0. Table of contents .................................................................................................................................. 2
1 . I n t r o d u c t i o n ............................................................................................................................... 6
1.1 Using the device 7
2. Version history ...................................................................................................................................... 8
3. Used abbreviations and designations ................................................................................................... 8
4. General instructions .............................................................................................................................. 9
4.1 Objective of the product manual 9
4.2 Warranty and liability 9
5. Safety instructions and warnings ........................................................................................................ 10
These operating instructions correspond with the "Radio and Telecommunications
Terminal.Equipment Act and Directive 2014/53/EU (RED) "
These operating instructions are intended for the operator who must pass these on to the personnel
responsible for installation, connection, use, and repairs of the machine.
The operator must ensure that the information contained in these operating instructions and in the
accompanying documents has been read and understood.
The operating instructions must be kept at a known place that is easy to reach, and they must be
consulted if there is the slightest doubt.
The manufacturer assumes no responsibility for damage to persons, animals, or objects or to the
unit itself arising from the improper use or the disregard or insufficient consideration to the safety
criteria contained in these operating instructions or based on modifications of the unit or the use of
unsuitable replacement parts.
The copyright for the operating instructions lies solely with
HERMOS AG
Track & Trace - RFID Division Gartenstr. 19
95490 Mistelgau
or its legal successor.
Reproduction or circulation of this document to third parties only by express written permission of
copyright holder. This also applies if only excerpts of the document are copied or circulated.
These same conditions apply to the disclosure of the document in digital format.
The device is exclusively used to read and write passive LF transponders.
Any other use of the machine or any use beyond its intended purpose is considered non-intended
and thus improper.
In this case, the device safety and the device protection provided may be compromised. HERMOS
AG is not liable for damages resulting from such use.
The device was developed for the use in an industrial environment as a built-in device in other
systems. It was not developed as a stand-alone or mobile device in a non-industrial environment,
such as dome- stic, vehicle or open air use.
Intended use also includes the following:
• Following all the operating instructions
• Following all the safety instructions
Improper use, which can endanger the unit, the user and third parties, include:
• The use of the device contrary to its intended use
• Changes to the device as well as attachments and conversions
• Operating the unit when there are obvious problems
WARNING
Danger of injury due to unauthorised modifications
There are risks from unauthorised modifications on the device.
Only original spare parts from the manufacturer must be used. No
modification, attachment or conversion may be performed on the device
WARNING
without the permission of HERMOS AG.
Danger of injury and interruption of operation due to improper use
There are risks through the improper use of the device.
The device must only be used according to its intended use.
All previous versions of this document lose their validity with the issue of this version.
We compiled the information in this document according to the best of our ability.
HERMOS AG does not guarantee the accuracy and completeness of the information
provided in this document and is also not liable for consequential damages based on
faulty or incomplete information.
4.1 Objective of the product manual
The product manual serves as support and contains all the necessary information
that must be followed for general safety, transport, installation and operation.
The product manual with all safety instructions (as well as all additional documents) must be:
•Followed, read and understood by all persons working with the unit (especially
knowledge of the safety instructions)
• Easily available at all times to all persons
• Consulted if even the slightest doubt arises (safety)
Objectives:
• Prevent accidents
• Increase the service life and reliability of the unit
• Reduce the costs of production downtime
4.2 Warranty and liability
The „General Terms and Conditions of Sale and Delivery“ of HERMOS AG shall apply.
The warranty period is 24 months beginning with the delivery of the device, which is
verified by the invoice or other documents.
The warranty includes repairs of all damages to the unit that occur during the warranty
period, and were clearly caused by material or manufacturing defects.
Warranty and liability claims in the event of personal injury or property damage are
excluded if they arise from one or more of the following causes:
• Improper use of the unit
• Disregarding the information in the operating instructions
• Unauthorised structural modifications of the unit
• Insufficient maintenance and repairs
• Disaster events due to impact with foreign objects or force majeure
Follow the general safety instructions as well as special safety instructions included
in the chapters.
The unit was built according to state-of-the-art technology and recognised safety regulations. In
order to prevent danger to life and limb of the user, third parties, or the unit, only use the unit for its
intended purpose and in perfect condition with regard to safety.
Bodily injuries and/or property damages resulting from non-compliance with the
instructions pro- vided in the operating instructions are the responsibility of the
company operating the unit or the assigned personnel.
Faults that may compromise safety must be eliminated immediately.
DANGER
Risk of death, injury and property damage.
There is a risk of danger due to disregard of the product manual and
the safety information contained therein.
Read the product manual carefully before putting the unit into
operation for the first time. Fulfil all required safety conditions.
5.2 Safety symbols - according to DIN 4844-2
The following special safety symbols in accordance with DIN 4844-2 are used at the
corresponding passages in the text of this product manual and require special attention
depending on the combi- nation of the signal word and symbol.
DANGER
Risk of injury due to disregarding the safety symbols.
Risks exist when disregarding warnings in the
operating instructions. Follow all warnings.
A safe condition and use of the unit is a requirement for a safe operation of the unit. For that reason, the operator has the obligation to ensure that the following points are adhered to:
The unit may only be operated by trained and authorised personnel.
Prohibit unsafe or dangerous working methods! If necessary, check the conduct
and actions of its personnel!
Have personnel who must be trained, instructed or within the scope of general
training work only on the unit under the supervision of an experienced person!
Have the personnel confirm by their signature that the operating instructions have
been understood!
Precisely establish responsibilities according to the various task
areas (operation, installation)!
Operating personnel must be required to immediately report any occurring and
identifiable safety deficiencies to their superior!
