Herrmidifier Herrtronic RDU-D User Manual

Engineered Humidification Systems
Supplemental Manual
Herrtronic® RDU-D
Herrmidifier® | www.herrmidifier-hvac.com
Installation, Operation, & Maintenance Manual
TABLE OF CONTENTS
I. Warranty Information ................................................................................................................................3
II. General Description .................................................................................................................................. 3
Mounting Option .................................................................................................................................. 3
Accessory Bag Contents .....................................................................................................................4
RDU-D Dimensions ............................................................................................................................. 4
III. Installation Preparation ............................................................................................................................. 4
Unit Clearances ................................................................................................................................... 4
IV. Direct Mount Option .................................................................................................................................. 5
MDS with Direct Mount RDU ............................................................................................................... 5
MDD with Direct Mount RDU ............................................................................................................... 5
V. Remote Mount Option ................................................................................................................................ 6
MDS with Remote RDU ....................................................................................................................... 6
MDD with Remote RDU .......................................................................................................................7
VI. RDU Operation..........................................................................................................................................7
Steam Plume Chart ............................................................................................................................. 7
VII. Troubleshooting Chart...............................................................................................................................8
VIII. Parts List...................................................................................................................................................9
Exploded View.......................................................................................................................................9
IX. Wiring Diagrams........................................................................................................................................10
RDU-D with Transformer 460/600V. .................................................................................................... 10
RDU-D with Transformer 380V. ........................................................................................................... 11
RDU-D without Transformer ................................................................................................................12
MDS/MDM Control to (2) RDU-D Units ............................................................................................... 13
2 www.herrmidifier-hvac.com
Herrtronic® RDU-D Supplement
Installation, Operation, & Maintenance Manual
I. LIMITED WARRANTY
Seller warrants the equipment of its manufacturing to be free from defects in workmanship and material for a period of 24 months after shipment. This warranty is limited, however, to the repair or replacement of defective equipment, which is returned, freight prepaid, to Seller’s factory.
This limited warranty does not apply to any part or component that is damaged in transit or when handling, has been subject to misuse, negligence or accident, has not been installed, operated or serviced according to Seller’s instructions, or has been operated beyond the factory-rated capacity or has been altered in any way.
Seller’s liability is limited to replacement of defective parts or components and does not include any cost of labor (including, but not limited to, labor required to remove and/
or reinstall any defective part) other than Trion/Herrmidier
factory labor.
Trion/Herrmidier shall not be responsible for loss of use
of any product, loss of time, inconvenience, or damage to other equipment, or any other indirect or consequential damage with respect to property whether as a result of breach of warranty, neglect, or otherwise.
THE WARRANTIES AND LIABILITIES SET FORTH ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESSED OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FORPARTICULAR PURPOSE.
The foregoing shall constitute the total liability of seller in the case of defective performance of all or any of the equipment or services provided to Buyer. Buyer agrees to accept and hereby accepts the foregoing as the sole and exclusive remedy for any breach or alleged breach of warranty by Seller.
II. GENERAL DESCRIPTION
The RDU-D Series Room Distribution Units are designed as a companion module for all MD Series Herrtronic
humidiers.
The RDU may be directly mounted on top of the Herrtronic cabinet or mounted remotely. The RDU consists of a fan, controls, & steam hose to distribute the steam directly into the space. RDU-D must he remotely mounted when used
with an MDM series humidier.
Figure 1 - Mounting Options
Model No
RDU-D-1 208-240-1-50/60
RDU-D-1T 480-600-1-50/60
RDU-D-2 208-240-1-50/60
RDU-D-2T 480-600-1-50/60
Electrical
Characteristics
Capacity
5-50 lbs/hr.
60-100 lbs/hr.
RDU-D-2R 208-240-1-50/60
RDU-D-2L 208-240-1-50/60
RDU-D-2TR 480-600-1-50/60
110-250 lbs/hr.
RDU-D-2TL 480-600-1-50/60
Note: 1T & 2T models include a transformer to provide
208/230 single phase power to the RDU.
