a CAN bus controller board, which is connected to the
bus system.
Anti-Two-Block Switch: The anti-two-block switch monitors the load block and it’s relationship with
the head of the boom. In working condition the switch is closed. When the load block strikes the
weight the circuit opens, disengaging a relay output to the lock out solenoid valves, where applicable.
To check the cable for damage, (short circuit to ground) there is a 4.7k resistor between ground and
the contact of the switch, to give a signal back to the central unit. The weight at the anti-two-block
switch keeps the switch closed until the load block strikes it.
Console: The graphic console displays all geometrical information such as length and angle of main
boom, working radius and head height of the boom. It also displays the actual load and the maximum
load permitted by load chart. Furthermore, it has an alarm horn, a warning light for overload, and a
pre-warning light. The graphic display allows for a simple interactive configuration setup, as well as
sensor calibration (zero adjustment), and troubleshooting sensor output screen. The console has a
warning light for anti-two-block conditions and an override switch for overload or anti-block condition.
Refer to Operator’s Handbook for detailed operation of the console.
Central Unit: Inside the central unit there is a CPU and connection board. The board has a hard
mounted connector for power, ground, bus controller, and slew indication. The board has a green
LED, indicating relay energized and a communication LED that flashes through red, yellow, and green
colors.
Slew Potentiometer: This component is not supplied by PAT/Hirschmann. It is part of the electrical
swivel (slip ring assembly). The potentiometer has two wipers which are used to determine the
slewing angle (rotational positioning) of the super structure in relation to the carrier. The slew input to
the central unit is not a CAN signal, but rather two 4..20mA analog signals.
So, what’s wrong? Assuming you are reading these pages because of some kind of problem with the
PAT system, let us try to guide you quickly to solving the problem. In most cases, your problem will
fall under the following categories:
4.1 I HAVE AN ERROR CODE INDICATED ON THE CONSOLE
Please go to section Error Codes!
4.2 THE DISPLAYED ANGLE DOES NOT MATCH THE ACTUAL BOOM ANGLE
Start in section Angle Sensing to check the indicated angle.
4.3 THE DISPLAYED LENGTH DOES NOT MATCH THE ACTUAL BOOM LENGTH
Start in section Length Sensing to check the indicated length.
4.4 THE DISPLAYED SLEWING DOES NOT MATCH THE ACTUAL SLEWING ANGLE
Refer to section Slewing Sensing to check the slew sensor.
4.5 THE DISPLAYED LOAD DOES NOT MATCH THE ACTUAL LOAD
Please note that the indicated load is calculated by the system from the geometry information in the
computer, the operator’s selections, and all the sensor inputs. If the load display is off, it can therefore
be due to an error in any or several of these inputs! Refer to section Load sensing to narrow down the
source of your problem.
4.6 THE CONSOLE DISPLAY IS BLANK
If the console does not show any sign at all (no lights, no buzzer, no display), the problem is either in
the wiring between console and central unit, or the console itself. Refer to section No console display
for further troubleshooting.
4.7 I HAVE AN A2B PROBLEM
Please go to sectionA2B PROBLEM
4.8 I HAVE A CAN-BUS PROBLEM
Please go to section CAN-Bus Communication!
4.9 I NEED TO IDENTIFY A SPARE PART
Please go to the Spare Part Listings!
4.10 I HAVE NOTICED WATER IN SOME PART OF THE SYSTEM
The System measures the angle of the main boom of the machine with an angle sensor. The angle
sensor is contained within the cable reel, located on the left side of the main boom.
Block Diagram
The signal runs from the angle sensor to the Can-Bus converter board, both located in the cable reel.
From there, it travels as digital information on the CAN-Bus to the pressure transducer, which acts as
a T-connector to the main CAN-Bus running to the central unit.
So, what do you do when you are having a problem with your angle read-out?
Start by verifying the angle display. Refer to the section “Troubleshooting A Sensor Problem Using
The Display” to call up the sensor signal on your console display. The CAN-Bus is digital and as such
will either transmit the signal correctly or not at all. If your readings are off, you have to determine
what is causing the problem (reference the following flow charts).
CAN-Bus electronics in cable reel.
