Hioki Hioki FT6031-03 Manual

Instruction Manual
FT6031
EARTH TESTER
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
July 2014 Edition 1 FT6031A981-00 14-07H

Contents

Introduction .........................................................................1
Verifying Package Contents ..............................................1
Options (sold separately) ..................................................2
Safety Notes ........................................................................ 3
Usage Notes ........................................................................ 8
1 Overview 13
1.1 Overview and Features .................................13
Overview ................................................................... 13
Features .................................................................... 13
1.2 Parts Names and Functions .........................15
1.3 How to Use Carrying Case ...........................20
2 How to Measure 21
2.1 Measurement Workfl ow ................................ 21
2.2 Attaching/Removing Protector ....................24
2.3 Inserting/Replacing Batteries ......................25
2.4 Inspection before Use ................................... 29
2.5 Setting Up Comparator (PASS/FAIL Test) ...31
How to set up comparator ......................................... 32
How to disable comparator ....................................... 32
2.6 Precise Measurement for Earth Resistance (Precise Measurement Method,
Three-pole Method) .......................................33
Performing zero adjustment ...................................... 35
Connecting measurement cables .............................36
Measuring earth resistance ......................................39
Stowing ..................................................................... 42
i
2.7 Simplifi ed Measurement for Earth Resistance (Simplifi ed Measurement Method,
Two-pole Method) ..........................................44
Performing zero adjustment ...................................... 46
Connecting test leads ...............................................48
Measuring earth resistance ......................................51
Stowing ..................................................................... 51
2.8 Cautions and Tips for Measurement ........... 52
Distance between earthing electrodes ...................... 52
Location to install auxiliary earthing rod .................... 53
How to insert / pull out auxiliary earthing rod ............54
2.9 Auto Power Save (Power-saving Function) 56
2.10 Activating the LCD All-on Display ............... 57
2.11 Displaying the Serial number ....................... 58
3 Specifi cation 59
3.1 General Specifi cation ...................................59
3.2 Measurement Function/Performance ..........61
4 Maintenance and Service 67
4.1 Repair, Inspection, and Cleaning .................67
4.2 Troubleshooting ............................................69
4.3 Error Display ..................................................72
Appendix Appx. 1
Appendix 1 Earth Resistance ...................Appx. 1
Appendix 2 Measurement Principle ......... Appx. 3
ii

Introduction

Introduction
Thank you for purchasing the HIOKI FT6031 Earth Tester. To obtain maximum performance from the product, please read this manual rst, and keep it handy for future reference.

Verifying Package Contents

When you receive the instrument, inspect it carefully to ensure that no damage occurred during shipping. In particular, check the accessories, panel switches, and connectors. If damage is evident, or if it fails to operate according to the specifi cations, contact your authorized Hioki distributor or reseller.
Check the package contents as follows.
FT6031
L9840 L9841 Measurement Cable
L9842-11 Measurement Cable
L9842-22 Measurement Cable
C0106 Carrying Case ×1
Protector
LR6 Alkaline battery × 4 Instruction manual
Accessory
Auxiliary Earthing Rod (2 piece set) ×1
(alligator clip, black 4 m) ×1
(yellow 10 m, equipped with winder) ×1
(red 20 m, equipped with winder) ×1
1

Options (sold separately)

Options (sold separately)
The following options are available for the instrument. Contact your authorized Hioki distributor or reseller when ordering.
L9787 Test Lead
L9840 Auxiliary Earthing Rod
L9841 Measurement Cable
L9842-11 Measurement Cable
(for simplifi ed measurement method, indoor use only, red and black 1.2 m each)
(for precision measurement method, 2 pcs in 1 set) (6 mm, entire length of 270 mm, straight section 235 mm, material: stainless SUS304)
(for precision measurement method, alligator clip, black 4 m)
(for precision measurement method, yellow 10 m, equipped with winder)
L9842-22 Measurement Cable
L9843-51 Measurement Cable
L9843-52 Measurement Cable
L9844 Measurement Cable
9050 Earth Nets
C0106 Carrying Case
(for precision measurement method, red 20 m, equipped with winder)
(for precision measurement method, yellow 50 m, equipped with fl at cable winder)
(for precision measurement method, red 50 m, equipped with fl at cable winder)
(for earthing terminal board, alligator clip, 3 cables in 1 set, red/yellow/black 1.2 m each)
(2 sheets in 1 set, 300 mm × 300 mm)
2

Safety Notes

Safety Notes
This instrument is designed to conform to IEC 61010 Safety Standards, and has been thoroughly tested for safety prior to shipment. However, using the instrument in a way not described in this manual may negate the provided safety features.
Before using the instrument, be certain to carefully read the following safety notes.
DANGER
Mishandling during use could result in injury or death, as well as damage to the instrument. Be certain that you understand the instructions and precautions in the manual before use.
WARNING
With regard to the electricity supply, there are risks of electric shock, heat generation, fi re, and arc discharge due to short circuits. If persons unfamiliar with electricity measuring instruments are to use the instrument, another person familiar with such instruments must supervise operations.
3
Safety Notes
Notation
In this manual, the risk seriousness and the hazard levels are classifi ed as follows.
Indicates an imminently hazardous situation
DANGER
WARNING
CAUTION
IMPORTANT
that will result in death or serious injury to the operator.
Indicates a potentially hazardous situation that may result in death or serious injury to the operator.
Indicates a potentially hazardous situation that may result in minor or moderate injury to the operator or damage to the instrument or malfunction.
Indicates information related to the operation of the instrument or maintenance tasks with which the operators must be fully familiar.
Indicates a high voltage hazard. If a particular safety check is not performed or the instrument is mishandled, this may give rise to a hazardous situation; the operator may receive an electric shock, may get burnt or may even be fatally injured.
Indicates prohibited actions.
Indicates the action which must be performed.
*
Additional information is presented below.
4
Symbols affi xed to the instrument
Indicates cautions and hazards. When the symbol is printed on the instrument, refer to a corresponding topic in the Instruction Manual.
Indicates a double-insulated device.
Indicates DC (Direct Current).
Indicates AC (Alternating Current).
Indicates the power switch mark.
Symbols for various standards
Indicates the Waste Electrical and Electronic Equipment Directive (WEEE Directive) in EU member states.
Indicates that the instrument conforms to safety regulations set out by the EC Directive.
Safety Notes
5
Safety Notes
Screen display
This instrument uses the following screen displays.
ABCDEFGH I J KLMNOPQRSTUVWXYZ
1234567890
Accuracy
We defi ne measurement tolerances in terms of f.s. (full scale), rdg. (reading) and dgt. (digit) values, with the following meanings:
(Maximum display value)
f.s.
The maximum displayable value.
(Reading or displayed value)
rdg.
The value currently being measured and indicated on the measuring instrument.
(Resolution) The smallest displayable unit on a digital measuring
dgt.
instrument, i.e., the input value that causes the digital display to show a “1” as the least-signifi cant digit.
6
Safety Notes
Measurement categories
To ensure safe operation of measuring instruments, IEC 61010 establishes safety standards for various electrical environments, categorized as CAT II to CAT IV, and called measurement categories.
DANGER
• Using a measuring instrument in an environment
designated with a higher-numbered category than that for which the instrument is rated could result in a severe accident, and must be carefully avoided.
• Using a measuring instrument without categories in
an environment designated with the CAT II to CAT IV category could result in a severe accident, and must be carefully avoided.
This instrument conforms to the safety requirements for CAT II 300V, CAT III 150 V, CAT IV 100 V measuring instruments. CAT II: When directly measuring the electrical outlet receptacles of
CAT III: When measuring the primary electrical circuits of heavy equipment
CAT IV: When measuring the circuit from the service drop to the service
the primary electrical circuits in equipment connected to an AC electrical outlet by a power cord (portable tools, household appliances, etc.).
(fi xed installations) connected directly to the distribution panel, and feeders from the distribution panel to outlets.
entrance, and to the power meter and primary overcurrent protection device (distribution panel).
Distribution Panel
Service Entrance
Service Drop
CAT IV
Power Meter
Internal Wiring
CAT III
Fixed Installation
CAT II
Outlet
7