Herrtronic® RDU-D Supplement
Note: MDD Units require two RDU units. For Direct
Mount you must use a specic right and left mount unit.
For remote mount, two Identical units may be used.
For remote mounting applications, the plumbing and electrical connections may be routed through the bottom or back of the RDU. There are two electrical knockouts, two steam supply knockouts and one condensate return knockout on both the bottom and back to facilitate installation.
www.herrmidifier-hvac.com
3
Installation, Operation, & Maintenance Manual
10.05"
16.91"
15.40"
As shipped, the RDU is set up for direct unit mounting. Longer wiring and condensate return tubing (supplied) will be required for remote mounting. Be sure to use 18 gauge (minimum) copper conductor wire with insulation rated for 600 VAC. Supply power may originate from the Herrtronic
humidier or a separate supply. If a separate source is
used, be sure to install a dedicated power disconnect. All hardware and accessory components required for installation are included as listed below:
Accessory Bag Contents
Item Quantity
¾” I.D. Plastic bushing 2
3” Diameter plastic hole plug 2
5/16” I.D. Plastic bushing 1
Steam inlet union 1*
2 ½” Stainless steel hose clamp 1*
¼” x 2” Lag screw 2
#8–32 x 3/8” Stainless steel machine screw 4
Wiring Kit
¼” O.D. Condensate return tubing
1
10’
*-Double quantity for RDU-D-2 series units
III. INSTALLATION PREPARATION
! WARNING !
Disconnect power to the humidier while
installing RDU.
The RDU unit must either be placed higher than the Herrtronic unit or provisions for handling the condensate via an external drain must be made. The following chart details the physical clearances around the cabinet for servicing the unit. Figure 13 details the clearances required due to the steam plume.
MINIMUM CLEARANCES AROUND CABINET LEFT - 15” RIGHT - 15” TOP* - 2” BOTTOM - 0” * Subject to output, fan speed and room conditions
NOTE:
The steam plume should not impinge on walls,
ceilings or other objects. Supply air registers, if
present, must be directed away from RDU.
Figure 2 - Overall Dimensions
1.20"
(4) 7/8" Holes
Power Access
(2) 7/8" Holes
Optional Condensate Drain
.56"
3.00"
Figure 3 - Bottom View Dimensions
2.30"
(4) 7/8" Knockouts
Power Access
3.00"
1.00" .99"
2.45"
4.14"
5.77"
7.13" 4.00"
4.99"
.99"
Front of Unit
12.00"
12.76"
2.45"
.50"
7.70"
(2) 3" Holes Steam Hose Inlet
(2) 5/16 X 5/8 Dia. Keyhole Mounting Slots
(2) 2 1/2" Holes Optional Steam Inlets
2.50"
4 www.herrmidifier-hvac.com
Figure 4 - Back View Dimensions
Herrtronic® RDU-D Supplement
Installation, Operation, & Maintenance Manual
SIDE
REMOVE THE COVER FROM THE RDU
1. Loosen the two hex socket head set screws on the fan speed control knob and remove knob (Figure 5).
2. Remove the phillips head screws which fasten the cover to the housing.
Figure 5
PHILLIPS HEAD SCREWS (6) PER SIDE
(1) ON FRONT
Fan Speed Control Knob
IV. DIRECT MOUNT OPTION (MDS, MDD)(Figure 6 & 7)
! WARNING!
Be sure to disconnect power to the Herrtronic
Humidier before beginning installation.
1. Assure that the mounting for the Herrtronic unit will support the additional 40 pound load of each RDU unit.
2. Remove the knock-out from the top of the Herrtronic cabinet and install the 5/16” I.D. plastic bushing for the condensate return.
3. Remove the rearmost 7/8” knockout from the top of the Herrtronic cabinet.
4. Install one 3/4” plasitc bushing from the inside into the rearmost 7/8” hole in the bottom of the RDU.
5. Place the RDU on the Herrtronic cabinet, guiding the steam hose(s) into the tank compartment.
6. Feed the wires (total of seven) through the 3/4” bushing and condensate tubing through the 5/16” bushing into the Herrtronic unit.
