Introduction
HIOKI IR4057B961-01
Introduction
Thank you for choosing the Hioki IR4053-10, IR4055-11, IR4056-20,
IR4056-21, and IR4057-50 Insulation Tester. To ensure your ability
to get the most out of this instrument over the long term, please
read this manual carefully and keep it available for future reference.
Hereinafter, the descriptions refer to models as shown on the
instrument.
Verifying Package Contents
When you receive the instrument, inspect it carefully to ensure that no
damage occurred during shipping. In particular, check the accessories,
panel switches, and connectors. If damage is evident, or if it fails to
operate according to the specications, contact your authorized Hioki
distributor or reseller. Conrm that these contents are provided.
□ Insulation Tester
IR4053, IR4055
IR4056
□ L9787 Test Lead
(IR4053-10 and IR4056-20 only)
IR4057-50
□□Instruction Manual
Operating Precautions
(0990A907)
□ LR6 Alkaline battery × 4
□ Neck strap
□ L9788-11 Test Lead Set with
Remote Switch
(IR4055-11 and IR4056-21 only)
1
2
3
4
5
6
7
□ L4930 Connection Cable Set
(IR4057-50 only)
□ L4938 Test Pin Set
(IR4057-50 only)
□ L4935 Alligator Clip Set
(IR4057-50 only)
付録索引
1
Verifying Package Contents
HIOKI IR4057B961-01
Options
The options listed below are available for the instrument. To order
an option, please contact your authorized Hioki distributor or
reseller.
Options are subject to change. Please check Hioki's website for the
latest information.
L9787 Test Lead (1.2 m)CAT III 600 V/CAT II 600 V, 10 A
3
L9787-91 Breaker PinCAT III 600 V, 10 A
4
L9788-10 Test Lead with Remote
5
Switch (Red)
L9788-92 Breaker PinCAT III 600 V, 2 A
6
L9788-90 Tip PinCAT III 600 V/CAT II 600 V, 2 A
7
L4930 Connection Cable Set
8
(1.2 m)
L4935 Alligator Clip SetCAT IV 600 V/CAT III 1000 V, 10 A
9
L4938 Test Pin SetCAT III 600 V/CAT II 600 V, 10 A
10
Z3210 Wireless Adapter
11
(for IR4057-50)
Maximum rated voltage and
maximum rated current
CAT III 600 V/CAT II 600 V, 2 A
CAT IV 1000 V, 2 A
CAT III 600 V/CAT II 600 V, 2 A
CAT IV 600 V/CAT III 1000 V, 10 A
–
1
2
3
4
5
6
7
付録索引
3
Notations
HIOKI IR4057B961-01
Notations
Safety notations
In this document, the severity levels of risk and hazard are classied
as follows.
DANGER
WARNING
CAUTION
IMPORTANT
Indicates an imminently hazardous situation that will
result in death or serious injury to the operator.
Indicates a potentially hazardous situation that may
result in death or serious injury to the operator.
Indicates a potentially hazardous situation that may
result in minor or moderate injury to the operator or
damage to the instrument or malfunction.
Indicates information or content that is particularly
important from the standpoint of operating or
maintaining the instrument.
Indicates a strong magnetic-eld hazard.
The effects of the magnetic force can cause
abnormal operation of heart pacemakers and/or
medical electronics.
Indicates prohibited actions.
Indicates the action which must be performed.
*
4
Additional information is presented below.
Symbols on the instrument
HIOKI IR4057B961-01
Indicates cautions and
hazards. When the symbol
is printed on the instrument,
refer to a corresponding
topic in the Instruction
Manual.
Indicates that dangerous
voltage may be present at
this terminal.
Indicates a instrument
that has been protected
throughout by double
insulation or reinforced
insulation.
Symbols for various standards
Notations
Indicates a grounding
terminal.
Indicates DC (Direct
Current).
Indicates AC
(Alternating Current).
Do not use in distribution
systems with voltage
higher than 660 V AC.
1
2
3
4
Indicates the Waste Electrical and Electronic Equipment
Directive (WEEE Directive) in EU member states.
Indicates that the product conforms to regulations set out by the
EU Directive.
Screen Display
The instrument screen displays the alphanumeric characters as follows.
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
1 2 3 4 5 6 7 8 9 0
5
6
7
付録索引
5
Notations
HIOKI IR4057B961-01
Accuracy
Hioki expresses accuracy as error limit values specied in terms of
percentages of reading and digits.
Reading
(Displayed value)
Digits
(Resolution)
Refers to the displayed value of the measuring
instrument. The limit values of reading errors are
expressed in percent of reading (% of reading, % rdg).
Refers to the smallest change in the indication on the
digital measuring instrument, i.e., the numeral one in
the rightmost place. The limit values of digit errors are
expressed in terms of digits (dgt).
Trademarks
• The Bluetooth® word mark and logos are registered trademarks
owned by Bluetooth SIG, Inc. and any use of such marks by
Hioki E.E. Corporation is under license.
Other trademarks and trade names are those of their respective
owners.
• Microsoft Excel is either registered trademarks or trademarks of
Microsoft Corporation in the United States and other countries.
6
Safety Information
HIOKI IR4057B961-01
Safety Information
This instrument is designed to conform to IEC 61010 Safety
Standards, and has been thoroughly tested for safety prior
to shipment. However, using the instrument in a way not
described in this manual may negate the provided safety
features.
Before using the instrument, be certain to carefully read the following
safety notes:
DANGER
Mishandling during use could result in injury or death,
as well as damage to the instrument. Be certain that
you understand the instructions and precautions in
the manual before use.
WARNING
Protective gear
Performing measurement using this instrument
involves live-line work. To prevent an electric shock,
use appropriate protective insulation and adhere to
applicable laws and regulations.
1
2
3
4
5
6
7
付録索引
7
Safety Information
HIOKI IR4057B961-01
Measurement Categories
To ensure safe operation of measuring instruments, IEC 61010
establishes safety standards for various electrical environments,
categorized as CAT II to CAT IV, and called measurement categories.
DANGER
• Using a measuring instrument in an environment
designated with a higher-numbered category than
that for which the instrument is rated could result in
a severe accident, and must be carefully avoided.
• Never use a measuring instrument that lacks
category labeling in a CAT II to CAT IV measurement
environment. Doing so could result in a serious
accident.
This instrument conforms to the safety requirements for CAT III 600 V
measuring instruments.
CAT II: When directly measuring the electrical outlet receptacles of the
primary electrical circuits in equipment connected to an AC electrical
outlet by a power cord (portable tools, household appliances, etc.)
CAT III: When measuring the primary electrical circuits of heavy equipment
(xed installations) connected directly to the distribution panel, and
feeders from the distribution panel to outlets.
CAT IV:
When measuring the circuit from the service drop to the service
entrance, and to the power meter and primary overcurrent
protection device (distribution panel).
Service entrance
Service drop
8
Distribution panel
CAT IV
Power meter
Internal wiring
CAT III
Fixed installation
CAT II
T
Outlet
Operating Precautions
HIOKI IR4057B961-01
Operating Precautions
Observe the following precautionary information to ensure that the
instrument can be used safely and in a manner that allows it to
perform as described in its specications.
Use of the instrument should conrm not only to its specications,
but also to the specications of all accessories, options, batteries,
and other equipment in use.
DANGER
• For your safe operation, do not connect any test
lead to the primary of the distribution panel.
• Do not short-circuit two wires to be measured by
bringing the test leads into contact with them. Arcs
or such grave accidents are likely to occur.
• To avoid short circuit or electric shock, do not touch
the metal part of the connecting test lead tip.
• To avoid electric shock, be careful to avoid shorting
live lines with the test leads tip.
If the test lead or the instrument is damaged, there
is a risk of electric shock. Perform the following
inspection before using them:
• Before using the instrument check that the coating
of the test leads are neither ripped nor torn and that
no metal parts are exposed. Using the instrument
under such conditions could result in electric
shock. Replace the test leads with those specied
by Hioki.
• Verify that the instrument operates normally to
ensure that no damage occurred during storage
or shipping. If you nd any damage, contact your
authorized Hioki distributor or reseller.
1
2
3
4
5
6
7
付録索引
9
Operating Precautions
HIOKI IR4057B961-01
WARNING
To avoid electric shock, short circuits and damage to
the instrument, observe the following precautions:
• Check the position of the rotary switch before
taking measurements.
• Disconnect the test leads from the measuring object
before switching the rotary switch.
• Do not use the instrument with circuits that exceed
its ratings or specications. Doing so may damage
the instrument, resulting in electric shock.
• Use only the specied test leads. Use of any test
lead not specied by Hioki does not allow safe
measurements.
• To prevent electrical accidents, turn off the circuit
before connecting the test leads.
• To avoid electric shock, do not exceed the lower of
the ratings shown on the instrument and test leads.
CAUTION
• The cable is hardened under the 0°C or colder
environment. Do not bend or pull it to avoid tearing its
shield or cutting cable.
• The protection rating for the enclosure of this device
(based on EN 60529) is IP40*.
* IP40:
This indicates the degree of protection provided by the enclosure of
the device against use in hazardous locations, entry of solid foreign
objects, and the ingress of water.
4: Protected against access to hazardous parts with wire measuring 1.0 mm
in diameter.
0: The equipment inside the enclosure is not protected against the harmful
effects of water.
10
Installing the instrument
HIOKI IR4057B961-01
Installing the instrument in inappropriate locations
may cause a malfunction of instrument or may give
rise to an accident. Avoid the following locations.
• Exposed to direct sunlight or high temperature
• Exposed to corrosive or combustible gases
• Exposed to a strong electromagnetic eld or
electrostatic charge
• Near induction heating systems (such as highfrequency induction heating systems and IH
cooking equipment)
• Susceptible to vibration
• Exposed to water, oil, chemicals, or solvents
• Exposed to high humidity or condensation
• Exposed to high quantities of dust particles
Operating Precautions
WARNING
1
2
3
4
CAUTION
Do not place the instrument on an unstable table or an
inclined place. Dropping or knocking down the instrument
can cause injury or damage to the instrument.