The operating personnel are obligated to contribute to the prevention of work accidents and their
consequences by their personal conduct.
WARNING
5.3.3 ESD Instructions
CAUTION
Risk of injury due to insufficient personnel qualifications
There are dangers to personnel and the proper operation due to
inadequately qua- lified personnel.
Only trained personnel may operate the unit.
New operating personnel must be instructed by the existing operating
personnel. The operator must precisely regulate the personnel’s areas
of responsibility, com- petence, and monitoring precisely.
The personnel for the areas of responsibility mentioned above must
have the corresponding qualification for this work (training, instruction).
If necessary, this can be done by the manufacturer on behalf of the
operator. In case of disregard, all warranty claims are void.
Static electricity can damage electronic components in the unit. All
persons who install or maintain the unit must be trained in ESD
protection.
Disconnect the power supply prior to removing or adding components!
Observe the basic principles of ESD protection
Take the appropriate ESD precautionary measures
ESD protective measures must be applied when opening the unit.
Despite all precautionary measures taken, there may still be residual risks that are not apparent.
Adhering to the safety instructions, the intended use, and the product manual as a whole can re- duce
residual risks.
DANGER
Danger caused by electrical current
Electrical residual energy remains in lines, equipment and devices after
shutting down the device.
Only qualified electricians may perform work on the electrical supply system.
ATTENTION
DANGER
WARNING
Disconnect the unit from the power supply system if active parts of the unit
can be accessed using tools. Access is only permitted by authorised
personnel.
Regularly check the electrical equipment of the unit. Regularly check all
moving cables for damage within the scope of maintenance and repair work.
Dangers of fire and explosion
There is a risk of fire and explosions in the vicinity of the device.
Smoking, exposed flames and fire are strictly prohibited in the vicinity of the unit.
Do not store any flammable liquids within the hazardous area of the device.
A fire extinguisher must be kept in the vicinity of the device.
Warning of electromagnetic radiation
Electromagnetic radiation develops when transmitting and receiving data. Arrange
the antenna in such a position that it is not in the vicinity or make
contact with the human body while transmitting.
The device satisfies the standard EN50364:2010 (Human Exposure).
Read and understand all safety and operating instructions prior to installing and operating
the device.
This documentation was written for specifically trained personnel. The installation,
operation and error handling may only be carried out by specifically trained personnel.
Keep these instructions. Keep this documentation in a location that is accessible to all
personnel involved with the installation, use, and error handling of the device.
Follow all warnings. Follow all warnings on and in the device and in the documentation.
Install the unit only in accordance with the manufacturer‘s instructions.
Use only the accessories and cables from the manufacturer.
Troubleshooting that is not described in the chapter a service and troubleshooting may
only be performed by the manufacturer.
When connecting cable connections, only pull on the plug and not on the cable.
Only use spare parts specified by the manufacturer.
The provisions of the accident-prevention regulations of the government safety organisations
always apply to all work on the unit.
Applicable binding regulations at the place of use
Technical standards for safety and professional work
Existing environmental protection regulations
Other applicable regulations
5.5.1 Regulations and certifications
The electrical design and documentation satisfy the DIN / VDE, EN / IEC regulations.
LF reading devices are radio frequency identification systems that use radio transmission to read
or write data of LF transponders (134,2 kHz), which operate as tamper-proof electronic tags. The
LF reading devices communicate with common transponders (134,2kHz) according to ISO 18000-2
and ISO 11785 that are available on the market.
The data is transmitted via the existing interface with the preset transmission parameters. If several interfaces are available and connected to the host, the transmission is always carried out on the
most recently used interface. The data is embedded in a defined communication protocol and
exchanged between the reader and host.
6.2 Basic functions - operating modes
During normal operation, the LF reading device supports various basic functions:
• Heartbeat function, software version query
• Scanning of transponders in the antenna area (UID)
• Reading data
• Writing data
• Locking data
• Setting and reading out parameters
• Setting and querying inputs and outputs
The LF devices can be set in 3 other operating modes by setting the parameters: Polling operation
(optional), sensor-triggered automatic reading and test mode.
6.2.1 Normal operation
During normal operation, the LF reading device is immediately ready for operation after a reset. It
does not perform any automatic actions in this mode (standby). During normal operation, actions are
triggered by protocol commands from the host.
A scanning procedure or reading in the data area is initiated by a command of the host system
using the communication protocol.¬
In addition to the actions triggered by the host, a corresponding message can be automatically sent
to the host and an automatic reading operation can be started by activating or releasing a sensor.
When the reading operation is successful, the read data is immediately transmitted to the host. If
several antenna ports are occupied simultaneously, the reading operations are processed sequentially.
Writing actions (data saved to a transponder) are generally only possible via commands from the
host.
6.2.2 Polling mode
LF reading devices can be set into a continuous reading state, which is referred to as
polling mode. The device then performs reading operations at regular intervals and
outputs the corresponding data of the read LF transponder.
The reading device also continues carrying out protocol messages in polling mode. This
may, however, result in delays in the poll rhythm. The polling functionality is optional
customer-specific available!
The HERMOS LF reading devices support a test mode that facilitates setting up the antenna and
checking the reading ranges during commissioning. HF reading devices feature several DIP switches on the housing. These switches can be used to activate test mode.
The functions in test mode are described on a sticker located on the reading device housing. The
evaluation of the DIP switch depends on parameters
If the device is in test mode, the red status LED flashes at about 1 Hz. The yellow status LED then
indicates the status of the test mode. If the read or write process was unsuccessful, the yellow LED
flashes at the read or write frequency. If the read or write process is successful, the yellow LED
remains permanently lit.
