Installation Instructions
1006 Series Electric Strike
Product Components
1
1006 Electric Strike Body
2
Trim Enhancer (with screws)
1
4
HES, Inc.
Phoenix, AZ
800-626-7590
www.hesinnovations.com
3
12 & 24 Volt Pigtails
4
Keeper Shims (2, with screws)
1
3
Electrical Specications
ELECTRICAL RATINGS FOR SOLENOID
CONTINUOUS DUTY
Resistance in Ohms
Amps
Solenoids are rated at +/- 10% indicated value.
12VDC
25
.48
24VDC
100
.24
2
MINIMUM WIRE GAUGE REQUIREMENTS
SOLENOID VOLTAGE
200 feet or less
200 - 300 feet
300 - 400 feet
12VDC
18 gauge
16 gauge
14 gauge
24VDC
18 gauge
18 gauge
16 gauge
ASSA ABLOY, the global leader
in door opening solutions
Installation Directions
CAUTION! Before connecting any device at the installation site, verify input voltage and polarity of service wiring with
a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage
exceeding10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
2
Prepare Strike
1. Select the appropriate Plug In Connector that matches system
power and electrically connect as illustrated in Diagram 2. For
12V DC, the pigtail marked “12 VDC” should be used. For 24V DC,
the pigtail marked “24 VDC” should be used. If no connector is
present, congure the wires as illustrated within Diagram 2.
2. If your strike is supplied with the LATCHBOLT MONITOR (LBM),
or LATCHBOLT STRIKE MONITOR (LBSM), see Diagrams 3 & 4 for
wiring instructions.
3. For available faceplate options, see page 4.
DIAGRAM 2: 12V or 24V SELECTOR
Make sure you check polarity
prior to connecting the wires.
Prepare Frame
4. Prepare frame using appropriate template for your lockset
and faceplate combination (see page 3).
Finish Installing
5. Attach the electric strike to the jamb using the screws
provided with the faceplate option kit.
Note: The electric strike solenoid is polarized and will
only operate if the current ow from the power source
is provided in the correct direction. Identify positive
(+) and negative (-) wires from the power source and
connect to one of the pigtails as shown in Diagram 2.
Violet
(+24 VDC)
Black
(-NEG)
Red
(+12 VDC)
Black
(-NEG)
IF CONNECTOR IS MISSING
CONNECT
STRIKE
ELECTRIC
BLACK
VIOLET
RED
RED/GREEN
TOGETHER
(+ 12 VDC)
(-NEG)
CONNECT
TOGETHER
STRIKE
ELECTRIC
VIOLET
BLACK
RED/GREEN
RED
DIAGRAM 3: LATCHBOLT MONITOR DIAGRAM 4: LATCHBOLT STRIKE MONITOR
LBM WIRING
White
Orange
Green Open When
Common
Closed When
Latch Present
Latch Present
White
Orange
Green
LBSM WIRING
Brown
Blue
Yellow Closed When Locked
Common
Open When Locked
Brown
Blue
Yellow
(+ 24 VDC)
CONNECT
TOGETHER
(-NEG)