7. Fasten the RDU in place using four #8-32 self-tapping screws installed from inside the Herrtronic cabinet.
8. Replace the RDU cover & fan speed control knob.
9. Insert the condensate return tubing into the grey
plastic ll tee. It will extend I” into the tee.
10. Connect wires # 1 -6 to the 6 pole RDU terminal strip located near the top of the Herrtronic high voltage electrical compartment. Connect the ground wire #24 to the Herrtronic ground terminal located near the bottom of the high voltage compartment.
Installation is now complete. Proceed to the RDU Operation section of this manual then to the Start-Up section of the Herrtronic Installation and Operation Manual OM-93.
HERRMIDIFIER
CYL FULL
FAULTPOWER
ON/OFF
BACK
ENTERFAULTS
HERRTRONIC MD
HERRMIDIFIER
Figure 6 - MDS Direct Mount
HERRMIDIFIER
HERRMIDIFIER
SLAVE
CYL FULL
ON/OFF
FAULTS
MASTER
CYL FULL
ON/OFF
FAULTS
HERRTRONIC MD
HERRMIDIFIER
FAULTPOWER
BACK
ENTER
FAULTPOWER
BACK
ENTER
NOTE
See Figure 15, 16 & 17 for standard electrical hookup
for MDM and MDS.
11. Remove jumper wire #39 from the Herrtronic 12 pole controls terminal strip located in the low voltage electrical compartment between poles #1 and #2.
Herrtronic® RDU-D Supplement
Figure 7 - MDD Direct Mount
www.herrmidifier-hvac.com
5
Installation, Operation, & Maintenance Manual
V. REMOTE MOUNT OPTION (MDM, MDS, MDD)
1. The RDU may hang directly on a wall using the two 1/4” x 2” lag screws included. There are two key-hole slots on the back of the cabinet which engage these screws. Be certain that: 1) the screws are fastened securely enough to the wall to support the 40 lbs. weight of each RDU unit, and 2) the screws are level. Turn the screws in until the heads are 1/8” away from the mounting surface.
2. Hang the unit on the wall and tighten the two lag screws.
3. The steam hose(s) is to be connected using the steam inlet union(s) (Figure 8).
4. Trim the steam hose(s) which is connected to the RDU
manifold so that it ts properly onto the union(s) and
secure connections with a hose clamp(s).
5. Fasten steam inlet union(s) to bottom or back of RDU cabinet with screws.
6. Remove the knockout from the top of the Herrtronic cabinet and install the 5/16” I.D. plastic bushing (included).
7. Remove the 18” piece of condensate return tubing connected to the manifold elbow.
8. Uncoil the 10’ piece of condensate return tubing (drain line), feed into the RDU cabinet, from the bottom or back, and connect to the manifold elbow.
9. Run the condensate return tubing down into the Herrtronic cabinet through the 5/16” I.D. plastic bushing.
10. The condensate tubing can be attached to the steam hose or electrical conduit interconnecting the RDU and Herrtronic with cable ties or equivalent.
11. After the condensate tubing is secured, insuring that there are no kinks or low spots, the length should be
trimmed so that it can extend 1” into the grey plastic ll
tee in the Herrtronic unit.
12. National, state or local electrical codes may require the use of two separate conduits - one for high voltage supply power and one for control wiring.
13. There are a total of seven wires which are to be connected between the RDU and the Herrtronic unit. The RDU receives all of its power and control from the Herrtronic unit. Use the two 7/8” holes or knockouts on the bottom or back of the RDU cabinet and the two 7/8” knockouts on the top of the Herrtronic cabinet for wiring conduit.
14. Wires #3 and #4 are the high voltage power supply and should be run in one conduit.
15. Along with the ground wire #24, wires #1, #2, #5, and #6 should be run in the second conduit.
16. Connect wires # 1-6 to the 6 pole RDU terminal strip located near the top of the Herrtronic high voltage electrical compartment. Connect the ground wire #24 to the Herrtronic ground terminal located near the bottom of the high voltage compartment.
NOTE
See Figure 15, 16 & 17 for standard electrical hookup
for MDM and MDS.
