HES 9400-605, 9400-605-LBM, 9400-605-LBSM, 9400-606, 9400-606-LBM Installation Instructions

...
HES 9400/9500/9600 Electric Strike
Installation Instructions and Frame Preparation
Product Components
A 9400/9500/9600 Strike Body
B 9400/9500/9600 Cover
C 1/4"-20 x 1" Mounting Screws
E #6-32 x 1/4" Cover Screws
F 5/64" Hex Key
G 12-Volt and 24-Volt Pigtails
Electrical Specifications
Electrical Ratings for Solenoid
Continuous Duty 12 V DC 24 VDC
Resistance in Ohms 24 96
Amps .50 .25
Diagram 1: Product Components
A
B
Solenoids are rated at +/- 10% indicated value.
Minimum Wire Gauge
Requirements
(Based on Round Trip)
200 feet or less 18 gauge 22 gauge
200 – 300 feet 16 gauge 22 gauge
300 – 400 feet 16 gauge 20 gauge
Solenoid Voltage
12 V DC 24 VDC
C
F
G
D
E
1
Installation
CAUTION Before connecting any device at the installation site, verify input voltage using a multimeter.
Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
Preparing the Strike
NOTE: For 12 VDC, the Plug In Connector (pigtail)
marked “12 VDC” should be used; for 24 VDC, the pigtail marked “24 VDC should be used.
1 SELECT the appropriate pigtail that
matches system power and electrically CONNECT as illustrated in Diagram 2.
2 IF no connector is present,
THEN CONFIGURE the wires as shown in Diagram 2.
3 IF using the Latchbolt Monitor (LBM)
or Latchbolt Strike Monitor (LBSM), THEN REFER to Diagrams 3 and 4 on Page 3 to complete wiring.
Diagram 2: 12V to 24V Conversion
or
NOTE 1: The 9400/9500/9600 ships in FAIL SECURE OPERATION mode.
NOTE 2: FAIL SAFE OPERATION mode should not be used in fire or windstorm-rated applications.
4 CONVERT the 9400/9500/9600 to
FAIL SAFE OPERATION, if needed, using Diagrams 5 and 6 on Page 3 as a guide.
Preparing the Frame
NOTE: When using a Corbin Russwin Series
5000 or Yale 7000 series equipped with an offset deadlatch, the deadlatch is located just above the Vertical Alignment line, as shown on the Installation Template on Page 4.
1 PREPARE the door jamb using
the Installation Template located on Page 4 (with the exception of the hole for final lockdown).
If Connector Is Missing
Connect Together
(+ 12 VDC)
(-NEG)
Connect Together
(+ 24 VDC)
(-NEG)
Strike
Electric
Red/green
Strike
Electric
Red/green
Red
Violet
Black
Red
Violet
Black
Connect Together
2