Usage Notes

Usage Notes
Follow these precautions to ensure safe operation and to obtain the full benefi ts of the various functions.
Verifying before usage
Before using the instrument, verify that it operates normally to ensure that no damage occurred during storage or shipping. If you fi nd any damage, contact your authorized Hioki distributor or reseller.
DANGER
Before using the instrument, check that the coating of the test leads and cables are neither ripped nor torn and that no metal parts are exposed. Using the instrument under such conditions could result in electric shock. Replace the test leads and cables with those specifi ed by our company.
IMPORTANT
Use only the specifi ed test leads and cables. Using a non- specifi ed cable may result in incorrect measurements due to poor connection or other reasons.
8
Usage Notes
Use environment of the device
The protection rating for the enclosure of this device (based on EN60529) is *IP65/67.
CAUTION
Although this device has a dust-proof, jet-proof and water­proof structure, it is not for completely shutting out the water intrusion into the inside. Please note that it can be a cause of failure.
*IP65/67:
This indicates the degree of protection provided by the enclosure of the device against use in hazardous locations, entry of solid foreign objects, and the ingress of water.
6: Protected against access to hazardous parts with
wire measuring 1.0 mm in diameter. Dust-proof type (Dust shall not penetrate the enclosure.)
5: The equipment inside the enclosure is protected
against the harmful effects of water projected in jets against the enclosure from any direction.
7: Watertight (Quantities of water that may harm the
enclosure when it is temporarily immersed in water shall not penetrate the enclosure.)
9
Usage Notes
For details on the operating temperature and humidity, see the specifi cations. (p. 59)
CAUTION
• Installing the instrument in inappropriate locations may cause a malfunction of instrument or may give rise to an accident. Avoid the following locations.
• Exposed to corrosive or combustible gases
• Exposed to water, oil, chemicals, or solvents
• Exposed to high humidity or condensation
• Exposed to a strong electromagnetic fi eld or electrostatic charge
• Near induction heating systems (such as high­frequency induction heating systems and IH cooking equipment)
• Susceptible to vibration
• Do not store or use the instrument where it could be exposed to direct sunlight or high temperature.
• To avoid damage to the instrument, protect it from physical shock when transporting and handling. Be especially careful to avoid physical shock from dropping.
• Do not place the device on an unstable table or an inclined place. Dropping or knocking down the device can cause injury or damage to the device.
10
Handling the cables
CAUTION
• To prevent cable damage, do not step on cables or pinch them between other objects. Do not bend or pull on cables at their base.
• The ends of the L9787 Test lead and L9840 Auxiliary earthing rod are sharp. Be careful to avoid injury.
• Use only the specifi ed auxiliary earthing rod, cables, and test leads. Using a non-specifi ed cable may result in incorrect measurements due to poor connection or other reasons.
Precautions during measurement
WARNING
If the instrument is used in locations where the rating indicated on the instrument or cords is exceeded, the instrument may be damaged resulting in personal injury. Do not use the instrument in such locations. See “Measurement categories” (p.7).
Precautions during shipment
CAUTION
• When transporting the instrument, use the original packing materials in which it was shipped, and pack in a double carton. Damage occurring during transportation is not covered by warranty.
• To avoid damage to the instrument, remove the accessories and optional equipment from the instrument before shipment.
Usage Notes
11
Usage Notes
12

Overview

1

1.1 Overview and Features

Overview

The grounding works applied to the distribution lines and electrical facilities are essential for preventing electric shock and fi re as well as for safeguarding the equipment. This instrument is an earth tester that is fully functional for measuring earth resistance for grounding works. It is capable of providing accurate and highly reliable measurement. The instrument can provide precision measurement (three-pole method) and simplifi ed measurement (two-pole method).

Features

High accuracy
Auto-range and
auto-check for
auxiliary earthing
electrode
High allowable
earth resistance for
auxiliary earthing
electrode
The accuracy of the 200.0 rdg. ±4dgt.
The measurement is performed by simply pressing MEASURE button. There is no need for cumbersome range-switching. In addition, the earth potential and auxiliary earthing electrode are automatically checked.
The resistance that the auxiliary earthing electrode can tolerate is now about 10 times higher than the conventional level. As a result, it can provide measurement under adverse conditions.
range is ±1.5%
Ω
13
Overview and Features
Dust-proof,
jet-proof and water-
proof
Supplied with a
winder
Drop-proof
(when equipped with
a protector)
The instrument can withstand water at a depth of 1m for 30 minutes.
The instrument is supplied with a useful winder so that it can be easily prepared and packed up before/after measurement.
Its robust structure can withstand a drop from 1 m onto concrete surface.
14
Parts Names and Functions

1.2 Parts Names and Functions

Front
Protector
Removed when replacing the batteries. (p. 24, p. 68)
Operation buttons
(p. 17)
Please do not press the buttons of the device with a sharp object. It may damage the device.
Measurement terminals
E Connected with the black cable. S(P) Connected with the yellow cable. H(C) Connected with the red cable.
Display
(p. 18)
15
Parts Names and Functions
Rear and Sides
Battery cover (side view)
Waterproof seal
It needs to be replaced when degraded. Please contact your authorized Hioki distributor.
Battery cover
Removed when replacing the batteries. (p. 25)
Serial number label
Please do not remove the label as it is needed for product control such as product warranty etc.
16
Operation Buttons
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
Parts Names and Functions
5
6
1
2
3
4
5
6
Start/stop for measuring earth resistance
• Displays the resistance of each earthing electrode. (p. 39)
• Display switching (three-pole method, two-pole method)
• DC/AC switching (when measuring earth potential)
• Function switching (three-pole method, two-pole method)
• Unlocks the retained value and displays the current earth potential value.
Power ON/OFF
Sets/cancels comparator setting (COMP lights up/goes off). (p. 31)
Sets/cancels zero adjustment setting. (p. 35, p. 46)
17
Parts Names and Functions
3
1 2
4
6
5
7
8
9
Display
8
1 2
3
4
7
9
6
5
18
Parts Names and Functions
1
2
3
4
5
6
7
8
9
Comparator
1
2
3
4
5
6
7
comparison result (PASS)
Comparator comparison result (FAIL)
Lights up when DC/ AC auto-detect setting is enabled for measuring earth potential.
Three-pole method (p. 33)
Two-pole method (p. 44)
Zero adjustment (p. 35, p. 46)
Displays when
COMP
comparator setting is enabled. (p. 31)
Retention of the measured value
Displays when earth potential exceeds allowable range.
Displays the battery level. (p. 27)
Displayed 30 sec. before auto-power-
APS
save function is activated. (p. 56)
8
9
See p. 72 for error display.
Indicates the terminal to be connected with measurement cable or test lead.
Turns on when the resistance of each (auxiliary) earthing
OPEN
electrode is high or a measurement cable is not connected.
Earth resistance of earthing electrode
Earth resistance of auxiliary earthing electrode S
Earth resistance of auxiliary earthing electrode H
Live wire warning indicator (red LED lights up as follows)
• For three-pole method, 30 V or higher between S(P)-E terminals or 85 V or higher between H(C)-E terminals and H(C)-S(P) terminals.
• For two-pole method, 30 V or higher between H(C)-E terminals.
• When measuring earth resistance.
19
How to Use Carrying Case