17. Remove jumper wire #39 from the Herrtronic 12 pole controls terminal strip located in the low voltage electrical compartment between poles #1 and #2.
18. Replace the RDU cover and the fan speed control knob.
Installation is now complete. Proceed to the RDU operation section then to the start-up section of the Herrtronic Installation, Operations and Service Manual OM-93.
BLOWER
STEAM HOSE
DRAIN LINE
STEAM INLET UNION (REMOTE MOUNT)
STEAM INLET UNION (ALTERNATE LOCATION)
Figure 8 - Steam Connections (Side View)
GRILL
DRAIN LINE
Figure 9 - Drain Line (Front View)
>50 lb/hr requires second hose
CYL FULL POWER FAULT
ON/OFF
BACK
FAULTS ENTER
HERRTRONIC MD
Figure 10 - MDS Remote Mount
6 www.herrmidifier-hvac.com
Herrtronic® RDU-D Supplement
Installation, Operation, & Maintenance Manual
Once operating, the fan speed can be adjusted continuously from 1—5 (slow—fast) by turning the fan speed control knob. Refer to the chart below for the optimum fan speed setting for your application.
When the Herrtronic unit is turned “off”, either by switch or controller, the RDU fan will continue to operate for 15 minutes to prevent the formation of condensate inside the cabinet. The steam plume direction can be controlled both horizontally and vertically by adjusting the louvers on the air discharge grille.Louvers adjusted as shown in Figure 12 produce the most consistent and shortest evaporation distance.
OPTIMUM LOUVER
HERRTRONIC MD
Figure 11 - MDD Remote Mount
DIRECTION, DOWN 30°
DRAIN LINE
STEAM HOSE
VI. RDU OPERATION
Upon starting the Herrtronic unit, the RDU fan will be
energized. If airow is not sensed within ten seconds, the
Herrtronic unit will shutdown and a fault will be registered.
STEAM INLET UNION (REMOTE MOUNT)
Figure 12 - Louver Details
Depress ‘”Fault” button to conrm fault condition and clear
fault by pressing “Enter” and then “Back” button to return to Menu 1.
STEAM PLUME (@75° F, 55% R.H.)
Output
lbs./Hr
1
(210)2 (240)3 (280)4(320)5 (365)1 (210)2 (240)3 (280)4(320)5 (365)1 (210)2 (240)3 (280)4(320)5 (365)
10 20 15 15 15
20 50 35 30 35 35 20 20 18 18 18
30 90 80 75 70 60 28 26 24 24 24 10
40 98 92 90 94 100 36 36 36 32 26 18 12 6
50 112 112 116 120 120 40 36 36 36 30 36 22 12 6
60 120 126 130 134 36 34 28 28 58 30 14 6
70 126 132 138 42 40 36 36 20 12
80 130 138 156 48 42 40 52 24 16
90 136 144 156 58 52 46 72 36 20
100 126 138 156 60 60 48 120 50 25
Throw (in.)
Blower Speed (CFM)
Breadth (in.)
Blower Speed (CFM)
Rise (in.)
Blower Speed (CFM)
BLOWER
Figure 13 - Steam Plume Characteristics
To avoid potential contact with steam, be certain to shut off the Herrtronic unit BEFORE
Herrtronic® RDU-D Supplement
! WARNING!
adjusting the louvers.
www.herrmidifier-hvac.com
7
Installation, Operation, & Maintenance Manual
VII. TROUBLESHOOTING
Problem/Symptom Reason / Correction
Steam Condensing on RDU sheetmetal or other objects. 1. Adjust louvers per gure 12
2. Fan not running. Check pressure switch for fail closed condition. Herrtronic unit should not operate if fan is not running.
3. Too little airow. Increase fan speed.
4. Room is very cold, very humid, or objects are cold. Decrease humidity setpoint at Herrtronic unit or humidity controller.
Fan not energizing 1. Check that the fan rotates freely.
2. Check fuses in RDU.
3. Check wiring to fan.
4. Check voltage to fan - should be 220 VAC +/- 10%.
5. Replace fan and capacitor.
Fan speed adjustment not working. 1. Replace rheostat.
