Heta Ambition, Ambition 5, Ambition 8 Operating And Installation Instructions

Page 1
OPERATING AND INSTALLATION
INSTRUCTIONS
AMBITION STOVE
is exemt for use in smoke control areas when burning dry wood.
www.heta.dk
DANISH DESIGN . DANISH QUALITY . DANISH PRODUCTION
EN
1
Page 2
Certifikat no. 2334
Declaration of Performance EN
__________________________________________________________________________________________________________________________________
Regulation No. 305/2011
DOP-Ambition 5 2334-2018
1. Unique identification code of product-type Stove
2. Product name Ambition 5
3. Intended use or uses of the construction product, in accordance with the applicable technical specification
4. Name and contact address of the manufacturer Heta A/S, Jupitervej 22, DK-7620 Lemvig. heta@heta.dk
5. Where applicable, name and contact address of authorized representative. E-mail.
6. System of assessment and verification of constancy of performance of the construction product
7. Notified body relevant to the assessment and verification of constancy of performance
8. Declared Performance
Harmonized technical specification EN 13240:2001/A2:2004
Emission CO 0,089%
Fire safety
Reaction to fire A1
Test of fire safety in connection with the burning of wood Approved
Distance to combustible materials Rear - whit insulation/whitout insulation Sides distance to combustible materials Distance to floor from lower edge of the door Furniture distance
Safety
Mechanical resistance (to carry a chimney / flue) Not tested (NPD)
Electrical safety NA
Surface temperature Approved
Cleanability No specification
Room heater burning solid fuel without hot water supply
Factory Manager Martin Bach, E-mail: martin.bach@heta.dk
System 3
Teknologisk Institut, DK-8000 Aarhus Notified body No. 1235 Rapport no. 300-ELAB-2334-EN
Nox 93 mg/Nm Dust 22 mg/Nm Dust (NS3058/3059) 0,78 g/kg OGC (CEN/TS 15883) 62 mgC/Nm
3
3
3
ved 13% O
2
Minimum distances in mm 150/200 400
---­1100
Thermal output
Nominal heat output 4,9 kW
Room heat output 4,9 kW
Energy efficiency
Fluegas temperature at nominal heat output T 200
Ƞ 85%
o
C
Water heating output NA
Maximum water operating pressure NA
9.
The performance of the product identified in points1 and 2 is in conformity with the declared performance in point 8. This declaration of performance is issued under the sole responsibility of the manufacturer.
Signed on behalf the manufacturer of
_____________________________________
Lemvig 13.06.2018 Martin Bach ____________________________________________________________________________________________________________________
In case of any change of the above-mentioned production type this Declaration of Performance becomes invalid.
Heta A/S, Jupitervej 22, DK-7620 Lemvig, Tlf. +45 9663 0600, www.heta.dk
Page 1 of 1
2
Page 3
Certifikat no. 2335
Declaration of Performance EN
__________________________________________________________________________________________________________________________________
Regulation No. 305/2011
DOP-Ambition 8 2335-2018
1. Unique identification code of product-type Stove
2. Product name Ambition 8
3. Intended use or uses of the construction product, in accordance with the applicable technical specification
4. Name and contact address of the manufacturer Heta A/S, Jupitervej 22, DK-7620 Lemvig. heta@heta.dk
5. Where applicable, name and contact address of authorized representative. E-mail.
6. System of assessment and verification of constancy of performance of the construction product
7. Notified body relevant to the assessment and verification of constancy of performance
8. Declared Performance
Harmonized technical specification EN 13240:2001/A2:2004
Emission CO 0,077%
Fire safety
Reaction to fire A1
Test of fire safety in connection with the burning of wood Approved
Distance to combustible materials Rear - whit insulation/whitout insulation Sides distance to combustible materials Distance to floor from lower edge of the door Furniture distance
Safety
Mechanical resistance (to carry a chimney / flue) Not tested (NPD)
Electrical safety NA
Surface temperature Approved
Cleanability No specification
Room heater burning solid fuel without hot water supply
Factory Manager Martin Bach, E-mail: martin.bach@heta.dk
System 3
Teknologisk Institut, DK-8000 Aarhus Notified body No. 1235 Rapport no. 300-ELAB-2335-EN
Nox 99 mg/Nm Dust 27 mg/Nm Dust (NS3058/3059) 0,6 g/kg OGC (CEN/TS 15883) 92 mgC/Nm
3
3
3
ved 13% O
2
Minimum distances in mm 175/225 400
---­1100
Thermal output
Nominal heat output 6,5 kW
Room heat output 6,5 kW
Energy efficiency
Fluegas temperature at nominal heat output T 250
Ƞ 80%
o
C
Water heating output NA
Maximum water operating pressure NA
9.
The performance of the product identified in points1 and 2 is in conformity with the declared performance in point 8. This declaration of performance is issued under the sole responsibility of the manufacturer.