With the existing I / O module, HERMOS LF readers with ASC-W1 protocol also show the successful or incorrect reading of the transponder at the respective first output port. See also behavior of
the output ports in test mode.
Three-pin socket for the connection of the 24V DC power supply.
Power-LED
The power LED indicates that the operating voltage is present and
the rea- ding device is ready for operation.
Status-LEDs
The two status LEDs are used for the reading and writing feedback in
test and polling mode. If the device is in test mode, the red status
LED flashes at about 1 Hz. The yellow status LED then indicates the
status of the test mode. If the read or write process was
unsuccessful, the yellow LED flas- hes at the read or write frequency.
If the read or write process is successful, the yellow LED remains
permanently lit.
In normal operation, if an error occurs, the display of this
occurs via the red LED:
Red LED constantly on: read error (no tag)
red LED flashing rapidly: antenna error (tuning, cable
break). This display will reset automatically with the next
valid reading.
After a restart, a short self-test of the LEDs, then display of the
protocol: SECS: The red LED goes on briefly
ASCII: The yellow LED goes on briefly
DIP-switch
DIP-switch 4 starts an automatic antenna
tuning. DIP-switch 3 activates a test
mode.
DIP-switch 1 and 2 serve the antenna selection.
Ethernet interface
The reading device features an Ethernet interface depending on the
de- vice model. The communication with the device can be carried
out via the 10/100 BaseT interface.
RS232 interface
Depending on the device model, the reading device features a RS232
in- terface. The communication with the device can be carried out via
the serial interface (9-pin Sub D)
The device label is located on the reading unit housing.
It contains a CE mark, article/serial number and the MAC address.
1. Designation
2. Article number (variants)
3. Serial number (example)
4. MAC address
5. Manufacturer
6.4.3 Device Label FCC ID 2AP5OLFM-4X
FCC
- The Federal Communications Commission (FCC) warns the users that changes or
modifications to the unit not expressly approved by the party responsible for compliance
could void the user's authority to operate the equipment.
RF exposure statement (mobile and fixed devices)
This device complies with the RF exposure requirements for mobile and fixed devices. However, the
device shall be used in such a manner that the potential for human contact during normal
operation is minimized.
- FCC §15.105 (a):
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
3 off: Start Antenna Tuning
3 on: Off-Read / On-Write
Testmode on/off
2 3 4
off on on
on off on
1
2
3
4
DIP Switches
DIP /Ant Port: 1
6.4.4 Test mode sticker
The device label is located on the reading unit housing.
By setting the DIP-switch3 the test mode is activated.
The test mode read or write is set with the DIP switch 4.
The selection oft he antenna port is changed by the DIP
switched 1 and 2.
The unit is exclusively designed for indoor use in an industrial
environment. The unit may only be installed indoors with a temperature
and humidity level with in the range of the specified technical module
parameters.
Never use the unit near or in water.
Never pour liquids of any type over the unit. However, if the unit
should still come in contact with liquid, disconnect it and have it
checked by a technician.
Do not install the device near heat sources such as radiators, heat
regis- ters, stoves or other devices (including amplifiers) that
generate heat.
Do not install the unit in a flammable environment.
Never expose the device to extreme temperature fluctuations,
since con- densation otherwise develops inside the unit and
causes damages.
Do not install the device in the vicinity of voltage lines or other power
lines with which they could collide (for example, drilling), which could
result in serious injuries or even death.
The device (especially the antenna) should not be installed in the
immediate vicinity of electrical equipment such as medical
devices, monitors, telephones, TV sets and magnetic disks, and
metal objects.
This could result in reduced read and write ranges.
Never use the unit in explosive areas (such as paint warehouses).
Do not use the device in areas where it is exposed to vibrations or
shocks.
The installation location must be adequately illuminated during the
installation.
Never install the unit during a lightning storm.
7. Installation
Follow the basic safety instructions in the chapter Safety instructions.
Make sure that the installation meets the requirements of the FCC
(country specific) for human exposure to radio frequencies.
The unit must only be installed by specially trained personnel. If you
have any doubts about the qualifications, please contact the
manufacturer.
If the unit is operated by untrained personnel, the reading
device and or connected devices may be damaged.
The packaging material consists of cardboard and foil.
Dispose of these materials separately under the respective
regulations of your country.
7.2 Qualified installation personnel
7.3 Unpacking
The LF reading device and the accessories can be packed customer-dependent in clean room
conditions. In order to maintain this condition, the devices must be unpacked in clean room conditions.
The mounting surface must be stable, non-flammable, dry and
clean. If necessary, clean it before you install the device.
Only use components, cable and mounting materials provided by
HERMOS.
Only mount the components at the designated locations and make
sure that the operating and ambient conditions specified in the
technical data are always maintained.
When installing the antenna, observe the required reading and
writing ranges. The reading device can only be used properly
if the transponder is located within the reading and writing range of the
antenna.
7.5 Installing the antenna
7.5.1 Positioning the antenna
The removal and alignment of the transponder tot he antenna is critical to ensure reliable
reading and writing. The following diagram displays the optimum alignment and position of
the transponder to the antenna. After positioning, the antenna must be tuned to the
ambient conditions.
The tuning function can be started with the DIP switch 4.
Use the antennas and antenna cable from the manufacturer to ensure
optimum reading and writing ranges.
There are risks if the device is supplied with the incorrect voltage.
Only use cables, plugs and adapters from the manufacturer.