1.3 How to Use Carrying Case

Please store the device, winder and other accessories/options into the C0106 Carrying Case as shown in the fi gure below.
• Please do not store commercially available pegs in this carrying case as those have sharp tips. It may damage the case.
• Please do not wash the carrying case.
• Winder
• Auxiliary Earthing Rod
20
Earth Tester
Please make sure to retract the winder knob before storing it in the carrying case.
Measurement Cable (Black)
Instruction Manual

How to Measure

2
2.1 Measurement Workfl ow
Before using the instrument, be sure to read “Usage Notes” (p.8).
Preparation
Insert the batteries. (p.25)
As necessary, have other
Perform the startup check. (p.29)
Measurement
Turn the power on and select the measurement method.
optional items available and ready.
Connect measurement cables or leads to the measurement terminals.
Perform zero adjustment. (three-pole method (p.35), two-pole method (p.46))
Start the measurement.
test
End of the measurement
Turn the power off and remove measurement cables or test leads from the measuring object.
21
Measurement Workfl ow
• This product should only be connected to the
secondary side of a breaker, so the breaker can prevent an accident if a short circuit occurs. Connections should never be made to the primary side of a breaker, because unrestricted current fl ow could cause a serious accident if a short circuit occurs.
• Connect the test lead to the instrument fi rst, and
then to the active lines to be measured. To avoid electric shock and short circuits, do not short­circuit two wires to be measured by bringing the metal part of the test lead's clip into contact with them. Never touch the metal end of the clip.
To avoid electric shock, observe the following precautions.
• Prior to measurement, please make sure that the
earthing electrode has been disconnected from the distribution system. The measurement cables L9841, L9842-11, L9842-22, L9843-51 and L9843-52 are measurement cables with the maximum rated voltage of 30 V (between input terminals and the ground) and are designed to measure the earth resistance of an earthing electrode disconnected from the distribution system.
• Turn off all power before connecting cables and test
leads.
• Confi rm that all connections of cables and test
leads are secure to the measurement terminals. The increased resistance of loose connections can lead to overheating and fi re.
DANGER
WARNING
22
Measurement Workfl ow
WARNING
To prevent electric shock, confi rm that the white
or red portion (insulation layer) inside the cable of L9787 test lead and L9844 measurement cable are not exposed. If a color inside the cable is exposed, do not use the cable.
CAUTION
• To avoid damaging the cables and test leads, grasp the connector, not the cable, when unplugging the cable.
23
Attaching/Removing Protector

2.2 Attaching/Removing Protector

Attaching the protector
Tilt the device and slide it into the protector, and then push the entire device into the protector.
Removing the protector
Hold it with both hands and push the one end of the protector down.
IMPORTANT
If the protector is removed, drop-proof (p.60) will be void.
24
Inserting/Replacing Batteries

2.3 Inserting/Replacing Batteries

Before using the instrument fi rst time, insert 4 LR6 alkaline batteries. Before measurements, check that the battery level is suffi cient. When the battery charge is low, replace the batteries.
WARNING
• To avoid electric shock, turn off the power and disconnect the cables and test leads before replacing the batteries.
• To prevent instrument damage or electric shock, use only the screws for securing the battery cover in place that shipped with the product. If you have lost any screw or fi nd that any screws are damaged, please contact your Hioki distributor for a replacement.
• Battery may explode if mistreated. Do not short- circuit, disassemble or dispose of in fi re. Do not recharge alkaline batteries. Handle and dispose of batteries in accordance with local regulations.
• After replacing the batteries, replace the cover, screws, and put on the protector before using the instrument.
25
Inserting/Replacing Batteries
CAUTION
Poor performance or damage from battery leakage could result. Observe the cautions listed below.
• Do not mix new and old batteries, or different types of batteries.
• Be careful to observe the battery polarity during installation.
• Do not use batteries after their recommended expiry date.
• Do not allow used batteries to remain in the instrument.
• To avoid corrosion from battery leakage and/or damage to the instrument, remove the batteries from the instrument if it is to be kept in storage for an extended period.
• If the battery level is low, mark blinks. To carry out measurement, the batteries need to be replaced with new ones.
• After use, be sure to turn off the instrument.
• Although rechargeable batteries (nickel-hydride) can be used for measurement, the battery level indicator will not be accurately displayed.
• When replacing the batteries after cleaning, the replacement should be carried out after the device has been completely dried.
• The operating temperature of the batteries included in the shipment is -10°C to 45°C (14°F to 113°F). When using this
device outside this temperature range, use batteries that can support such a low or high temperature range.
26
Battery warning indicator
Fully charged.
As the battery charge diminishes, black charge bars disappear, one by one, from the left of the battery indicator.
The battery voltage is low. Replace the batteries as soon as possible.
(Blinks) The battery is exhausted. Replace the batteries.
Inserting/Replacing Batteries
27
Inserting/Replacing Batteries
ter
r
y
y
y
y
y
y
y
y
Rear
Battery Cover
Screwdriver
Have the following items
1
available and ready.
Phillips screwdriver
LR6 Alkaline battery × 4
Turn off the device and
2
remove the measurement cables or test leads from the device.
Remove the protector. (p.24)
3
Unscrew the screws of the
4
battery cover with a phillips screwdriver.
Remove the battery cover.
5
Do not remove the waterproof seal from the battery cover.
When replacing the batteries,
6
all of the old batteries should be removed.
Pay attention to the
7
polarities of the batteries when inserting 4 new batteries (LR6).
Reattach the battery cover
8
onto the device and tighten the screws.
Attach the protector. (p.24)
9
28
Inspection before Use

2.4 Inspection before Use

Before using the instrument, verify that it operates normally to ensure that no damage occurred during storage or shipping. If you fi nd any damage, contact your authorized Hioki distributor or reseller.
Check items Solution
Is the battery level suffi cient? Check the battery level indicator on the upper
Is there any missing segment in the display items?
Is there any damage or crack in the device?
Is there any foreign material (sand etc.) inside the measurement terminals?
Is there any damage or exposed internal white part or metal in the coating of measurement cable or test lead?
right corner while the power has been turned on. If Replace the batteries with new ones. (p.25)
Check by activating the LCD all-on display. (p.57) If there is a missing segment, the device needs to be repaired.
Conduct visual checking. If damage is found, the device should not be used and needs to be repaired as it can cause electric shock.
Remove all foreign materials if any. If it cannot be removed, the device needs to be repaired.
If damage is found, it should not be used and needs to be replaced as it can cause electric shock.
is blinking, the battery level is low.
29
Inspection before Use
Check items Solution
Check for open circuit in measurement cable or test lead in the following method:
1. • For three-pole method Press Fn button to
display
• For two-pole metho Press Fn button to
display
2. Connect measurement cables or test leads to the device and short­circuit their tips.
3. Press MEASURE button to check that approx. 0
is indicated.
Ω
.
.
If not indicating approx. 0
• The measurement cables or test leads have not been fully inserted. Fully insert the leads.
• The measurement cables or test leads may have an open circuit. Replace it with another lead that is
d
specifi ed by Hioki.
If the symptom persists even after the measurement cables or test leads are replaced, the device may have a failure. The device needs to be repaired.
Ω
30
Setting Up Comparator (PASS/FAIL Test)

2.5 Setting Up Comparator (PASS/FAIL Test)

The device has a comparator function, which can indicate PASS or FAIL with the display indicator and beep. The earth resistance can be measured without setting up the comparator.
The comparator function operates as follows:
Comparison result Display Buzzer sound
Measured value Reference
value (PASS)
Measured value > Reference
value (FAIL)
The comparison reference value can be chosen from the reference values in the following table.
Reference value (Ω)
12345
6789
10 20 30 40 50
60 70 80 90
100* 200 300 400 500 OFF
Intermittent
Continuous
*Default
31
Setting Up Comparator (PASS/FAIL Test)
1
2,3

How to set up comparator

Press Fn button to set to
1
(three-pole method), or
(two-pole method).
Press COMP button.
2,3
1
3
2
blinks, and the resistance for the
comparison reference appears.
Press COMP button again and then choose a comparison reference.
If there is no operation for approx. 2 seconds after the desired comparison reference has been chosen, the comparator is enabled and
The comparator setting is saved even after the power is turned off.
lights up in the display.