Signed on behalf the manufacturer of
_____________________________________
Lemvig 13.06.2018 Martin Bach ____________________________________________________________________________________________________________________
In case of any change of the above-mentioned production type this Declaration of Performance becomes invalid.
Heta A/S, Jupitervej 22, DK-7620 Lemvig, Tlf. +45 9663 0600, www.heta.dk
Page 1 of 1
3
Page 4
Congratulations on your new stove. We confident that you will be more than satisfied with your new Heta stove, especially if you follow the advice and instructions we have put together in these operating instructions. Ambition series have been approved per the EN 13240, NS 3058/3059 and 15a B-VG. These approvals, means that the wood stove meets a variety of specifications and requirements, ensuring it is made of quality materials, minimum environmental im­pact and that it has an optimum fuel economy. The Ambitions are recommended as exempt for use within smoke control areas (SCA) throughout the UK (see clean air act Appendix A). of the air supply regulation so that it can`t be closed completely.
Operating Instructions Contents
Declaration of Performance Ambition 5 ............................................. 2
Declaration of Performance Ambition 8 ............................................. 3
Before installation ........................................................................... 5-6
1. Operating instructions ........................................................................ 7
1.1 Before using ....................................................................................... 7
1.2 First firing ........................................................................................... 7
1.3 Regulating the airflow ......................................................................... 7
1.4 Lighting the stove ............................................................................... 7
1.5 Refueling ............................................................................................ 7
1.6 Emptying the ash ............................................................................... 8
1.7 Reduced burning ................................................................................ 8
1.8 Risk of explosion ................................................................................ 8
1.9 Draft conditions in the chimney ......................................................... 8
1.10 Fuel ..................................................................................................... 9
1.11 Operating problems ......................................................................... 10
1.12 Chimney fire ..................................................................................... 10
1.13 Maintenance ..................................................................................... 10
1.14 Cleaning the glass ............................................................................ 10
1.15 Troubleshooting ............................................................................... 11
1.16 Diagram for maintenance ................................................................. 12
1.17 Cleaning/Replacing bicks after chimney sweeping ......................... 13
1.18 Stove data table EN 13240 .............................................................. 14
1.19 Garantee ........................................................................................... 14
1.20 Parts ............................................................................................ 15-15
2. Installation Instructions .................................................................... 16
Heta A/S
Jupitervej 22, DK-7620 Lemvig
Phone: +45 9663 0600 E-mail: [email protected]
4
Copyright © 2014 Heta is a registered trademark of Heta A/S
Printed in Denmark Subject to printing errors and changes.
13.06.2018 0037-1526 Version 1,0
Page 5
BEFORE INSTALLATION
Heta wood stoves are quality products, therefore, your first impression is very important! We have a good logistics network, which transports Heta products with great care for our dealers. Neverthe­less, when in transport or handling, damage of the often-heavy stoves can occur. It is important that upon receipt check your Heta product completely and report any damage or defects to your dealer.
The packaging must be disposed of as follows: Wood is untreated and able to burn in the stove. Plastic and cardboard you can drop off at your local recycling center.
Unpacking the stove
5
Page 6
1
BETJENI NGS- OG
OPSTILL INGSVEJLEDN ING
DANSK DESIGN . DANSK KVALI TET . DAN SK PRODUKTI ON
www.heta.dk
DK
AMBITIO N BRÆNDEOVN
With your new wood stove you should find the following:
8056-0000-D
K
w
t
Operating /
Instruction manual
Heta glove
Flue collar 4025-0007
Q.C. check
Data plate
Stove door handle
CE
DOP-Scan-line 1000 -XXXX-2016
Heta A/S Jupitervej 22 7620 Lemvig Denmark
Produk�ons år: 2016
DS/EN 13240, AEA, NS 3058/3059, Aus §15A
Produkt beskrivelse Produk�onsnummer
Scan-Line 1000 brændeovn
Afstand �l brændbart materiale - bag ovn Afstand �l brændbart materiale - side af ovn Afstand �l møbel Middel CO emission nominel last ved 13% O2 Middel CO emission I Mg/Nm3 ved 13% O2 656 Mg. Røggas Temp. Nominel last 261 C° Støv > 3 Mg/Nm3 OGC 32 Mg/Nm3 Ydelse nominel last 4,5 k Virkningsgrad nominel last 81% Støv (NS 3058/3059) samlet vægtet par�kelemission 0,63 g/kg Brændsel Træ ovnen er egnet �l intermiterrende drif Anvend kun godkendt brændsel Følg fabrikantens brugervejledning
120 mm
350 mm
850 mm
0,05%
Required tools are not supplied.
6
Page 7
1. OPERATING INSTRUCTIONS
1.1 Before using
Before the wood stove is used make sure re­quired installation conditions, are met. See page
16.