Precautions when transporting the instrument
During shipment of the instrument, handle it carefully so that it is not
damaged due to a vibration or shock.
5
6
7
付録索引
11
Operating Precautions
HIOKI IR4057B961-01
Handling the Instrument
Persons wearing electronic medical devices such
as a pacemaker should not use the 9804-01, 9804- 02
Magnet Adapter. Such persons should avoid even
proximity to the 9804-01 and 9804-02, as it may
be dangerous. Medical device operation could be
compromised, presenting a hazard to human life.
To avoid damage to the instrument, protect it from physical
shock when transporting and handling. Be especially
careful to avoid physical shock from dropping.
Test leads
• Removable sleeves are attached to the metal pins
at the end of the test leads. To prevent a short circuit
accident, be sure to use the test leads with the sleeves
attached when performing measurements in the CAT III
measurement category. Remove the sleeves before
starting CAT II measurements. You can use the test
leads with the sleeve removed for secondary side of
the circuit breakers turned off. (See “Measurement
Categories” (p. 8))
• If the sleeves are inadvertently removed during
measurement, stop the measurement. (p. 26)
DANGER
CAUTION
CAUTION
12
1
HIOKI IR4057B961-01
Overview
1.1 Product Overview
This instrument is an insulation ohmmeter that shortens work times
associated with insulation testing. It is not designed for use on
manufacturing lines and should not be used in such applications.
For manufacturing line applications, use the ST5520 Insulation
Tester.
High-speed response
• Considerably improved response time compared to previous models.
• The instrument can be used like models with a meter needle.
Enhanced comparator function
• Can be used similarly to the continuity check with a tester due to judgment
after the start of measurement being extremely short.
• The backlight lights up in red for a FAIL judgment (defective).
Low variation in measured values
• The instrument generates little variation in measured values when used in a
typical measuring environment.
Easy-to-view display
• Backlight source is a white high-intensity LED.
• Wide viewing angle LCD
High-accuracy voltage measurement function
• The instrument incorporates a DC/AC voltmeter with the same accuracy as
a card tester.
• There is no need to switch to a card tester when you need to measure
voltage.
PVΩ measurement function (IR4053 and IR4055 only)
• Insulation resistance can be measured accurately for solar battery panel.
Controls L9788-10 Test Lead with Remote
Switch (Red)
Turns on and off the backlight.
Performs zero-adjustment for the low
resistance range.
Press with the COMP key simultaneously:
congures the wireless communications
function (p. 51) (IR4057-50)
Lights up when voltage remains between
input terminals.
COMP key
HIOKI IR4057B961-01
9
RELEASE key
10
Names and Functions of Parts
Sets the comparator’s judgment reference
value.
Press with the 0
congures the wireless communications
function. (p. 51) (IR4057-50)
Press before measurement to set the instrument
to the 500 V or 1000 V range (to prevent
erroneous application of the test signal).
ADJ key simultaneously:
Ω
1
2
IR4053, IR4055
500 V↔1000 V key
1
COMP key (1 s)
2
500 V/1000 V
3
RELEASE key
(The illustration shows the IR4055)
12
Switches between 500 V and 1000 V when using
PV
range.
Ω
Congures wireless communications function
(p. 51) (IR4055)
• Press before measurement to set the instrument
to the 500 V or 1000 V range (to prevent
erroneous application of the test signal).
• Applied voltage is conrmed when PVΩ range
is set.
(Other functions are the same as
IR4056 and IR4057-50.)
3
4
5
6
7
付録索引
15
Names and Functions of Parts
HIOKI IR4057B961-01
MEASURE key
MEASURE key
operation
Pull*
Description in
this manual
*: Convenient way for performing measurement repeatedly
Turn on the MEASURE key.
Press and hold
right side
Power OFF
Rotary switch
status
Fold down
(or release).
Turn off the
MEASURE key.
Description in
this manual
Turn off the rotary
16
switch.
Display
HIOKI IR4057B961-01
IR4057-50
Names and Functions of Parts
1
Bar graph
Battery indicator (three levels) (p. 29)
Turns on when the voltage measured with the V range is DC.
Turns on when the voltage measured with the V range is AC.
Blinks when the measured value is less than the minimum display
value.
Blinks when the measured value is greater than the maximum
display value.
Turns on when the measured value is retained.
Turns on when the comparator judgment is PASS (good). (p. 31)
Turns on when the comparator judgment is FAIL (defective).
(p. 31)
Blinks when a dangerous voltage exists between the
measurement terminals.
Judgment result buzzer (only when comparator is set) (p. 31)
Appears 30 s before auto power save function is activated.
(p. 30)
Turns on when zero adjustment is performed during low
resistance measurement. (p. 42)
Measured value
Comparator judgment reference value or
1-minute value
17
2
3
4
5
6
7
付録索引
Names and Functions of Parts
HIOKI IR4057B961-01
Displaying 1-minute values (p. 37)
• Turns on when 1 minute has passed since the start of insulation
resistance measurement.
• Indicates that the resistance value on the bottom of the display
is a 1-minute value (the measured value 1 minute after the start
of measurement).
Turns on when the comparator function is enabled. (p. 31)
Turns on when the instrument is set to the 500 V range or the
1000 V range.
Pressing
measurement.
Indicates wireless communications function status. (p. 51)
turns off the indicator and enables insulation
IR4056
Turns on when the reference value is indicated by the
comparator function.
Measured value
or comparator reference value
(Other functions are the same as
the IR4057-50.)
18
Names and Functions of Parts
HIOKI IR4057B961-01
IR4053, IR4055
REAR (Serial number label)
The serial number consists of nine digits. The rst two indicate the year
of manufacture (the last two digits of the Western year), and the next two
indicate the month of manufacture.
(The illustration shows the IR4055)
Measured value
or comparator reference value
(Other functions are the same as the
IR4056 and the IR4057-50.)
Turns on when the PVΩ measurement mode is selected.
Turns on when selecting 500 V range in the PVΩ measurement
mode.
Turns on when selecting 1000 V range in the PVΩ measurement
mode.
Indicates wireless communications function status. (p. 51)
(IR4055)
1
2
3
4
5
6
7
付録索引
19
Names and Functions of Parts
HIOKI IR4057B961-01
L9788-10 Test Lead with Remote Switch (Red)
CAUTION
The MEASURE key of the instrument is enabled even
when the L9788-10 is connected to an insulation
resistance tester. Note that the testing voltage is output
when the MEASURE key of the instrument is turned ON
while the L9788-10 is connected.
Refer to “Attaching the L9788-92 Breaker Pin” (p. 26)
Sleeve
Enlarged tip view
35
16
1 23
Plug
1.8
φ
Light
1
MEASURE key
2
Judgment display
3
3.0
φ
20
Unit: mm
Lights up interlocked with the backlight of the
instrument.
• Starts insulation resistance measurement.
• Lights up in red interlocked with the live wire
warning indicator of the instrument.
Lights up in accordance with the comparator
judgment result.
• PASS: Green
• FAIL: Red
Preparing for Measurement
HIOKI IR4057B961-01
2
CAUTION
Attach the strap securely to the four ttings on the
instrument. If insecurely attached, the instrument may fall
and be damaged when carrying.
Attach the strap.
1
Slightly extend each of the four
double-loop split rings and pass
the ring through a lug-hole on
the instrument.
Secure the strap at
4 positions.
Insert the batteries. (p. 22)
2
Connect the test leads to the terminals.
3
1
2
3
4
5
EARTH terminal
Connect the black
test lead.
Attach each test pin or alligator clip to a lead.
4
LINE terminal
Connect the red
test lead.
6
7
Fully insert the test lead to the
test pin or alligator clip.
or
付録索引
21
Replacing Batteries or Fuse
HIOKI IR4057B961-01
2.1 Replacing Batteries or Fuse
WARNING
• To avoid electric shock, turn off the MEASURE key,
disconnect the test leads from the measuring object
before replacing the battery cover.
• After replacing the batteries, reattach the cover and
secure the screw before using the instrument.
• Battery may explode if mistreated. Do not
shortcircuit, recharge, disassemble or dispose of in
re.
• Replace the fuse only with one of the specied type,
characteristics, rated current, and rated voltage. Do
not use fuses other than those specied (especially,
do not use a fuse with higher-rated current) or do
not short circuit and use the fuse holder. Doing so
may damage the instrument and result in bodily
injury.
Fuse type: FF0.5 AH/1000 V (70 172 40.0.500:
SIBA GmbH) (Fast blow, arc-extinguishing material
included, and high breaking capacity)
The fuses can be purchased via authorized Hioki
distributor or reseller. (Fuse replacement not
required for the IR4053 or IR4055)
• To prevent instrument damage or electric shock,
use only the screw for securing the battery cover
in place that are originally installed. If you have lost
a screw or nd that a screw is damaged, please
contact your authorized Hioki distributor or reseller.
22
Replacing Batteries or Fuse
HIOKI IR4057B961-01
CAUTION
Poor performance or damage from battery leakage could
result. Observe the cautions listed below.
• Do not mix old and new batteries, or different types of
batteries.
• Pay attention to the polarity markings “+” and “−”, so
that you do not insert the batteries the wrong way
around.
• Do not use batteries after their recommended expiry date.
• Do not leave depleted batteries inside the instrument.
• Replace batteries only with the specied type.
• Use batteries with low internal resistance.
• The battery indicator blinks when the remaining battery capacity
is low. In this case, measurement is not possible. Replace the
batteries with new ones. (p. 29)
• Handle and dispose of batteries in accordance with local
regulations.
1
2
3
4
5
6
7
付録索引
23
Replacing Batteries or Fuse
HIOKI IR4057B961-01
Procedure (The illustration shows the IR4056)
You will need:
• LR6 Alkaline battery ×4
• Phillips-head screwdriver (No. 2)
Turn off the rotary switch and
1
OFF
remove the test lead from the
instrument.