How to disable comparator

Press COMP button while the comparator has been enabled.
1
2
blinks.
Press COMP button and then select [OFF].
If there is no operation for approx. 2 seconds, the comparator is disabled.
32
Precise Measurement for Earth Resistance
(Precise Measurement Method, Three-pole Method)

2.6 Precise Measurement for Earth Resistance (Precise Measurement Method, Three-pole Method)

WARNING
This device can output a voltage of approx. 30 V. Although the device has a dust-proof, jet-proof and water-proof structure, the device should always be dried before using it for measurement so as to avoid electric shock.
CAUTION
Do not connect the test leads if any foreign material remains inside. It may cause failure.
There are two types of measurement method for earth resistance: precision measurement method (three-pole method) and simplifi ed measurement method (two-pole method), and the precision measurement method (three-pole method) is the basic measurement method for earth resistance. The simplifi ed measurement method is used when measurement cannot be performed by the precision measurement method. The precision measurement is performed by inserting two auxiliary earthing rods into the ground as shown in the fi gure on p.38.
33
Precise Measurement for Earth Resistance (Precise Measurement Method, Three-pole Method)
Measurement of large-scale earthing electrodes
When measuring a large-scale earthing electrode such as a mesh earthing electrode, ring earthing electrode, or earthing electrode provided by a large building structure, it cannot be accurately measured since the H(C) electrode and S(P) electrode come inside the earth resistance area of E electrode. If long cables are used to avoid the H(C) electrode and S(P) electrode getting inside the earth resistance area, accurate measurement cannot be carried out as it is signifi cantly affected by noise. Generally, measurement of large-scale earthing electrode requires a large measurement current of approx. 20 A. Use measuring instrument designed for measuring large-scale earthing electrodes for this measurement. (No measuring instrument available for this purpose from Hioki)
34
Precise Measurement for Earth Resistance
1
5
6
7
3
8
4
(Precise Measurement Method, Three-pole Method)

Performing zero adjustment

Always perform zero adjustment prior to measurement.
Remove the cover that protects the
1
2
7
3
6
8
5
1
measurement terminals.
Make sure that no sand, gravels
2
or small stones remain inside the measurement terminals.
Connect black, yellow and red
3
measurement cables respectively to E, S(P) and H(C) terminals of the device.
Short-circuit the tips of the three
4
measurement cables.
Press the button to turn it on.
5
Press Fn button to display
6
(three-pole method).
Earth potential appears on the display.
Press MEASURE button.
7
4
A measured value of approx. 0 Ω appears in approx. 8 seconds, and
When OPEN appears below the measurement terminal ( not have been connected to a measurement terminal, or the cable may have an open circuit. cable check with a tester etc.
), the measurement cable may
Check the connection and perform
lights up.
Press 0ΩADJ button.
8
adjustment is completed.
lights up and then zero
35
Precise Measurement for Earth Resistance (Precise Measurement Method, Three-pole Method)
If the measured value exceeds 3 Ω, [Err 1] appears and zero adjustment will not be executed. Zero adjustment settings will be saved even if the power is turned off.
How to disable zero adjustment
Hold down
Ω
0
ADJ button for at least one second, while is on.

Connecting measurement cables

WARNING
• The maximum rated voltage between input terminals
and the ground is as follows; (CAT II): 300 V rms (CAT III): 150 V rms (CAT IV): 100 V rms Attempting to measure voltages exceeding this level with respect to ground could damage the instrument and result in personal injury.
• To avoid electric shock, be careful to avoid shorting
live lines with the test leads.
36
Precise Measurement for Earth Resistance
(Precise Measurement Method, Three-pole Method)
CAUTION
• To prevent cable damage, do not step on cables or pinch them between other objects. Do not bend or pull on cables at their base.
• The ends of the auxiliary earthing rod are sharp. Be careful to avoid injury.
• To ensure safe operation, use only the accessory cables.
• The cable is hardened under the 0 degree or colder environment. Do not bend or pull it to avoid tearing its shield or cutting cable.
• If the cable melts, the metal part may be exposed and can pose a hazard. Do not touch the area that is generating heat.
Red
Yellow
Black
53
Auxiliary Earthing Electrode H
10 m 10 m
Auxiliary Earthing Electrode S
1
Earthing Electrode E
E
HS
37
Precise Measurement for Earth Resistance (Precise Measurement Method, Three-pole Method)
Use the measurement cable (black)
1
to connect between earthing electrode and E terminal.
Carry two winders along to the
2
measuring location while pulling out the measurement cables.
2
At the location where the
3
measurement cable (yellow) has been fully pulled out, insert the auxiliary earthing rod into the ground and connect the measurement cable (yellow).
Carry the winder (measurement
4
cable: red) along the straight line to a further distance between the earthing electrode E and auxiliary earthing electrode S while pulling out the measurement cable.
At the location where the
5
measurement cable (red) has been fully pulled out, insert the auxiliary earthing rod into the ground and connect the measurement cable (red).
• Insert the auxiliary earthing rods into a moist layer in the ground. Since this device can accept a large resistance of auxiliary earthing electrode, the auxiliary earthing rods do not need to be inserted unnecessarily deep into the ground.
• For accurate measurement, the distance between E-S-H needs to be approx. 5 m. The measurement cables (yellow) and (red) should be positioned approx. 10 cm away from each other. Make sure the cables do not tangle or overlap together.
38
Precise Measurement for Earth Resistance
1
2
3
(Precise Measurement Method, Three-pole Method)

Measuring earth resistance

Press the button to turn it on.
1
3
2 1
When NOISE Appears
If the earth potential is high (10 V rms or 14.3 Vpk or higher),
and the earth potential peak value appears on the display. When is on, or when (live wire warning indicator) is blinking, it is not possible to measure earth resistance.
Since leak current is fl owing into the earthing electrode, fi rst disconnect any electric equipment connected to the earthing electrode and then press MEASURE button again.
Press Fn button to display
2
(three-pole method).
Earth potential appears on the display.
Press MEASURE button so that the
3
device automatically executes the earth potential checkauxiliary earth resistance checkearth resistance measurement in sequence.
The measurements will be completed in approx. 8 seconds, and then the measured value appears and
Check the measured value.
4
lights up.
39
Precise Measurement for Earth Resistance (Precise Measurement Method, Three-pole Method)
• This device automatically detects AC/DC ( / ) of the
earth potential. If AC/DC needs to be switched, it can be switched by pressing
DISPLAY button while the current earth potential has been
displayed.
• To check earth potential After measurement of earth resistance, press DISPLAY button while is lit up so that the earth potential will be displayed. When is lit up, press Fn button so that the retained value is unlocked and the current earth potential will be displayed.
When OPEN Appears
This device automatically check whether or not each earth resistance is within the allowable range by measuring the earth resistance of the auxiliary earthing rod prior to measuring the resistance of the earthing electrode E. If the earth resistance of the auxiliary earthing electrode exceeds the allowable range, OPEN appears below the measurement terminal that exceeds the allowable range and the earth resistance of the earthing electrode E will not be measured.
Countermeasures when OPEN appears
Take the following actions for the auxiliary earthing rod connected with the measurement terminal for which OPEN appears.
• Pour water
• Stick in deeper
• Insert the auxiliary earthing rod into another location
• If the clip connecting point is dirty, wipe and clean the auxiliary earthing rod with a soft cloth.
40
Precise Measurement for Earth Resistance
(Precise Measurement Method, Three-pole Method)
DISPLAY button allows to display the earth resistance and earth
potential of each earthing electrode.
Earth resistance of earthing electrode E
Earth resistance of auxiliary earthing electrode S
Earth resistance of auxiliary earthing electrode H
V
Earth potential
When the resistance (RH) of auxiliary earthing electrode exceeds 5 kΩ, the display range becomes the range of 200 Ω without displaying the digit of 0.01 Ω even though the resistance of earthing electrode is 20 Ω or less. The following table shows examples. If the digit of 0.01 Ω is required, pour some water over the auxiliary earthing rod (H) to reduce the earth resistance to 5 kΩ or less.
Resistance RH of
auxiliary earthing
electrode H
0 to 5 k
Ω
to 50 k
5 k
Ω
Ω
Example of indicated
value (1)
When 9.52
measured
9.52 Ω (Range: 20 Ω) 13.48 Ω (Range: 20 Ω)
9.5 Ω (Range: 200 Ω) 13.5 Ω (Range: 200 Ω)
is
Ω
Example of indicated
value (2)
When 13.48
measured
is
Ω
41
Precise Measurement for Earth Resistance (Precise Measurement Method, Three-pole Method)