1
Air control
Stove door handle
1.2 First firing
42% for Ambition 8 of its fully open position. A permanent amount of air will therefore enter the firebox to feed the fire producing negligible amounts of smoke and unburnt hydrocarbons. The appliances will only be considered as an exempt appliance if this stop is in place.
Use the glove when regulating the conbustion air. The handle will be hot.
1.4 Lighting the stove
Place two pieces of wood on the bottom. Stack kindling on top in layers with air between. Set ting fire starter (bag, brick, paraffin) on the top, now you are ready to light the fuel. The flames must work from the top down.
3
Heta wood stoves are, treated with a heat-resi­stant coating, which hardens at a temperature of about 250° C.
This curing process will cause some smoke and odor, so there should be sufficient ventilation in or­der to avoid the door seal sticking to the stove du­ring this curing process, open the door every ten minutes during the first two hours of the first firing.
1.3 Regulating the air flow
The stoves combustion air is regulated by means of a handle below the firing door.
2
See fig. 2.
from use in a wood stove.
We recommend, all of the first fuel is burned with the combustion air fully open in the opera­ting position. This ensures the stove and chim­ney are thoroughly heated.
Startup/Lighting Scan the code and select a language.
The use of lighter fluid, oils or any
liquid fuels is strictly forbidden
1.5 Refueling
Closed Open
The Ambition stoves are designed and tested to burn extremely cleanly with very little smo­ke discharge and are exempt for use in smoke control areas throughout the UK when burning dry wood logs. To comply, a permanent stop is fitted to ensure that the air control slider can­not be closed beyond 33% for Ambition 5 and
Refueling of your stove should be done while there is still a good layer of embers. Distribu­tethe embers with the majority of them to the front. Place pieces of wood equivalent to about 1,2 kg for Ambition 5 and 1.8 kg for Ambition 8 on top of the embers perpendicular to the door. See fig. 4.
Now open the combustion air completely. If the stove and/or chimney cools down too much, it­may be necessary to have the door ajar.
7
Page 8
4
1.6 Emptying the ash
It is advantageous to leave a layer of ash in the bottom of the combustion chamber on top of the grate as insulation.
Be careful when emptying the ashes out. There can be hot embers left for a long time.
Never empty ash into a combustible container.
The wood will then ignite within a very short time (Typically 1 to 3 minutes). Once the fuel is Igni­ted. Close the door and regulate the air back to operating air. When the fire is well established, you can now regulate the operating air to the desired combustion level.
The nominal output Ambition 5 / Ambition 8:
4.9/6.5 kW is equivalent to a firing interval of approx. 45/55 minutes at 61/69% open combu­stion air and 1.2/1.8 kg of wood.
Ensure when refueling that the wood is not too close, it will cause poorer combustion, less heat out-put and lower efficiency.
5
Vermiculite (stone)
The door must be closed during operation.
Maximum wood filling
1.7 Reduced burning
The stove is, approved for intermittent use.
Never turn down the air down so much that there does not come any flames from the tree. Wait to close the air until the flames haveburnt out and the tree is transformed into glowing charcoal.
If you are looking for less heat out-put, achieve this by fueling with smaller volumes of wood and a lower operating air. You may not completely close the operating air during firing.
Be aware that the stove will naturally soot if the operating air is too low. This is not good for the environment. There is also a risk for the glass, t
he chimney and other parts will become sooted.
By a combination of the above and possibly burning damp wood. Can lead to high levels of soot that it becomes sticky. Causing the sealing of the door to tear off when opening the door the next day.
seals are loose.
Never use the stove if the
The fuel load, must be maintained below the top series of air holes and within the outer vent in each side. Fig. 5.
W
hen refueling be careful to place the fuel into the combustion cham­ber gently, (use the provided glove). By not doing so you risk cracking or breaking the vermiculite.
If there is reduced draft in the chimney, we re­commend opening a window at stoking. This will give better ventilation to the room and more oxy­gen for combustion.
8
1.8 Explosion!!!
It is very important never to leave The stove after start up or refueling, before the fire is established. (Typically
Explosion hazard may be possible, if filled with too much wood on the stove and the air supply is to low. As large amounts of gas are being de­veloped and this may cause a flue gas explosion.
1/2 -1
minutes)
Warning!
One must always use cation around the stove seen, as it gets very warm during use. (In excess of 90° C).
Children should avoid contact with the stove.
Setting up a fence if you have small children may be necessary.
Page 9
Do not place flammable objects like drying racks, furniture, curtains too close to the stove.
1.9 Draft conditions and the chimney
Poor draft will not allow the stove to burn, as it should. The glass can soot, requires cleaning of the chimney more often, smoke can escape out when the door is open and it gives poor fuel ef­ficiency. Leading to unnecessary polluting of the environment.
