Installation Instructions
5200 Series Electric Strike
Product Components
HES, Inc.
22630 N. 17th Ave.
Phoenix, AZ 85027
800-626-7590
www.hesinnovations.com
1
1
5200 Electric Strike Body
2
Trim Enhancer (with screws)
1
1
3
12 & 24 Volt Pigtails
2
3
Diagram 1: Electrical Specifications
ELECTRICAL RATINGS FOR SOLENOID
Resistance in Ohms
Amps
Solenoids are rated at +/- 10% indicated value.
*10% max duty cycle (2 min. max on time)
Indoor use only
ASSA ABLOY, the global leader
in door opening solutions
CONTINUOUS DUTY
12VDC
50
.24
24VDC
200 50 200
.12 .24-.32 .12
INTERMITTENT DUTY*
12-16VAC 24VAC
MINIMUM WIRE GAUGE REQUIREMENTS SOLENOID VOLTAGE
200 feet or less
200 - 300 feet
300 - 400 feet
12VDC
18 gauge
16 gauge
14 gauge
24VDC
20 gauge
18 gauge
16 gauge
Installation Directions
CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter.
Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding
10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
2
Prepare Strike
1. Select the appropriate Plug In Connector that matches
system power and electrically connect as illustrated in
Diagram 2. For 12V AC/DC or 16V AC, the pigtail marked “12
VDC” should be used. For 24V AC/DC, the pigtail marked
“24 VDC” should be used.
2. Verify that the strike is in the correct mode of operation.
This unit ships in Fail Secure mode. If you need to convert to
fail safe see Diagram 5.
3. If using Latchbolt Monitor (LBM) or Latchbolt Strike
Monitor (LBSM) see Diagram 3 & 4 to complete wiring.
DIAGRAM 2: 12V to 24V CONVERSION
Prepare Frame
4. Prepare frame using appropriate template for your
faceplate (see pages 3-6).
5. Attach faceplate to strike body
Finish Installing
6. Connect wires from the power source to the strike.
7. Install the electric strike unit in jamb cutout using the
screws provided with the faceplate option kit. If horizontal
adjustment is needed, see Diagram 6.
IF CONNECTOR IS MISSING
CONNECT
RED
VIOLET
STRIKE
BLACK
ELECTRIC
RED/GREEN
TOGETHER
(+ 12 VDC)
(-NEG)
CONNECT
TOGETHER
ELECTRIC
RED
VIOLET
STRIKE
BLACK
RED/GREEN
(+ 24 VDC)
CONNECT
TOGETHER
(-NEG)
DIAGRAM 3: LATCHBOLT MONITOR DIAGRAM 4: STRIKE MONITOR
LBM WIRING
White
Orange Normally Open
Green
Common
Normally Closed
White
Orange
Green
LBSM WIRING
Brown
Normally Open
Blue
Yellow
Normally Closed
Common
Brown
Blue
Yellow