Rear
Battery cover
Batteries
(LR6 ×4)
Check the
polarity.
Fuse
FF0.5 AH/1000 V
(70 172 40.0.500:
SIBA GmbH)
24
Loosen the fastening screw
2
and remove the battery cover.
Replace all four batteries or
3
the fuse.
Slide the battery cover back
4
into place and tighten the
screw.
Using the L9788-10 Test Lead with Remote Switch (Red)
HIOKI IR4057B961-01
2.2 Using the L9788-10 Test Lead with
Remote Switch (Red)
Pre-measurement inspection
Turn off the rotary
1
switch.
Fully insert the L9788-10 plug
2
into the LINE terminal of the
instrument.
1
2
OFF
Set the rotary switch to insulation resistance range.
4
Turn on the MEASURE key of the L9788-10.
5
Check the red indicator of the MEASURE key of L9788-10 and display
interlocked with the live wire warning indicator of the instrument.
0 M
Ω
6
Press .
OK
Short the test lead tips each other.
3
0 M
Ω
Check that the L9788-10 tip lamp
lights up.
NO
3
4
5
6
7
付録索引
25
Using the L9788-10 Test Lead with Remote Switch (Red)
HIOKI IR4057B961-01
Replacing the Tip Pin (optional) for the L9788-10
When the tip pin of the L9788-10 Test Lead with Remote Switch
(Red) (option) is worn out or broken, it can be replaced. The tip pin
can be purchased via authorized Hioki distributor or reseller.
Turn off the rotary switch and
1
OFF
disconnect the L9788-10.
Wrench
(size: 7 mm width)
L9788-90 Tip Pin
Remove the tip pin by rotating
2
with a wrench.
Attach the new tip pin to the
3
L9788-10 by rotating with a
wrench.
(Tightening torque: 0.3 N·m)
Check the operation.
4
Measure a measuring object of known
values and use after checking that the
resistance is correct.
Attaching the L9788-92 Breaker Pin
Remove the sleeve of the L9788-10 and attach the breaker pin.
Fully insert.
L9788-92 Breaker Pin
Removing and attaching the test lead sleeves
Safely store the removed sleeves so as
not to lose them. (p. 12)
26
Installing the Z3210 Wireless Adapter (IR4057-50 only)
HIOKI IR4057B961-01
Removing the sleevesAttaching the sleeves
Hold the bottom of the sleeves
and pull the sleeves off. (For
safety reasons, the cap has been
manufactured to t snugly so that
it cannot be easily removed.)
Insert the metal pins of the test leads into
the holes of the sleeves, and rmly push
them all the way in.
1
2.3 Installing the Z3210 Wireless
Adapter (IR4057-50 only)
The wireless communications function can be used by installing the Z3210
Wireless Adapter (option) to the instrument.
WARNING
• To avoid electric shock, turn off the MEASURE
key and remove the test leads from the measuring
object before removing the battery cover.
• After installing or removing the Z3210, be sure to
reattach the battery cover and secure it in place
with the screw before using the instrument.
• To prevent instrument damage or an electric shock,
use only the screws that are originally installed for
securing the battery cover in place. If you have lost
any screws or nd that any screws are damaged,
please contact your authorized Hioki distributor or
reseller.
CAUTION
After touching any metallic part, such as a doorknob,
to eliminate static electricity from your body, connect or
disconnect the Z3210. Failure to do so could cause static
electricity to damage the Z3210.
2
3
4
5
6
7
付録索引
27
Installing the Z3210 Wireless Adapter (IR4057-50 only)
HIOKI IR4057B961-01
Procedure
You will need:
• Phillips-head screwdriver (No. 2)
• Flat-head screwdriver
• Z3210 Wireless Adapter (option)
Rear
2, 5
2
5
3
4
Turn off the rotary switch and remove the test leads.
1
Unscrew the screws and remove the battery cover.
2
Remove the protective cap with a at-head screwdriver.
3
Exercising care to orient the Z3210 correctly, install the
4
Z3210 as far as it will go.
Reattach the battery cover and tighten the screws.
5
28
Measurement
HIOKI IR4057B961-01
3
3.1 Pre-measurement Inspection
Before using the instrument, verify that it operates normally to ensure that no
damage occurred during storage or shipping. If you nd any damage, contact
your authorized Hioki distributor or reseller.
Checking the remaining battery charge
Is the battery level adequate?
Set the rotary switch away
from OFF and conrm the
battery indicator.
Turns on
Checking the test lead
Is the white portion
(insulation layer) inside
the cable exposed?
Not Exposed
1. Set the rotary switch to
insulation resistance
range.
2. Short the test lead tips.
3. Is 0 M
displayed when
Ω
the MEASURE key is
turned on?
Displayed
Blinks
Exposed
Not
displayed
Replace with the new batteries.
(p. 22)
Do not use and replace with
those specied by Hioki if
damage is present as you could
receive an electric shock.
The following issues may be
occurring:
• The test lead has not been
inserted all the way.
Insert the test lead all the way in.
→
• There is a broken connection in
the test lead.
→ Replace them with those
specified by Hioki.
1
2
3
4
5
6
7
付録索引
Inspection complete
Please read the “Operating Precautions” (p. 9) before use.
29
Auto Power Save (Power-Saving Function)
HIOKI IR4057B961-01
3.2 Auto Power Save (Power-Saving
Function)
When the rotary switch is not in the OFF position, the instrument changes to
the auto power save state approx. 10 minutes after the last operation or live
wire warning indication.
To avoid battery depletion, turn off the rotary switch after use (the auto power
save consumes a small amount of current).
Canceling the auto power save
Other than
the OFF
position
.
Turn on the instrument while
holding down
Recovering from auto power save state
Set the rotary switch to OFF and then return it to its original
position.
3.3 Auto Backlight-off (Automatic
Light-off Function)
The backlight of the instrument will automatically turn off after approx.
3 minutes has passed since the last operation.
The automatic light-off function can be canceled when working continuously
in a dark location.
Canceling the automatic light-off function
Backlight: OFF
Press for approx. 2 seconds.
30
Continuous
short beep
Set the rotary switch to any
position other than OFF.
With the backlight off, press
for approx. 2 seconds until the
instrument beeps.
The automatic light-off function is enabled
setting the rotary switch to OFF.
.
by
Comparator Function
HIOKI IR4057B961-01
3.4 Comparator Function
This function compares the measured value with the preset value and judges
whether the result is PASS (good) or FAIL (defective).
Comparator settings for each range will be saved, even if the rotary switch is
turned off.
See the table on the next page for criteria that can be set.
Indication lights up
PASS (good) judgmentFAIL (defective) judgment
LED
display
Backlight:
No change
* When using the L9788-10 Test Lead with Remote Switch (Red)
Type of measurements that can be judged
Function
Insulation
Resistance
Low resistance
PV
Ω
VoltageComparator cannot be set.
Lights up in
green*
PASS judgmentFAIL judgment
State of
measured
value
Criterion or
higher
Criterion or
lower
Criterion or
higher
Backlight: Lights
up in red
BuzzerBacklightBuzzer
Short beep
Long beepShort beep
Short beepLong beep
Lights up in
red
Lights up in
red*
Long beep
1
2
3
4
5
6
7
付録索引
31
Comparator Function
HIOKI IR4057B961-01
Setting the Comparator
Select a judgment reference from the table below.
1
RangeReference valueUnit
0.01 0.02 0.03 0.04 0.05
50 V
125 V
250 V
500 V/PV
1000 V*
500 V
Ω
3
/PVΩ 1000 V
Ω
*1: Factory default setting
*2: Factory default setting when PV
*3: Reference values 0.1 to 0.5 are only for models IR4053 and IR4055.
0.10.20.30.40.5‒
1
2345‒
1*
10‒‒‒‒Off
0.10.20.30.40.5‒
1
2345‒
1*
1020‒‒‒Off
0.10.20.30.40.5‒
1
2345‒
1*
1020304050Off
0.10.2*
1*
2
1
0.30.40.5‒
2345‒
1020304050‒
100‒‒‒‒Off
0.10.20.30.4*
12345‒
1
20304050‒
10*
2
0.5‒
100200300400500Off
0.10.20.30.40.50.6
123456
1
1020*
30405060
100200‒‒‒Off
function is selected.
Ω
M
Ω
Ω
32
Comparator Function
HIOKI IR4057B961-01
Set the rotary switch to the range for which you wish to set
2
the judgement reference.
RangeOperation
500 V
1000 V
PV
Ω
or
COMPREF
2
Press
Press to select the applied voltage and press to
release the lock.
4
to release the lock.
Press .
3
Blinks
3
[COMP] or [REF] blinks and the
resistance value that will be used as
the judgement reference is displayed.
IR4053, IR4055, IR4056: REF
IR4057-50: COMP
Press or to select the
4
judgement reference.
If there is no operation for about 2
seconds after you select the judgment
reference, the comparator will be set,
and [COMP] or [REF] will light up.
Canceling the Comparator
oFF
Press several times to select
[oFF].
If there is no operation for for about 2
seconds after you select, [COMP] or [REF]
will go off, and the comparator function will
be canceled.
1
2
3
4
5
6
7
付録索引
33
Insulation Resistance Measurement
HIOKI IR4057B961-01
3.5 Insulation Resistance Measurement
The instrument is used to measure the insulation resistance to
determine the insulation performance of circuits and equipment.
Before starting a measurement, the voltage to be applied to the
measuring object needs to be selected.
WARNING
Observe the following to avoid electric shock, short
circuit, or damage to the instrument.
• Do not attempt to measure insulation resistance
on a live conductor. Doing so could damage the
instrument or cause an accident that might result
in injury or death. Always turn off power to the
measuring object before starting.
• When measuring insulation resistance, dangerous
voltage is applied to the measurement terminals. To
avoid electric shock, do not touch the metal part of
the test leads.
• Do not touch the measuring object immediately after
measurement. Doing so may cause electric shock
due to a highly charged voltage.
