Herz H7990-08 Series Manual

items: working states (cool, heat or ventilation), the speed of fan coil, room
temperature,
set-point.
There
are
following
the
panel: On/Off “ , Exchange
mode (cool, heat or
ventilation) “ ”, Select fan speed (high, medium, low or auto) ,
set-
point temperature “
and “”.
H7990 adopt digital control technology with large LCD display, It shows the
following
BASIC FEATURES STATUS DISPLAY
Room temperature setting
Manual or Auto 3-speed changeover
Defrost (low temperature protection)
IR remote control (Option)
Blue Backlight (Option)
Working Status: Cool , Heat
, Ventilation
Fan Speeds: Low
, Medium
, High
and Auto. Room temperature display Temperature setting display
SPECIFICATIONS
Sensing element: NTC
Accuracy : ± 1
Set-point range: 5℃ to 35
Display range: 050
Operation environment: 045
Operating Humidity: 590%RH (non-condensing)
Power supply: AC 85260V, 50/60Hz
Switch current rating: Resistive: 2A, Inductive: 1A
Rated Power: 2 W
Wirings: Screw-in terminals, each terminal capable of
accepting 2 x 1.5 mm2 or 1 x 2.5 mm2 wires
Housing: ABS + PC Flame Retardant
Dimensions: 86 × 86 × 13 mm ( W × H × D )
Hole pitch: 60 mm ( Standard )
Protection Class: IP30
Display: LCD
OPERATION
On/Off: Press “ ” to turn on, press “ ” again to turn off thermostat and its output. Setting temperature: Press
to reduce set-point, press ” to raise set-point, and 0.5 changed once.
Mode Selection: Press “ ” to change system working in cooling , heating or ventilation mode, the related
icon will flash, and it will be confirmed automatically after 5 seconds. The ventilation function is invalid for H7990 08.
Fan Speed Selection H7990 08
:Press “ ” to change fan speed among “ (Hi)”,(Med)”, “ (Low)”
or “Auto”.
Under
auto fan speed Auto, the fan-speed will be changed automatically. Auto LOW-speed When the difference
MODEL DENOMINATIONS
H7990 08 –
R: IR remote function. Blank is invalid. (Remote controller should be ordered additionally) L: Backlight available. Blank is invalid.
Y: Control damper to open or close. DA/DA2: Control Motorized Valve (DA: Control 2-wire N.C. FCU valve; DA2: Control 3-wire FCU valve) and 3-speed
fan; When the temperature reaches the set-point, it will close the Motorized Valve with the fan still running.
DB/DB2: Control Motorized Valve (DB: Control 2-wire N.C. FCU valve; DB2: Control 3-wire FCU valve) and 3-speed
fan; When the temperature reaches the set-point, it will close the Motorized Valve and Fan both.
FCV2: Control 4 pipe fan coil units, Control two Motorized Valves and 3-speed fan, when the temperature reaches
the set-point, it will close the Motorized Valves with the fan still running.
Data sheet for H7990 08, Issue 0916
HERZ Armaturen Gws.m.b.H Richard-Strauss-Strasse 22,1230 Vienna, Austria.
1
HERZ H7990-08 Series Thermostat
H7990 Series thermostats are available for individual room temperature control
in residential, industrial and business premises. Suitable for 2-pipe or 4-pipe Fan Coil configuration.
between room-temperature and set-point exceed 1, Auto MED-speed When exceed 2
, Auto HI-speed When exceed 3.
Control Damper (H7990 Y): The damper will be
open when (1) room temperature is higher than set-point in cooling;(2)
room temperature is lower than set-point in heating, Otherwise the damper will be closed.
Control Motorized Valve under 2-pipe configuration (H7990 08 DA/DB/DA2/DB2): If the
difference between room temperature and set-point exceed 1, FCU valve will be open; if room temperature and set-point are equal, H7990 08 DA/DA2 will close the FCU valve with the fan still running, H7990 08 DB/DB2 will close the FCU valve and Fan both.
Control FCU Valve under 4-pipe configuration (H7990 08 FCV2): In cooling, when the room temperature is higher than set-point, the cooling Valve will be opened. Otherwise it will be closed. Heating valve is always closed. In heating, When the room temperature is lower than set-point, the heating valve will be opened. Otherwise it will be closed. Cooling valve is always closed.
DEF
ROST (LOW TEMPERATURE PROTECTION)
Description: when the thermostat turns off and the room temperature is lower than 5˚c, it will be turned on automatically in heating mode with “ ” showing, under H7990 08 DA/DB/DA2/DB2/FCV2 models, the system will be in heat mode and fan runs in high speed. Under H7990 08 Y model, the motorized damper will be open. The thermostat will turn off when room temperature is higher than 7˚c
Set low temperature protection: Turn off the thermostat, press “ ” and ” buttons simultaneously and hold for 3 seconds, it will display “00” or “01”, press or key to adjust. “00” indicates low temperature protection invalid, “01” indicates low temperature protection function valid. The default is “00”.
WIRING DIAGRAMS
MOUNTING
1. Open the main control panel: put the screwdriver (3.5mm) into the block 4mm along the bevel. Prize up, open the clips.
2. Take off the wires. 3. As per wiring diagram, connect it with terminals, fixed by the screwdriver.
4. Put the connected thermostat onto the back panel in the wall, then fix it with the two screws in the packing box.
5. Put the cover with 30 degree angle, then fix the up two clips.
6. Push the places of the two down clips, fix the cover, and finish the installation.
H7990 08 DA/DB
L
N
Val
Med
Low
Fan
Valve
AC85~260V 50/60Hz
N L
Hi
H7990 08Y
N
L
Damper
VC VO
AC85260V 50/60Hz
N L
H7990 08 DA2/DB2
L
N
VO
Med
Low
Fan
Valve
VC
AC85260V 50/60Hz
N L
Hi
H7990 08 FCV2
L
Cooling
N
Med
Low
Fan
Val 1
Val 2
Heating
AC85260V 50/60Hz
N L
Hi
HERZ Armaturen Gws.m.b.H Richard-Strauss-Strasse 22,1230 Vienna, Austria.