Good draft will allow the stove to achieve op­timal combustion and the highest possible ef-
The chimney height and diameter, as well as the temperature difference between the flue gas and outside temperature generates the chimney draft. Chimney insulation is therefore important as new efficient stoves create lower flue tempe­ratures. Wind and weather conditions also in­fluence draft, in some cases it may be disad­vantageous wind direction, combined with the position of the chimney can cause negative draft (it blows through the chimney), causing smoke escape from the stove.
Before using after a long period of inactivity, check that the chimney is free for any blocka­ges. (soot build-up, bird nests, leaves etc.).
6
combustion air
ficiency. Heta wood stoves are constructed so that it itself provides an optimal blend of com­bustion air. This provides a high efficiency/heat, clean glass and low environmental impact.
Reduced draft can occur when:
• The temperature difference is too small between smoke gasses and outdoor temperature, for eg. poorly insulated chimney
• To short of a chimney
• The outside temperature is high, and indoor temperature is low for eg. in summer
• False air in the chimney
• Chimney is blocked
• Air tight house (lack of combustion air supply)
• Poorly placed chimney for the surroundings, for ex. the ridge and trees may cause turbulence
Good draft occurs when:
• The difference in temperature in the chimney (warmer) and outside temperature (colder)
• It is clear weather
• The chimney has the right height min 4 meters above the stove, and clear of the roof ridge.
Minimum chimney draft
It is the draft that the stove has been tested and approved on. The minimum draft is necessary to provide clean burning, beautiful flame picture, as well as achieving the rated efficiency.
There is a risk of smoke escaping into the room if the door is opened during vigorous firing, or if there is a lack of air supply to the room, for ex. if an extraction fan is in use.
Ambition 5: 200°C, relative to 250
°C relative to
Flue gas flow is: Ambition 5: 4,5 g/sek. Ambition
8: 5,9 g/sek. Corresponding to 17 m3/hr of com­bustion air by burning 1,2 kg of wood.
20°C.
: 12
pascal
.
20°C. Ambition 8:
1.10 Fuel
Your new stove is EN approved for firing with wood fuel. You must therefore only burn clean, dry wood in your stove. Never use your stove to burn driftwood, as this may contain a lot of salt which can damage both the stove and the chimney. Similarly, you must not fire your stove with refuse, painted wood, pressure-impregna­ted wood or chipboard, as these materials can emit poisonous fumes and smoke.
Correct firing using well seasoned wood pro­vides optimal heat output and maximum effi­ciency. At the same time, correct firing prevents environmental damage in the form of smoke emissions and reduces the risk of chimney fires.
9
Page 10
If the wood is damp and inadequately seasoned, a large proportion of the energy in the fuel will be used to vaporize the water and this will all disap­pear up the chimney. Thus, it is important to use dry, well seasoned wood, for eg. wood with a moisture content of less than 20 %. Achieve this by storing the wood for 1–2 years before use.
Pieces of firewood with a diameter of more than 10 cm should be split before before storing. The pieces of firewood should be of an appropriate length (approx. 35-40 cm) so that they can lie flat on the bed of embers. If you store your wood outdoors, it is best to cover it.
Examples of fuel values
for different woods and their typical densities per cubic meter, specified for 100% wood with a moisture content of 18%.
Wood kg/m3Wood kg/m
Beech 710 Willow 560
Oak 700 Alder 540
Ash 700 Scotch pine 520
Elm 690 Larch 520
Maple 660 Lime 510
Birch 620 Spruce 450
Mountain pine 600 Poplar 450
It is advised not to use oil-containing woods like teak tree and mahogany, as this can cau­se damage to the glass.
3
nal association of chimney sweeps) registered chimney sweep.
In the event of smoke or malodorous fumes are being produced, you must first check to see whether the chimney is blocked.
T
he chimney must, of course, always provide the minimum draft necessary to ensure that it is pos­sible to regulate the fire. Please note, how-ever, that chimney draft is dependent on the weather conditions. In high winds, the draft can become so powerful that it may be necessary to fit a damper in the flue gas pipe to regulate the draft.
When cleaning the chimney, soot and other deposits may come to fall on the baffle plate, remove and clean it. In cases where the wood burns too quickly, this may be due to excessive chimney draft. You should also check to make sure that the door seal and ash pan seal is intact and correctly fitting.
If the stove it generating too little heat, this may be because you are firing with wet wood. In this case, much of the heating energy is used to dry the wood, resulting in poor efficiency, poten­tially damaging the vermiculite and an increased risk of soot deposits in the chimney.
1.12 Chimney fire
In case of a chimney fire, which often results from incorrect operation/maintenance or prolonged use of damp wood, close the door and the air supply completely, to help slow/smother the fire.