Observe power ratings provided in the technical data.
PIN
Signal
1
+24V DC
2
0 V
3
GND
7.5.3 Connecting the antenna
Connect the antenna at the antenna connection at the rear of the
reading unit. Observe the label here.
7.6 Power Supply
The device can be connected to the system‘s internal power supply or an external power
supply.
If the device is connected to the power supply, the power LED lights up.
off, off … Antenna connection 1
off, on … Antenna connection 2
on, off … Antenna connection 3
on, on … Antenna connection 4
2
3
off: Operation mode
on: Activated test mode
4
DIP 3 off: Deactivated test mode
off->on Start Antenna Tuning
DIP 3 on: Activated test mode
Selection of the test function:
off = Read, on = Write
7.7 DIP-switch
Test mode can be activated via the 4 DIP switches on the device. In test mode, a
continuous reading operation is performed at the set antenna port and the result
of the reading operation is displayed on the status LED.
The test mode is activated by setting DIP switch 3DIP switch 4 can be used to
select between test reading and test writing The selection of the antenna port is
changed using the DIP switches 1 and 2.
The following requirements must be fulfilled for smooth device operation.
1. The operating temperature must be within the scope of the values
specified in the technical data.
2. The device must be connected to the
power supply (provide PoE is not used).
3. An antenna must be properly connected to the reading device.
4. A transponder must be within the reading and writing ranges of
the connected antenna.
5. For normal operation, deactivate test mode after
installation. (All DIP switches off).
8.2 The serial interface parameters
The following settings of the serial interfaces are set on delivery. The baud rate
can be changed in the SECS protocol with the parameter 0x01. If you want to
change the baud rate in the ASCII protocol, then please contact the manufacturer
HERMOS.
The unit is connected to the customer network via a 10/100BaseT Ethernet interface. The
DHCP (Dynamic Host Configuration Protocol) is activated on delivery.
If there is not a DHCP server available in your network, a random IP address is set from
the Zero- Conf range (169.254.0.0/16) and operations must still be performed to obtain an
IP address. If an IP address could be obtained or with a static IP address, the device can
be connected via TCP / IP port 3241 in the delivery state.
The HERMOS „DeviceDiscoverer“ is available for configuring the network setting.
8.3.1 Change networksettings with DeviceDiscoverer
HERMOS components can be found in the LAN network and settings can be
easily changed using the „DeviceDiscoverer“.
1. Select your network interface if you have several options on your PC.
2. Your network is automatically scanned for all HERMOS reading devices using the
„Search Devices“ button.
3. Select the desired reading device in the list to open the network settings.
Here, you can edit the network settings and apply them to the
reading device by pressing the respective button. Use „HERMOS“ if
you are asked to enter a password!
After parameters are changed, the reading device reboots and can be read in using
„Search Devices“.
CAUTION
Changing network settings generally cause the reading
device to reboot. This closes an existing HSMS host
connection.
Firmware updates can also be performed using the HERMOS „DeviceDiscoverer“. Start
the tool with administrator rights and scan the network for all HERMOS devices.
To do an update, mark the desired reading device and select „Firware Update”.
Use „HERMOS“ if you are asked to enter a password!
1. Click the "Firmware Update" button to open the new Firmware Download window for
the selected reader.
2. It is usually not necessary to open the download connection as this
happens automatically. Otherwise, pressing the Connect button will open
the download connection.
3. Select the new firmware file using the load image button.
4. Start the download process.
Wait until the „Download Finished“ message appears.
CAUTION
During the download process, do not disconnect the power supply or interrupt the
network connection.
This feature is not yet supported by all HERMOS readers and is only available for the
LFM4x as of software version V1.5.
Readers can also be tested with the HERMOS "Device Discoverer" if you have one
support feature. Start the tool with administrator rights and search for the HERMOS device
under test in the network. Select the desired reader and select the "Device Test" button
independently of your interface. A further "Device Test" view is opened with which the
addressed reader can be tested via the UDP protocol without having to disconnect any
existing TCP / IP connection.
Expert Mode:
In the "Expert Mode" tab you can select from a list of test commands and send this after
any modification. The Trace window below shows all traffic generated when testing with
UDP. The success code of the response message is displayed in the status bar at the
bottom left.
Below is the structure of the UDP action commands to own test actions on the reader
to be able to define. Depending on the command, the head number and data may be
optional data elements
Parameters:
In the "Parameters" tab you can choose from a list of parameters that can be read and
written.
CAUTION
When setting and reading parameters, it must be carefully considered
which communication protocol is currently set. Some parameters are
defined differently in different protocols.
LF Module:
In the register "LF Module" a test reading can be carried out. One or more pages of a
multipage transponder can be read out. The success code of the triggered reading is
displayed in the status bar at the bottom of the window. Via a scan, the first page of every
readable 134.2 kHz LF transponder is read out and displayed.
The device should only be operated by specially trained personnel. If you have any
doubts about the required qualifications, please contact the manufacturer.
The operation of the device without special expertise can result in damages to the
device or on connected devices.
9.2 Protocol change
9.2.1 General
To communicate with a connected host system, the reader supports ASCII or SECS /
HSMS protocols. The protocol selection takes place by means of automatic protocol
recognition.
The currently set protocol is displayed on the status LED during the boot process.
SECS: The red LED goes on briefly after self test
ASCII: The yellow LED goes on several times
9.2.2 Automatic protocol detection
The reader automatically adjusts to the protocol used by checking and evaluating the first
message after a reset. The interface is changed accordingly when the protocol is changed
and reinitiali- zed. This process can take several seconds. Already sent messages are lost.