Stowing

Press the button to turn it off.
1
Remove the measurement
2
cables from the measurement terminals and fi t the cover of the measurement terminal.
Remove the measurement cables
3
from the auxiliary earthing rods and pull out the auxiliary earthing rods without bending them.
(See p.54 for how to pull out.)
Rewind the measurement cables
4
(red, yellow) with the respective winders and stow the winders in the carrying case with the auxiliary earthing rods inserted into the winder's holders.
Remove the measurement cable
5
(black) from the earthing electrode and fold it, and then stow it into the carrying case. (p.20)
Always fi t the cover of the measurement terminals immediately after use. Any foreign object entering the measurement terminal may cause a failure.
42
Precise Measurement for Earth Resistance
(Precise Measurement Method, Three-pole Method)
Measurement on concrete
Since concrete is conductive, auxiliary earthing electrodes can be installed on concrete. Place an auxiliary earthing rod on concrete and pour water over it, or cover the auxiliary earthing rod with a wet rag to form an auxiliary earthing electrode. If the earth resistance of the auxiliary earthing electrode is not reduced by the above methods, place the optional 9050 earth net on concrete and then position the auxiliary earthing rod on the earth net and pour water over it. Before measurement, allow some time for the water to well soak into the concrete. As an alternative to the earth net, a metal plate or aluminum foil etc. may be used. However, the earth net will provide better reduction in the earth resistance of auxiliary earthing electrode. Since asphalt is insulator, it is generally not possible to install the auxiliary earthing electrode on asphalt. However, measurement may be possible on asphalt that has water permeability.
9050 Earth Nets
43
Simplifi ed Measurement for Earth Resistance (Simplifi ed Measurement Method, Two-pole Method)
2.7 Simplifi ed Measurement for Earth Resistance (Simplifi ed Measurement Method, Two-pole Method)
DANGER
• Use the neutral side (ground side) of the commercial
power supply for this measurement. Prior to connection, use a voltage detector etc. to make sure that it is going to be connected with the neutral side and take caution for electric shock.
• This device can be connected to the neutral side of
an outlet with a voltage-to-ground of 300 V or less, or to the wire on the neutral side of the breaker's secondary side with a voltage-to-ground of 150 V or less. Do not connect with anything other than those specifi ed above. It can be hazardous.
WARNING
• Use the optional test lead L9787 for simplifi ed
measurement for safety. Connecting the measurement cables L9841, L9842-11, L9842-22, L9843-51 and L9843-52 to a commercial power supply may cause electric shock.
• This device can output a voltage of approx. 30 V.
Although the device has a dust-proof, jet-proof and water-proof structure, the device should always be dried before using it for measurement so as to avoid electric shock.
44
Simplifi ed Measurement for Earth Resistance
(Simplifi ed Measurement Method, Two-pole Method)
CAUTION
• When the device is set to two-pole method, even if it is connected to the earth side of a commercial power supply, it will not trigger the earth leakage breaker since the measurement current is suppressed to 4 mA or less. However, do not use this method for measurement at a location where an earth leakage breaker or leakage relay with the current sensitivity of less than 10 mA has been installed, since such an earth leakage breaker or leakage relay may be triggered.
• The simplifi ed measurement function of this device is a function for measuring earth resistance with small inductance component. Therefore, a resister connected in series with inductance component of 3 mH or more may not be accurately measured.
• Removable sleeves are attached to the metal pins at the ends of the test leads. To prevent a short circuit accident, be sure to use the test leads with the sleeves attached when performing measurements in the CAT III measurement category. For the measurement categories, see “Measurement categories” (p.7).
• If the sleeves are inadvertently removed during measurement, stop the measurement.
• When carrying out measurements with the sleeves in place, be careful to avoid damaging the sleeves. If the cover cap accidentally comes off during measurement, it should be handled carefully to avoid electric shock.
• Since the tip of the metal pin is sharp, care needs to be taken to avoid injury.
• L9787 is a test lead specifi cally designed for indoor use. Do not use it outdoor.
45
Simplifi ed Measurement for Earth Resistance (Simplifi ed Measurement Method, Two-pole Method)
Removing and attaching the sleeves of L9787 Test lead
Removing the sleeves Gently hold the bottom of the sleeves and pull the sleeves off. Safely store the removed sleeves so as not to lose them.
Attaching the sleeves Insert the metal pins of the test leads into the holes of the sleeves, and fi rmly push them all the way in.
What is simplifi ed measurement method (two-pole method)?
Simplifi ed measurement method (two-pole method) is a measurement method to check the earth resistance of the equipment earthing with an earth system called TT method. In case of not being able to insert an auxiliary earthing rod, the earth resistance is obtained with use of an existing low earthing resistor as an auxiliary electrode. In this method, the measured value is the sum (Rx+Ro) of the earth resistances of the measuring object and existing earthing resistor, according to the measurement principle. Therefore, the earth resistance of the existing earthing resistor used needs to be lower than that of the earthing electrode of the measuring object.
In the simplifi ed measurement method, the resistance of the earthing element used is added to the measurement result. It is very diffi cult to measure 10
or less in the simplifi ed method.
Ω

Performing zero adjustment

The range that this device can provide zero adjustment for is 3 Ω or less. If the measured value exceeds 3 not be executed.
, [Err 1] appears and zero adjustment will
Ω
46
Simplifi ed Measurement for Earth Resistance
3
4
6
5
(Simplifi ed Measurement Method, Two-pole Method)
Remove the cover of the
1
6
4
3
2
E
H(C)
7
1
measurement terminals.
Connect the E terminal and H(C)
2
terminal of this device respectively with the L9787 test lead (black) and L9787 test lead (red).
Press the button to turn it on.
3
Press Fn button to display
4
(two-pole method).
A measured value (approx. 0 V) of the earth potential appears
Connect (short-circuit) the tips of
5
test leads.
Press MEASURE button.
6
5
A measured value of approx. 0 Ω appears in approx. 3 seconds, and
When appears below the measurement terminal, a test lead may not have been connected to the measurement terminal, or the lead may have an open circuit. Check the connection and perform cable check with a tester etc.
.
lights up.
Pressing 0ΩADJ button will turn
7
adjustment.
How to disable zero adjustment
Hold down 0
ADJ button while
Ω
on and complete zero
is on.
47
Simplifi ed Measurement for Earth Resistance (Simplifi ed Measurement Method, Two-pole Method)