• Discharge the measuring object with the discharge
function of the instrument after a measurement. (p. 39)
• Insulation resistance is the ratio of applied voltage to leakage current.
Displayed value may not stabilize depending on the measuring object,
but it is not a failure of the instrument.
• Press the MEASURE key fully down until a live circuit indicator lights
up. If the button is not pressed down fully, a proper measurement cannot
be made.
• Turn off the rotary switch after use.
• Disconnection when measuring is recommended of any equipment
having a lower withstanding voltage than the test voltage, or equipment
or parts having an unknown withstanding voltage connected to the circuit
to be measured.
34
Insulation Resistance Measurement
HIOKI IR4057B961-01
Lock Function
This function is used to avoid applying high voltage such as 500 V
or 1000 V to equipment having a lower withstanding voltage. This
function will prevent the test voltage from being output even if the
MEASURE key is pressed while the rotary switch is set to the 500
V or PVΩ range.
1000
Releasing the lock
1
V,
2
or
1
or
The screen is locked 1 minute after the last measurement or operation
again.
Turns on
Blinks
Turns off
2
Turns off
Set the rotary switch to the
1
500 V, 1000 V or PVΩ range.
Press .
2
Pressing this key unlocks the
instrument and switches to the
measurement screen.
3
4
5
6
7
付録索引
35
Insulation Resistance Measurement
HIOKI IR4057B961-01
Measuring Insulation Resistance
CAUTION
To avoid electric shock, turn off the measuring line
breaker.
Example: When measuring the insulation resistance between the circuit
2
5
7
3
4
5
6
and the ground
Turn off the MEASURE key.
OFF
1
ON
OFF
6
Connect the black test lead to the ground side of the
object being measured.
Connect the red test lead to the measuring object.
If there is any remaining voltage on the measuring object, red and white
blink alternately on the backlight.
Press and hold the MEASURE key.
To make continuous measurements, pull up the MEASURE key. (p. 16)
Check the value after the indicator has stabilized.
1
Set the rotary switch to a test voltage
2
of 50 V to 1000 V.
In the 500 V or 1000 V range, press to
release the lock. (p. 35)
3
Source (primary side)
OFF
4
Load (secondary side)
36
Insulation Resistance Measurement
HIOKI IR4057B961-01
Turn off the MEASURE key with the test leads connected
7
to the measuring object.
The last measured values and are displayed and starts
discharging. (p. 39)
• Do not switch the function to other function or rated voltage when the
measurement is in progress.
• The instrument will return to the locked state when about 1 minute of no
operation elapses during measurement in the 500 V and 1000 V ranges. To
continue measurement, release the lock. (p. 35)
1
2
Displaying 1-minute Values (IR4057-50 only)
This function is only available on the IR4057-50.
The function cannot be used if the comparator function has been
enabled. Disable the comparator function before use. (p. 33)
This function automatically retains the measured value (1-minute
value) 1 minute after the start of measurement (after the MEASURE
key is turned on). Use this function when measuring a object such
as a cable that includes a capacitance component.
• No value is shown if less than 1 minute has
elapsed since the start of measurement.
Retained measured value
3
4
5
6
7
付録索引
37
Insulation Resistance Measurement
HIOKI IR4057B961-01
Voltage Characteristics of Measurement Terminals
1200
1000
800
600
400
200
Voltage generated [V]
100
0
0.05 0.12 5
00.1 0.25 0.5110 100 1000
Resistance of measuring object [MΩ]
Rated 1000 V
Rated 500
Rated 250
Rated 125
V
Rated 50
∞
V
V
V
38
Discharging Function
HIOKI IR4057B961-01
3.6 Discharging Function
After measurements are completed, discharge the measuring object.
When objects with capacitance component are measured, a charge
equivalent to the rated measurement voltage remains in the object
that may cause electric shock.
When measuring a solar panel,
the instrument will continue to detect the panel’s voltage once
discharging ends.
mark may not disappear since
1
2
OFF
Discharging
Discharged
Turned on
Off
Without removing the test leads
from the measuring object, turn off
the MEASURE key.
The built-in discharge resistor
automatically discharges the item.
In the IR4057-50, the bar graph level
decreases according to discharge.
However, measuring objects with smaller
capacitance component discharge quickly
and the bar graph level may not change.
When the discharge is completed,
mark is turned off.
The time required for discharge depends
on the capacitance value.
39
3
4
5
6
7
付録索引
Voltage Measurement
HIOKI IR4057B961-01
3.7 Voltage Measurement
This instrument can measure the AC voltage and DC voltage of
commercial power. The instrument can check to ensure that the
measuring object is not live before measuring insulation resistance.
• During measuring, do not switchover to other functions.
• For waveforms other than sine waves, some errors may occur.
• Displayed values can frequently uctuate due to induction
potential even when no voltage is applied. This, however, is not a
malfunction.
Example: When measuring the voltage between the circuit and ground
Earth
2
Line
4
Source
(primary side)
3
Load
(secondary side)
1
Set the rotary switch to V.
1
Connect the black test lead to the earth side of the object
2
being measured.
Connect the red test lead to the line side of the breaker.
3
Check the value after the indicator has stabilized.
4
40
Always connect the test lead
to the secondary side of the
breaker.
Voltage Measurement
HIOKI IR4057B961-01
Negative Voltage Notication Function (IR4053 and
IR4055 only)
This function is only available on the IR4053 and the IR4055.
You can check whether P and N are connected in reverse while
measuring the open voltage of solar battery string.
Set the rotary switch to V
1
while pressing
The [‒] and [V] blinks and [ON] or
12
Press to switch between ON and OFF.
2
ON
(Factory setting)
OFFDisabled
If there is no operation for approx. 2 seconds after ON or OFF
is selected, the setting is conrmed, and the screen changes to
measurement screen.
When the voltage is −1 V or lower, red and white
of the backlight blinks alternately.
[OFF] is displayed.
.
1
2
3
4
5
6
7
付録索引
41
Low Resistance Measurement (IR4056 and IR4057-50 only)
HIOKI IR4057B961-01
3.8 Low Resistance Measurement
(IR4056 and IR4057-50 only)
This function is only available on the IR4056 and the IR4057-50.
WARNING
Do not measure under a live circuit condition.
CAUTION
• If active circuits are connected to the measuring object
circuit in parallel, the impedance and transient current of
the parallel circuit could cause measurement errors.
• Auto range selection may not operate in a stable
manner depending on the measuring object (for
example, a motor, transformer, or coil).
• The instrument may not be able to obtain an accurate
measured value if there is a capacitance component in
parallel with the measuring object.
The comparator function can be used during low resistance
measurement. See “3.4 Comparator Function” (p. 31)
For accurate measurements, be sure to perform zero adjustment
before measuring, to cancel the wire resistance of the test leads.
Zero adjustment can be performed with readings of up to a
maximum of 3
[Err 0ΩADJ] will be displayed, and zero adjustment will not be
possible. Wire the instrument so that the wiring resistance is 3
less.
In the following circumstances, repeat the zero adjustment procedure:
• After changing test leads
• When the ambient temperature changes by 1°C or more
• After replacing the fuse
42
. When the reading exceeds 3
Ω
, [Err 1] or
Ω
or
Ω
Low Resistance Measurement (IR4056 and IR4057-50 only)
HIOKI IR4057B961-01
Example: Checking continuity of grounding wire
2
ON
3
OFF
4
1
5
ON
7
OFF
8
Connect the test lead to the measuring object.
6
Press and hold the MEASURE key to check the displayed
7
value.
To make continuous measurements, pull up the MEASURE key.
Turn off the MEASURE key after measurement.
8
6
Set the rotary switch to the Ω.
1
Short circuit the tip of the test
2
lead.
Turn on the MEASURE key.
3
Turn off the MEASURE key to
4
retain the measured value.
Press .
5
Do not measure
live wires.
6
1
2
3
4
5
6
7
付録索引
43
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
3.9 PVΩ Measurement Function
(IR4053 and IR4055 only)
This function is only available on the IR4053 and the IR4055.
This function allows accurate insulation resistance measurements
between the solar panel and ground without any inuence from
power generation. For measurements between the coupling box
output terminals and ground or between power conditioner and
ground, use the normal insulation resistance range.
See “Appx. 1 Measurement Principles” (p. Appx.1)
DANGER
Do not cause a short-circuit between another wire and
the wire to be measured with the test leads. Arcs or
such grave accidents are likely to occur.
WARNING
Observe the following to avoid electric shock,
shortcircuit, or damage to the instrument.
• When measuring insulation resistance, dangerous
voltage is applied to the measurement terminals. To
avoid electric shock, do not touch the metal part of
the connecting test leads.
• Check that the connection of the measurement
terminals has been secured. If the terminal is loose,
the contact resistance will increase, resulting in
overheating, equipment burnout, or re.
• Do not touch the measuring object immediately after
measurement. A highly charged voltage may cause
electric shock.
• Discharge the measuring object with the discharge
function of the instrument after a measurement. (p. 39)
44
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
WARNING
Observe the following to avoid electric shock, short
circuit, or damage to the instrument.
• Turn off any disconnector devices and separate
from the power conditioner before starting the
measurements for the solar battery panel.
• Do not attempt to measure insulation resistance
on a live conductor. Doing so could damage the
instrument or cause an accident that might result
in injury or death. Always turn off power to the
measuring object before starting.
• Photovoltaic cells produce electricity continuously
during daylight hours, resulting in hazardous
voltages. Exercise care during measurement to
avoid electric shock.
• Do not touch any metal parts such as connection
box and disconnector devices directly with bare
hands. Doing so may cause electric shocks due to
the voltage of the generator.
• Maximum rated voltage between terminals of the
IR4053 and IR4055 is 1000 V DC/600 V AC. Do not
use the instrument for equipment with rated voltage
over 1000 V DC or 600 V AC. Doing so may cause
electric shock or failure.
• If the solar battery panel has failed, do not perform
any insulation resistant measurement. Doing so
may damage the bypass diode of the solar battery
panel.
