Specifications
Safet
Fuse and BatteryReplacement
3118
INSTRUCTION MANUAL
November 2002 Revised edition 1
3118A981-01 02-11H Printed in Japan
Introduction
Thank you for purchasing the Hioki 3118 MΩ HiTESTER. To obtain
maximum performance from the product, please read this manual first,
and keep it handy for future reference.
Inspection
When you receive the product, inspect it carefully to ensure that no
damage occurred during shipping. If damage is evident, or if it fails to
operate according to the specifications, contact your dealer or Hioki
representative.
Maintenance and Service
To clean the product, wipe it gently with a soft cloth moistened with
water or mild detergent. Never use solvents such as benzene, alcohol,
acetone, ether, ketones, thinners or gasoline, as they can deform and
discolor the case.
If the product seems to be malfunctioning, confirm that the batteries are
not discharged, and that the test probes are not open circuited before
contacting your dealer or Hioki representative.
Pack the product carefully so that it will not be damaged during
shipment, and include a detailed written description of the problem. Hioki
cannot be responsible for damage that occurs during shipment.
General Specifications
Operating
temperature and
humidities
Storage temperature
and humidities
Operating
environment
Power source
Maximum rated power
Continuous operating
time
Dielectric strength
Dimensions
(excluding protrusions)
Mass
Accessories
Option
0to40 (32 to 104 ), 90% RH max
(with no condensations)
-10 to 50 (-4 to 122 ), 90% RH max
(with no condensations)
Altitude up to 2000 m (6562 feet)
Rated power voltage: 1.5 VDC X 6,
R6P manganese battery X 6
External power (DC8.5 V/600mA, MAX. 10 V)
4VA
Approx. 8 hours at 500 V, 1 MΩ
(using mannganese batteries)
3 kVAC 50/60 Hz for one minute
Between electric circuit and case
106W X 145H X 52D mm approx.
4.17"W X 5.71"H X 2.05"D approx.
500 g, (17.6 oz.) approx. (including batteries)
9294 TEST PROBE
9363 CARRYING CASE (3118-11)
9364 CARRYING CASE (3118-12)
Instruction Manual, Instruction label
R6P manganese battery X 6, Spare fuse
9288 BREAKER PIN, 9289 TEST PROBE,
9257 CONNECTION CORD
Specifications
Guaranteed at 23 5 (73 9 ), 90% RH or less, for 1 year.
Model 3118-11 3118-12
Rated voltage 250 V 500 V 500 V 1000 V
Maximum effective
reading
1st effective
measurement
range
2nd effective
measurement
range
Other accuracy
Measurement
terminal voltage
accuracy
Effective of
temperature
(0 to 40 )
Measurement
current (when
short-circuited)
Response time
Overload
protection
(measurement
terminal)
Discharge function Yes No Yes No
Resistance range
and accuracy
Effective of
temperature
(0 to 40 )
Open terminal
voltage
Overload
protection
AC voltage range
and accuracy
Effective of
temperature
(0 to 40 )
Input resistance Approx. 160 kΩ Approx. 3.3 MΩ
Overload
protection
50 MΩ 100 MΩ 200 MΩ 2000 MΩ
0.05 to 20 MΩ 0.1 to 50 MΩ 0.1 to 50 MΩ 2to500MΩ
5% of scale reading
20 to 50MΩ 50 to 100MΩ 50 to 200MΩ 500 to 2000MΩ
10% of scale reading
0.7% of scale length
(including 0 and reading)
10% of rated voltage at infinity
90% min. of rated voltage at 1 MΩ
(3118-12: 1000 V range at 20 MΩ)
5% of scale reading plus basic allowance at 1 MΩ
(3118-12: 1000 V range at 20 MΩ)
0.7% of scale length plus basic allowance at 0 and
3.4 mA 0.32 mA
3 s or less at 1 MΩ or 0
(3118-12: 1000 V range at 20 MΩ)
280 V rms 600 V rms 600 V rms 1100 V rms
0to100Ω/ 3% of scale length
3% of scale length plus basic allowance
310 mV max.
(Fuse protection: 1 A/250 V with non-arcing type)
7% of maximum scale value (50/60 Hz)
250 V rms
0 to 600 V
7% of maximum scale value
700 V rms
This manual contains information and warnings essential for safe
operation of the product and for maintaining it in safe operating condition.
Before using the product, be sure to carefully read the following safety
notes.
Safety Symbols
・
・
Indicates that dangerous voltage may be present at this
terminal.
Indicates AC (Alternating Current).
Indicates DC (Direct Current).
The following symbols in this manual indicate the relative importance of
cautions and warnings.
