Hioki Hioki CM3286-01 Quickstart

Page 1
AC CLAMP POWER METER CM3286
99 Washington Street
Visit us at www.TestEquipmentDepot.com
Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
Precisely identify
electricity theft
Voltage Current Power Power factor Phase detection
Simple integral power
consumption
CM3286-01 only
Frequency Peak Harmonics
*
Page 2
2
Use the Bluetooth-equipped
CM3286-01 for even more
convenient measurement.
Use the Bluetooth-equipped
CM3286-01 for even more
convenient measurement.
Meter tam-
pering
Meter tam-
pering
Direct
theft
Direct
theft
Accurately detect electricity theft
• The CM3286 is ideal for verifying electricity theft since it can measure both AC
power and current.
• The instrument’s electricity theft detection-and-report function can be used to quickly and easily make measurements and generate reports (CM3286-01 only).
Tampering of electric meters
Tampering so that meters underreport usage
Direct theft
Stealing electricity by directly
tapping power lines
Detect by comparing electric me-
ter readings and measurements
Proper operation of electric meters can be conrmed by com­paring meter readings and actual values.
Mechanical meter
L1/R/A
N
CONNECTION
CORD L9257
or
Choose the type of probe that best suits your measurement
Electronic meter
location (see options)
Detect by measuring
current
Electricity theft can be detected by measuring current on the power supply side of the illegal connection.
Illegal connection
Measure currents as low as 60 mA simply by clamping the instrument to two lines at once, ensuring you’ll de­tect any theft.
Power supply side
[Proper operation]
Energy (Measured value)
Available for Android
and iOS devices
Energy ratio (Measured value/ theoretical value)
Energy difference
(Measured value −
theoretical value)
Energy (Theoretical value)
[Faulty operation] [Proper operation] [Faulty operation]
The energy ratio is
Result
greater than 100%.
Quick and easy data recording Hold measured values to send them to a smartphone
When you freeze the mea­sured value, it is automatically transferred to a smartphone or tablet, eliminating the need to jot down readings by hand. You can also create a simple PDF report right there in the field, and save data in CSV format for later editing in Excel.
Current peak value
Current frequency
Current value
Result
Current detected.
*Screen values represent example measurements.
Electricity theft detection-and­report function
Simply follow the measurement procedure to take mea sureme nts and ph otographs at four lo catio ns and the instrument will automat icall y generate a report, complete with pho tos.
Since t he repor t is gen erated a utomati-
in the field based on captured mea-
cally sureme nt data, it’s impossible f or others to alter the data.
Page 3
Delivering a broad range of measurements at sites from manufacturing plants to households
• Accurately measure power from 5 W at a current as low as 60 mA to 360 kW at a maximum of 600 A (single-phase power measurement).
• In addition to current, voltage, and power, measure simple integral power
consumption and phase sequence.
• Obtain accurate readings with true RMS measurement.
3
Simple wiring guide
The CM3286 provides a simple on-screen guide indicating how to connect it to a 3-phase circuit.
Example: 3-phase AC measurement (3P3W, balanced)
Power supply side
L1(R)
L2(S)
L3(T)
Jaw
Load side
Measurement
screen
Measurement line
Measure power in sin­gle-phase to balanced three-phase circuits (with estimated values) 1-phase/ 2-wire 1-phase/ 3-wire balanced 3-phase/ 3-wire balanced 3-phase/ 4-wire
*The instrument generates estimated power values when measuring 3-phase circuits.
AUTO HOLD
The clamp meters beep when the measured value sta­bilizes and then automatically hold the display value. This is useful when using the instrument in loca-
tions where it is difcult to see the display or press
the hold button.
I can’t see the screen…
HOLD
Rotary switch that can be turned with a single hand
White backlight
All related parameters are shown on a single screen
[Power display] [Current display]
Voltage RMS value
Current RMS value
Power factor
Active power
Current peak value
Current frequency
Current value
Easily check power supply uctuations
Since it can display maximum (MAX), minimum (MIN), and average (AVG) values, the CM3286 is useful when you need to ascertain the magnitude
of uctuations.
And since it can also measure crest (PEAK) val­ues, you can use it to check fluctuations at the crest value level.
|PEAK|
MAX MIN
Measured value
(RMS value)
Has the measured
Black Red
Quickly check for unbalance
The CM3286 can measure unbalanced power in a 3-phase/ 3-wire circuit by measuring the single-phase power twice and then automatically adding the re­sults. (The instrument can also measure 3-phase/4­wire circuits in three separate measurements.)
