Hioki 3280-70F Instruction Manual

AC CLAMP METER
Instruction Manual
Nov. 2015 Edition 1 Printed in Japan 3280H961-00 15-11H
3280-10F 3280-20F
EN
Device may be connected to or disconnected from a live conductor Flexible sensors can be connected to or disconnected from
live conductors when using appropriate protective insulation. Other sensors can only be connected to or disconnected from insulated conductors suited to the voltage of the conductor under measurement.
Grounding terminal
DC (direct current)
AC (alternating current)
Measurement categories
This instrument’s current measurement part conforms to the safety requirements for CAT III 600 V and the voltage measurement part conforms to the safety requirements for CAT II 600 V CAT III 300 V measuring instruments.
Service entrance
Distribution panel
Service drop
Internal wiring
Power meter
Fixed Installation
Outlet
CAT IV
CAT III
CAT II
DANGER
Measuring a location with a higher category number than the measurement category indicated on this device may result in a serious accident such as electric shock.
To avoid electric shock do not touch the portion beyond the protective barrier during use.
Never apply voltage to the test leads when the resistance and continuity functions are selected. Doing so may damage the instrument and result in bodily injury. To avoid electrical accidents remove power from the circuit before measuring.
WARNING
• To avoid electric shock short circuits and damage to the instrument disconnect the test leads from the measurement object before switching the rotary switch.
• To prevent electric shock when measuring the voltage of a power line use a test lead that satisfi es the following criteria:
• Conforms to safety standards IEC61010 or EN61010
• Of measurement category III or IV
• Its rated voltage is higher than the voltage to be measured
The optional test leads for this instrument conform to the safety standard EN61010. Use a test lead in accordance with its defi ned measurement category and rated voltage.
• Installing the instrument in inappropriate locations may cause a malfunction of instrument or may give rise to an accident. Avoid the following locations:
• Exposed to direct sunlight or high temperature
• Exposed to corrosive or combustible gases
• Exposed to a strong electromagnetic fi eld or electrostatic charge
Near induction heating systems (such as high-frequency induction heating systems and IH cooking equipment)
• Susceptible to vibration
• Exposed to water oil chemicals or solvents
• Exposed to high humidity or condensation
• Exposed to high quantities of dust particles
WARNING
• Since there is a risk of electric shock check that the insulation on the test lead and fl exible sensor (optional) are neither ripped nor torn and no metal conductor inside the wire are exposed before using the instrument. If damaged replace them with those specifi ed by our company.
• To prevent a short circuit accident be sure to use the test leads with the sleeves attached when performing measurements in the CAT III measurement category.
• If the sleeves are inadvertently removed during measurement stop the measurement.
With regard to the electricity supply there are risks of electric shock heat generation fi re and arc fl ash due to short circuits. If persons unfamiliar with electricity measuring instrument are to use the instrument another person familiar with such instruments must supervise operations.
• This instrument is measured on a live line. To prevent electric shock use appropriate protective insulation and adhere to applicable laws and regulations.
• Handle and dispose of batteries in accordance with local regulations.
CAUTION
Do not place foreign objects between the jaw tips (or exible loop couplings) or insert foreign objects into the gaps of the jaws (or fl exible loop couplings). Doing so may worsen the performances of the sensor or interfere with clamping action.
Poor performance or damage from battery leakage could result. Observe the cautions listed below:
• Do not use batteries after their recommended expiry date.
• Do not allow weak batteries to remain in the instrument.
• Replace batteries only with the specifi ed type.
• Remove the batteries from the instrument if it is to be stored for a long time.
• The indicator lights up when the remaining battery capacity is low. In this case the instrument's reliability is not guaranteed. Replace the battery immediately.
• To avoid battery depletion turn the rotary switch OFF after use (the auto power save feature consumes a small amount of current).
Inspection Before Measurement
• Verify that the instrument operates normally to ensure that no damage occurred during storage or shipping. If you fi nd any
damage contact your authorized Hioki distributor or reseller.
• If damage is suspected check the section below before contacting
your authorized Hioki distributor or reseller.
(1) Check that the test lead is not broken.
Replace with the specifi ed L9208 Test Lead.
(2) Check that the resistance measurement and continuity test
operates normal ly.