Heating value in wood
You have to use about 2.4 kg normal wood to replace one litre of heating oil. All woods have almost the same heating value per kg, which is about 5.27 kW/hour for absolute dry wood. Wood with a moistness of 18% has a efficiency of about 4.18 kW / hour per kg, and one litre heating oil contains about 10 kW / hour.
CO2 release
At combustion 1000 litres of heating oil forms 3.171 tons CO2. As wood is a CO2 neutral heat/energy source, you save the environment about 1.3 kg CO2 every time you have used 1 kg normal wood.
1.11 Operational problems
The chimney must be swept at least once a year, we recommend the use of a NACS (natio-
Call the fire department. The stove and chimi­ney must be inspected before use again.
1.13 Maintenance
The surface of the stove is treated with a heat­resistant paint. The stove should be cleaned with a damp cloth. Any damage to the surface in the form of chips or scratches can be repaired using touch-up paint, which is available in spray cans.
1.14 Cleaning the glass
Incorrect firing, for example using wet wood, can result in the viewing window becoming covered in soot. This soot can be easily and effectively removed by using proprietary stove glass cleaner.
10
Page 11
1.15 Troubleshooting table - applies to all stove types
Fault Cause Troubleshooting Solution
Lighting problems. When the stove is cold, smoke seeps into the room. Once the com­bustion chamber has heated up, the stove burns well.
The stove burns poorly after the warm-up phase, glass slowly soots up.
If the stove burns poorly after start-up, and the glass slowly soots up.
The vermiculite in the combustion chamber is becoming very worn.
Too rapid combustion. Too much chimney draft. T
The vermiculite in the combustion chamber is cracked.
Steel surfaces in the combustion chamber have oxidised.
The stove whistles Too much chimney draft To test, you can open the cleaning
The stove 'clunks' Usually due to tension in the
The stove ticks Normal expansion and
The stove creaks. The temperature in the com-
The stove smells. The surface is steaming.
Condensation in the combustionchamber.
Condensation from the flue pipe.
and the
Inadequate chimney draft. The chimney only has sufficient draft when it is hot.
Soot in the flue pipe. Check the flue pipe regularly, as the
Inadequate chimney draft.
Insufficient air supply. Check the air supply. Read the operating instructions and
Damp wood. Use clean, dry wood with a maximum
Firewood pieces too large. The optimum size is a length of 25 cm
Insufficient air supply to the room. Range hoods, airtight windows, etc.
Insufficient air supply to the room. Range hoods, airtight windows, etc
Wood and flue gases wear down the vermiculite.
The door or ash pan/drawer seal is defective.
Shocks or impacts while adding firewood.
The temperature in the combustion chamber is too high.
metal plates.
contraction due to temperature changes.
bustion chamber is too high.
The paint on the stove sur­ace is not yet fully hardened.
Moisture in the vermiculite. C
Damp wood. Measure the moisture content. Use dry firewood.
The pipe is too long or the chimney is too cold.
Damp wood Measure the moisture content. Use dry firewood.
You can test using a lighter whether flame is drawn into the combustion chamber.
problem arises slowly.
The fault usually already occurs during lighting. Measure the chimney draft
moisture content of 20%.
and max. diameter of 10 cm.
Ensure there is sufficient fresh air supply, open a window, check the outdoor air supply.
Ensure there is sufficient fresh air supply, open a window, check the outdoor air supply.
Investigate whether the wear is normal.
o test, you can open the cleaning
hatch, but remember to close it again.
While cold, close a piece of paper in the door – the seal should hold the paper gently in place so it does not fall out by itself. Normal wear.
Normal wear Cracks only have cosmetic signifi-
Unsuitable fuel is being used (such as coal). Check the quantity of firewood being used, read the operating instructions.
hatch, but remember to close it again.
Generally only occurs while heating up and cooling down.
A normal sound. Ensure that the temperature in the
Use less firewood. Also check the seal in the ash pan/drawer.
See the operating instructions regarding the first firing.
heck the condition of the vermiculite.
Check the flue pipe's length and heat loss.
Improve the chimney.
Clean regularly, and limit the use of horizontal flue pipes. Do not use firewood which generates large quantities of ash.
Improve the chimney draft.
.
instruct all users.
Firewood should ideally be dried for at least one year after splitting.
Use smaller pieces of firewood.
Depending on the cause, windows must be opened or the outdoor air connection cleaned.
Depending on the cause, windows must be opened or the outdoor air connection cleaned.
Normal wear and minor cracks are of no significance. It should be replaced when the steel of the combustion chamber is visible.
Measure the chimney draft and install a damper in the flue pipe if necessary.
Replace the seal.
cance. Replace when the steel of the combustion chamber is visible.
If there are clear cracks or weak­nesses in the stove body, it must be replaced.
Install a damper.
Adjust the metal plates.
combustion chamber is as constant as possible.
See the operating instructions.
Ensure there is sufficient ventilation.