The newly recognized protocol is used for further communication. A renewed change is
only pos- sible after another reset. Automatic protocol detection can be disabled by setting
parameter 98 (0x62).
If the reader receives undefined or random characters, this may result in an
accidental protocol change.
Automatic protocol detection can be deactivated in parameter 98 (0x62).
The reader LFM 4x is equipped with 4 antenna ports. Each of these ports has its own
antenna tuning with which the connected antenna is tuned to the ambient conditions.
In the set protocol, the read or write commands are always executed by port. The 4 antenna
ports from 1 to 4 are numbered consecutively and are addressed accordingly in the logging
command.
In the ASCII protocol, the reader ID decides on the selection of the antenna port.
The reader ID („1“ to „4“) responds to the respective antenna port 1 to 4. Depending on the
Factoryparameterset, it is possible to select the value range of the reader ID from „0“ to „3“ or
from „1“ to „4“.
In the SECS protocol, the target ID is used to select the antenna port: Target ID „01“ to „04“
responds to the respective antenna port 1 to 4.
For customer-specific solutions, another reader (eg HFS ESN) can be connected to the
RS232 interface. This reader is then used to communicate via the Target ID „05“ or Reader
ID „05“.
The reader LFM 4x can be delivered with a few Factoryparametersets. The settings of the
Factoryparameterset is part of the factory settings and can only be changed by Hermos. If
customer needs another Factoryparameterset setting, please ask Hermos for the
necessary steps. The installed Factoryparameterset can be read by parameter 64 (use
command “G164”).
Factoryparameterset 0: (standard ASC-I1 mode)
The antenna will be addressed by the ReaderID or TargetID „1“ to „4“.
At the rs232 connector a HFS ESN reader is connected and can be adressed by ReaderID
“5”. For SECS protocol there is no MID area defined.
Factoryparameterset 1: (standard ASC-I1 mode)
The antenna will be addressed by the ReaderID or TargetID „1“ to „4“. For SECS protocol
there is no MID area defined.
The rs232 connector can be used for serial host communication.
Factoryparameterset 2: (standard ASC-I1 mode)
The antenna will be addressed by the ReaderID or TargetID „1“ to „4“.
For SECS protocol the default MID area of 2 pages / 16 characters is defined. The rs232
connector can be used for serial host communication.
Factoryparameterset 3: (ASC-W1 mode)
The antenna is addressed by the ReaderID „0“ to „3“, or TargetID „1“ to „4“. For SECS
protocol there is no MID area defined.
The rs232 connector can be used for serial host communication.
For the TCP/IP communication the complete end packet of the ASCI-I1 protocol will be
transmitted (end character and 4 bytes checksum).
P-command: The parameter value will be interpreted as hexadecimal value.
The additional F-command can be used to deliver the parameter value with hexadecimal
interpretation. X/R/W-command: The page value will be interpreted as hexadecimal value.
Errors will be send with the command “E”. With default settings a confirmation has to be
send. The additional B-command can be used for signal the detection of an object.
Factoryparameterset 4: (standard ASC-I1 mode)
The antenna will be addressed by the ReaderID „0“ to „3“ or TargetID „1“ to „4“.
For the SECS protocol, the standard MID range of 2 pages / 16 characters is defined. The
RS232 port can be used for serial host communication.
Factoryparameterset 5: (standard ASC-I1 mode)
The antenna will be addressed by the ReaderID „0“ to „3“ or TargetID „1“ to „4“.
For the SECS protocol, the standard MID range of 2 pages / 16 characters is defined. The
RS232 port can be used for serial host communication.
This mode supports the 24 volt I / O module with 6 sensors and 8 outputs. The two
additional sensors are represented by an extended range for ReaderID or Portnumber
PTN.
The communication is carried out via ASCII packets.
After each command to the reading device, a specific reply is transmitted. We recommend
waiting for this reply before transmitting a new command.
10.2 Packet content
Each message packet consists of a packet header (header = 3 characters), the message
data (2 or more characters) and the packet end.
Packet header
The packet header contains a start character and the message length. The message length
consists of 2 hexadecimal bytes and defines the number of characters in a message.
Start Start character (ASCII character „S“)
Length 1 High byte of the message length (ASCII character „0“-“F“)
Length 2 Low byte of the message length (ASCII character „0“-“F“)
Advanced ASCII-format:
The advanced ASCII format is defined for ASCII messages whose message length
exceeds 255 characters. The packet header contains two start characters and the
message length. The message length consists of 4 hexadecimal bytes and defines the
number of characters in a message.
Start 1 First start character (ASCII-character „S“)
Start 2 Second start character (ASCII-character „X“ = advanced ASCII protocol)
Length 1 High byte of the message length (ASCII-character „0“-„F“)
Length 2 Byte packet length (ASCII character „0“-“F“)
Length 3 Byte packet length (ASCII character „0“-“F“)
Length 4 Low byte of the message length (ASCII character „0“-“F“)
Message data
The message contains a command character, a target or source address, the
number of the antenna port (head) and the actual message data.
The number of the antenna port is not required for all messages.
Command The command is defined by an ASCII character. (See protocol
commands)
Address Target/source address (ASCII characters „0“, „1“, …) *
Data The definition of the message data depends on the protocol command.
* Depending on Factoryparameterset, the readers are addressed via the address
„0 ... 3“ or „1 ... 4“.
Packet end
The end of the packet contains an end character and a checksum consisting of 4
characters.
End character ASCII end character <CR> (hex 0x0D).