The angle sensor has a potentiometer built in that is driven by a pendulum. As the angle changes, so
will the pendulum and with it the potentiometer’s axle. The converter board supplies a constant
voltage of 5V to the angle sensor and in return monitors the voltage of the potentiometer. The terminal
used is X21. The angle sensor is connected as follows:
The system measures the length of the main boom of the machine with a length sensor. The length
sensor is contained within the cable reel, located on the left side of the main boom.
Block Diagram
The signal runs from the length sensor to the CAN-Bus converter board, both
located in the cable reel. From there, it travels as digital information on the
CAN-Bus to the pressure transducer, which acts as a T-connector to the main
CAN-Bus running to the central unit.
So, what do you do when you are having a problem with your length read-out?
Start by verifying the length display. Refer to the section “Troubleshooting A Sensor Problem Using
The Display” to call up the sensor signal on your console display. The CAN-Bus is digital and as such
will either transmit the signal correctly or not at all. If your readings are off, you have to determine
what is causing the problem (reference the following flow charts).
CAN-Bus electronics in cable reel.
The length sensor has a potentiometer built in that is driven by a gear drive from the cable drum. As
the length changes, the cable drum will turn and with it the potentiometer’s axle. The converter board
supplies a voltage of about 4.7V to the length potentiometer and in return monitors the output voltage
of the potentiometer. The terminal used is X20. The length sensor is connected as follows:
Fully retract the boom and turn the
screw of the length potentiometer
with a small screwdriver counterclockwise to a soft stop, bringing the
sensor voltage to 0V (+/- 0.1 Volt).
Measure voltage between
Pin 5 (-) and Pin 3 (signal)
of terminal X20 and compare.
Return to the indication screen and again
compare the indicated and actual length.
The length sensor returns a voltage between 0.16V at 0 turns of the length pot (= fully retracted) and
4.84V at 10 turns. How many turns you get at full extension depends on the gear ratio, the boom
length, the length cable used and the spooling pattern, so we cannot provide a standard table for it.
What we can give you for trouble-shooting, however is the following table that shows the expected
output voltage (measured between X20-5 and X20-3 Signal) for each complete turn of the length
potentiometer. Note that this does not sync to the number of turns of the cable reel, though:
Note: Actual voltages will vary slightly.
For the boom control system, the length sensors are the same as described above with the exception
of cable reel internals (location of hardware, wiring, and gear wheels). Refer to the LWG520 and
LG152 spare part list for these differences.
If the reading is slightly off, small variations can be adjusted;
see section Service Screen For Sensor Calibration.
NO
Ensure that the pressure lines
are drained and disconnected.
Replace pressure transducers.
YES
7 PRESSURE SENSING
The System measures the pressure of the boom lift cylinder for both rod- and piston-side. Both
sensors are contained within one box that also contains the electronics needed for amplification and
creation of the CAN-Bus signal.
Block Diagram:
7.1 PRESSURE SENSING ERROR - FLOW CHART
Note: After exchanging the pressure transducer block, BOTH transducer channels need to be zeroed,
see procedure Zero-Setting The Transducer Inputs.
The signal runs from the pressure transducer as
digital information on the CAN-Bus to the central
unit.
Service Manual iFLEX5
12
0
500
1000
1500
2000
2500
3000
3500
4000
04590135180225270315360
SLEW ANGLE
MILLIVOLTS
Potentiometer 1
Potentiometer 2
0 45 90 135 180 -135 -90 -45 0
ANGLE
(deg)
SL ANG 1
(mv)
SL ANG 2
(mv)
0
717
2161
30.3
1174
2645
60
1680
3150
89.9
2158
3595
120.1
2641
3141
150.1
3144
2639
180
3595
2161
-150.1
3144
1681
-120.1
2642
1180
-90
2160
718
-60.1
1681
1168
-30
1172
1680
0
718
2161
iFLEX5
CU
Slip Ring Assembly
Slew
Potentiomet
er with (2)
outputs
Current
Converter
Modular Slew Pot - Voltage on Service Screen
Display screen
for sensor inputs
8 SLEWING SENSING
The system measures the slewing (rotational position) of the crane’s upper with a slewing sensor. The
slewing sensor is contained within the slip ring assembly.
Block Diagram
The slew potentiometer has two potentiometers built in that are driven by the slip ring axle. As the
slewing angle changes, so will the axle and with it the potentiometer’s outputs. Use the display screen
by pressing ‘i’ (info) twice to show all sensor inputs.
