HID Global SDC1000 User Manual

Page 1
MOTOROLA
SDC1000
MOTOROLA SDC1000
SINGLE DOOR ACCESS CONTROLLER
- 1 -
Page 2
MOTOROLA
SDC1000
CONTENTS
SINGLE DOOR ACCESS CONTROLLER
1. Important Safety Instructions
2. General
3. Features
4. Specifications
5. Name of the Parts
6. Identifying supplied parts
7. Installation of the Product
8. Wire Color Table of the Main Unit
9. Wire Connection in of basic application
10. Initial Setup
11. Operation
12. Setting Changes
13. FCC REGISTRATION INFORMATION
14. Warranty and Service
- 2 -
Page 3
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
1. Important Safety Instructions
When using your door access controller, basing safety precautions should always be followed to reduce the risk of fire, electrical shock, and injury to persons including following:
1. Read and understand all instructions.
2. Follow all warnings and instructions marked on the product
3. Do not use liquid cleaners, or aerosol cleaners. Use a damp cloth for cleaning. if necessary, use a mild soap.
4. Do not use this product near water, for example near a bath tub, wash bowl, kitchen sink, or laundry tub, in a wet basement, or near a swimming pool.
5. This product should be operated only from the type of power source indicated on the marking label. if you are not sure of the type of power supply to your home, consult your dealer or local power company.
6. Never push objects of any kind into this product though the cabinet slots as they may touch voltage points or short out parts that could result in a risk of fire or electric shock. Never spill liquid of any kind on the product.
7. To reduce the risk of electric shock, do not disassemble this product, but take it to a qualified serviceman when some service or repair work is required. Opening or removing covers may expose you to dangerous voltages or other risks. incorrect reassembly can cause electric shock when the appliance is subsequently used.
8. Unplug this product from the wall outlet and refer to qualified service personnel under the following conditions: a. When the power supply cord or plug is damaged or frayed. b. If liquid has been spilled into the product c. If the product has exposed to rain or water. d. If the product doses not operate normally by following the operating instructions. Adjust only those controls, that are covered by the operating instructions. Improper adjustment of other controls in damage and will often require extensive work by a qualified technician to restore the to normal operation.
e. If the product exhibit a distinct change in performance.
2. General
SDC1000 is an intelligent one door Access Controller based on powerful 8 bit Microprocessor to meet a simple and cost-effective access control market requirement. User friendly device allows you to register max. 128 USER IDs and easy to add or delete USER RFIDs. There are 5 inputs to connect EXIT Button, door contact, PIR sensor , Fire sensor and extra and you can program related output sources and activate timing from the front keypads. System will make alarm in case of number of times wrong entry and Temper switch opens and one TTL output can be connected to Auto-dialer (option) will make a call to the pre-defined phone numbers (max 4ch) and report the alarm to Police, Fire station and/or to your cellular phone by voice message. All event transaction report to the computer by RS232C communication. The modern design and easy installation will provide you an accurate access control for single door and 3 LED indicators informs you all system operating at real time. SDC1000 will give you field proven reliability and cost-effective solution anywhere the access controls and high security is required.
3. Features
- One door Access Controller
- Powerful dual 8 bit Microprocessors
- Built-in 4” Proximity Reader
- 128 USER Access RFIDs including one Master RFID
- Independant 5 inputs and 4 outputs including 2 output Relays
- All I/Os and activating Times user front programmable
- Door Lock and Unlock function
- Setting for Safe/Secure mode
- Numbers of Try-out error Alarm
- RS232 communication port for remote control and events report
- 3 LEDs for system operation status
- Modern design and easy operation
- 3 -
Page 4
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
4. Specification
.CPU : Dual 8 bit Microprocessors .Memory : 8 KB Program memory 512 bytes Flash memory .User PIN numbers : 128 User RFIDs including one Master RFID .Proximity Reader : Built-in 4” Proximity reader .Input/Output : 5 Inputs max. rating at DC 12V/20mA
: 2 Relay outputs : DC12V/2A : 1 chime bell output : 5V/150mA ,
: 1 TTL output : 5V/20mA .Communication : One RS232C port, 9600 Baud Rate,N,8,1 .Keypads : 12 Numeric Keypads .LED : 3 LEDs(RED, GREEN, YELLOW) .Power : DC 12V/ 200mA .Operating Environment : 0°C to +60°C, 10% to 90% Humidity .Reset : Power ON Reset
5. Name of each part
SDC1000 Main Unit
6. Identifying supplied parts
Please unpack and check the contents of the box.