Checksum 1 High byte XOR logic of all data (packet header, data and end character).
(ASCII character „0“…“F“)
Checksum 2 Low byte XOR logic of all data (packet header, data and end character).
(ASCII character „0“…“F“)
Checksum 3 High byte addition of all data (packet header, data and end character).
(ASCII character „0“…“F“)
Checksum 4 Low byte addition of all data (packet header, data and end character).
The checksum is not necessary when using the TCP/IP interface (No
transmission). The end character is only transmitted.
If the device is operated in ASC-W1 mode, the complete end packet is
transmitted (end character and 4 bytes checksum).
Tuning value
2 Byte
CMD
1 Byte
Data
16 Bytes
„08“ … automatic tuning from the reader
„10“ … manual tuning 0x00
„1F“ … manual tuning 0x0F
10.3 Data elements
The data elements that are used by default ASCII messages, which are described in the
message details section, are defined in this section.
The tuning value is a set value for the optimal antenna tuning. For optimum read and write
ranges, the value is automatically determined by the reader. The value is measured in 16
steps (0-F). He can also be targeted.
Example:
Command of the message, see table in Chapter “Commands“.
The data is represented in HEX format by 2 ASCII characters. The data always includes
every 8 bytes of the corresponding page of the transporter.
Example:
Transponder data in ASCII-Format „12345678“ (8 bytes)
Transponder data in HEX-Format 0x31 0x32 0x33 0x34 0x35 0x36 0x37 0x38
Data in message „3132333435363738“(16 ASCII-characters)
The Output Index defines the index of the output of a Readerhead that is addressed. Each
Readerhead has 2 LEDs.
The data element shows or sets the current status of the outputs.
The Data Element Output State includes the status of each output on the reader. The
status is displayed as 1 byte for each sensor.
0
1
2
3
4
Switch off the output permanently
Switch on the output permanently
output flashes with approx. 1 Hz
output remains unchanged
output flashes with approx. 2 Hz
The number of the parameter is displayed as an ASCII character (1 byte) in HEX format.
With single-digit parameter numbers from „0“ to „F“, the actual parameter value
can be decimal or hexadecimal depending on the mode.
In the standard ASC-I1 mode, the data element displays the value of a parameter
using 2 ASCII characters (2 bytes) in decimal format (“00” bis“99”).
Example: Value 45 „45“
In ASC-W1 mode the data element indicates the value of a parameter by means of 2
ASCII characters (2 bytes) in hexadecimal format („00“ to „FF“).
Example: Value 45 (decimal) “2D“(hexadecimal)
The reader ID defines the address of the antenna port.
The reader LFM 4x can be read at all 4 antenna ports (1-4).
The antenna port is selected via the reader ID and is continuous.
In ASC-W1 -mode the 4 antenna ports with the reader ID „0“ to „3“ are addressed. General
messages also possible at address F (HF). Value range of 1-4, or 0-3.
This feature is not required for the individual device. This code is always „0000“.
The page of the transponder for a read / write operation is defined by 2 ASCII characters
(2 bytes) in decimal format
If the device is operating in ASC-W1 mode, the page should be interpreted in hexadecimal
form: The page of the transponder for a read / write operation is defined by 2 ASCII characters
(2 bytes) in hexadecimal format.
Contains 4 byte of the serial number.
The serial number is also on the adhesive label of the device.
Example: „1707HAG04660“ complete serial number
Decimal „04660“ (the last 5 characters of the complete serial
number) Hexadecimal serial number „1234“
The gateway ID is the last two digits and has the value 0x34
The data element Timeout defines the period of time that elapses until the LEDs are switched
off. The timeout is defined in hexadecimal notation.
When the timeout expires, the LED turns off.
Query Parameter (Device is operated in ASC-W1 mode)
P
Set Parameter
N
Reset
e
Error message
E
Error message (Device is operated in ASC-W1 mode)
H
Heartbeat
V
Software-Version
L
Lock side of a transponder
l
Coordinate RF-modules
J
Querying the coordination of the RF-module
Command
Description
O
Set Output
Q
Query Output/Input State
A
Sensor event: Sensor removed
B
Sensor event: Sensor detected (Device is operated in ASC-W1
mode)
For customer-specific device variants (->Factoryparametersets),
another reader can be connected to the RS232 interface.
The commands specified for this device are not part of this
documentation.
Reading the page defined in parameter 2 (readpage)
1
sequential reading of a transponder to the end character(‚E‘ - end character or ‚F‘ empty) in ID bit 0 ... 3
2
Reading the entire transponder (all pages)
Device
Host
CMD
Reader-ID
Page
Data
R
1 Byte
2 Bytes
16 Bytes
Host
Device
CMD
Reader-ID
r
1 Byte
If there is no transponder in the reading range of the antenna, the reader repeats the reading
function several times before an error message is sent. The number of repetitions is defined in
parameter 4 (‚r / w maxrepeat‘). If reading is still not possible, the reader sends the error
message ‚no tag (4)‘ to the host after the repetitions have been carried out.
No confirmation is expected from the host.
For a multipage read request (98 or 99), the protocol is retried. At the end of reading, the
reader sends an additional packet.
If the sensor check is activated (parameter 1: readmode), the assignment of the external input
is checked before the initiation of a read process by the host. The reading process is only
started if the sensor is occupied, otherwise the error message ‚no tag (4)‘ is sent.
10.4.2 R – Automatic read
By assigning the external input, an automatic read operation can be triggered.