1
2
3
4
5
6
7
付録索引
45
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
• Insulation resistance is the ratio of applied voltage to leakage
current. Displayed value may not stabilize depending on the
measuring object, but it is not a failure of the instrument.
• Press the MEASURE key fully down until a live circuit indicator
lights up. If the button is not pressed down fully, a proper
measurement cannot be made.
• Turn off the rotary switch after use.
• Disconnection when measuring is recommended of any
equipment having a lower withstanding voltage than the test
voltage, or equipment or parts having an unknown withstanding
voltage connected to the circuit to be measured.
• The ground capacitance of the solar battery panel is high,
therefore the measured values may take some time to stabilize.
• Accurate measurements are not possible when open voltage
of the solar battery string is higher than the test voltage. Use
the PVΩ 500 V range for open voltage 500V or less and PVΩ
1000 V range for open voltage 1000 V or less.
• If a voltage higher than the test voltage is detected, the buzzer
sounds and measurement is not possible.
• Use an insulation resistance range other than PVΩ to perform
measurements by shorting P and N.
• Perform measurements by shorting P and N when the solar
battery panel is not generating power, such as during the night.
• For the PVΩ measurement function, the output voltage is
divided by the 1 MΩ resistor and the resistor connected
between measurement terminals because a 1 MΩ current
limiting resistor is connected to the EARTH terminal.
Example: When a 10 MΩ resistor is measured, the voltage is
divided by 1 MΩ and 10 MΩ.
46
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
The method to measure the insulation resistance between the solar
battery panel and ground without shorting P and N will be explained.
See “Appx. 3 Insulation Resistance Measurements for Solar Cell
Array” (p. Appx.3)
Measurement preparation 1
Turn off the main switch of the connection box to be
1
disconnected from the power conditioner.
Turn off all the disconnector devices of the strings.
2
Disconnect lightning arresters from the measuring circuit.
3
Disconnection is not required for the gure (solar generator facility)
shown below because a lightning arrester is not present at the string
side of the disconnector device.
String
OFF
2
Disconnector devices
Lightning
arrester
OFF
1
Main switch
Connection
box
Power
1
2
3
4
5
Conditioner
Measurement preparation 2
OFF
1
2
(Example: Solar generator facility)
Check that the MEASURE key is
1
turned off.
If the MEASURE key is on, turn it off.
(p. 16)
Set the rotary switch to PVΩ.
2
Press to set 500 V or 1000 V
34
3
as the test voltage.
Press to release the lock.
4
6
7
付録索引
47
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
Start Measuring
WARNING
Observe the following to avoid damage to the
measuring object.
• If the insulation has deteriorated between the
terminal P and the ground, do not measure between
the terminal N and the ground.
• Connect the red test lead to the string side of the
disconnector device.
Power conditioner, main switch
5
Pterminal
(Black)
Ground
terminal
6
Disconnector devices
Connect the black test lead to the ground terminal.
5
Connect the red test lead to the terminal P of the string side.
6
If a voltage is detected between the P and the ground terminals, the
insulation may have deteriorated. When there is a voltage on the
measuring object, the voltage detection function makes the backlight
light in red and white alternately.
48
(Red)
N terminal
String
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
Power conditioner, main switch
(Black)
ON
7
OFF
9
Press and hold the MEASURE key.
7
To make continuous measurements, pull up the MEASURE key.
Do not remove any test leads from the terminals until the resistance is
displayed. Doing so results in incorrect measurements. (p. 72)
Check the resistance displayed after approx. 4 seconds.
8
Subsequently, the resistance will be updated every second.
If there is any deteriorated insulation and the resistance is lower than
the reference value, do not measure the terminal N of procedure 10.
Doing so may damage the solar battery panel. Check the reference
insulation resistance with safety regulations.
Turn off the MEASURE key.
9
If the MEASURE key is on, turn it off. (p. 16)
Discharge starts and the
cleared even if the discharge is completed because a voltage is
generated by the solar battery.
When measuring terminal P and insulation has not
10
deteriorated, connect the red test lead to the terminal N
of the string side and repeat the procedures 7 to 9.
Ground
terminal
(Red)
String
mark blinks. The mark may not be
Pterminal
Disconnector devices
10
N terminal
1
2
3
4
5
6
7
付録索引
49
PVΩ Measurement Function (IR4053 and IR4055 only)
HIOKI IR4057B961-01
After Measurements
After measuring insulation resistance for all the strings,
1
remove the black test lead from the ground terminal.
Reconnect the lightning arrester connection if
2
disconnected.
Turn on all the disconnector devices of the strings.
3
Turn on the main switch of the connection box.
4
1 minute after the last measurement or operation, the
turns on and the 500 V/1000 V RELEASE key blinks. Press the key
to release the lock.
50
Wireless Communications Function
HIOKI IR4057B961-01
3.10 Wireless Communications Function
Using the GENNECT Cross
(IR4055 and IR4057-50 only)
This function cannot be used at the same time as the HID function.
(p. 55)
When the wireless communications function is enabled, you can
review measurement data and create measurement reports on
mobile devices. For details, see the Help function in the GENNECT
Cross (application software, free of charge).
GENNECT Cross Ofcial Website
https://gennect.net/en/cross/index
(IR4057-50 only) Install the Z3210 Wireless Adapter (option)
1
to the instrument. (p. 27)
Install the GENNECT Cross on your mobile device.
2
Turn on the IR4055 or
3
IR4057-50 to enable the
wireless communications
function.
mark or mark
On: Enabled
Off: Disabled
Blinks: Communicating
Launch the GENNECT Cross and pair it with model IR4055
4
or IR4057-50. (p. 52)
IR4055
COMP key
1 s
IR4057-50
0Ω ADJ key
+
COMP key
1
2
3
4
5
6
7
付録索引
51
Wireless Communications Function
HIOKI IR4057B961-01
Select the standard
5
measurement function and
start measurement.
• The communication distance is approx. 10 m (line of sight). The
distance over which data can be sent and received varies greatly
depending on whether there are any obstructions between the
paired instruments (for example, walls, metal barriers, etc.) and
on the distance between the instrument and the oor (or ground).
To ensure stable communication, verify adequate signal strength.
• Although the GENNECT Cross is provided free of charge,
downloading or using the application software may incur Internet
connection charges. Such charges are the sole responsibility of
the user.
• The GENNECT Cross is not guaranteed to operate on all mobile
devices.
• The Z3210 uses 2.4 GHz band wireless technology. It may not be
possible for the device to establish a wireless connection when
used in the vicinity of other devices that use the same frequency
band, for example Wi-Fi devices (IEEE 802.11.b/g/n).
52
Pairing the App
HIOKI IR4057B961-01
Wireless Communications Function
1
1
Home>Other
• When the app is launched for the rst
time (before being paired with any
instrument), the connection setup
screen will be displayed.
• While the mobile device is displaying
the connection setup screen, simply
move it close to the IR4055 or the
IR4057-50 to automatically pair it with
the instrument (the app can be paired
with up to 8 instruments).
• Allow about 5 to 30 seconds for the
instrument to pair with the app after
being turned on. If the instrument
fails to pair within 1 minute, relaunch
GENNECT Cross and cycle the
instrument’s power.
• Instruments that have been registered
do not require to be registered again.
2
Instrument
Settings
3
The instrument is
automatically registered.
Returns to the
4
screen.
Home
2
3
4
5
6
7
付録索引
53
Wireless Communications Function
HIOKI IR4057B961-01
Making Measurements with the Wireless
Communications Function
On the home screen, select the standard measurement function from
the options, standard measurement, logging and waveform display, to
start a measurement. For more information about each function, see
the help function in the GENNECT Cross.
The values displayed by the instrument may be different from the
values displayed by the application software due to communication
delays or differences in the update timing.
Standard measurement
Measured values of multiple channels
are saved.
54
Wireless Communications Function
HIOKI IR4057B961-01
Excel® Direct Input Function (HID function)
(IR4057-50 only)
This function cannot be used at the same time as GENNECT Cross
(p. 51).
The human interface device (HID) prole, with which the Z3210
Wireless Adapter is equipped, is a prole same as that wireless
keyboards use.
HID ONPreparatory to data entry, open an Excel® le on
your mobile device or computer and choose a cell.
Freezing the instrument’s display can enter the
measured values on the cells.
HID OFFSelect this setting when using GENNECT Cross.
The setting whether the HID function has been enabled or disabled
will not be saved in the instrument but in the Z3210.
Enter measured values.
Measured value input method
Insulation resistance, low resistance:
Press and release the MEASURE key.
Voltage: Press the MEASURE key.
1
2
3
4
5
6
7
付録索引
55
Wireless Communications Function
HIOKI IR4057B961-01
Checking and changing the HID setting
Set the rotary switch to OFF.
1
Install the Z3210 Wireless Adapter (option) to the
2
instrument.
See “2.3 Installing the Z3210 Wireless Adapter (IR4057-50 only)”
(p. 27)
If the wireless communications function is off, you won’t be able to check or
change the HID setting. Enable the wireless communications function rst
before attempting to check or change the HID setting (Step 3 on p. 51).
Check the HID setting.
3
Turn on the instrument while holding down the RELEASE key to display
the serial number screen.
Press and hold the RELEASE key for at least 3 s to display the HID
setting saved by the Z3210.
or
To leave the HID setting unchanged
Set the rotary switch to OFF.
To change the HID setting
Proceed to Step 4.
If the instrument beeps and the display doesn’t change
Using GENNECT Cross (Ver. 1.8 or later), update the Z3210 to the latest
version.
Change the HID setting.
4
Toggle the HID setting on and off by pressing the 0
COMP key.
Accept the setting
5
Press the RELEASE key to accept the HID setting. The instrument will
automatically turn off.
56
ADJ key or the
Ω
Wireless Communications Function
HIOKI IR4057B961-01
IMPORTANT
To switch from the HID function to GENNECT Cross
If you launch GENNECT Cross without unpairing the mobile phone and
the instrument, the application may fail to recognize the instrument as a
connected device.