Water spitting out of manifold 1. Check condensate drain hose. If it is clogged, clean.
2. Make sure condensate drain hose is sloped properly and there are no low spots or kinks.
Fan does not continue to operate for 15 minutes after Herrtronic unit shuts down.
Air pressure switch not closing. 1. Fan speed setting too low. Increase fan speed.
Blown fuses in RDU 1. Check fan for short circuit.
1. Check wiring to relay/timer.
2. Check that the 24 VAC is present between terminal #2 and #3 on relay timer. If so, replace timer.
2. Check tubing on switch for clogging or out of position.
3. Faulty air pressure switch. Replace.
2. Check RDU wiring for short circuit.
8 www.herrmidifier-hvac.com
Herrtronic® RDU-D Supplement
Installation, Operation, & Maintenance Manual
1847C Quick Connects EST-1404 Rheostat
120096-006 Hole Plug EST-1405 Relay Timer
165475-001 Dierential Pressure Switch Kit EST-1407 Blower Speed Control Knob
165538-001 Fuse, 8/10 A EST-1408 Capacitor
265544-001 Fuseholder EST-1409 Bushing
265561-001 Transformer (RDU-D-1T & 2T) for 480/600 EST-1415 1/4” Tubing
265561-002 Transformer (RDU-D-1T & 2T) for 380 EST-1416 Fuseholder
DH-052 Foam Tape EST-1417 Fuse, 1 A
EST-230 Steam Hose EST-1447-1
EST-353 Bushing
EST-1447-2
EST-531 5-Pole Terminal Rail EST-1458 Steam Inlet Union
EST-1401 Distribution Grille EST-1538 Rubber Grommet
EST-1402 Blower EST-1563 Stainless Steel Hose Clamp
EST-1403 Blower Inlet Ring GT-20-20 Elbow
Manifold Assembly (Specify Unit Model Number)
EST-1401
EST-1447
DH-052
DH-052
GT-20-20
EST-1404
EST-1407
EST-230
EST-1563
EST-353
EST-1415
265544-001
1847C
EST-531
165475-001
165538-001
EST-1417 EST-1416
120096-006
265561
EST-1538
EST-1402
EST-1403
EST-1405
EST-1409
1847C
EST-531
EST-1408
Herrtronic® RDU-D Supplement
Figure 14 - Exploded View
EST-1458
www.herrmidifier-hvac.com
9
Installation, Operation, & Maintenance Manual
Figure 15 - RDU-D with 460/600V Transformer
H2 FOR 460V INPUT H3 FOR 600V INPUT
10 www.herrmidifier-hvac.com
Herrtronic® RDU-D Supplement
Installation, Operation, & Maintenance Manual
Figure 16 - RDU-D with 380V Transformer
Herrtronic® RDU-D Supplement
www.herrmidifier-hvac.com
11
Installation, Operation, & Maintenance Manual
Figure 17 - RDU-D w/o Transformer
12 www.herrmidifier-hvac.com
Herrtronic® RDU-D Supplement
Installation, Operation, & Maintenance Manual
Figure 18 - MDS/MDM Control to (2) RDU-D Units
Notes:
1. Disconnect wire number (16) from the common terminal of the differential pressure switch in the RDU-D unit number (2). Remove the spade connector and cap with a wire nut.
2. Disconnect Blue wire number (5) from terminal strip number (1) on RDU-D unit number (1) remove the spade connector and cap with a wire nut.
3. This wire is connected to RDU-D unit number (1) at terminal strip number (1). Position number (4) to the RDU-D number (2) common terminal of the differential pressure switch.
Herrtronic® RDU-D Supplement
www.herrmidifier-hvac.com
13
Engineered Humidification Systems
Herrmidifier
®
101 McNeill Rd. | Sanford, NC 27330
P: 800.884.0002 | F: 800.458.2379 | www.herrmidifier-hvac.com | cs@herrmidifier-hvac.com
Form No. OM-102 09/13 ©Herrmidier 2013. All Rights Reserved.