Evaporates by itself after the stove has been lit a few times.
Improve the flue pipe, insulate the chimney.
11
Page 12
1.16 Diagram for the maintenance
Maintenance / Period
Cleaning the chimney (see. Chimney)
Cleaning the chimney and stove
Cleaning the stoves firebox
Cleaning combustion air intake
Cleaning of the firebox
Checking / switch, gasket for door
Checking / changing, gasket for glass
Checking / changing gasket for flue pipe
Checking / changing vermiculite
Lubricate hinges
Lubricate lock
Stove Owner
Before Autum
Daily
1 week
30 days
60-90 days
Qualified Technicia
1st Year 2st Year
C C C C VI C C C C VI C
C/S VI C/S C/S VI C/S C/S VI C/S
C/S VI C/S
L VI L L VI L
For the lubricant used a heat-resistant product. (300c) C = Cleaning C/S = Checking /Switch L = Lubricate VI = Visual Inspection, pos. cleaning/replacing/adjusting
12
Page 13
1
2
1.17 Cleaning after sweeping or before replacing vermiculite stones
Note: it may be necessary to clean/vaccum the holes and air ducts behind the rear stone.
Order of removing Fire bricks.
1
3
2
4
4
5
5
1
2
Replace in reverse order. Starting with Fig. 5.
13
Page 14
1.18 Stove data table in accordance with en 13240 testing
Tested as a freestanding oven and with uninsulated flue
Stove type Nominal
fluegas temperature
C°
Ambition 5
Ambition 8
200 ø125 1,2
250 ø125 1,8
Flue
mm
Fuel volume
kg
Draft min.
mbar
0.12
0.12
Nominal output tested
kW
Actual efficiency
%
4,9 85 400 200 1100 98
6,5 80 400 225 1100 110
Distance to flamable materials
at the sides
mm
rear the stove
mm
to furnitures
mm
Stove weight
kg
The nominal output is the output to which the stove has been tested. Testing is conducted with the combustion air around 61% open for Ambition 5 and 69% open for Ambition 8.
1.19 Guarantee
Heta wood stoves, subjected to a strict quality control during production and before delivery to the dealer.
Therefore, the stoves guarantee is
FOR FIVE YEARS
Against defects in manufacturing
- Damage caused by improper use.
- Transportation costs for warranty repair.
- Assembly / disassembly of warranty repair.
Should you have cause to make a complaint, please quote our invoice no.
The guarantee does not cover: Wearing parts / fragile parts such as:
- Vermiculite stones in the combustion chamber, glass, seals and the casted bottom or shaking grate.
1.20 Parts - Doors
5
11
1
8
12
14
7
9
6
10
13
4
3
8
Warning
Any unauthorized alterations to the stove and the use of non-original parts will void the warranty.
Pos. No. Name Qty.
1 0030-000034 Stove door 2 0021-000170 Glass 1 3 0023-000356 Door gasket L=1.7 m 1 4 0023-000358 Glass gasket L=1.6 m 1 5 0008-9086 Hinge pin ø6x40 SS 2 6 0016-0031 Handle 1 7 1013-0732 Door hock 1 8 0008-1007 Flat screw M6x6 4 9 0008-0040 M5x10 Ch 2 10 0008-9015 Pin ø5x26 1 11 0008-3503 Brass disc M6/6,4/11/1,6 1 12 1013-0733 ABracket by hook 1
2
13 0008-9042 Disc spring ø18/ø6.2x0.4 1 14 0008-0014 M6x6 with flat head 1 15 1013-0529 Glass clips 4 16 0008-2004 UH M4x10 indv. 6kt 4
15
16
14
Page 15
Ambition 5 Parts - Inside fire chamber
6
2
1
5
Pos. No. Name Qty.
1 0023-000103 Back stone top, left 1 2 0023-002740 Side stone, left 1 3 0023-002742 Baffle 1 4 0023-002741 Side stone, right 1 5 0023-000387 Back stone bottom, left 1 6 1013-004304 Stiffener 1 7 0023-004882 Back stone top, right 1 8 0023-004879 Back stone bottom, right 1
3
4
7
8
Ambition 8 Parts - Inside fire chamber
3
1
2
Pos. No. Name Qty.
1 0023-005003 Back stone top, left 1 2 0023-004994 Back stone bottom, left 1 3 0023-000105 Side stone, left 1 4 0023-000106 Baffle 1 5 0023-000108 Side stone, right 1 6 1013-004304 Stiffener 1 7 0023-005004 Back stone top, right 1 8 0023-004995 Back stone bottom, right 1
6
4
7
8
5
15
Page 16
Installation Instructions Contents
2. Installation instructions ..................................................................... 17
2.1 Distance requirements ...................................................................... 17
2.2 Floor .................................................................................................. 17
2.3 Chimney connection ......................................................................... 17
2.4 Combustion air and ventilation ......................................................... 18
2.5 Stovedrawings/measurments ..................................................... 18-20
2.6 Connecting direct air - nehind ........................................................... 20
2.7 Clearances for installation EN 13 240 ............................................... 21
2.8 Changing to back outlet .................................................................... 22
3. Data plate .......................................................................................... 23
Appendix A ........................................................................................ 23
16
Remember
The stove and chimney installation, must comply with local regulations, including those referring to national and European standards.