Reconnect the instrument to GENNECT Cross as follows:
1. Delete the instrument from your device’s Bluetooth
2. Turn off the Z3210’s HID function. (p. 56)
3. Reconnect the instrument using GENNECT Cross’s connected device
settings.
®
settings.
1
2
For details, please check the Z3210’s website.
https://z3210.gennect.net
3
4
5
6
7
付録索引
57
Wireless Communications Function
HIOKI IR4057B961-01
58
Specications
HIOKI IR4057B961-01
4
4.1 General Specications
Operating
environment
Operating
temperature
and humidity
Storage
temperature
and humidity
Dustproof and
waterproof
Drop proofOn concrete: 1 m
Indoors, Pollution Degree 2,
altitude up to 2000 m (6562 ft.)
• IR4053, IR4055
0°C to 40°C (32°F to 104°F), 90% RH or less (no
condensation)
40°C to 50°C (104°F to 122°F), at 50°C and below
relative with linear decrease up to 50% RH (no
condensation)
• IR4056, IR4057-50
−25°C to 40°C (−13°F to 104°F), 90% RH or less (no
condensation)
40°C to 65°C (104°F to 149°F), at 65°C and below
relative with linear decrease up to 25% RH (no
condensation)
IR4053, IR4055IR4056, IR4057-50
• IR4053, IR4055
−10°C to 50°C (−13°F to 122°F),
90% RH or less (no condensation)
• IR4056, IR4057-50
−25°C to 65°C (−13°F to 149°F),
90% RH or less (no condensation)
IP40 (EN 60529)
1
2
3
4
5
6
7
付録索引
59
General Specications
HIOKI IR4057B961-01
Standards
EMC:
EN 61326
Safety: EN 61010
EN 61557-1
EN 61557-2
EN 61557-4*
EN 61557-10*
Insulation resistance testers: JIS C 1302*
1 *2
2
3
*1: Subclause 4.3 of Part 4 (Interchanging of test leads) is not applicable
when model L9788-10 is used.
*2: The IR4053 and the IR4055 are not applicable.
*3: IR4053 and IR4055 only
Power supplyLR6 Alkaline battery ×4
Rated supply voltage: 1.5 V DC ×4
Maximum rated power: 3 VA
Continuous
operating time
When using four
LR6 Alkaline
batteries
(reference value
Approx. 20 hours (without Z3210 installed, comparator
off, backlight off, measured with measurement terminal
open at 500 V range)
Approx. 15 hours (with Z3210 installed, using wireless
communications, comparator off, backlight off, measured
with measurement terminal open at 500 V range)
at 23°C)
Dimensions
(excluding
protrusions)
Mass (including
battery,
Approx. 159W × 177H × 53D mm
(6.26″W × 6.97″D × 2.09″D)
• IR4053, IR4055, IR4056: Approx. 600 g (21.2 oz.)
• IR4057-50: Approx. 640 g (22.6 oz.)
excluding test
lead)
Product warranty period: 3 years
Fuse
(Replacements)
FF0.5 AH/1000 V (70 172 40.0.500: SIBA GmbH)
(Very fast-blow, arc-extinguishing material included, high
breaking capacity) (IR4056 and IR4057-50 only)
DC current supply, voltage detection
(IR4056 and IR4057-50 only)
Voltage measurement:
Automatic DC/AC detection
AC voltage measurement rectication method:
Mean rectication RMS value indication
measurement:
PV
Ω
DC voltage supply, current detection
(IR4053 and IR4055 only)
600 V AC/DC (Voltage measurement)
600 V AC/1000 V DC (Voltage measurement,
IR4053 and IR4055 only)
600 V AC/DC, Measurement Category III,
Anticipated Transient Overvoltage: 6000 V
Position: Standard position ±90°
External magnetic eld: 400 A/m or less
Battery voltage: Available effective battery voltage
600 V AC/DC max.
*: The nominal circuit voltage refers to the nominal
voltage of an electric distribution circuit that
can be measured by the instrument (based on
EN 61557).
Accuracy guarantee period: 1 year
Accuracy guarantee period after adjustment
made by Hioki: 1 year
Accuracy guarantee temperature and humidity
range: 23°C±5°C (73°F±9°F), 90% RH or less
Position: Standard position ±5°
External magnetic eld: None (Earth’s magnetic
eld)
Battery voltage: Available effective battery voltage
1
2
3
4
5
6
7
付録索引
61
Basic and Accuracy Specications
HIOKI IR4057B961-01
Insulation Resistance Measurement
Rated
measurement
50 V125 V250 V500 V1000 V
voltage (DC)
Effective maximum
displayed value
Medium displayed
value
1st effective
measuring
range [M
Accuracy
(Tolerance)
2nd effective
measuring range
]
[M
Ω
Accuracy
(Tolerance)
Other measuring
range [M
Accuracy
(Tolerance)
100 M
Ω
2 M
Ω
0.200 to
10.00
]
Ω
10.1 to
100.0
]
Ω
250 MΩ500 MΩ2000 MΩ4000 M
5 M
0.200 to
25.0
IR4056, IR4057-50: ±2% rdg ±2 dgt
25.1 to
250
IR4053 and IR4055: ±8% rdg
IR4056, IR4057-50: ±5% rdg
10 M
Ω
0.200 to
50.0
IR4053, IR4055: ±4% rdg
50.1 to
500
0 to 0.199
±2% rdg ±6 dgt
50 MΩ100 M
Ω
0.200 to
501 to
2000
0.200 to
500
1010 to
Ω
Ω
1000
4000
62
Basic and Accuracy Specications
HIOKI IR4057B961-01
Insulation Resistance Measurement (continued)
Display range1 M
Maximum
displayed value
Resolution0.001 MΩ0.001 MΩ0.001 MΩ0.001 MΩ0.001 M
Display range10 M
Maximum
displayed value
Resolution0.01 MΩ0.01 MΩ0.01 MΩ0.01 MΩ0.01 M
Display range100 MΩ100 MΩ100 MΩ100 MΩ100 M
Maximum
displayed value
Resolution0.1 MΩ0.1 M
Display range‒250 MΩ500 MΩ1000 MΩ1000 M
Range conguration
Maximum
displayed value
Resolution‒1 M
Display range‒‒‒2000 MΩ4000 M
Maximum
displayed value
Resolution‒‒‒10 M
1.000 M
10.00 M
100.0 M
1 M
Ω
1.000 MΩ1.000 MΩ1.000 MΩ1.000 M
Ω
10 M
Ω
10.00 MΩ10.00 MΩ10.00 MΩ10.00 M
Ω
100.0 MΩ100.0 MΩ100.0 MΩ100.0 M
Ω
‒250 M
‒‒‒2000 M
1 M
Ω
10 M
Ω
0.1 MΩ0.1 MΩ0.1 M
Ω
500 MΩ1000 MΩ1000 M
Ω
1 M
Ω
1 M
Ω
10 M
Ω
1 M
Ω
Ω
Ω
Ω
Ω
Ω
1 M
10 M
1 M
4000 M
10 M
Ω
Ω
1
Ω
Ω
Ω
2
Ω
Ω
Ω
3
Ω
Ω
Ω
4
Ω
Ω
Ω
5
Ω
6
7
付録索引
63
Basic and Accuracy Specications
HIOKI IR4057B961-01
Insulation Resistance Measurement (continued)
1st effective
measuring range
±4% rdg
(0°C to 50°C)
±8% rdg
Fluctuations caused
by temperature
)*
effects (E
3
Effect of humidity
Effect of magnetic
eld
Fluctuations caused
by positioning effect
)
(E
1
Fluctuations caused
by supply voltage
)
effects (E
2
Effects of
capacitance
components
*: Applicable to the operating temperature range other than 18°C to 28°C.
Rated
measurement
voltage (DC)
Possible number of
measurements
Overload protection
(Greater than or
equal to −25°C and
less than 0°C, or
greater than 50°C
and less than or
equal to 65°C)
(Only for IR4056
and IR4057-50)
±4% rdg and within
allowance
±2.4% rdg‒‒
±4% rdg and within
allowance
Within ±10% for capacitance of 5 μF or less (including
variation)
50 V125 V250 V500 V1000 V
660 V AC (10 s), 1200 V DC (10 s) (IR4053 and IR4055 only)
2nd effective
measuring range
±8% rdg
(0°C to 50°C)
±16% rdg
(Greater than or
equal to −25°C and
less than 0°C, or
greater than 50°C
and less than or
equal to 65°C)
(Only for IR4056
and IR4057-50)
±8% rdg and within
allowance
Not applicable
±8% rdg and within
allowance
1000 times or more
600 V AC (10 s)
Other measuring
range
±2% rdg ±6 dgt
(0°C to 50°C)
±4% rdg ±12 dgt
(Greater than or
equal to −25°C
and less than 0°C,
or greater than
50°C and less than
or equal to 65°C)
(Only for IR4056
and IR4057-50)
±2% rdg ±6 dgt
±2% rdg ±6
dgt and within
allowance
660 V AC
(10 s)
64
Basic and Accuracy Specications
HIOKI IR4057B961-01
Insulation Resistance Measurement (continued)
Display update
interval
Open-circuit
voltage
Lower limit
resistance
value to be
maintained rated
measurement
voltage
Rated current1 mA to 1.2 mA
Short-circuit
current
Measurement terminal voltage characteristic
Response time
Judgment time
IR4053, IR4055, IR4056: Within 1.0 s (with resistance load)
(When switching from an open state to 10 times the default
IR4053, IR4055, IR4056: Within 1.0 s
(no update during response)
IR4057-50: Within 0.6 s (no update during response)
1 to 1.2 times of rated measurement voltage
0.05 MΩ0.125 MΩ0.25 MΩ0.5 M
1.2 mA or less
IR4057-50: Within 0.6 s (with resistance load)
IR4053, IR4055, IR4056: Within 0.8 s
IR4057-50: Within 0.3 s
judgment reference value)
1
2
1 M
Ω
Ω
3
4
5
6
7
付録索引
65
Basic and Accuracy Specications
HIOKI IR4057B961-01
Low Resistance Measurement (IR4056 and IR4057-50 only)
Open-circuit voltage4.0 V to 6.9 V
Measuring current
Effect of temperature*
Effect of supply
voltage*
Response timeWithin 1 s (measurement terminal open → short)
Possible number of
measurements
Overload protection600 V AC 10 s (by fuse protection)
Zero adjustment range0
Display update intervalWithin 1 s
Display range
(Auto range)
10
Ω
100
1000
Ω
Ω
Range conguration
*: Display value is applicable after zero adjustment
(When the temperature changes more than 1°C, zero adjustment is necessary.)