Main Unit Wall Mount O-Ring Instructions (1 EA) (1 EA) (5 EA) (1 EA)
- 4 -
Page 5
MOTOROLA
SDC1000
7. Installation of the Product
7-1. Drill two 6-32 holes and one 1/2" hole on the proper location of the wall.
(If the gang box is already installed on the wall then skip this step.) 7-2. Using 2 screws, install wall mount to the wall. 7-3. Insert 5 O-rings to the wall mount as indicated, then route the cable of the main unit through the center hole and push the main unit to wall mount to lock the main unit and make sure that the main unit is locked with wall mount.
SINGLE DOOR ACCESS CONTROLLER
* CAUTIONS *
When the main unit is once fixed to wall mount, the locking pins will tighten the main unit therefore the operation test of the main unit should be required prior to fix the main unit to wall mount. If the main unit has to be disassembled from the wall mount, then you need another
wall mount to be replaced as the locking pins of wall mount will be broken when the main unit detached from the wall mount.
- 5 -
Page 6
MOTOROLA
SDC1000
8. Wire Color Table of the Main Unit
POWER
Power(DC 12V) +12V Red wire, Red with White stripe Power(DC 12V) 0V(GND) Black wire, Black with White stripe
OUTPUT
Door RELAY(2A) COM Gray wire with Red stripe Door RELAY(2A) NC Blue wire with White stripe Door RELAY(2A) NO White wire with Red stripe
Alarm RELAY(2A) COM White wire Alarm RELAY(2A) NC Purple wire with White stripe Alarm RELAY(2A) NO Purple wire
TTL Output TTL Orange wire with White stripe CHIME BELL Output BELL Brown wire with White stripe
INPUT
Exit Button EXIT Yellow wire with Red stripe Door Sensor CONTACT Green wire External Input #1 IN#1 Orange wire External Input #2 IN#2 Green wire with White stripe External Input #3 IN#3 Brown wire Extra Reader Input DATA0 Pink wire Extra Reader Input DATA1 Cyan wire
SINGLE DOOR ACCESS CONTROLLER
RS232C INTERFACE
RS232-TX TXD Grey wire RS232-RX RXD Blue wire RS232-GND GND Yellow wire
- 6 -
Page 7
MOTOROLA
SDC1000
9. Wire connection for basic application
This connection can be changed for different applications.
SINGLE DOOR ACCESS CONTROLLER
- 7 -
Page 8
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
9-1. Power Connection
Connect (+)wire of DC 12V power to Red wire and Red/White stripe wire and
connect Power GND(-)wire of DC 12V to Black wire and Black/White stripe wire.
. Door Lock connection
9-2
9-2-1 Connection of POWER FAIL SAFE: Door Lock
- Connect Door RELAY(COM),Grey/Red stripe wire to DC +12V.
- Connect (+)wire of Door Lock to Door RELAY(NC),Blue/White stripe wire.
- Connect (-)wire of Door Lock to Power GND(-) wire.
9-2-2 Connection of POWER FAIL SECURE Door Lock
- Connect Door RELAY(COM),Grey/Red stripe wire to DC +12V.
- Connect (+)wire of Door Lock to Door RELAY(NO),White/Red stripe wire.
- Connect (-)wire of Door Lock to Power GND(-) wire.
. Alarm Device connection
9-3
- Connect Alarm RELAY(COM),white wire to DC +12V.
- Connect (+)wire of Alarm Device to Alarm RELAY(NO),Purple wire.
- Connect (-)wire of Alarm Device to Power GND(-) wire.
9-4. Exit Button connection
- Connect one of the wire of Exit Button to Exit Button Input, Yellow/Red stripe wire.
- Connect the other wire of Exit Button to Power GND(-) wire.
(In case of using Normal Closing Contact for Exit Button then please make setting
change of ACTIVE level of Exit Button in section 8-20)
9-5. Door Contact sensor connection
- Connect Door Contact sensor(COM) wire to Door Contact Input, Green wire.