Page 17
2. Installation instructions
The stove installation must be in accordance with national, European and possibly local regu­lations. You must follow local regulations with regard to installation of chimney and connection to the chimney. We recommend that you let a professional Heta dealer install the stove. Alter­natively, you can ask the local chimney sweep before installation. Be aware that it is always the owner himself who has responsibility for ensu­ring that applicable rules are complied with.
A modern stove places heavy demands on the chimney due to the high efficiency. It may be necessary to enhance or even replace an old chimney.
Remember
1. Always ensure free access to any cleaning doors in a chimney.
2. Always ensure ample fresh air to the room.
3. Exhaust/extraction fans in the house can re­duce or create negative draft in the chimney. Reduced draft can lead to the stove having a
dverse combustion properties. It may result in smoke coming out of the stove when the door is open. A negative draft due to an exhaust/extraction fan can cause the chim­ney to work in reverse, drawing smoke into the house because of the fan.
4. Any air vents must not be covered.
applicable national and local regulations. Pro­tecting your floor from embers that may fall out of the oven.
Distances see data table page 21.
2.3 The chimney connection
The chimney opening must follow national and local regulations. However, the area of the ope­ning should never be less than 115 cm2, which corresponds to a diameter of 121 mm. If a damper is fitted in the flue gas pipe, there must always be at least 20 cm2 of free passage, even when the damper is in its “closed” position.
If local regulations permit, two contained stoves can be connected to the same chimney. How­ever, you must abide by local regulations regar­ding the distance between the two connections.
The stove must never be connected to a chimney that is linked to a gas fire stove.
An efficient stove makes high demand on chimney – so always have your local chimney sweep evaluate your chimney.
properties
Connection to a brick chimney
2.1 Distance Provisions
There is a difference between installation next flammable wall or non-flammable wall. If the wall is made of non-flammable material, the stove principle may be placed flush against it.
We recommend a minimum of 5 cm to facilitate air circulation around the stove.
The minimum distance to combustibles can be found on the model plate provided with the sto­ve or on page 21 of this manual.
to
in
2.2 Floor
You must ensure that the floor can support the weight of the stove and a top-mounted steel chimney.
In front of the fireplace stove, the substrate must consist of non-combustible material, for ex. Steel/glass plate, stone or tile floor. The size of the non-combustible surface must follow the
Brick a thimble into the chimney and seat the flue gas pipe in this.
The thimble and flue gas pipe must not penetra­te the chimney opening itself, but must be flush with the inside of the chimney duct. Joins bet­ween brickwork, the thimble and flue gas pipe m
ust be sealed with fireproof material and / or beading im
portance that this is done correctly with very tight joints that setup and installation be left to a profes­sional Heta dealer.
. Heta A/S stresses that it is of utmost
. As mentioned earlier, we recommend
Connection to a steel chimney
When fitting a connection from a top outlet stove directly to a steel chimney, we recommend fit­ting the chimney tube inside the flue gas spigot so that any soot and condensation drops into the stove itself rather than collecting on the ex­terior surface of the stove.
17
Page 18
345
100
Ø125
137
550
619
516
157
619
345
383
For connections to chimneys that are run through ceilings, all national and local regulations regar­ding distance to flammable material must be fol­lowed. It is important that the chimney is fitted with roof support so that the top panel of the stove is not required to bear the entire weight of the chimney (excessive weight may damage the stove).
• If the vent leads out into the open air, please note that the grille must be fitted with suitable wind protection. There must be no risk that the grille can get clogged by leaves, etc.
• The stove has been tested with 3 m of 100 mm pipe, with 3 90 degree bends.
Ventilation
2.4 Combustion air and Ventilation
The stove is approved as a room air depen stove in accordance with EN 13240. All the combustion air in the inset stove comes from the room in which it is fitted. However, by con­necting a sealed air inlet to the stove’s air intake connector, the stove can be supplied with exter­nal combustion air. In this respect, the following requirements must be met:
• Only approved materials may be used from the ventilation unit to the air inlet vent.
• The air inlet vent must be fitted correctly and insulated to prevent formation of condensate. The cross section of the vent and grille must be at least 78 cm².
dent
2.5 Stovedrawings/measurments
Adequate ventilation must be provided in ac­cordance with building regulations (Doc J Oct
2010) especially when installing in newer build properties when the stove is not going to be in­stalled to an outside air supply.