(display value before zero adjustment at 6
(applied in the operating temperature range excluding
Maximum
displayed value
10.00
100.0
1000
Ω
200 mA or more
±3% rdg ±2 dgt
18°C to 28°C)
±3% rdg ±2 dgt and within allowance
200 times or more
to 3
Ω
Ω
ResolutionAccuracy*
Ω
Ω
±3 dgt (0 Ω to 0.19 Ω)
±3% rdg ±2 dgt
to 10.00 Ω)
(0.20
Ω
±3% rdg ±2 dgt
0.01
Ω
Ω
0.1
1
Ω
or less)
Ω
66
Basic and Accuracy Specications
HIOKI IR4057B961-01
Voltage Measurement
AC/DC automatic
detection range
Effect of temperature
Overload protection
Display update interval
Response time
Input resistance100 kΩ or more (50 Hz/60 Hz)
Frequency range50 Hz/60 Hz
Display range
(Auto range)
420 V
(minimum displayed
value: 30.0 V)
AC Voltage Measurement
600 V750 V1 V
AC detected at 30 V or greater (50 Hz/60 Hz).
(pulsating currents with an overlapping AC component of
30 V or more are detected as AC)
Measurement accuracy per 1°C × 0.1
(applied in the operating temperature range excluding
1200 V DC (10 s) (IR4053 and IR4055 only)
(when input voltage is changed from 0 V to 600 V)
Range conguration
Maximum
displayed value
420.0 V0.1 V
18°C to 28
750 V AC (10 s), 750 V DC (10 s)
Within 1 s
Within 1.2 s
ResolutionAccuracy
°C)
±2.3% rdg ±8 dgt
(ranges in excess of
600 V are outside the
accuracy guarantee)
1
2
3
4
5
Input resistance100 kΩ or more
Display range
(Auto range)
4.2 V4.200 V0.001 V
42 V42.00 V0.01 V
420 V420.0 V0.1 V
IR4053, IR4055:
1000 V
DC Voltage Measurement
IR4056, IR4057-50:
600 V
* Over 1000 V for IR4053 and IR4055 only
Range conguration
Maximum
displayed value
IR4053, IR4055:
1100 V
IR4056, IR4057-50:
750 V
ResolutionAccuracy
±1.3% rdg ±4 dgt
(ranges in excess of
are outside the
600 V
*
1 V
accuracy guarantee)
6
7
付録索引
67
Basic and Accuracy Specications
HIOKI IR4057B961-01
Measurement voltage (DC)
Maximum displayed value
1st effective measuring range [MΩ]
Accuracy (Tolerance)
2nd effective easuring range [M
Accuracy (Ttolerance)
Other measuring range [MΩ]
Accuracy (Tolerance)
Effect of temperature (E
Effect of humidity
Effect of magnetic eld
Impact of positioning (E
Effect of supply voltage (E2)
Effect of superimposing DC voltage
Possible number of measurements
Overload protection
Display update interval
(no update during response)
Open voltage*
Lower limit resistance value to
maintain rated measurement
voltage
Rated current
Short-circuit current
Response time
Range conguration
Ω
)Accuracy × 1.0 (applicable to the operating
3
)
1
]
500 VPVΩ 1000 V
PV
Ω
2000 M
Ω
0.200 to 5000.200 to 1000
501 to 20001010 to 4000
temperature range other than 18°C to 28°C)
Accuracy × 1.0 and within allowance
Accuracy × 1.0 and within allowance
660 V AC (10 s), 1200 V DC (10 s)
1 to 1.2 times of rated measurement voltage
20 MΩ ±5%20 MΩ ±5%
0.025 mA ±20% 0.05 mA ±20%
Within 4.0 s (Measurement start → Display)
±4% rdg
±8% rdg
0 to 0.199
±2% rdg ±6 dgt
Accuracy × 0.5
Not applicable
Within ±10%
1000 times or more
Within 1.0 s
1.2 mA or less
4000 M
See explanation for 500 V and 1000 V of
the insulation resistance measurement
* For the PVΩ measurement function, the output voltage is divided by the
resistor and the resistor connected between measurement terminals
1 M
PVΩ Measurement (IR4053 and IR4055 only)
Ω
because a 1 M
Example: If a DMM with input impedance 10 M
current limiting resistor is connected to the EARTH terminal.
Ω
voltage, the voltage is divided by 1 M
is used to measure an open
Ω
and 10 MΩ.
Ω
Ω
68
Functionality specications
HIOKI IR4057B961-01
4.3 Functionality specications
Live circuit
indicator
Automatic electric
discharge
Auto power save (APS) The power will go off automatically approx.
Automatically discharges the electric charge
still present in the capacitance of the
measuring object after the insulation resistance
measurement.
Bar graph display of residual voltage
• Discharge resistance:
• Maximum capacitive load: 5 μF
•
Discharge time: Max. 30 s (when connected to
5 μF)
10 minutes after the last operation or last live
circuit indicator display.
Can be canceled using the power supply
activation options.
• Light automatic OFF function: Available (3 min.
after last operation)
• Turns red when the comparator judgment result
is FAIL.
• Operation at erroneous input: Alternates white
and red.
The instrument’s rmware can be updated using
GENNECT Cross.
Required: GENNECT Cross (Ver. 1.8 or later)
or less (IR4053 and IR4055)
1.2 M
Ω
or less (IR4056 and IR4057-50)
800 k
Ω
Instrument rmware (Ver. 2.00 or later)
1
2
3
4
5
6
7
付録索引
69
Functionality specications
HIOKI IR4057B961-01
Power-on Options
Canceling the
power-saving
function
(p. 30)
Displaying the
serial number
Checking the
HID setting
(p. 56)
Displaying
the software
version
Turn on the instrument while holding down the LIGHT
key.
Turn on the instrument while holding down the RELEASE
key.
The serial number will be displayed three digits at a time.
In the following example, the month and year of
manufacture are May 2021.
Example: [210] → [512] → [345]
After checking the number, set the rotary switch to OFF.
1. Turn on the instrument while holding down the
RELEASE key.
The serial number screen will be displayed.
2. Press RELEASE key for 3 s or more.
The HID setting saved by the Z3210 will be displayed.
1. Turn on the instrument while holding down the 0
ADJ key and the COMP key.
2. Press the RELEASE key while the [vEr] display is
active.
The display will alternate between the version number
vx.xx
and model
[
]
After checking the number, set the rotary switch to OFF.
405x
[
.
]
Ω
70
Maintenance and Service
HIOKI IR4057B961-01
5
WARNING
Touching any of the high-voltage points inside
the instrument is very dangerous. Customers are
not allowed to modify, disassemble, or repair the
instrument. Doing so may cause re, electric shock,
or injury.
Calibrations
The calibration period varies with the conditions and environment
of use. It is recommended to determine a calibration period based
on those factors and to have the instrument regularly calibrated by
Hioki. Please contact your authorized Hioki distributor or reseller to
have your instrument periodically calibrated.
Precautions when transporting the instrument
When transporting the instrument, be sure to observe the following
precautions:
• To avoid damage to the instrument, remove the batteries from
the instrument. Moreover, be sure to pack in a double carton.
Damage that occurs during transportation is not covered by the
warranty.
• When sending the instrument for repair, be sure to include details
of the problem.
Disposal
Handle and dispose of the instrument in accordance with local
regulations.
Cleaning
• To clean the instrument, wipe it gently with a soft cloth moistened
with water or mild detergent.
• Wipe the display gently with a soft, dry cloth.
• Wipe the dust from metal parts of alligator clips with a soft cloth to
avoid any impact on the measurements.
1
2
3
4
5
6
7
付録索引
71
Troubleshooting
HIOKI IR4057B961-01
5.1 Troubleshooting
Before Returning for Repair
If damage is suspected, check the following before contacting your
authorized Hioki distributor or reseller.
SymptomCheck ItemsRemedy and Reference
The power is not
turning on.
The batteries run
out immediately.
The MEASURE
key is not working
for the lead with a
switch.
During insulation
resistance, low
resistance, or PV
measurement, the
live circuit indicator
and the display
blinks in red, and
the buzzer sounds.
Does the battery have
sufcient charge?
Have the batteries been
installed improperly?
Are you using alkaline
batteries?
Is the plug of the lead with
a switch fully inserted?
Does the voltage applied
between the measurement
terminals exceed the
Ω
following values?
Insulation resistance, PV
approx. 20 V
Low resistance: approx. 5 V
Replace with the new
batteries. (p. 22)
Install the batteries in the
proper orientation.(p. 22)
Replace the batteries with
alkaline batteries.(p. 22)
Fully insert the plug to the
limit without any gaps.
(p. 25)
Make sure that the
measuring object is
disconnected from a live
circuit. If voltage exists in
:
the measuring object, the
Ω
live circuit indicator blinks.
72
Troubleshooting
HIOKI IR4057B961-01
SymptomCheck ItemsRemedy and Reference
Unable to perform
measurement.
Unable to perform
measurement in
500 V, 1000 V or
range.
PV
Ω
In the 500 V range,
1000 V range or
range, turning
PV
Ω
on the MEASURE
key enables the
lock function that
has been released.
Are you setting the rotary
switch while the MEASURE
key turned on?
Is the voltage between the
measuring terminals over
any of the following values
before turning on the
MEASURE key?