The table to the right show measured millivolt reading for
the slew potentiotmeter.
The slew unit output can be found on pins 8 and 9. In order to
measure current, however, you must disconnect a pin and
measure in line (between the cable from the slew unit and the
central unit). *The two outputs will vary as shown in chart below.
NO
YES
Ensure that the slew pot unit
is supplied with crane voltage.
Pin 7 must carry crane
voltage and Pin 2 is GND.
You can also leave the wires connected as use your meter in
Voltage-mode to measure the output signals. In this case, you
will see the 4…20mA range as a 1.1 to 5.5 Volt range.
If the voltage or currents do not fall in line with the
charts and tables shown below, and no system errors
are present, the problem may be mechanical.
Open the slip ring unit and determine if the slew potentiometer is set correctly.
The converter board is supplied with 12V from the central unit. The potentiometer and the board
output two signals between 4 and 20mA that go to the central unit. You can measure them at the 12pin crane interface connector.
8.1 SLEW SENSING ERROR - FLOW CHART
(When the crane is over front, you should
see about 4mA in one channel (wire #2) and
12mA in the other channel (wire #3)).
Please note that the load displayed by the LMI is not a direct measurement, but a calculated value
that is based on a lot of factors. Outside of the measured values (sensors), those include:
Operator settings such as:
o Operating mode/configuration
o Parts of Line/Reeving
Rigging parts such as:
Hookblock weight
Sling weights, etc.
Tip height (length of load line used)
Boom weights
Boom attachments such as
Stowed jibs
Auxiliary boom nose, etc.
Pin 1 Shield
Pin 2 + Ub
Pin 3 Ground
Pin 4 CAN High
Pin 5 CAN Low
Pressure Transducer
E63
iFLEX5
CU
Cable Reel
CAN-Bus
Converter
E65
E64
E61
E62
12 CANN-BUS COMMUNICATION
The System measures the length of the main boom, the angle of the main boom, the pressures of the
lift cylinder, and the A2B state of the machine via a CAN-Bus connection. Since this is a digital bus
connection, it is not possible to measure the signals on the bus with a multimeter. Instead, the LMI
provides you with error codes that give you an indication of the bus state.
The error codes are one of the following:
E61 Error in the CAN bus data transfer for all CAN units
E62 Error in the can bus data transfer of the pressure transducer sensor unit
E63 Error in the can bus pressure transducer sensor unit
E64 Error in the can bus data transfer of the length/angle sensor unit
E65 Error in the can bus length/angle sensor unit
Block Diagram
The block diagram tries to clarify that: If the CU does not see any CAN-Bus component, it will report
an E61. If it sees only the cable reel, it will report an E62 (pressure transducer missing). If it sees only
the pressure transducer, it will report an E64 (cable reel missing). E63 means that the pressure
transducer is available, but is reporting an internal error. E65 means that the cable reel unit is
available, but is reporting an internal error.
So, what do you do when you are having a problem with one of those codes?
12.1 E61
In case of an E61, start by connecting the two cables on the transducer block together. If an E62
appears, the transducer block must be replaced. If an E61 appears, reconnect the cable from the
from the central unit to the transducer block. At this point, if an E61 still appears check your cabling.
You can verify that power is being supplied to the sensor by testing the CAN connectors per this
layout:
Connect the two cables on the
Transducer block together
E61
Yes
Disconnect cables and connect cable
from c/u to transducer block
E61
Yes
No
Ohm cable from c/u to the
transducer block. If cable checks
good replace c/u
Connect the cable reel can bus cable to
the transducer block. Remove can bus
connector at cable reel
E61
Yes
Replace can bus cable between
Cable reel and transducer block
No
Ohm out connector in cable reel. If connector
Checks good replace can bus converter board.
E62
Replace Transducer Block
E64
E64
Measure between pins 3 and 2 for crane voltage. If you see voltage, check all pins for continuity.
The central unit must be replaced if this cable is functioning correctly. If the E61 error code has
become an E64, connect the cable reel can bus cable to the transducer block and remove the can
bus connector at the cable reel. If this causes an E61 to appear, the can bus cable between the cable
reel and transducer block must be replaced. If an E64 remains, use the Ohm-meter to check the
connector in the cable reel. Either the connector has failed or the can bus converter boards must be
replaced.