Herrmidifier Drain Tempering Reservoir User Manual

Engineered Humidification Systems
READ & SAVE THESE INSTRUCTIONS
Drain Tempering Reservoir
Installation, Operation, & Maintenance
Herrmidifier® | www.herrmidifier-hvac.com
TABLE OF CONTENTS
Warranty ...............................................................................................................................................3
Introduction ........................................................................................................................................... 4
Operational Characteristics ..................................................................................................................4
Operating Sequence ............................................................................................................................. 4
Installation Instructions .........................................................................................................................4
Adjusting the Temperature Actuated Valve ........................................................................................... 5
Replacement Parts ...............................................................................................................................5
2 www.herrmidifier-hvac.com
Drain Tempering Reservoir
I. WARRANTY
Limited 2-Year Warranty
Seller warrants the equipment of its manufacturing to be free from defects in workmanship and material for a period of 24 months after shipment or 24 months after initial commissioning,
whichever occurs rst. This warranty is limited, however, to the
repair or replacement of defective equipment, which is returned, freight prepaid, to Seller’s factory.
This limited warranty does not apply to any part or component that is damaged in transit or when handling, has been subject to misuse, negligence or accident, has not been installed, oper­ated or serviced according to Seller’s instructions, or has been operated beyond the factory-rated capacity or has been altered in any way.
Seller’s liability is limited to replacement of defective parts or components and does not include any cost of labor (including, but not limited to, labor required to remove and/or reinstall any
defective part) other than Trion/Herrmidier factory labor.
Each of the Herrtronic series of steam generating humidiers
contains a plastic steam generating cylinder that is to be consid­ered a routinely disposable part to be changed at regular main­tenance intervals at the user’s expense. This steam generating
cylinder is not covered by this Warranty. If, after the rst instal­lation of your Herrtronic humidier, you feel the steam generat-
ing cylinder is not operating normally, you should contact your
Herrmidier Representative with an explanation of the problem. However, in the continuing operation of this humidier, replace-
ments of this part are your responsibility as part of routine main­tenance.
Trion/Herrmidier shall not be responsible for loss of use of
any product, loss of time, inconvenience, or damage to other equipment, or any other indirect or consequential damage with respect to property whether as a result of breach of warranty, neglect, or otherwise.
THE WARRANTIES AND LIABILITIES SET FORTH ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EX­PRESSED OR IMPLIED, IN LAW OR IN FACT, INCLUDING IM­PLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE.
The foregoing shall constitute the total liability of seller in the case of defective performance of all or any of the equipment or services provided to Buyer. Buyer agrees to accept and hereby accepts the foregoing as the sole and exclusive remedy for any breach or alleged breach of warranty by Seller.
Drain Tempering Reservoir
www.herrmidifier-hvac.com
3
II. INTRODUCTION
Herrmidier’s Drain Tempering Reservoir mixes cool supply water with hot discharge water from steam humidiers to
ensure drain water temperatures are below the limits that may be set for municipal sewer systems and by local/state
plumbing codes. Herrmidier’s Drain Tempering Reservoir
may be used if municipalities prohibit draining water hotter than 140 °F (60 °C) into their sewer systems. PVC drain pipes are susceptible to damage from excessively hot drain water. The Drain Tempering Reservoir may replace or supplement the drain tempering feature available on Herrtronic steam
humidiers. When used with the Herrmersion RE, the Drain
Tempering Reservoir can successfully temper hot discharge water from the skimming port. The integral mounting bracket
simplies installation.
III. OPERATIONAL CHARACTERISTICS:
Hot drain water being discharged from a humidier enters
the Drain Tempering Reservoir through the top threaded
connection. The vacuum breaker prevents backow into
potable water systems. Cold supply water enters through the temperature-actuated valve and mixes with the hot drain water. The sensing bulb, located inside the reservoir, ensures that water leaving the Drain Tempering Reservoir is 140 °F (60 °C) or less before entering the buildings drain system.
water leaving the reservoir is less than the temperature that the valve is adjusted to. Most municipalities set this limit at 140 degrees Fahrenheit. Tempered water exits the reservoir through the side outlet which is connected to the drain piping. The horizontal orientation allows for the drain piping to be pitched.