Connecting test leads

WARNING
• Do not use this device for measuring the voltage of
commercial power supply.
• If there is a large voltage on the neutral side, (live
wire warning indicator) blinks and beep sound goes off. Immediately remove the test leads from the commercial power supply.
• If the earth potential is high, attention needs to be
paid for the risk of electric shock.
The fi gure below shows an example of connection in the case of using a commercial power supply that is grounded on its N (neutral) side.
Pole-mounted Transformer
5R
48
Outdoor
5[
Home Distribution Panel
Indoor
Master Breaker
Central Earth Terminal
Earth Leakage
Breaker
Branch Breaker
Simplifi ed Measurement for Earth Resistance
2
3
4
5
(Simplifi ed Measurement Method, Two-pole Method)
Use a voltage detector etc. to make
1
sure that there is no voltage on the N (neutral) side of commercial power supply.
Press the
2
Press Fn button to display
3
4
3 2
5
E
H(C)
(two-pole method).
When (three-pole method) is chosen, the earth leakage breaker etc. may be triggered due to its large measurement current.
Connect the L9787 test lead (black)
4
with the earthing electrode of measuring object.
Connect the L9787 test lead (red) with
5
the N (neutral) side of commercial power supply.
Earth potential appears on the display.
button to turn it on.
49
Simplifi ed Measurement for Earth Resistance (Simplifi ed Measurement Method, Two-pole Method)
• When appears, a large earth potential (10 V rms or 14.3 Vpk or
higher) exists between the earth and the N (neutral) side of commercial
power supply. A large leak current may be flowing through the earthing
electrode of the measuring object or through the earthing element of the
commercial power supply used for measurement.
insulation resistance test or leakage current test etc. In addition, disconnect
any electric equipment from the earthing electrode.
• This device automatically detects AC/DC of the earth potential.
• If AC/DC needs to be switched during earth potential measurement, it
can
be switched by pressing
• After measurement of earth resistance, press DISPLAY button while
is lit up so that the earth potential will be displayed.
When
unlocked and the current earth potential will be displayed.
When
it is not possible to execute earth resistance measurement.
is lit up, press Fn button so that the retained value is
is on, or when (live wire warning indicator) is blinking,
DISPLAY
button.
Therefore, conduct an
50
Simplifi ed Measurement for Earth Resistance
(Simplifi ed Measurement Method, Two-pole Method)

Measuring earth resistance

Press MEASURE button so that the device automatically executes the following measurements in sequence. The measured value appears in approx. 3 seconds and lights up.
Check earth potential.
1
Check whether or not the peak value of the earth potential is within the allowable range.
Measure earth resistance.
2
Measure the sum (Rx + Ro) of the earth resistance of earthing electrode and the earth resistance on the neutral side of commercial power supply.

Stowing

Press the button to turn it off for safety.
1
Remove the test leads from the measurement terminals and
2
t the cover of the measurement terminal. (p.42)
Fold the test leads together and stow it into the carrying case.
3
51
Cautions and Tips for Measurement

2.8 Cautions and Tips for Measurement

Distance between earthing electrodes

When the distance between E-H(C) is I m as shown in Figure (a), if the resistance of the earthing element E is measured while changing the distance x m between the electrodes E-S(P), measurement results such as shown in (b) are obtained. Therefore, its error becomes greater as the location of the auxiliary earthing rod S(P) moves closer to the earthing element E or auxiliary earthing rod H(C). In addition, if the distance between the electrodes E-H(C) is short, the measurement error is greater as the earth resistance under test (Rx) and the earth resistance of auxiliary earthing rod (Rc) cannot be separated from each other. If earthing is provided by a building structure etc. in a large area, the resistance area indicated in (a) becomes very wide. In order to carry out accurate measurement, the auxiliary earthing rods (S(P) and H(C)) need to be installed at a location well away from the earthing element (Rx). As to confi rm the above, carry out measurements at several locations while moving the location of the auxiliary earthing rod S(P) from the earthing element (Rx) to the auxiliary earthing rod H(C) and check whether or not there is an almost fl at section shown in (b) in the measured resistance even though the auxiliary earthing rod S(P) has been moved. If no fl at section is seen, the measurement distance is insuffi cient. Move the installation locations of the auxiliary earthing rods (S(P) and H(C)) to further locations.
52
Cautions and Tips for Measurement
Measured Value
Ground Surface
S(P)
Resistance Area of E Electrode
The distance between E-H(C) of this device can be up to 50 m by using the optional L9843-51 and L9843-52. In principle, it is possible to carry out measurement even if the distance is more than 50 m. However, the measurement result cannot be guaranteed.
Resistance Area of H(C) Electrode
Flat Section

Location to install auxiliary earthing rod

It is ideal to install the auxiliary earthing rod S(P) at the middle point of the straight line between the earthing electrode E and auxiliary earthing rod H(C). However, if installation is not possible due to an obstacle etc., the measurement error can be reduced by installing the auxiliary earthing rod (S(P)) within 29° from the straight line between the earthing electrode E and auxiliary earthing rod H(C), wherein the location should be outside the radius of 5 m from the earthing element E and auxiliary earthing rod H(C) as shown in the fi gure.
E
5 m
S(P) H(C)
29°
5 m
53
Cautions and Tips for Measurement

How to insert / pull out auxiliary earthing rod

How to Insert
The accessory auxiliary earthing rods are suitable for providing auxiliary earthing electrodes and are designed for thickness and hardness that allow insertion into a general ground by hand. Since it is skinnier than conventional models, it can be inserted into a small gap. When inserting the rod, wear gloves and insert it perpendicular to the ground surface.
If the ground is too hard for inserting by hand, use a hammer to perpendicularly drive into the ground. Hammering the auxiliary earthing rod too hard may result in bending it. In case of not going into the ground with gentle taps, use the optional 9050 earth net for measurement.
How to Pull Out
• Hold the loop part of the auxiliary earthing rod and pull it out while turning it.
54
• If it does not come out by hand, put a hard metal bar etc. (other than auxiliary earthing rod) through the loop part of the auxiliary earthing rod and pull the auxiliary earthing rod while turning it. If pulling the auxiliary earthing rod with another auxiliary earthing rod put through the loop, it will result in bending it.
• Do not apply force to the auxiliary earthing rod from the side as it may result in bending the auxiliary earthing rod.
Cautions and Tips for Measurement
55
Auto Power Save (Power-saving Function)

2.9 Auto Power Save (Power-saving Function)

Approx. 10 min after the last operation or the last time (live wire warning indicator) turns on or blinks, the auto power save becomes
active and the screen turns off.
How to recover from auto power save
Press the
How to disable auto power save
Turn the power on while pressing 0
The settings of an disabled auto power save will not be saved when the power is turned off.
button to turn the screen on.
ADJ button.
Ω
56
Activating the LCD All-on Display

2.10 Activating the LCD All-on Display

Turn the power on while pressing DISPLAY button.
1
If any button is pressed, its normal measurement screen
2
will appear.
57
Displaying the Serial number