- Connect Door Contact sensor(NO) wire to Power GND(-) wire. (In case of using Normal Closing(NC) Contact for Door Contact sensor then please make setting change of ACTIVE level of Door Contact in section 8-21)
9-6. Auxiliary Input Device connection(Applied to AUX Input#1,#2,#3)
- Connect one wire of Auxiliary Input Device to AUX Input wire (Input#1 Orange, Input#2 Green/White stripe, Input#3 Brown wire).
- Connect the other wire of Auxiliary Input Device to Power GND(-) wire. (In case of using Normal Closing(NC) Contact for Auxiliary Input Device then please make setting change of ACTIVE level of AUX Input in section 8-17 ~ 8-19)
- 8 -
Page 9
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
9-7. Auto-dialer connection(Extra Purchase, If Necessary)
- Connect the input wire of Auto-dialer to TTL output, Orange/White stripe wire.
- Connect (+)wire of Auto-dialer to DC +12V.
- Connect (-)wire of Auto-dialer to Power GND(-) wire.
- Connect Telephone Line plug(RJ-14) to Auto-dialer. (In case of using Low ACTIVE for Auto-dialer then please make setting change of ACTIVE level of TTL Output in section 8-22)
9-8. RS232C Communication port Connection 9-pin connector(COM Port, female) is required to connect Serial communication (RS232C) between Main Unit to Personal Computer. Purchase 9-pin Female Connector, then connect wires as follow.
- Connect RS232-TX, Grey wire of Main Unit to pin number 2 of 9-pin connector.
- Connect RS232-RX, Blue wire of Main Unit to pin number 3 of 9-pin connector.
- Connect RS232-GND, Yellow wire of Main Unit to pin number 5 of 9-pin connector.
- Plug in 9-pin connector to COM1 or COM2 Port of Personal Computer.
- Install and run SDC1000 Time & Attendance Software.
9-9. Chime Bell Unit connection(Extra Purchase, If Necessary)
- Connect Red(+) wire of Chime Bell Unit to Bell Output, Brown/White wire of Main Unit.
- Connect Black(-) wire of Chime Bell Unit to Power GND(-) wire.
9-10. Extra Proximity Reader connection(Extra Purchase, If Necessary)
- Connect (+)wire of Reader to DC +12V.
- Connect (-)wire of Reader to Power GND(-) wire.
- Connect Wiegand output DATA0 of Reader to Pink wire
- Connect Wiegand output DATA1 of Reader to Cyan wire.
- 9 -
Page 10
MOTOROLA
SDC1000
10. Initial Setup
SINGLE DOOR ACCESS CONTROLLER
Main Unit has Flash Memory to retain all setting values and when it delivered to customer there is no data in the memory therefore Initial Setup is required for the first use.
10-1. Registration of RF Cards for RF CARD ONLY MODE * This mode is only applicable when the extra proximity reader is connected. ¨ç Turn switch on DC12V Power Supply.
All 3 LEDs will be flashing with starting sound. ¨è Press 0 1 ENT from the keypad.(RF CARD ONLY MODE )
¨é Present RF Cards as follow to register Master Card and User Access Cards.
........
Master Card User Access Cards Master Card(Finish setup)
¨ê First read card is registered as Master Card and the RF Cards followed to Master Card are registered as User Access Cards then present Master Card again to finish setup. (Please keep Master Card at the secure location for further setting changes.) ¨ë Now, the Main Unit is entered to normal operation mode with default setting.
10-2. Registration of RF Cards with PIN for RF CARD + PIN MODE * This mode is only applicable when the extra proximity reader is connected. ¨ç Turn switch on DC12V Power Supply.
All 3 LEDs will be flashing with starting sound. ¨è Press 0 2 ¨é Present RF Cards as follow to register Master Card and User Access Cards and type
4~6 digits Personal Identification Number(PIN) followed by each User Access Card.
ENT
from the keypad.(RF CARD + PIN MODE )
........
Master Card User Access Cards+PIN
ENT
Master Card(Finish setup)
¨ê First read card is registered as Master Card and the RF Cards+PINENT followed to Master Card are registered as User Access Cards with PIN numbers then present
Master Card again to finish setup. (Please keep Master Card at the secure location for further setting changes.)
