Http://www.hexin-technology.com/
HXSP-2108B RS-232/RS-485/RS-422
Converter Instruction
Product introduction
HXSP-2108B is a multifunctional converter with external power supply, it
compatible with RS-232/RS-485/RS-422 standard. It can change the
single-ended RS-232 signal to balanced RS -485/RS-422 signal, RS-232
interface use the DB9 female connector connect with the serial of
computer ,on the other side RS -485/RS-422 use the DB9 male connect
with 6 terminal board, Or you can choose the RJ -45 port connect with the
device which has the RJ -45 connector . Since the RS -485 support two
wire half duplex, which means the RS-485 only have two lines to receive
data and send data. Handshaking signal usually control the direction of
data sending, the inner circuit of HXSP-2108B converter is able to auto
sensing the direction of data flow, and switch to ENABLE CONTROLS
automatic. A RS-485 network can be built convenient without any
handshaking signal; the RS-485 ENABLE CONTROLS is full transparent ,
no need to modify any software for the old working method based on
RS-232. HXSP-2108B converter comes with external power supply, the
characteristic have small in design, long transmission distance,
performance stable, etc. it is mainly used for the field of electricity,
industrial automatic control, IC card billing system and time attendance,
one card solution, access control system, parking system, and so on.
Specification
1. Standard: Accord EIA RS-232, RS-485, RS-422 standard.
2. Connector: DB9 female on RS -232 side, DB9 male with 6 terminal block
on RS-485/RS-422 side or RJ-45 connector.
3. Work methods: asynchronous, point to point or multi -point, 2 wire
half-duplex.
4. Transmission medium: twisted pair cable or shielded Wire
5. Baud rate: 300~115000bps.
6. Signal indication: three signal indication LEDs(TXD,RXD,POWER).
7. Surge Protection: 1500W.
8. Transmission distance: 5 meters (RS-232 side) and 1800 meters
(RS-485/RS-422 side).
9. Dimension: 93mm x 23mm x 62mm.
10. Environment: -10℃ to 85℃ working temperature, 5% to 95% relative
humidity.
11. Loading Capacity: 32~128 units device.
Pin Definition:
RS-232 pin definition
DB9 Female
RS-485/RS-422 pin definition
Application
Please read the instruction carefully before using HXSP-2108B converter, the
9pin female side of RS-232 cable comes with HXSP-2108B connect to the
RS-232 connector of Main Host Computer. And the other side connects to the
RS-232 connector of the HXSP-2108B. The power AC Adapter connect to +9V
connector. Connect RS-45 or 6 terminal blocks on RS-485/RS-422 as
required, when connect all the terminal blocks, it must be according to the Pin
Definition.HXSP-2108B converters support 4 kinds of communication method
as below:
(1) Point to point /four wires full-duplex
(2) Point to points /four wires full-duplex
(3) Point to point /two wires half-duplex
(4) Point to points / two wires half-duplex
The factory settings is auto adaptation status, when the customer use external
connection as RS-485 , the HXSP-2108B will be in the half-duplex RS-485
status , and when the customer use external connection as RS -422 , the
HXSP-2108B will be in the full-duplex RS-422 status.
(1) When the HXSP-2108B connects as RS-232/RS-422, the device connects
as RS-422 connection method.
A. RS-232/RS-422 communicate as point to point four wire, asynchronous,
full-duplex method, this method is mainly used for control -side equipment
connector is RS-232, and the connector of equipment un der control is RS-422,
The two side can not communicate directly because of disaccord of two side
electrical specialty, HXSP-2108B converter can be used for transparent
change the RS-232 signals to RS-422 signals.
Http://www.hexin-technology.com/
Problem analysis:
1. Data communication unsuccessful
A. Check RS-232 interfaces whether to be correct;
B. Check RS-485 interfaces whether to be correct;
C. Check whether RS-232 signal level(TXD、DTR、RTS) lower than+5V,
if that, it can get through power from 6th pin of DB9 Male.
2. Data missing or messy code
A. Check whether the baud rate and format of both sides of data
communication equipment are same.
B. If possible, add the matched resistance on the terminal circuit (120Ω,1/4
w)
B. RS-232/RS-422 communicate as point to point s four wire, asynchronous,
full-duplex method, this method is mainly used for control -side equipment
connector is RS-232, and the connector of equipment un der control is
RS-422,and it will connect many RS -422 devices. From device (RS -422
SLAVE) MAX connection is 32~128 RS -422 devices. In order to avoid signal
reflex and interfering signal, it should be add the matched resistance on the
terminal circuit (120Ω, 1/4 w)
(2) When the HXSP-2108B connects as RS-232/RS-4485, the device
connects as RS-485 connection method.
A. RS-232/RS-485 communicate as point to point two wire , half-duplex
method, this method is mainly used for control -side equipment connector is
RS-232, and the connector of equipment un der control is RS-485, The two
side can not communicate directly because of disaccord of two side electrical
specialty, HXSP-2108B converter can be used for transparent change the
RS-232 signals to RS-485 signals, and it need not RTS.
B. RS-232/RS-485 communicate as point to point s two wire, half-duplex
method, this method is mainly used for control -side equipment connector is
RS-232, and the connector of equipment un der control is RS-485,and it will
connect many RS -485 devices. From device (RS -485 SLAVE) MAX
connection is 32~128 RS -485 devices. In order to avoid signal reflex and
interfering signal, it should be add the matched resistance on the terminal
circuit (120Ω, 1/4 w)
Power Supply and Surge Protection
1. HXSP-2108B converter can get the power from the 9V adapter or from other
DC power or device. Power supply voltage should be +9V, electric should be
100mA.
2. Surging protection
Ordinary interface converters do not provide large energy protection
equipment, and they try to release the energy to the Earth through the smallest
resistance route for the transient high voltage in the interface data line of wire
sensor. So it is easy to make the interface component’s damage. Interface
Converters during the process should avoid grounding vacant in order to
ensure the safety of use and reliable communications .