2.11 Displaying the Serial number

Turn the power on while pressing Fn button. The fi rst 4 digits and the last 5 digits of the serial number (9 digits) appear alternately. If any button is pressed, its normal measurement screen will appear.
58
First 4 digits
(Example of a serial number: 123456789)
Last 5 digits
Specifi cation
3
3.1 General Specifi cation
Product warranty period 3 years
Guaranteed accuracy period
Nominal range of use
Operating temperature and humidity
Position Power supply voltage Earth potential Resistance of auxiliary earthing electrode External magnetic fi eld
Storage temperature and humidity
Operating environment (scope of application)
Power source LR6 Alkaline battery × 4
Rated power supply voltage
Maximum rated power 3 VA
Available effective battery voltage
1 year
-10°C to 40°C (14°F to 104°F): 80%RH or less (non-condensing) 40°C to 45°C (104°F to 113°F): 60%RH or less (non-condensing) 45°C to 50°C (113°F to 122°F): 50%RH or less (non-condensing) 50°C to 55°C (122°F to 131°F): 40%RH or less (non-condensing) Level ±90° Available effective battery voltage Refer to: “Allowable earth potential” (p.63) Refer to: “Allowable resistance of auxiliary earthing electrode” (p.62) 400 A/m or less, DC and frequency 50/60 Hz
-20°C to 60°C (-4°F to 140°F): 80%RH or less (non-condensing)
Indoor, outdoor (excluding farmland*), pollution degree 3, altitude up to 2,000 m (6,562-ft.)
According to the requirements regarding the
*
regulations for open-circuit voltage in EN 61557-5
1.5V DC × 4
4.5 V ±0.19 V to 6.8 V
59
General Specifi cation
Possible number of measurements
IP protection code IP65/IP67
Drop-proof 1 m above concrete (with protector attached)
Maximum rated voltage between input terminals and the ground
Withstand voltage 3510 V, 50/60 Hz,
Dimensions Approx. 185 W × 111 H × 44 D mm (7.28” W ×
Mass Approx. 570 g (20.1 oz.) (including batteries
Accessories
Options Refer to: “Options (sold separately)” (p.2)
Applicable standards Safety
400 times (measurement conditions: three-pole method, auxiliary earthing electrode resistance
, measure 10 Ω with the range of 20 Ω,
100
Ω
measure at 10 seconds interval)
(EN 60529)
100 V AC/DC (measurement category IV) 150 V AC/DC (measurement category III) 300 V AC/DC (measurement category II) anticipated transient overvoltage 2500 V
between measurement terminals (together) and case, for 15 seconds, sensed current 1 mA
4.37” H × 1.73” D) (including protector, excluding terminal covers)
and protector, excluding other accessories)
Refer to: “Verifying Package Contents” (p.1)
Device : EN 61010
Measuring circuit : EN 61010 EMC : EN 61326 Earth tester : EN 61557
60
Measurement Function/Performance

3.2 Measurement Function/Performance

Temperature and humidity: 23°C ± 5°C (73°F ± 9°F), 80%RH or less
Measurement of earth resistance
(auxiliary earthing electrode resistance 100 Ω±5%, earth potential 0 V)
RE: Earth resistance of measuring object, RH: Earth resistance of H
Operation system
Measurement system
Output voltage AC without DC component
Open-circuit voltage
Measurement current
Measurement current waveform
Measuring frequency
Measuring time Three-pole method: Within 8 seconds
electrode, R
Voltage application, measurement of voltage and current (effective resistance is measured by synchronous detection)
Two-pole method / three-pole method, switchable
30 V rms or less and 42.43 Vpk or less
Three-pole method: 25 mA rms or less
Two-pole method: 4 mA rms or less
Sine wave
128 Hz ±2 Hz
Two-pole method: Within 3 seconds
: Earth resistance of S electrode
S
61
Measurement Function/Performance
Range confi guration
(auto range)
Effect of positioning (
E
Effect of supply
E
voltage (
)
2
Effect of temperature
*5
E
)
(
3
Effect of earth
E
potential (
)
4
Applied
(RE and
RH)
*1
R
E
R
H
Display range
conditions
Display range
Resolution
Accuracy
3-pole 0.01
2-pole 1
*3
(specifi c uncertainty A)
Allowable
resistance of
auxiliary earthing
electrode
Operation
R
H
R
S
±30%rdg. (applied to three-pole
uncertainty
Guaranteed range
of operation uncertainty
Not applicable due to digital type
)
1
*4
Accuracy × 0.5 and within accuracy
Accuracy × 1.0 (-10 Accuracy × 2.0 (50
50 Hz, 60 Hz
DC, 16 2/3 Hz,
400 Hz
°C to 50°C)
°C to 55°C)
0 to 3 V Accuracy × 1.0
3 to 10 V Accuracy × 2.0
0 to 3 V Accuracy × 1.0
*2
20
Ω
20 Ω or
less
5 kΩ or
less
0 to
20.00
Ω
Ω
±1.5
%rdg.
8 dgt.
±
5 k
Ω
5 k
Ω
method)
5.00 to 2000
200 Ω2000
200 Ω or
less
2 k
or
less
50 kΩ or
Ω
50 k
0 to
200.0
0.1
2000
Ω
Ω
Ω
±1.5 %rdg.
±4 dgt.
50 k
Ω
50 k
Ω
Ω
200 Ω to
or less
Ω
less
200 to
1
Ω
1
Ω
Ω
Ω
62
Measurement Function/Performance
Allowable earth potential
Effect of the resistance of auxiliary earthing
E
electrode (
)
5
Effect of system
E
frequency (
)
7
Effect of system voltage (
E
)
8
Effect of external magnetic fi eld
Earth resistance of auxiliary earthing electrode auto­check
(auto-check after start of measurement)
Auto-check for earth potential
*6
(auto-check after start of measurement)
Overload protection
Effect of earth capacity (two­pole method)
10 V rms (DC or sine wave)
Either R
or RS electrode Variable value
H
or less Accuracy × 1.0
10 k
Ω
Above 10 k
to 50 k
Ω
Ω
Accuracy × 2.0
Not applicable
Not applicable
Accuracy × 0.5
Display range
Maximum display
value
Resolution 10 Ω0.1 k
1000 Ω10 kΩ100 kΩ200 k
1000 Ω10.0 kΩ100 kΩ200 k
1 k
Ω
Ω
Accuracy Not specifi ed
Display range 42 Vpk
Maximum display
value
42.0 Vpk
Accuracy ±2.3 %rdg.±8 dgt.
360 V AC (for 1 min, between each terminal)
360 V DC(for 1 min, between each terminal)
Up to 10 nF Within accuracy specifi cation
Above 10 nF to
500 nF
Accuracy × 2.0
Above 500 nF Not specifi ed
10 k
Ω
Ω
Ω
63
Measurement Function/Performance
Zero adjustment allowable range
*1 Automatically select the minimum display range that can meet both R
and R *2 Three-pole method only. *3 Applied after zero adjustment, ±0.3
(with use of L9481). *4 It shall be the range in which the operation uncertainty within ±30% is
guaranteed; applied to three-pole method. *5 Applied in the range excluding 18 to 28°C. *6 Function to check whether or not the peak of earth potential is within the
allowable range; no AC coupling; display the peak value (peak on + side).
values.
H
3
or less
Ω
is added before zero adjustment
Ω
E
Earth potential measurement
DC/AC
auto-detection range
Measurement system
Terminal for voltage measurement
Overload protection
Display refresh interval
Input resistance 4 M
Response time
0.3 V DC ± 0.2 V or higher is detected as DC Manual switching function provided Pulsating fl ow with superimposed AC component that periodically zero-crosses is detected as AC
Average value rectifi cation effective value indication
Three-pole method: Between S terminal (+) E terminal (-)
Two-pole method: Between H terminal (+) E terminal (-)
360 V AC for 1 min
360 V DC for 1 min
Within 1 second
or higher (DC / 50 Hz / 60 Hz)
Ω
Within 2 seconds (when input voltage is changed from 0 V to 30 V)
64
Measurement Function/Performance
Effect of temperature
Range confi guration
Accuracy × 1.0 (applied in the range excluding 18 to 28°C)
Display range 30 V rms
Maximum
display value
Resolution 0.1 V
Accuracy
50 / 60 Hz ±2.3 %rdg.±8 dgt.
30.0 V rms
DC ±1.3 %rdg.±4 dgt.
65
Measurement Function/Performance
66