The Ambition has a nominal output of less than Ambition 5: 4,9 kW and Ambition 8: 6,5 kW and does not need additional ventilation in older properties where it will be ventilated by natural leakage.
Houses built after 2008 where the air leakage rate is less than than 5 m3 / hour / m2 then a ven­tilator equivalent to 550 mm2 per kW output will be required (4.5 kW x 550 mm = 2475 mm2) un­less the stove is connected to an outside fresh air supply.
Ambition 5
18
Page 19
Ambition 5
416
ø100
ø125 mm
138
454
416
619
619
550
516
156
550
381
345
920
345
Ambition 8
920
100
Ø125
137
817
458
19
Page 20
Ambition 8
416
457
817
550
920
Ø125
135
454
416
920
Ø125
2.6 Connecting direct air - behind
When installing external air supply, connect the air intake to the direct air pipe using flexi-pipe,
Flexi-pipe not included.
Ø 100
20
Page 21
2.7 Clearances for installation EN 13 240
Combustible material
Non-flammable substrate
Ambition
B
C
150 150
300
- Non-flammable substrate
A
B
B
D
Furnitures
The dimensions are the minimum dimensions, unless otherwise stated.
Clearances for installation EN 13 240
Stove
Minimum dimensions in mm
Ambition 5
Ambition 8
Distance to flamable materials
A rear the stove with insulation / without insulation
150/200 400
175/225 400 385 1100
B
at the sides
C
over the stove
385
D
By flammable floor material the stove must be mounted on the log store base and a non-flammable substrate.
D
to furniture
1100
21
Page 22
2.8 Changing to back outlet
1
3
4025-0007-
2
1500-001146-
4
5
6
22
Page 23
3. Data plate
Note your own number here _______________________
8058 002597-EN
Jupitervej 22 . DK-7620 Lemvig . Denmark
EN 13240:2001/A2:2004 - AEA - NS 3058/3059
Testrapport: 300-ELAB-2334-EN
SN No. 150835 06-2018 Ambition 5
Distance to combustible back wall: 200/150 mm Distance to combustible at the side wall: 400 mm Distance to furniture: 1100 mm
Average CO emission at 13% O2 0,089% Emission of CO in combustion products: 1110 mg/Nm Average flue outlet temperatur: 200 Dust: 22 mg/Nm Heat output: 4,9 kW Engery efficiency: 85% NOx 93 mg/Nm OGC 62 mgC/Nm
Fuel Wood
The stove is approved for intermittent use. Read the instructions carefully.
Heta A/S
o
C
3
3
8058 000081-EN
Jupitervej 22 . DK-7620 Lemvig . Denmark
EN 13240:2001/A2:2004 - AEA - NS 3058/3059
Testrapport: 300-ELAB-2335-EN
SN No. 150836 06-2018 Ambition 8
Distance to combustible back wall: 200/150 mm Distance to combustible at the side wall: 400 mm Distance to furniture: 1100 mm
3
3
Average CO emission at 13% O2 0,077% Emission of CO in combustion products: 968 mg/Nm Average flue outlet temperatur: 250 Dust: 27 mg/Nm Heat output: 4,9 kW Engery efficiency: 80% NOx 98 mg/Nm OGC 22 mgC/Nm
Fuel Wood
The stove is approved for intermittent use. Read the instructions carefully.
Heta A/S
3
o
C
3
3
3
DOP Ambition 5 2334-2018
Appendix A
The Clean Air Act 1993 and Smoke Control Areas
Under the Clean Air Act local authorities may declare the whole or part of the district of the authority to be a smoke control area. It is an of­fence to emit smoke from a chimney of a buil­ding, from a furnace or from any fixed boiler if located in a designated smoke control area. It is also an offence to acquire an” unauthorized fuel” for use within a smoke control area unless it is used in an” exempt” appliance (” exempted” from the controls which generally apply in the smoke control area).
In England appliances are exempted by publi­cation on a list by the Secretary of State in ac­cordance with changes made to sections 20 and 21 of the Clean Air Act 1993 by section 15 of the Deregulation Act 2015. Similarly, in Scot­land appliances are exempted by publication on a list by Scottish Ministers under section 50
DOP Ambition 8 2335-2018
of the Regulatory Reform (Scotland) Act 2014. In Wales and Northern Ireland these are autho­rized by regulations made by Welsh Ministers and by the Department of the Environment re­spectively.
Further information on the requirements of the Clean Air Act can be found here: https://www.gov.uk/smoke-control-area-rules Your local authority is responsible for implemen­ting the Clean Air Act 1993 including designa­tion and supervision of smoke control areas and you can contact them for details of Clean Air Act requirements
The Ambition 5 and 8 have been recommended as suitable for use in smoke control areas when burning dry wood logs.
23
Page 24
24
Loading...