First measure­ment
+
Second measurement
value stabilized?
Double warnings with sound and light
When the clamp power meter detects excessively over current or voltage input during a continuity check, it alerts you with a red backlight and beep­ing tone in order to help prevent accidents.
GENNECT Cross (freeware) is required to use instruments with a smartphone or tablet. GENNECT Cross available from the Google Play or Apple Store.
General measurement
Tap "Save measu red valu e" in the app o r press t he HOLD key on t he measuring instrument to save the data . Measured values from multiple channels can be saved.
Simple logging function
Convenient for observing fluct uatio ns over a sho rt perio d of time when it’s not prac tical t o set up large-scale recording equipment.
|PEAK|Waveform
Display refresh interval
CAT IV 600 V
The CM3286 can safely measure service wires with a wire-to-ground voltage of up to 600 V as well as wires found in distribution panels. The clamp meters also feature a safe design that can withstand a transient overvoltage of 8 kV in case of a lightning strike.
Harmonic measure­ment function
The CM3286- 01 can measure the har monic level, cont ent percentage, and total harmonic distor tion of voltag e or curr ent for the 1st th rough 3 0th orders.
Android support scheduled for fall
2017. iOS support scheduled for 2018. Prototype screen shown.
Instantly create reports
Page 4
Specications
Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year
Measurement line
Measurement
items
AC voltage
AC current
Power
Harmonic
(CM3286-01only *2)
Other functions
Maximum rated
voltage to earth
Maximum rated
voltage to terminal
Crest factor
Operating and stor­age temperature and humidity ranges
Dustproof and waterproof
3
*
Single-phase, Three-phase (should be balanced with no distortion)
Voltage, Current, Voltage/ current peak, Active/ reactive/ ap­parent power, Power factor, Phase angle * Active Energy Consumption (Single-phase) [CM3286-01 only*
[Measurement range] 80.0 V to 600.0 V, Single range, Basic accuracy 45 Hz - 66 Hz: ±0.7% rdg. ±3 dgt. (Frequency characteristics: 45 Hz to 1 kHz, True RMS)
[Measurement range] 0.060 A to 600.0 A, 3 range, Basic accuracy 45 Hz - 66 Hz: ±1.3% rdg. ±3 dgt. (Frequency characteristics: 45 Hz to 1 kHz, True RMS)
[Single phase] 0.005 kW to 360.0 kW Basic accuracy: ±2.0% rdg. ±7 dgt. [Balanced three-phase 3-wire] 0.020 kW to 623.5 kW Basic accuracy: ±3.0% rdg. ±10 dgt. [Balanced three-phase 4-wire] 0.040 kW to 1080 kW Basic accuracy: ±2.0% rdg. ±3 dgt.
Voltage/ current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio
[Phase angle *1] lead -180.0° to lag 179.9°, [Power factor]
-1.000 to 1.000 [Frequency] 45.0 Hz to 999.9 Hz, PEAK, phase detection, max/min/avg value display, auto hold, electric meter comparison, unbalanced 3-phase power estimate display, etc.
600 V AC (Measurement category IV) 1000 V AC (Measurement category III)
6 A/ 60 A range 3 or less, 600 A/ 600 V range 1.6 or less
-25°C to 65°C or less (-13.0°F to 149.0°F) 80% RH or less (no condensation, less than 40°C)
Grip: IP54 (EN60529), Jaw: IP50 (EN60529)
2
] Voltage/ current harmonic levels
1
, Frequency, Simple
(50/ 60 Hz, Power factor=1)
(50/ 60 Hz, Power factor=1)
(50/ 60 Hz, Power factor=1)
Standards
Power supply
Continuous oper­ating time
Core jaw diameter
Dimensions and
Mass
*1) Phase angle obtained from zero cross of current / voltage. *2)
Harmonic can be displayed by dedicated application software (Gennect Cross). Android support scheduled for fall 2017. iOS support scheduled for 2018. *3)
Although CM3286 is designed to resist the ingress of dust and dripping water, it is not entirely waterproof or dustproof. Therefore, to prevent an electric shock, do not use it in a wet or dusty environment.