Maintenance and Service

4

4.1 Repair, Inspection, and Cleaning

DANGER
Customers are not allowed to modify, disassemble, or repair the instrument. Doing so may cause fi re, electric shock, or injury.
Calibrations
IMPORTANT
Periodic calibration is necessary in order to ensure that the instrument provides correct measurement results of the specifi ed accuracy.
The calibration frequency varies depending on the status of the instrument or installation environment. We recommend that the calibration frequency is determined in accordance with the status of the instrument or installation environment and that you request that calibration be performed periodically.
Cleaning
• To clean the instrument, wipe it gently with a soft cloth moistened with water or mild detergent. When rinsing with water, make sure that the battery cover has been attached. Make sure that the protector has been removed and rinse with room-temperature water.
• After cleaning, thoroughly wipe off water of the device and protector. Completely dry them before putting the protector on.
• Rinse with room-temperature water. If rinsing with hot water, the waterproof performance may be impaired.
• Do not put water while the battery cover has been taken off. It may cause failure due to water intrusion.
67
Repair, Inspection, and Cleaning
• When replacing the batteries after cleaning, the replacement should be carried out after the device has been completely dried.
• This device is waterproof to a water depth of 1 m for 30 min. Do not soak and wash the device. Do not soak the device into hot water.
• Do not wash the device with a washing machine.
• Do not use any electronic appliance such as a dryer or microwave for drying this device.
Wipe the LCD gently with a soft, dry cloth.
IMPORTANT
Never use solvents such as benzene, alcohol, acetone, ether, ketones, thinners or gasoline, as they can deform and discolor the case.
If the instrument is not to be used for an extended period of time
IMPORTANT
To avoid corrosion from battery leakage and/or damage to the instrument, remove the batteries from the instrument if it is to be kept in storage for an extended period.
Disposal
Handle and dispose of the instrument in accordance with local regulations.
Protector
A protector is available as a service part. Contact your authorized Hioki distributor or reseller.
68
Troubleshooting

4.2 Troubleshooting

When a malfunction of the instrument is suspected, check the information in “Before sending the instrument for repair” (p.70) and then, if necessary, contact your authorized Hioki distributor or reseller.
Pack the instrument so that it will not sustain damage during shipping, and include a description of existing damage. We do not take any responsibility for damage incurred during shipping.
When sending the instrument for repair, remove the batteries and pack carefully to prevent damage in transit. Include cushioning material so the instrument cannot move within the package. Be sure to include details of the problem. Hioki cannot be responsible for damage that occurs during shipment.
Reference: “Precautions during shipment” (p.11)
IMPORTANT
The 4 screws that secure the upper and lower cases in the underside of the device have a special shape. Do not unscrew the screws with a tool other than the specialized tool as the screws may be damaged if trying to unscrew them with a tool other than the specialized tool, making it impossible to carry out repair.
69
Troubleshooting
Before sending the instrument for repair
If it is not operating correctly, check the following items.
Symptom Cause, check, countermeasure
The power does not turn on. There are no batteries inside.
The resistance of auxiliary earthing electrode does not come down (precision measurement).
The batteries have been incorrectly installed.
Refer to how to install the batteries.
Have the batteries been depleted?
Replace the batteries with new ones.
If the power still will not turn on, the device has a failure and needs to be repaired. (p. 25)
Bad connection of measurement cable, the ground is dry.
Make sure that the measurement
cables are connected to the earthing electrode/auxiliary earthing rod.
Short-circuit the tips of the
measurement cables and then carry out the measurement. If the measured value is approx. 0 Ω, it is caused by a high earth resistance of the earthing electrode. Insert the auxiliary earthing rod deeper. Alternatively, pour water over the auxiliary earthing rod. still will not come down, move the auxiliary earthing electrode to another location. The measurement cables (yellow) and (red) should be positioned approx. 10 cm away from each other.
If the resistance
70
Troubleshooting
Symptom Cause, check, countermeasure
appears and
measurement is not allowed (cannot measure the earth resistance due to high earth potential).
Trying to carry out measurement on a newly built residential building, but the simplifi ed measurement (two-pole method) is not allowed.
The measured value becomes approx. 0 measuring with use of an existing auxiliary earthing electrode for measurement.
Small noise occurs inside the device during measurement.
The measured value is high. It has been set to two-pole method.
Measurement is not allowed when trying to measure with an earth net laid on asphalt.
Ω
The earth potential exceeds the value that can be accepted by this device. A large leakage current may be fl owing into the earthing electrode from equipment that has been connected to the earthing electrode. Or, the earth resistance of earthing electrode may be high and a large earth potential may have occurred by a small leakage current.
Remove the equipment that has been
connected to the earthing electrode and then carry out the measurement. (p. 39)
Measurement is not allowed if the electricity has not been distributed from the power company.
The earthing electrode and the auxiliary
when
electrode for measurement may have been connected through concrete.
Drive an auxiliary earthing rod
into the ground and then carry out measurement instead of using an auxiliary electrode for measurement.
It is the noise from the oscillator circuit inside the device. It is not a failure.
Press Fn button to select three-pole method.
Since asphalt is insulator, measurement is not possible with an earth net.
71
Error Display
Symptom Cause, check, countermeasure
Auxiliary earthing rod has been bent.

4.3 Error Display

It is recommended to purchase the L9840 Auxiliary Earthing Rod. (Commercially available pegs have sharp tips, which may damage the carrying case.)
Error
display
Zero adjustment is outside the
Err1
Err2 Abnormality in setting data
Err3 Adjustment data damaged
Err4 Adjustment data not yet written
Err5
Err6 Abnormality in rmware
allowable range, zero adjustment has been executed while it is not on HOLD.
Abnormality in measurement circuit
Description Solution
72
Execute zero adjustment again in accordance with the zero adjustment procedure. (p. 35, p. 46)
Device failure. Contact your authorized Hioki distributor or reseller to organize repair.

Appendix

Appendix 1 Earth Resistance

The resistance between earthing electrode and ground is usually called earth resistance. To be exact, it is the sum of the resistance of earthing conductor, the contact resistance between earthing conductor and ground, and the resistance of ground. Earth resistance is different from commonly known resistors and has the following special characteristics.
Polarizing action Since the ground has characteristics just like electrolyte, it has the polarizing action, and if DC current fl ows through, an electromotive force occurs in the opposite direction to the current, interfering with correct measurement. Therefore, rectangular wave or sine wave of several tens Hz to 1 kHz is usually used to measure the earth resistance.
Special con guration Earth resistance is a resistance between earthing electrode and ground. It is not possible to take it out from the ground and measure it. Since the resistivity of ground is relatively high, a voltage drop occurs near the electrode through which the current to be measured fl ows. Therefore, each electrode (E electrode, S(P) electrode, H(C) electrode) needs to be away from each other to approx. 10 m to accurately measure the resistance of earthing electrode.
Presence of disturbance factors There are disturbance factors such as effects from earth potential and auxiliary earthing electrode in the measurement of earth resistance. The earth potential caused by a leakage current from a device that has been connected to the earthing electrode affects the measured value as it is superimposed over the signal to be
Appx.
1
Earth Resistance
detected by the earth tester. In addition, if the earth resistance of auxiliary earthing electrode is high, the measurement current is reduced, making it susceptible to noise such as earth potential. This device employs a system that is less susceptible to these disturbances and allows accurate measurement under adverse conditions.
Appx.
2
Measurement Principle

Appendix 2 Measurement Principle

While applying a voltage of AC power supply between H(C) electrode and E electrode, the fl owing AC current I is measured with an ammeter. In addition, the voltage V between S(P) electrode and E electrode that is caused by the fl ow of the current I is measured by an AC voltmeter. The earth resistance current I and voltage V. It is not possible to accurately measure the voltages between H(C) - E electrodes and between H(C) - S(P) electrodes.
E Electrode
=
V/I
R
X
R
of E electrode is derived from the measured
X
AC Power
Ammeter
Supply
I
l
Voltmeter
=
×
V
R
I
X
S(P) Electrode H(C) Electrode
Appx.
3
Measurement Principle
Appx.
4
13-09
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431