Have the instrument repaired by the your authorized Hioki distributor or reseller. The instrument may have been subject to a voltage of greater than 600 V during resistance measurement or continuity
testing.
(3) Check that the battery voltage is not low.
Replace the batteries.
Maintenance/Inspection
Cleaning
Measurements are degraded by dirt on the mating surfaces of the jaw (or fl exible loop coupling) so keep the surfaces clean by gently wiping with a soft dry cloth.
• To clean the device wipe it gently with a soft cloth moistened with water or mild detergent.
• Wipe the LCD display gently with a soft dry cloth.
Insert/Replace Batteries
Necessary tool: Phillips screwdriver and CR2032 Coin-shaped lithium battery
NO
OK
12
3
4
Do not turn the adjustment screw inside the battery case. Doing so will cause the instrument to report abnormal measured values.
Functions
Display will automatically turn off if the instrument is not used for 30 min. (Auto power-saving function)
To resume instrument operation in the previous state select the “OFF” position with the rotary switch and then move the switch to the desired function.
To cancel auto power-saving function
1. Select the desired function with the rotary switch while holding
down
key.
2. The LCD display will change from [APS] to [OFF] and the auto
power-saving function will be disabled.
3. Setting the rotary switch to “OFF” and then reselecting the
desired function will enable the auto power-saving function.
Automatically sets the measurement range to the most appropriate range (Auto-range function)
Displays [AUTO]
To set the measurement range arbitrarily (Manual-range function)
1.
Select the desired function with the rotary switch while holding down
key.
2.
Press
key to switch the range.
(Can set the range as desired except during continuity testing.)
Indication when input exceeds the measurement range (Overfl ow indication)
Displays [OF] or [-OF]
Parts Names
RearFront
Jaw
Barrier
Operation grip
LCD Display
Rotary switch
key
HOLD key
(Press to hold the display value.)
Test lead or fl exible sensors plug
Example: 3280-10F
Measurement terminal
Battery cover
Warranty
Warranty malfunctions occurring under conditions of normal use in conformity with the Instruction Manual and Product Precautionary Markings will be repaired free of charge. This warranty is valid for a period of three (3) years from the date of purchase. Please contact the distributor from which you purchased the product for further information on warranty provisions.
Introduction
Thank you for purchasing the Hioki 3280-10F 3280-20F AC Clamp Meter. To obtain maximum performance from the instrument please read this manual fi rst and keep it handy for future reference.
3280-10F Average value measurement RMS conversion model 3280-20F True RMS measurement model
Safety Notes
This instrument is designed to conform to IEC 61010 Safety Standards and has been thoroughly tested for safety prior to shipment. However using the instrument in a way not described in this manual may negate the provided safety features. Before using
the instrument be certain to carefully read the following safety notes.
Notation
In this document the risk seriousness and the hazard levels are classifi ed as follows.
DANGER
Imminent risk of operator death or serious injury
WARNING
Potential for operator death or serious injury
CAUTION
Potential for minor operator injury or device damage or malfunction
Risk of electric shock Prohibited actions Actions that must be performed
Symbols affi xed to the device
Precaution or hazard (See corresponding topic.) Risk of electric shock Protected throughout by double insulation or reinforced insulation
Sleeves
(Red)
(Black)
Test leads AC Flexible Current Sensor *
Cap (Approx.
7
mm)
Cap
Flexible loop
Instruction plate
*Optional
Measurement Methods
AC Current Measurement [ ]
Measuring with the instrument
1 2
OK NO
3
Measuring with Model CT6280 AC Flexible Current Sensor (optional)
12 34
Do not pull with excessive force.
Wire band
Do not force the fl exible loop into a bent position.
Do not store while bent.
OK
NO
NO N
NO
NO
Voltage Measurement
AC Voltage Measurement [
]
12
3
DC Voltage Measurement [ ]
12
3
Black()
Red (+)
Red (+) Black()
Resistance Measurement [ ]
21 34
Continuity check [ ]
2134
Specifi cations
Accuracy
We defi ne measurement tolerances in terms of rdg. (reading) and dgt. (digit) values with the following meanings:
rdg. (reading or displayed value)
The value currently being measured and indicated on the measuring instrument.
dgt. (resolution)
The smallest displayable unit on a digital measuring instrument i.e. the input value that causes the digital display to show a “1” as the least-signifi cant digit.