*The indi cated value for thre e-phase power i s based on t he assum ption of a balance d condition and si ne wave wit h­out dist ortion a t 50/60 Hz. Acc urate me asure ment is no t possibl e on an unba lanced o r inverte r contr olled thre e­phase lin e. Also, if th e phase (ze ro cross) ca nnot be de tected d ue to signi fican t wavefor m distor tion, i t cannot b e measured nor displayed. *The powe r factor / ph ase angle a re value s obtaine d from the z ero cros s of the cur rent an d voltage. If t he phase (zero cros s) cannot be detec ted due to signif icant wavefor m distortion , it cannot be mea sured nor displ ayed.
Software specications
Interface
Name
Supported de­vices
Supported OS
*The Bluetooth® word mark a nd logos are regi stered trade marks owned by B luetooth SIG, Inc . and any use of suc h marks b y HIOKI E.E. COR PORATION is und er license. *Android, Go ogle Play and the Goog le Play logo are trad emarks of Googl e Inc. *iOS is a re gistered tra demark of Cisco Tech nology, Inc. an d/or its affilia tes in the United St ates and certa in other count ries. *iPhone , iPad, iPad mini, iPa d Pro and iPod touc h are trademar ks of Apple Inc. *Apple and the App le logo are trade marks of Apple Inc . App Store is a ser vice mark of Apple Inc . *Microsoft, Windows, Windows Vista, and Excel are either registered trademarks or trade marks of Micro soft Corpora tion in the Unite d States and/or o ther countr ies. *Other t rademarks a nd trade names a re those of their re spective own ers.
Safety: EN61010, EMC: EN61326
LR03 Alkaline battery ×2
Approx. 25 hours (Backlight OFF, Bluetooth® OFF) Approx. 18 hours (Backlight OFF, Bluetooth
φ 46 mm (1.81 in)
82 mm (3.23in) W × 241 mm (9.49in) H × 37 mm (1.46in) D, 450 g (15.9 oz)
®
ON)
(CM3286-01 only)
Bluetooth® 4.0LE
GENNECT Cross (freeware)
TM
Android
(Only for Bluetooth® low energy models)
®
iOS (iPhone 5th generation iPod Touch
AndroidTM 4.3 or later, iOS 8 or later
5, 3rd generation iPad®, iPad miniTM, iPad ProTM,
®
or later)
Order code/ Options
AC CLAMP POWER METER CM3286
Model No. (Order Code) (Note)
CM3286 CM3286-01
Options (Test leads) Options (for L9257, L4930, L4931)
CONNECTION CABLE SET L4930
(1.2m)
Options (Clamp adapter)
CLAMP ON ADAPTER 9290-10
(1000 A AC, φ55 mm, CT ratio of 10:1)
Built-in Bluetooth® wireless technology
TEST PIN SET
L4938 EXTENSION CABLE SET L4931
(1.5m,
Expands the
length of the L4930)
BREAKER
PIN SET
L4939
TEST LEAD L9207-10
Options (Test leads)
Accessories:
CONNECTION CORD L9257 ×1 CARRYING CASE C0203 ×1
LR03 Alkaline battery ×2 Instruction manual ×1
[CM328 6- 01 only]
Precautions Concerning Use of Equipment That Emits Radio Waves
Tip options (Red/ Black: 1 each). Attaches to the tip of the banana plug cable.
ALLIGATOR CLIP SET L4935
TEST PIN SET L4932
Connection app (CM3286-01 only)
GENNECT
Cross
(freeware)
BUS BAR CLIP SET L4936
GRABBER CLIP 9243
Accessories
CONNECTION CORD L9257
(Combination of
L4930 and L4935)
MAGNETIC ADAPTER SET L4937
MAGNETIC ADAPTER 9804
CARRYING CASE C0203
*The Bluetooth® word mar k and logos are reg istered tra demar ks own ed by Blu etooth S IG, Inc. a nd any use of such m arks b y HIOKI E .E. CORPORAT ION is un der lice nse.
Note: Comp any na mes and P roduc t name s appea ring in t his cat alog are t rade mark s or regi stered trade mark s of vari ous co mpani es.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
All in form ation co rrec t as of May 19, 2017. All specic ations are subj ect to change wit hout not ice. CM3286_ tft _E1-75M Printe d in Japa n
Loading...