V. INSTALLATION INSTRUCTIONS:
IV. OPERATIONAL SEQUENCE:
HOT WATER
INLET
VACUUM
ACTUATED
COLD WATER
INLET
CAPILLARY
TUBE
VALV E
BREAKERTEMPERATURE
TEMPERED WATER
OUTLET
Hot water discharged from a humidier enters the drain
tempering reservoir through the piping connected to the threaded connection on the top. The vacuum breaker
prevents backow.
Cold water enters the reservoir through the temperature actuated valve. The valve sensor is located in the bottom of the reservoir near the discharge port. This ensures that the
1. Mount the Drain Tempering Reservoir to the wall or a bracket using the integral mounting holes.
2. Verify that the maximum ow rate of hot water into the Drain Tempering Reservoir will not exceed 6 gallons per minute.
3. There are three piping connections that need to be made to the Drain Tempering Reservoir:
Cold Water Supply
Hot Water Inlet
Tempered Water Drain Outlet
4. Position the Drain Tempering Reservoir to allow the most direct path of piping. This will allow a minimal use
of pipe ttings.
5. Install unions as close to the Drain Tempering Reservoir as is practical. This will allow service personnel to easily remove the unit for maintenance and cleaning.
6. Cold Water Supply:
The cold water supply connection is 3/8” female
pipe thread.
Connect a 3/8” water line directly into the valve from
4 www.herrmidifier-hvac.com
Drain Tempering Reservoir
the main water supply.
Ensure that adequate pressure (25 psi minimum) will be supplied to the Drain Tempering Reservoir. Do not use water lines that are dedicated to other appliances.
Do not branch off of the water supply line that feeds the humidier.
Install a cold water shut off valve before the service
union in the supply line.
7. Hot Water Inlet Connection:
The hot water inlet connection is 1” male pipe thread.
Run a 1” pipe as directly as possible to the reservoir
hot water inlet. If the piping is coming from a horizontal run, ensure that adequate pitch to the Drain Tempering Reservoir is at least 1% (1/8” per foot).
8. Tempered Water Drain Outlet:
The tempered water drain outlet is 2” male pipe thread.
Run a 2” pipe as directly as possible from the Drain Tempering Reservoir to the drain. Ensure that adequate pitch to the drain is at least 1% (1/8” per foot).
Make sure to leave a 1” air gap between the drain piping and the drain.
Once installed, simply open the cold water shut off valve. The Drain Tempering Reservoir will temper the drain water whenever hot water from
the humidier enters the reservoir. No electrical
connections are necessary.
.VII. REPLACEMENT PARTS:
5
6
4
2
1
3
.
Item Description Part Number
1 Drain Tempering Tank Welded Ass’y 266514-001
2 Vacuum Relief Valve 166524-001
3 Pipe Elbow, Brass (1/4”) 266207-001
4 Nipple, Schedule 40, 1/4” MPT AH-166-4
5 Reducing Bushing, 1/4” To 3/8” 143903-004
6 Temperature Actuated Mounting
Valve
266534-001
VI. ADJUSTING THE TEMPERATURE ACTUATED VALVE:
Using a thermometer to measure the tempered water discharging from the unit, turn the adjusting screw to raise or lower the temperature. Raising the valve opening point will increase the tempered water temperature. Lowering the valve opening point will decrease the tempered water temperature. To raise the valve opening point on direct­acting valves, turn the adjusting screw counterclockwise. To lower the valve opening point, turn the range adjusting screw clockwise..
Drain Tempering Reservoir
www.herrmidifier-hvac.com
5
Engineered Humidification Systems
Herrmidifier
®
101 McNeill Rd. | Sanford, NC 27330
P: 800.884.0002 | F: 800.458.2379 | www.herrmidifier-hvac.com | cs@herrmidifier-hvac.com
Form No. OM-DTR 0612 ©Herrmidier 2012. All Rights Reserved.