- 10 -
Page 11
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
¨ë Now, the Main Unit is entered to normal operation mode with default setting.
10-3. Registration of PIN ONLY MODE ¨ç Turn switch on DC12V Power Supply.
All 3 LEDs will be flashing with starting sound. ¨è Press 0 3 ENT from the keypad.(PIN ONLY MODE )
¨é Enter a 8 digits PIN number + digits PIN number +
ENT
ENT
to register Master PIN number then type 4~6
to register User Access PIN numbers then type 8 digits
Master PIN number to finish setup.
8digits PINENT 4~6digits PINENT ... 8digits Master PINENT
Master PIN User Access PIN ... Master PIN(Finish setup)
¨ê First 8 digits PIN number is registered as Master PIN and 4~6 digits PIN followed to Master PIN are registered as User Access PIN numbers then type Master PIN
again to finish setup. (Please write and remember Master PIN number for further setting changes.)
¨ë Now, the Main Unit is entered to normal operation mode with default setting.
10-4. Default Setting Values
After the Initial Setup, the Main Unit stores its default setting values as follows and run normal operation mode. If you want to change the setting values, add or delete USER Access Cards(or PIN) then please refer to "Setting Changes" in section 8.
¨ç When User Access Card(or PIN) is granted
- Door RELAY activates for 3sec.
- Green LED lights on for 3sec.
¨è When User Access Card(or PIN) is denied
- Alarm RELAY activates for 2sec.
- Red LED lights on for 2sec.
- 11 -
Page 12
MOTOROLA
SDC1000
11. Operation
SINGLE DOOR ACCESS CONTROLLER
11-1. Normal Operation Mode(Safe Mode) When the Main Unit is running in normal operation mode, Yellow LED is flashing every second.
11-2. Open the Door User Access Card(or PIN) is granted, Door opens for 3 seconds
with "do-mi-sol-do" melody.
Registered card(or PIN)
11-3. Exit(Open the Door)
To exit, press Exit Button and Door opens for 3 seconds.
11-4. Alarm by Unregistered Card(or PIN) User Access Card(or PIN) is not registered and access is denied,
then Alarm RELAY activates for 2 sec. with "sol-do-sol-do" melody.
Unregistered card(or PIN) (If you do not want to activate Alarm, then please change settings in section 8-22.)
11-5. Secure Mode
Last exit person can change the mode from Safe Mode to Secure Mode by pressing.
Secure Code from the keypad so that the Alarm will generate by AUX Inputs.
-> Change to Secure Mode.
It will canceled automatically when the registered card(or PIN) is present. 11-6. DURESS Alarm In case of opening the door by Duress condition, press Duress PassWordENT and open the door as usual then Duress Alarm(TTL Output) will activate.
- 12 -
Page 13
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
11-7. Chime Bell operation
When the guest presses ESC(Bell) Button from the keypad, Chime Bell melody is activating for 5 seconds.
12. Setting Changes
To change previous setting values, you need Master Card(or PIN) to get in to Setting Change mode. First present Master Card(or press Master PIN) and enter 2-digit command code. Present Master Card(or PIN) and press 2digit command code.