50 V to 250 V range:
Approx. 90 V
500 V and PV
ranges: Approx. 500 V
1000 V and PV
ranges: Approx. 1000 V
Is the instrument locked so
as to prevent inadvertent
voltage application?
Is the battery new?
Does the battery have
sufcient charge?
Is alkaline battery used?
Is the temperature low (0°C
or less)?
Has 1 minute lapsed after
the last operation?
500 V
Ω
Ω
1000 V
Turn off the MEASURE key
and then press it again.
Separate the measuring
object from all sources of
power before performing
measurement.
Release the lock function.
(p. 35)
Replace the batteries with
new alkaline batteries. *
(p. 22)
Remove the batteries and
warm them up, or replace
them with new alkaline
batteries. (p. 22)
Release the lock function
again. (p. 35)
1
2
3
4
1
5
6
7
The measured
value is shown
as the maximum
display value.
Is there a broken
connection in a test lead?
Are the test leads securely
connected?
Check the continuity of the
test lead with a tester.
Check the connection
between the test leads and
the instrument, and check
the connection of the tips of
the test leads.
73
付録索引
Troubleshooting
HIOKI IR4057B961-01
SymptomCheck ItemsRemedy and Reference
Measured values
vary and fail to
stabilize.
Measured
values acquired
through insulation
resistance
measurement or
measurement
PV
Ω
uctuate over time.
(If using the
IR4057-50, use
the 1-minute value
display function.)
Is a charging circuit located
near the measurement
object?
When the measuring object
connected is a capacitor:
Does the measuring object
have a large capacitance
component (capacitor)?
When the measuring
object connected is not a
capacitor:
This phenomenon
reects the inuence of
the measuring object
capacitance component.
This is not a malfunction or
error.
Disconnect the circuit
breaker for any nearby
charging circuits. If this is
not possible, use the lowest
measured value as the
measurement result.
If it is possible to remove
the capacitor, do so.
If not, use the lowest
measured value as the
measurement result.
Select measured values
acquired one minute
after the start of the
measurement.
If a large capacitance
component included in the
measuring object causes
the uctuation of measured
values, select measured
values after they have
stabilized.
74
Troubleshooting
HIOKI IR4057B961-01
SymptomCheck ItemsRemedy and Reference
A different
measured value
results each
time the same
measuring object
is measured.
The output
voltage polarity is
reversed.
Is there any impact due
to the material of the
measuring object?
Is there any impact due to
the temperature/humidity
characteristics of the
measuring object?
The reversal is due to
the characteristics of the
insulation ohmmeter.
This does not represent a
malfunction.
Allow an adequate amount
of time (about 1 hour to
1 day) to pass after the
rst measurement before
repeating measurement.
The effects of polarization*
increase as the insulation
resistance increases.
Measure the object under
the same temperature
and humidity conditions.
In general, an insulator’s
insulation resistance
value will decrease as
temperature and humidity
increase.
Reference: the insulation
resistance value of some
insulated cables decreases
to 1/4 or less when the
temperature increases 10°C.
–
1
2
2
3
4
5
6
7
付録索引
75
Troubleshooting
HIOKI IR4057B961-01
SymptomCheck ItemsRemedy and Reference
When the
instrument is
calibrated, the
accuracy of
the insulation
resistance range
falls outside
the device
specications.
*1 Batteries with high internal resistance may not be able to deliver enough
energy to power the instrument, even if you’re using new alkaline batteries
or batteries with sufcient charge. If the instrument does not operate even
though its batteries have just been replaced, try batteries from a different
manufacturer.
*2 Polarity: A phenomenon whereby a substance’s positive and negative
electric charges move in opposite directions when an electric eld is
applied to it, causing the center position of the positive and negative
charges to shift.
Has the supplied or
optional test lead used?
Has the insulation of the
test lead deteriorated?
Use the test leads that
came with the instrument
or its optional test leads
to perform the calibration
procedure. With standard
wiring, characteristics are
affected when the resistance
in the 1000 V range reaches
or exceeds 100 M
Replace the deteriorated
test lead with a new one.
.
Ω
76
Troubleshooting
HIOKI IR4057B961-01
Errors and status codes
When an error is displayed on the LCD screen, repair is necessary.
Please contact your authorized Hioki distributor or reseller.
IR4053, IR4055, IR4056
1
CodeDescriptionRemedy and Reference
Err1
Err2
Err3
Err4
Err6
Err8
FUSE (blinks)
bAtt
The instrument was
unable to perform
zero adjustment.
(Low resistance
measurement)
The specied fuse has
not been installed.
Settings data
damaged.
Adjustment data
damaged.
Abnormality in
measurement circuit.
Abnormality in voltage
generation circuit.
Wireless
communications error.
The protective fuse has
tripped.
Low battery voltage.Replace the batteries. (p. 22)
• Verify that there is no broken
connection in the test leads.
• Zero adjustment can be
performed for readings of up
. Ensure that the wiring
to 3
Ω
resistance is 3 Ω or less. (p. 42)
Use only the specied type of
fuse. (p. 22)
Repair is required.
Replace the batteries.
If there is no apparent
improvement, the instrument
needs repair.
Repair is required.
Replace the indicated fuse.
(p. 22)
2
3
4
5
6
7
付録索引
77
Troubleshooting
HIOKI IR4057B961-01
IR4057-50
CodeDescriptionRemedy and Reference
• Verify that there is no broken
connection in the test leads.
• Zero adjustment can be
performed for readings of
up to 3
. Ensure that the
Ω
wiring resistance is 3
less. (p. 42)
Repair is required.
Replace the batteries.
If there is no apparent
improvement, the instrument
needs repair
Take the following actions
(p. 27):
• Reinstall the Z3210.
• Install a different Z3210.
If the error persists, you are
experiencing a instrument
failure. Contact your authorized
Hioki distributor or reseller to
organize repair.
Use GENNECT Cross to
update the rmware again.
(p. 69)
Replace the indicated fuse.
(p. 22)
Replace the batteries. (p. 22)
Err 0ΩADJ
Err1
Err2
Err4
Err5 01
Err5 02
Err8
Err9
FUSE (blinks)
APS → P.oFF
bAtt → P.oFF
Zero adjustment is outside
the allowable range.
(Low resistance
measurement)
Program data corrupt.
Adjustment data damaged.
The EEPROM used to
store settings data has
failed (including failure
to communicate with the
EEPROM).
Abnormality in
measurement circuit.
Abnormality in voltage
generation circuit.
Z3210 communications
error
(connection failure; Z3210
or hardware failure)
Firmware update error
The protective fuse has
tripped. (The fuse is userreplaceable.)
Powered off by APS.–
Instrument powered off
due to supply voltage drop
or
Ω
78
Appendix
HIOKI IR4057B961-01
Appx. 1 Measurement Principles
1. Insulation resistance measurement
The measuring object’s insulation resistance Rx is calculated by applying a
voltage V to the object, measuring the leak current I that ows to the object as
a result, and dividing the voltage V by the leak current I.
2. Low resistance measurement (IR4056, IR4057-50)
The measuring object’s resistance Rx is calculated by applying a current I
to the measuring object, measuring the voltage V that occurs between the
measurement terminals as a result, and dividing the voltage V by the current I.
measurement (IR4053, IR4055)
3. PV
Ω
The resistance Rx is calculated using the equation (Applied voltage V)/
(Leakage current I) by applying a voltage V to the measuring object, and then
measuring the leakage current I owing through the measuring object and
applied voltage V. (Voltage and current generated from the measuring object
are subtracted.)
1
2
3
4
5
6
7
Appx.
索引
Appx.1
Operation Uncertainty
HIOKI IR4057B961-01
Appx. 2 Operation Uncertainty
The operation uncertainty and the variations of measurement value for the
respective inuence quantity approved by EN/IEC61557 are as follows:
Intrinsic uncertainty/
inuence quantity
Intrinsic
A
uncertainty
E2Supply voltage4.5 V to 6.8 V±4% rdg±3% rdg ±2 dgt
E
Temperature0°C to 35°C±4% rdg±3% rdg ±2 dgt
3
Operation
B
uncertainty
Guaranteed range of operation
Inuencing factor non-applicable for E1 and E4 to E
uncertainty
Operation
range
Reference
condition
resistance
1st effective
measurement
Variation
Insulation
±5% rdg±3% rdg ±2 dgt
±12% rdg±30% rdg
range
10
Low resistance
0.2
to 2
Ω
Ω
Appx.2
Insulation Resistance Measurements for Solar Cell Array
HIOKI IR4057B961-01
Appx. 3 Insulation Resistance
Measurements for Solar Cell
Array
There are two insulation resistance measurements for solar cell arrays.
Characteristics of them are as follows:
Measurement with P-N opened
PVΩ measurement of this manual is explained with this measurement.
As solar cell voltage inuences the test voltage, the measurement may not
be accurate. Incorrect procedure may damage the solar panel. If earth fault is
occurred due to earth leakage as shown in the following gure, current being
generated inuences the insulation resistance meter resulting in inaccurate
measurement with a normal insulation resistance meter. PV
mode of the IR4053 and IR4055 allows accurate measurements without the
effect from power generation.
P
measurement
Ω
Connection box
1
2
3
4
N
PV
Earth
PV
leakage
P
N
Earth
Connection box
Earth
Insulation resistance meter
Measurement with P-N shorted
This measurement allows accurate measurements but is also a highly
dangerous method as arc discharge may be generated due to the short
circuit. There is also a re risk depending on the deterioration level of the
solar panel.
PV current
current reading
5
6
7
Appx.
索引
Appx.3
Insulation Resistance Measurements for Solar Cell Array
HIOKI IR4057B961-01
Appx.4
HIOKI IR4057B961-01
HIOKI IR4057B961-01
HIOKI IR4057B961-01
Ueda, Nagano 386-1192 Japan 65760
HIOKI IR4057B961-01
Rudolf皿 Diese卜Strasse 5
Eschborn, Germany
hioki@hioki.eu
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.