HES, Inc.Phoenix, AZ 800-626-7590www.hesinnovations.com
3
12 & 24 Volt Pigtails
4
Keeper Shims (2, with screws)
1
3
Electrical Specications
ELECTRICAL RATINGS FOR SOLENOID
CONTINUOUS DUTYResistance in Ohms
Amps
Solenoids are rated at +/- 10% indicated value.
12VDC
25
.48
24VDC
100
.24
2
MINIMUM WIRE GAUGE REQUIREMENTS
SOLENOID VOLTAGE
200 feet or less
200 - 300 feet
300 - 400 feet
12VDC
18 gauge
16 gauge
14 gauge
24VDC
18 gauge
18 gauge
16 gauge
ASSA ABLOY, the global leader in door opening solutions
Installation Directions
CAUTION! Before connecting any device at the installation site, verify input voltage and polarity of service wiring with a multimeter. Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
2
Prepare Strike
1. Select the appropriate Plug In Connector that matches system power and electrically connect as illustrated in Diagram 2. For 12V DC, the pigtail marked “12 VDC” should be used. For 24V DC, the pigtail marked “24 VDC” should be used. If no connector is present, congure the wires as illustrated within Diagram 2.
2. If your strike is supplied with the LATCHBOLT MONITOR (LBM), or LATCHBOLT STRIKE MONITOR (LBSM), see Diagrams 3 & 4 for wiring instructions.
3. For available faceplate options, see page 4.
DIAGRAM 2: 12V or 24V SELECTOR
Make sure you check polarity prior to connecting the wires.
Prepare Frame
4. Prepare frame using appropriate template for your lockset and faceplate combination (see page 3).
Finish Installing
5. Attach the electric strike to the jamb using the screwsprovided with the faceplate option kit.
Note: The electric strike solenoid is polarized and will only operate if the current ow from the power source is provided in the correct direction. Identify positive (+) and negative (-) wires from the power source and connect to one of the pigtails as shown in Diagram 2.