+ Command code +
Command Change setting values 11 Add User Access Cards(RF CARD ONLY MODE) 12 Add User Access Cards and PIN(RF CARD + PIN MODE) 13 Add User Access PIN numbers(PIN ONLY MODE) 14 Delete User Access Cards(or PIN) 21 Change Door open time when User Access Card(or PIN) is granted 22 Change Alarm time when User Access Card(or PIN) is denied 23 Change Alarm time when Try Our error detected 24 Change Alarm time when Door Contact error detected 25 Change Alarm time when AUX#1 Input detected 26 Change Alarm time when AUX#2 Input detected 27 Change Alarm time when AUX#3 Input detected 28 Change Alarm time when magnet detected 29 Register 2 digits Duress Alarm Code 30 Change Alarm time when Duress Alarm detected 31 Test Door open time set by command "21" 32 Test Alarm time set by command "22" 33 Test Alarm time set by command "23" 34 Test Alarm time set by command "24" 35 Test Alarm time set by command "25" 36 Test Alarm time set by command "26" 37 Test Alarm time set by command "27" 39 Change Chime Bell activating time
- 13 -
Page 14
MOTOROLA
SDC1000
Command Change setting values 41 Unconditional Door Open 42 Unconditional Door Close 43 Enable QUICK ACCESS MODE(Operate only PIN MODE) 44 Disable QUICK ACCESS MODE(Operate only PIN MODE) 51 Disable Melody sound 52 Enable Melody sound 60 Change keypad lock time when Try Out error detected 61 Detect AUX#1 Input from 'L' to ‘H' 62 Detect AUX#1 Input from 'H' to ‘L' 63 Detect AUX#2 Input from 'L' to ‘H' 64 Detect AUX#2 Input from 'H' to ‘L' 65 Detect AUX#3 Input from 'L' to ‘H' 66 Detect AUX#3 Input from 'H' to ‘L' 67 Detect Exit Button Input from 'L' to 'H' 68 Detect Exit Button Input from 'H' to 'L' 69 Detect Door Contact sensor Input from 'L' to 'H' 70 Detect Door Contact sensor Input from 'H' to 'L' 71 Activate TTL output to ‘H' 72 Activate TTL output to ‘L' 77 Enable Chime Bell Output 78 Disable Chime Bell Output 80 Set delay time to activate SECURE MODE 81 Set watch-dog time for Door Contact sensor 82 Set number of times of Try-Out 83 Set input limit time from the keypad 84 Set Temper Alarm port 88 Enable Temper Alarm 89 Disable temper Alarm 99 Initialize and erase all setup data
SINGLE DOOR ACCESS CONTROLLER
- 14 -
Page 15
MOTOROLA
SDC1000
12-11. Add User Access Cards(RF CARD ONLY MODE)
SINGLE DOOR ACCESS CONTROLLER
11ENT .....
Master card Command Cards to be registered .... Master card
12-12. Add User Access Cards(RF CARD + PIN MODE)
12
ENT
PIN
ENT
.....
Master card Command Cards to be registered .... Master card
12-13. Add User Access PIN(PIN ONLY MODE)
MasterPIN
ENT
13
ENT
PIN
ENT
..... MasterPIN
ENT
Master PIN Command PIN to be registered .... Master PIN
12-14.1. Delete User Access Cards(RF CARD ONLY MODE, RF CARD+PIN MODE)
14ENT CardNumberENT .....
Master Card Command Cards to be deleted .... Master Card
12-14.2. Delete User Access PIN(PIN ONLY MODE)
MasterPINENT 14ENT PINENT ..... MasterPINENT
Master PIN Command PIN to be deleted .... Master PIN
- 15 -
Page 16
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
<Table 1> Settings for command 21~28
Symbol Setting Values Examples/Remarks
Output Mode OM
(You must add value ¨ç and ¨è) Setting value for activating time ¨ç Activate Time Value Activate only Secure Mode : 00 Activate all the time : 50
____________________________________________
Setting Value for activate Output Port ¨è Activate Output Port Value Activate only Door Relay : 01 Activate only Alarm Relay : 02
Activate only TTL Output : 04 Activate Door Relay & TTL : 05 Activate Alarm Relay & TTL : 06
EX1)Activate Door Relay all the time Door RELAY 01 All the time 50 OM = 51
EX2)Activate Alarm Relay and TTL during the Secure mode Alarm+TTL 06 Secure Mode 00 OM = 06
tt
PW
mm
tt is the activating time value(seconds) from 01sec. to 99sec.
PW is the 2 digits PassWord for Duress Alarm.
mm is activating time value(minutes) from 01min. to 99min.
tt value 00sec. means no operation.
Do not use ‘77’ as it Is used for Secure Mode
mm value 00min. means no operation.