Basic Specifi cations
Maximum input current
• Jaw (3280-10F 3280-20F) 2000 A AC continuous (45 Hz to 66 Hz)
• Flexible loop (3280-10F+CT6280 or 3280-20F+CT6280) 4200 A AC continuous (50 Hz to 60 Hz)
Maximum input voltage
600 V AC/DC and 3×106 V·Hz or less (ACV/DCV)
Overload protection
600 V AC/DC (ACV/DCV/
Ω
/continuity)
Maximum rated voltage to earth
• Jaw CT6280 600 V AC (Measurement category III) 300 V AC (Measurement category IV) (Anticipated transient overvoltage: 6000 V)
• Voltage measurement terminal 600 V AC (Measurement category II) 300 V AC (Measurement category III) (Anticipated transient overvoltage: 4000 V)
AC measurement method
3280-10F Average value measurement RMS method 3280-20F True RMS measurement method
Display update rate
400 ms±25 ms
Noise rejection characteristics
NMRR DCV 40 dB or more (50 Hz/60 Hz) CMRR DCV −100 dB or more (−50 Hz/60 Hz 1 k
Ω
unbalance) ACV −60 dB or more (50 Hz/60 Hz 1 k
Ω
unbalance)
But 45 dB or more for 600 V range.
Crest factor (3280-20F only)
For 2500 counts or less 2.5 Reduces linearly to 1.5 or less at 4200 counts
Zero-display range
5 counts (AC Current jaw - fl exible loop)
Effects of conductor position
• 3280-10F 3280-20F: within ±5.0%
• CT6280: within ±5.0%
(At all positions around the sensor’s centerpoint reference)
Maximum measurable conductor diameter
• 3280-10F 3280-20F: 33 mm or less
• CT6280: 130 mm or less
General Specifi cations
Operating environment
Indoors pollution degree 2 altitude up to 2000 m (6562 ft.)
Operating temperature and humidity
• Temperature;
25°C to 65°C (13.0°F to 149.0°F) (40 M
Ω
range: up to 40°C)
• Humidity (no condensation); Less than 40°C (104.0°F): 80% RH or less At least 40°C (104.0°F) but less than 45°C (113.0°F): 60% RH or less At least 45°C (113.0°F) but less than 50°C (122.0°F): 50% RH or less At least 50°C (122.0°F) but less than 55°C (131.0°F): 40% RH or less At least 55°C (131.0°F) but less than 60°C (140.0°F): 30% RH or less At least 60°C (140.0°F) but less than 65°C (149.0°F): 25% RH or less
Storage temperature and humidity
25°C to 65°C (13°F to 149°F) 80% RH or less (no condensation)
Dustproof and waterproof
IP40 (EN60529)
Drop-proof distance
1 m on concrete
Standards Safety: EN61010
EMC: EN61326
Power supply CR2032 Coin-shaped lithium battery ×1 (3 V DC)
Maximum rated power: 15 mVA
Continuous operating time
• 3280-10F: Approx. 120 hours
• 3280-20F: Approx. 70 hours
(AC current measurement mode continuous unloaded)
Dimensions
• 3280-10F 3280-20F: Approx. 57W×175H×16D mm (2.24W × 6.89H × 0.63D)
• CT6280: Approx. 42W×65H×18D mm (1.65W × 2.56H × 0.71D) (excluding the fl exible loop and output cable)
Mass • 3280-10F 3280-20F: Approx. 100 g (3.5 oz.)
(including battery)
• CT6280: Approx. 71 g (2.5 oz.)
Product warranty period
3280-10F 3280-20F CT6280: 3 years
Accessories • 9398 Carrying Case
(C0205 Carrying Case when CT6280 is attached)
• L9208 Test lead
• CR2032 Coin-shaped lithium battery
• Instruction Manual
Options • CT6280 AC Flexible Current Sensor
(Attachment is included)
• 9209 Test Leads Holder
• L4933 Contact Pin Set (Can be connected to the tip of the L9208 which comes with the instrument.)
• L4934 Small Alligator Clip Set (Can be connected to the tip of the L9208 which comes with the instrument.)