The command „R“ sends the read data to the host. The host then has to confirm the
message. Depending on the setting of the reader (parameter 1: readmode), the reader
reads the following pages:
When reading several pages (par. 1: readmode„tag“ or „everything“) the command is repeated
for each read page. The last package contains the command ‚R‘ and the reader ID.
The host expects a confirmation of the read data. If there is no confirmation from the host, the
command is repeated. (par.5: ‚RS232 repeat time‘, par.6: ‚RS232 maxrepeat‘).
If a reading is not possible, the reader automatically repeats the reading with the set
parameters. (par.3: ‚r / w delay time‘, par.4 ‚r / w maxrepeat‘).
If no reading is possible, the reader sends the error message ‚no tag (4)‘ to the host.
The delay time for the presence sensor can be set (parameter 0: ‚sensor delay‘).
An automatic reading is only possible if all messages to be confirmed have been confirmed by
the previous reading or the waiting time (par.5: ‚RS232 repeat time‘, par.6: ‚RS232 maxrepeat‘)
has elapsed after the last transmission.
10.4.3 W - Write data
The command W starts writing a defined data area of a transponder.
If there is no transponder in the write range of the antenna, the reader sends an
error message (error 4 - no transponder).
If the describing of the tag fails, the reader repeats the writing operation several times before
sending an error message. The number of repetitions is defined in parameter 4 (‚r / w
maxrepeat‘). If writing is still not possible, the reader sends the error message ‚no tag (4)‘ to the
host after the repetitions have been carried out.
If the sensor check is activated (parameter 1: readmode), the assignment of the external input
is checked before the start of the write process by the host. The write process is started only
when the sensor is busy, otherwise the error message ‚no tag (4)‘ is sent.
With the command „G“ the values of all public parameters of the device can be queried.
The reader sends an individual protocol packet for each available public parameter. After the
last parameter, the reader sends a last packet including the command ‚g‘ and the reader ID.
From the list of public parameters only the parameter 0 to 7 and parameter F will be send.
The values returned for the data item parameter value in the response are decimal values
(00-99). The values for the data item Parameter No. are hexadecimal values (0-F).
In the case of two-digit hexadecimal parameter numbers (Parameter
No.), the parameter number and the parameter value double-digit
hexadecimal are also used in the response.
10.4.5 F – Query parameter
The command „F“ can be used to query the value of a public parameter of the device.
The reader sends an individual protocol packet for the requested public parameter.
The values returned in the response for the data elements parameter number and parameter
value are each hexadecimal values (0-F or 00-FF).
For two-digit hexadecimal parameter numbers (Parameter No.), the
parameter value must always be sent in two digits hexadecimal.
10.4.6 P – Set parameter
The command „P“ can be used to change the value of individual parameters. After a
parameter has been successfully changed, the reader sends a confirmation message.
Depending on the Factoryparameterset selected, the data elements parameter number and
parameter value must be interpreted differently. For single-digit hexadecimal parameter no. the
following interpretations must be observed:
In the standard ASC-I1 protocol mode the data element „Parameter Value“ with decimal values
(00-99) has to be used. The values for the data item „Parameter No.“ are hexadecimal values
(0-F).
Only in ASC-W1 mode (Factoryparameterset 3) the data elements „Parameter No.“ and „ParameterValue“ have to be used as hexadecimal values (0-F or 00-FF).
This message is only available in standard ASC-I1 mode!
If an error occurs the device will send an error message with the respective error code.
Further information about error codes and the corresponding corrective measures can be found
in the chapter Error Codes.
10.4.9 E – Error message
This message is only available in ASC-W1 mode. If there is an error, the device sends an error
messa- ge with the appropriate error code to the host.
The reader expects a confirmation of the error message. If there is no confirmation from the
host, the command is repeated. (Par.5: ‚RS232 delay time‘, par.6: ‚RS232 maxrepeat‘).
More about error codes and the corresponding corrective measures can be found in the
chapter Error Codes.
The command „H“ sends a heartbeat request to the reader.
The reader responds with its serial number and a response code.
The heartbeat function can be performed for all 4 antenna ports (1-4).
If another reader is operated as a customer variant on the RS232 port, a heartbeat can be sent
to the external reader via reader ID „5“.
The response code is part of the protocol but is not used for this device. The response code is
The command V is used to query the software version of the device.
The 8 characters of the software version are represented by 16 ASCII characters. Each
character is described in hex format and transmitted by 2 ASCII characters.
Locking a page cannot be reversed.
This page is permanently write protected.
10.4.12 L - Lock data area
A single page of a multipage transponder can be disabled. The page can still be read, but not
rewritten. The process cannot be reversed.
If the lock of the transponder page fails, the reader repeats the procedure several times before
an error message is sent. The number of repetitions is defined in parameter 4 (‚r / w
maxrepeat‘). If writing is still not possible, the reader sends the error message ‚no tag (4)‘ to the
host after the repetitions have been carried out.
If the page was already locked, a positive confirmation will be sent (same as the first block).
If the sensor check is activated (parameter 1 readmode), the assignment of the external input is
checked before the blocking process is started by the host. The locking process is only started
when the sensor is occupied, otherwise the error message ‚no tag (4)‘ is sent.
It is necessary to adjust the RF module in ordert to adapt an antenna tot he ambient conditions
optimally. The tuning achieves an optimal read / write range for the present installation
environment. Tuning is performed one at a time for each antenna port and the determined
tuning value is stored for each antenna.
For optimal results, the vote should be automatic, but the voting value can also be set
manually.
To start the auto-tuning process, select the value 08.
