HES 8500 Installation Instructions Manual

Installation Instructions
8500 Series Electric Strike
Product Components
HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com
1
1
8500 Electric Strike Body
2
Horizontal Lockdown Shims
3
#4-40 Screws
12 & 24 Volt Pigtails
4
1
2
3
4
Electrical Specifications
ELECTRICAL RATINGS FOR SOLENOID CONTINUOUS DUTY
12VDC
Resistance in Ohms
Amps
Solenoids are rated at +/- 10% indicated value. *10% max duty cycle (2 min. max on time)
MINIMUM WIRE GAUGE REQUIREMENTS
200 feet or less
200 - 300 feet
300 - 400 feet
50
.24
24VDC
200
.12 .12
SOLENOID VOLTAGE
12VDC
18 gauge
16 gauge
14 gauge
INTERMITTENT DUTY*
12-16VAC
50
.24-.32
24VDC
20 gauge
18 gauge
16 gauge
24VAC
200
ASSA ABLOY, the global leader in door opening solutions
Installation Directions
CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
2
Evaluate Opening
1. Verify opening is plumb and square and evaluate latch bolt condition. For important details, see “Troubleshooting Tips” on page 3.
Prepare Strike
2. The electric strike ships in fail secure mode. If you need to convert the unit to fail safe, see Diagram 2 on page 5. Please note that operation in fail safe mode removes the fire rating of the electric strike.
Prepare Frame
3. Remove dustbox and prepare door jamb per the template detail on page 6. Be sure to allow enough room behind the electric strike in the cut out to avoid pinching the wires.
Install Deadlatch Platform
4. Select correct option. Determine platform position appropriate for the lockset (see Diagram 4 on page 5).
5. Insert deadlatch platform into the keeper slot as shown in Diagram 5 on page 5, ensuring that the screw holes in the deadlatch platform foot and outer casing are aligned. It may be necessary to slightly retract the keeper in order to properly seat the deadlatch platform fastening foot.
6. Fasten the deadlatch platform to the electric strike using
the #4-40 screw provided.
Install Strike in Frame
7. Select and electrically connect the appropriate 12 or 24 Volt pigtail to match system power as illustrated in Diagram 1 below. For 12V AC/DC or 16V AC, the pigtail marked “12 VDC” should be used. For 24V AC/DC, the pigtail marked “24 VDC” should be used. If no connector is present, configure the wires as shown in Diagram 1.
8. If using Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), see Diagram 3 on page 5.
9. Connect the 12 or 24 Volt pigtail to the electric strike.
10. Insert electric strike in jamb cutout and install the appropriate faceplate using the #12-24 screws provided. Partially tighten screws and close the door.
11. Verify lockset’s deadlatch is positioned on top of the deadlatch platform, and does not touch the faceplate. See troubleshooting tips for more information.
Set Horizontal Adjustment
12. Open the door and pull the electric strike flush with the inside face of the frame (in the direction of the opening), and tighten screws.
13. Close the door. If excessive movement (door play) or preload exists when latched, remove strike from the jamb cutout, and add one or two of the horizontal lockdown shims to the front face of the electric strike (See Diagram 6 on page 6). Ensure the horizontal lockdown shim is making contact with the inside face of the frame. Check again and add or remove additional shims until proper horizontal adjustment is achieved.
DIAGRAM 1: 12V to 24V CONVERSION
or
IF CONNECTOR IS MISSING
CONNECT
RED
VIOLET BLACK
STRIKE
ELECTRIC
RED/ GREEN
TOGETHER
(+ 12 VDC)
(-NEG)
CONNECT TOGETHER
RED
VIOLET
BLACK
STRIKE
ELECTRIC
RED/GREEN
(+ 24 VDC)
CONNECT
TOGETHER
(-NEG)