DANGER
WARNING
CAUTION
NOTE
symbol printed on the product indicates that
The
the user should refer to a corresponding topic in the
manual (marked with the
relevant function.
In the manual, the
important information that the user should read before
using the product.
Indicates that incorrect operation presents an
extreme hazard that could result in serious
injury or death to the user.
Indicates that incorrect operation presents a
significant hazard that could result in serious
injury or death to the user.
Indicates that incorrect operation presents a
possibility of injury to the user or damage to
the product.
Advisory items related to performance or
correct operation of the product.
symbol) before using the
symbol indicates particularly
Notes on Use
DANGER
Before connecting probes to the product, check that the
probes are disconnected from the object to be measured.
WARNING
To avoid electric shock, do not allow the product to get
wet, and do not use it when your hands are wet.
Before using the product, make sure that the
insulation on the probes is undamaged and that no
bare conductors are improperly exposed. Using the
product in such conditions could cause an electric
shock. Replace the test probes with the specified
Hioki Model 9294.
Do not use the product where it may be exposed to
corrosive or combustible gases. The product may be
damaged or cause an explosion.
Do not store or use the product where it could be exposed to
direct sunlight, high temperature or humidity, or condensation.
Under such conditions, the product may be damaged and
insulation may deteriorate so that it no longer meets
specifications.
To avoid damage to the product, protect it from vibration or
shock during transport and handling, and be especially careful
to avoid dropping.
NOTE
Before use check that batteries are charged. Replace the old batteries
with fresh one if they are low.
When not in use for a long time, to prevent possible corrosion caused
by battery leakage, remove the batteries before storage.
Always release the MEASURE button after use.
The meter display is glass, so avoid subjecting it to strong impacts.
This product is provided with a label containing measurement
instruction and precautions. After purchase, be sure to fix this label to
the battery cover on the back of the product.
Before use, check whether the product operates properly. You can do
this by performing Insulation Resistance Measurement, then pressing
the MEASURE button in the MΩ setting (the indicator should read
zero).
If the needle remains in the position, the fuse has blown. In this case,
replace the fuse with a new one of the same rating (refer to "Fuse and
Battery Replacement").
CAUTION
WARNING
To avoid electric shock when replacing the batteries,
first disconnect the test probes from the object to be
measured. Before using the product after replacing
the batteries, replace the cover and screw.
Do not mix old and new batteries, or different types of
batteries. Also, be careful to observe battery polarity
during installation. Otherwise, poor performance or
damage from battery leakage could result.
To avoid the possibility of explosion, do not short
circuit, disassemble or incinerate batteries.
Keep batteries away from children to prevent
accidental swallowing.
Replace the fuse only with one of the specified
characteristics and voltage and current ratings. Using
a non-specified fuse or shorting the fuse holder may
cause a life-threatening hazard.
Fuse type: MF51NR1-S 1 A, 250 V (non-arcing) 20 mm
X5mmdia.
1. Rotate the decorative screw with a
coin or similar object.
2. Remove the battery cover.
Spare fuse
3. Insert six new batteries.
If the fuse has blown, replace it
with a new one.
Battery cover

Names and Functions of Parts
3
2
4
9
1
10
13
5
1. MEASURE button
Press to measure insulation resistance.
2. Zero-ajustment 3. Display and scale 4. Indicator needle
5. Function selector (Ω/ACV/MΩ)
6. Earth measurement terminal
Connect the EARTH probe (black).
7. Guard terminal
8. Battery check terminal
Use with LINE probe.
9. DC IN: External power supply jack (DC8.5 V/600mA, MAX. 10 V, has
φ5 mm-dia.-terminals and has a center pin with negative polarity)
10. Line measurement terminal
Connect the LINE probe (red).
11. Battery cover 12. decorative screw
13. Instruction label (fix the label here)
Measurement Procedure
Insulation Resistance Measurement
Observe the following to avoid electric shock and short
circuits.
Do not attempt to measure insulation resistance on a
live conductor. Doing so could damage the product or
cause an accident that might result in injury or death.
Always turn off power to the conductor being
measured before starting.
The maximum permissible input is indicated in the
specifications. Do not measure voltage in excess of
these limitations, as doing so may damage the
product or cause an accident that might result in
injury or death.
When measuring insulation resistance, dangerous
voltage is applied to the measurement terminals. To
avoid electric shock, do not touch the probe.
To avoid electrical shock, never touch the external
power input terminal and BATT.CHECK terminal while
measuring insulation resistance.
When discharging, do not set the function selector to the Ω
position. It may result in damage to the product.
Always turn off the breaker
or the measurement LINE.