- 16 -
Page 17
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
12-21. Change Door open time when User Access Card(or PIN) is granted
(Please refer to Table 1 for tt)
21
ENT
tt
ENT
tt
ENT
Master card or Command Door time TTL time
MasterPIN
ENT
12-22. Change Alarm time when User Access Card(or PIN) is denied
(Please refer to Table 1 for OM, tt)
22ENT OMENT ttENT ttENT ttENT
Master card or Command Output Mode Door time Alarm Time TTL time
MasterPINENT
12-23. Change Alarm time when Try Our error detected
(Please refer to Table 1 for OM, tt)
Master card or Command Output Mode Door Time Alarm Time TTL Time MasterPINENT
12-24. Change Alarm time when Door Contact error detected
23
ENT
OM
ENT
tt
ENT
tt
ENT
tt
ENT
(Please refer to Table 1 for OM, tt)
24ENT OMENT
Master card or Command Output Mode Door Time Alarm Time TTL Time MasterPINENT
ENT ttENT ttENT
tt
12-25. Change Alarm time when AUX#1 Input detected 12-26. Change Alarm time when AUX#2 Input detected
12-27. Change Alarm time when AUX#3 Input detected
(Please refer to Table 1 for OM, tt)
25 26ENT OMENT
ENT
ENT ttENT ttENT
tt
27ENT
Master card or Command Output Mode Door Time Alarm Time TTL Time MasterPIN
ENT
- 17 -
Page 18
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
12-28. Change Alarm time when magnet detected (Please refer to Table 1 for OM, tt)
28
ENT
OM
ENT
tt
ENT
tt
ENT
tt
ENT
Master card or Command Output Mode Door Time Alarm Time TTL Time MasterPINENT
12-29. Register 2 digits Duress Alarm PassWord
(Please refer to Table 1 for PW)
29ENT PW
Master card or Command PassWord MasterPINENT
* ‘00’ is registered as default PassWord.
12-30. Change Alarm time when Duress Alarm detected
(Please refer to Table 1 for OM, tt)
30ENT OMENT
ENT ttENT ttENT
tt
Master card or Command Output Mode Door Time Alarm Time TTL Time MasterPIN
ENT
12-31. Test Door open time set by command "21" 12-32. Test Alarm time set by command "22" 12-33. Test Alarm time set by command "23" 12-34. Test Alarm time set by command "24" 12-35. Test Alarm time set by command "25" 12-36. Test Alarm time set by command "26"
12-37. Test Alarm time set by command "27"
Outputs set by command will be tested.
31~37ENT
Master card or Command MasterPIN
ENT
- 18 -
Page 19
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
12-39. Change Chime Bell activating time (Please refer to Table 1 for tt)
39
Master card or Command Chime Bell Time MasterPINENT
ENT
tt
ENT
12-41. Unconditional Door Open
Master card or MasterPINENT
12-42. Unconditional Door Close
Master card or MasterPINENT
12-43. Enable QUICK ACCESS MODE
When QUICK ACCESS MODE is enabled in PIN ONLY MODE,
Door will open just press ENT key.
Master card or 43ENT MasterPINENT
12-44. Disable QUICK ACCESS MODE
Master card or 44ENT MasterPINENT
12-51. Disable Melody sound
Master card or 51 MasterPIN
ENT
12-52. Enable Melody sound
Master card or 52ENT MasterPINENT
12-60. Change keypad lock time when Try Out error detected
41
42
ENT
ENT
ENT
(Please refer to Table 1 for tt)
60ENT
Master card or Command Keypad Lock Time MasterPIN
ENT
tt
ENT
- 19 -
Page 20
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
12-61. Detect AUX#1 Input from 'L' to ‘H'
AUX#1 input is detected on the raising edge of AUX#1 input Master card or
MasterPIN
ENT
61
ENT
12-62. Detect AUX#1 Input from 'H' to ‘L'
AUX#1 input is detected on the falling edge of AUX#1 input Master card or 62ENT
MasterPINENT
12-63. Detect AUX#2 Input from 'L' to ‘H'
AUX#2 input is detected on the raising edge of AUX#2 input Master card or 63ENT
MasterPINENT
12-64. Detect AUX#2 Input from 'H' to ‘L'
AUX#2 input is detected on the falling edge of AUX#2 input Master card or 64
MasterPIN
ENT
ENT
12-65. Detect AUX#3 Input from 'L' to ‘H'
AUX#3 input is detected on the raising edge of AUX#3 input Master card or 65ENT
MasterPINENT
12-66. Detect AUX#3 Input from 'H' to ‘L'
AUX#3 input is detected on the falling edge of AUX#3 input Master card or
MasterPINENT
66
ENT
12-67. Detect Exit Button Input from 'L' to 'H'