CALIFORNIA USA ONLY
This product contains a CR Coin Lithium Battery which contains Perchlorate Material - special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate
Function Specifi cations
Display Maximum count: 4199 counts Battery indicator
warning voltage
mark lights up at 2.3 V±0.15 V or less
Accuracy Specifi cations
Conditions of guaranteed accuracy
• Guaranteed accuracy period: 1 year (Number of jaw and fl exible loop open/close cycles: 10000 or less)
• Guaranteed accuracy period after adjustment made by Hioki: 1 year
• Temperature and humidity for guaranteed accuracy: 23°C±5°C (73.0°F±9.0°F) 80% RH or less
• Temperature characteristic: Measurement accuracy × 0.1/°C is added (excluding 23°C±5°C)
AC Current - Jaw (3280-10F)
Range Accuracy range
Accuracy 50 Hz f 60 Hz
42.00 A 4.00 A to 41.99 A ±1.5% rdg.±5 dgt.420.0 A 40.0 A to 419.9 A
1000 A 100 A to 1000 A
AC Current - Jaw (3280-20F)
Range Accuracy range
Accuracy 40 Hz f < 45 Hz
45 Hz f 66 Hz
66 Hz < f 1 kHz
42.00 A 4.00 A to 41.99 A
±2.0% rdg. ±5 dgt.
±1.5% rdg. ±5 dgt.
±2.0% rdg. ±5 dgt.
420.0 A 40.0 A to 419.9 A
1000 A 100 A to 1000 A Accuracy is not defi ned for currents of 5×105 A·Hz or more.
AC Current - Flexible loop (3280-10F)
Range Accuracy range
Accuracy 50 Hz f 60 Hz
420.0 A 40.0 A to 419.9 A ±3.0% rdg.±5 dgt.
(includes accuracy of CT6280 AC Flexible Current Sensor: ±1.0% rdg.)
4200 A 400 A to 4199 A
AC Current - Flexible loop (3280-20F)
Range Accuracy range
Accuracy 40 Hz f < 50 Hz
50 Hz f 60 Hz
60 Hz < f 1 kHz
420.0 A 40.0 A to 41 9. 9 A
±3.5% rdg. ±5 dgt.*
1 *2
±3.0% rdg. ±5 dgt.*
1
±3.5% rdg. ±5 dgt.*
1 *2
4200 A 400 A to 4199 A *1: Includes accuracy of CT6280 AC Flexible Current Sensor: ±1.0% rdg. *2: Accuracy is not defi ned for currents of 1000 A or more or currents of 5×10
5
A·Hz or more.
AC Voltage
Range Accuracy range
Accuracy
Input impedance
45 Hz f 66 Hz66 Hz < f
500 Hz
4.200 V 0.400 V to 4.199 V
±1.8% rdg. ±7 dgt.
±2.3% rdg. ±8 dgt.
11 M
Ω
±5%
42.00 V 4.00 V to 41.99 V 10 MΩ±5%
420.0 V 40.0 V to 419.9 V 10 MΩ±5%
600 V 400 V to 600 V 10 M
Ω
±5%
DC Voltage
Range Accuracy range Accuracy Input impedance
420.0 mV 40.0 mV to 419.9 mV
±2.5% rdg. ±5 dgt.
100 MΩ or more
4.200 V 0.400 V to 4.199 V
±1.0% rdg. ±3 dgt.
11 M
Ω
±5%
42.00 V 4.00 V to 41.99 V 10 MΩ±5%
420.0 V 40.0 V to 419.9 V 10 M
Ω
±5%
600 V 400 V to 600 V 10 MΩ±5%
Resistance
Range Accuracy range Accuracy
Open circuit voltage
420.0
Ω
40.0 Ω to 419.9
Ω
±2.0% rdg.±4 dgt.
3.4 V or less
4.200 k
Ω
0.400 kΩ to 4.199 k
Ω
42.00 kΩ4.00 kΩ to 41.99 k
Ω
420.0 kΩ40.0 kΩ to 419.9 k
Ω
4.200 MΩ0.400 MΩ to 4. 199 MΩ±5.0% rdg.±4 dgt.
42.00 M
Ω
4.00 MΩ to 41.99 MΩ±10.0% rdg.±4 dgt.
Continuity Check
Range Accuracy
Threshold of buzzer sound
Open circuit voltage
420.0
Ω
±2.0% rdg.±4 dgt.
50
Ω
±40 Ω or
less
3.4 V or less
OK
NO
Loading...