12
WARNING
CAUTION
2
4
3
Load
(secondary side)
1
8
7
11
Source
(primary
side)
1. Set the function selector to either MΩ position.
(3118-11: 250/500 V, 3118-12: 500/1000 V)
2. Connect the black EARTH probe to the ground side of the object
being measured.
3. Connect the red LINE probe to the LINE to be measured.
4. Press the MEASURE button. (To make continuous measurements,
pull the button up.)
5. Read the value after the needle has stabilized.
NOTE
Insulation resistance is the ratio of leakage current to input voltage,
and is therefore unstable. Depending on the circuit being measured
6
the needle may stabilize, but this in not a meter malfunction.
When measuring insulation between communication cables or other
systems with a capacitance element, the needle will move first quickly
to the left, then gradually return to the right, and it may take some time
to become stabilized. This is not a sign of malfunction. Read the
value after the needle has stabilized.
Discharge Function
When measuring an insulation resistance that contains a capacitance
element, that element will be charged with an electric load proportional
to the measurement voltage.
After measuring a circuit with capacitance, release the MEASURE
button and set the function selector to 250 V (3118-11) or 500 V
(3118-12) before detaching the probes. This will activate the 3118
built-in discharge circuit.
Circuit to be measured
EARTH terminal
+
-
Capacitance
LINE terminal
The time required for discharge depends on the capacitance value. As
a reference, observe the indicator needle. During discharge, it will go
beyond, then return gradually. discharge is practically completed when
needle reaches the
Make it a practice to discharge the subject conductor after measurement.
Guard terminal use
The guard terminal
eliminates the effects of
test object surface leakage
resistance to measure
only volumetric resistance.
For measurement of
cables and similar objects,
as indicated in the
diagram, wrap a bare wire
(about 0.5 mm in diameter) around the insulator to be measured and
connect this to the GUARD terminal. The leakage current flowing
through the surface of the insulator will not be displayed, making it
possible to accurately measure volumetric resistance.
ON
OFF
MEASURE button
symbol.
Mete
Power
suppl
3118
Ω
Low voltage MΩ
High voltage MΩ
ACV
Function selecto
3118
LINE
GUARD
EARTH
Discharge
resistance
Core
Insulato
Sheathings
AC Voltage Measurement
DANGER
Test probes should only be connected to the secondary
side of a breaker, so the breaker can prevent an accident
if a short circuit occurs. Connections should never be
made to the primary side of a breaker, because
unrestricted current flow could cause a serious accident
if a short circuit occurs.
The maximum permissible input is 700 Vrms.
Attempting to measure voltage in excess of the
maximum rating could destroy the product and result
in personal injure or death.
To avoid electrical shock, never touch the external
power input terminal and BATT.CHECK terminal while
measuring voltage.
To avoid electrical shock, be careful to avoid shorting
live lines with the test probes.
WARNING
Never press the MEASURE button while measuring
voltage. Doing so could damage the circuitry or cause a
life-threatening accident.
Source
Do not press the
MEASURE button.
2
(primar
side
3
Load
secondaryside
Always connect the probe
1
1. Set the function selector to ACV.
2. Connect the black EARTH probe to the ground.
3. Connect the red LINE probe to the line to be measured.
4. Read the voltage value on the AC scale after the needle stabilizes.
Resistance Measurement
Never apply voltage to test probes when the Resistance
function is selected. Doing so may damage the product
and result in personal injury.
To avoid electrical accidents, remove power from the
circuit before measuring.
1. Set the function selector to Ω.
2. Press the MEASURE button and attach the LINE and EARTH probes.
3. Read the resistance value on the Ω scale.
to the secondary side of
the breaker.
DANGER
BatteryCheck Method
Do not press the
MEASURE button.
1
2
1. Set the function selector to B CH.
2. Connect the LINE probe tip to the BATT CHECK terminal.
3. If the needle is within the B range, the batteries can be used. If it is
to the outside of the B range, replace the batteries with new ones.
Usingthe CarryingCase
Hook
For use, fold the cover back as shown.
Attach the belt to the hook as indicated when carried from your shoulder.
9288 BREAKER PIN
Remove the hook if the product is to be used while hung aroud your
neck. Carry probes here. Carry the 9288 BREAKER PIN (option) here.
Option
DANGER
To avoid electrical shock, be careful to avoid shorting
live lines with the breaker pin.
9288 BREAKER PIN
Attach this to the tip of the LINE probe or pin
type EARTH probes. It allows the tip to be
extended, when otherwise it would be too short
to make a measurement.
9289 TEST PROBE
The black EARTH probe is a pin type probe like
the LINE probe. This can not be attach to the 9288 BREAKER PIN.
9257 CONNECTION CORD
The black EARTH probe is a clip type probe like the LINE probe.