Exit Button input is detected on the raising edge of Exit Button input Master card or 67ENT
MasterPINENT
12-68. Detect Exit Button Input from 'H' to 'L'
Exit Button input is detected on the falling edge of Exit Button input Master card or 68ENT
MasterPINENT
12-69. Detect Door Contact sensor Input from 'L' to 'H'
Door Contact input is detected on the raising edge of Door Contact input Master card or 69
MasterPIN
ENT
ENT
- 20 -
Page 21
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
12-70. Detect Door Contact sensor Input from 'H' to 'L'
Door Contact input is detected on the falling edge of Door Contact input Master card or
MasterPIN
ENT
70
ENT
12-71. Activate TTL output to ‘H'
TTL output changes the state from logic '0' to logic '1' when it activates. Master card or 71ENT
MasterPINENT
12-72. Activate TTL output to ‘L'
TTL output changes the state from logic '1' to logic '0' when it activates. Master card or 72ENT
MasterPINENT
12-77. Enable Chime Bell Output
Master card or 77 MasterPIN
ENT
ENT
12-78. Disable Chime Bell Output
Master card or 78ENT MasterPINENT
12-80. Set delay time to activate SECURE MODE
(Please refer to Table 1 for mm)
80ENT
Master card or Command Delay Time MasterPIN
ENT
mm
ENT
12-81. Set watch-dog time for Door Contact sensor (Please refer to Table 1 for tt)
81ENT ttENT
Master card or Command Watch-dog Time MasterPINENT
- 21 -
Page 22
MOTOROLA
SDC1000
SINGLE DOOR ACCESS CONTROLLER
12-82. Set number of times of Try-Out NN is the Try-out numbers from 00 to 99 times.
82
ENT
NN
Master card or Command Try-out Numbers MasterPINENT
12-83. Set input limit time from the keypad
(Please refer to Table 1 for tt from 10 ~ 99)
83
Master card or Command Input Limit Time MasterPINENT
ENT
tt
12-84. Set Temper Alarm port (Please refer to Table 1 for OM)
84ENT OMENT
Master card or Command Alarm Port MasterPIN
ENT
12-88. Enable Temper Alarm
Master card or 88ENT MasterPINENT
12-89. Disable temper Alarm
Master card or 89ENT MasterPINENT
12-99. Initialize and erase all setup data
Please use this command when you really want to erase all data and start
the unit from the begining.
Master card or 99 MasterPIN
ENT
ENT
ENT
ENT
- 22 -
Page 23
MOTOROLA
SDC1000
13. FCC REGISTRATION INFORMATION
SINGLE DOOR ACCESS CONTROLLER
FCC REQUIREMENTS PART 15
Caution: Any changes or modifications in construction of this device which are not expressly approved by the responsible
for compliance cold void the user's authority to operate the equipment.
NOTE: This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions;
1. This device may not cause harmful interface, and
2. This device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
- 23 -
Page 24
MOTOROLA
SDC1000
14. Warranty and Service
SINGLE DOOR ACCESS CONTROLLER
The following warranty and service information applies only to the United States of America and Republic of Korea. For the information in other countries, please contact your local distributor. To obtain in or out of warranty service, please prepay shipment and return the unit to the appropriate facility listed below.
IN THE UNITED STATES RF LOGICS Inc. Service Center
3026 Scott Blvd., SANTA CLARA, CA95054 USA Tel.: (408) 980-0001 Fax.: (408) 980-8060 E-mail: rflogics@rflogics.com Web-site: www.rflogics.com
OUTSIDE OF THE UNITED STATES ID TECK CO., LTD. Service Center
5F Ace Techno Tower Bldg., 684-1 Deungchon-dong, Gangsuh-gu, SEOUL 157-030, KOREA Tel.: +82 (2) 659-0055 Fax.: +82 (2) 659-0086 E-mail: webmaster@idteck.com Web-site: www.idteck.com
Please use the original container, or pack the unit(s) in a sturdy carton with sufficient packing to prevent damage, include the following information:
1. A proof-of-purchase indicating model number and date of purchase.
2. Bill-to address
3. Ship-to address
4. Number and description of units shipped.
5. Name and telephone number of person to contact.
6. Reason for return and description of the problem. NOTE: Damage occuring during shipment is deemed the responsibility of the carrier, and claims should be made directly to
the carrier.
- 24 -