Example: I108 …automatic tuning of antenna 1
If the reader can not determine the appropriate calibration, the error „5 - Invalid“ is sent instead
The command „J“ can be used to query the tuning values of the individual antennas. Each
antenna port has its own tuning value.
The tuning value is a set value for the optimal antenna tuning.
For optimum read and write ranges, the value is automatically determined by the reader
(I-message). The value is measured in 16 steps (0-F).
In parameter 1 „Read Mode“ the sensor can be deactivated.
10.4.15 A – Sensor event object removed
The message of sensor events can be activated in the parameter „Watch-Port“ (par. 07). If this
is activated, the reader reports every drop of the external sensor.
The sensor message must be confirmed by the host.
The sensor event is detected after an adjustable delay time (par. 0 Sensor Delay). During the
delay time, the sensor signal must be stable.
The assignment of the external sensor results in an automatic reading and
is not sent as a sensor event in standard ASC-I1 mode. In the ASC-W1
mode, however, a sensor event B is present.
In parameter 1 „Read Mode“ the sensor can be deactivated.
10.4.16 B – Sensor event object detected
The message of sensor events can be activated in the parameter „Watch-Port“ (par. 07). If this
is activated, the reader reports any recognition of the external sensor.
The sensor message must be confirmed by the host.
The number of available outputs depends on the reader version used.
Device
Host
CMD
Reader-ID
Head-ID
o
1 Byte
1 Byte
10.4.17 O – Set output
The command O can be used to set the state of the outputs.
The status of all outputs is changed in a message. In the current version, the value of the data
element Head-ID always has the value „1“ for the outputs.
* The specification of a time duration (timeout) is optional.
10.4.18 Q – Querying the status of the inputs and outputs
The Q command can be used to query the current status of all outputs. The status of the
outputs is queried in a message. In the current version, the value of the data element Head-ID
always has the value „1“ for the outputs.
Example: Status LEDs Port 1
>> Q11
<< q1121 LED1 (2 = flash), LED2 (1 = on)
The status of all 4 (The number of sensor states may vary between 4 and 6, depending on the
custo- mer mode.) input sensors can be queried via head ID „0“.
In this case, the answer contains the 4 (The number of sensor states may vary between 4 and
6, depending on the Factoryparameterset.) sensor states instead of the 2 output states.
Example: Status of all 4 sensors
>> Q10
<< q100000
The parameters 0, 1, 2 and 7 are only valid if the reader is equipped
with a corresponding I / O module and provides one input per antenna
port.
*): Since software revision V1.5 some parameters are implemented
for each antenna port.Addressing of the parameter takes place via
the reader ID of the message. In this realisation, the parameter is
present once per antenna port. If no parameter arrays should be
used, please ask the manufacturer (parameter 63)!
Nr.
(dez)
Nr.
(hex)
Parameter
name
Description
0
0x00
Sensor delay
Delay time for the presence sensor.
01 .. 99 (0,1 Sekunden)
Default: 10 … (1 second)
Realisation: a separate parameter for each port *)
1
0x01
Read mode
Read mode for reading automatically started by external
input. 00 - read only one page
01 - read until the end character or empty
character2) 02 - read all pages
10 - read only one page with previous sensor Check1)
11 - read until the end character / empty character
with previous sensor check 1) 2)
12 - read all pages with previous sensor
Check1) 99 - Disable sensor
1) If the Sensor Check (first byte = 1) is activated, the assignment of
the potential-free input is checked before initiating a read / write
process. When used, the read / write process is started, otherwise the
error message „NOTAG“ is sent.
2) ‚E‘ or ‚F‘ in ID bits 0...3 of the read ID
Default: 00 … (read only one page)
Realisation: a separate parameter for each port *)
2
0x02
Read page
Page for readmode „00“.
01 First page of each transponder
02.. 17 Side of a multipage
transponder Default: 01 (read first
page)
Realisation: a separate parameter for each port *)
3
0x03
r/w repeat
time
Time between two read / write attempts.
01 .. 99 (0,1 s)
Default: 05 … (0,5 seconds)
Realisation: a separate parameter for each port *)
10.5 Parameter
The data element „Parameter No.“ can have the following values. List of public paramters:
Default: 05
Realisation: a separate parameter for each port *)
5
0x05
RS232 repeat
time
If no confirmation message was received from the host, the device
waits for this time before sending another message.
The number of repetitions is defined in parameter 6 (‚RS232
max repeat‘).
01 .. 99 (0,1 s)
Default: 45 … (4,5 seconds)
6
0x06
RS232 max
repeat
If an acknowledgement is not sent by the host, the device repeats the
message according to the set value.
Only then is an error message sent.
00 - endless
01 .. 99 - Number of attempts
Default: 3
7
0x07
Watch port
Activates / deactivates the event message to the host that the dry
contact (external output) has been opened (Bit0).
Bit0 (=0x01) reporting of contact has been opened:
0 - deactivated
1 - activated
Default: 1
Realisation: a separate parameter for each port *)
F
0x0F
Reader
address
Address of the first antenna port (0 ... E)
Default: 1
Nr.
(dez)
Nr.
(hex)
Parameter
name
Description
2
0x02
Read page
Page for readmode „00“.
00 First page of each transponder
01 … 17 Side of a multipage transponderDefault: 00 (read first page)Realisation: a separate parameter for each port *)
7
0x07
Watch port
Activates / deactivates the event message to the host that the dry
contact (external output) has been opened (Bit0) or closed (Bit1).
Bit0 (=0x01) reporting of contact has been opened:
0 - deactivated
1 - activated
Bit1 (=0x02) reporting of contact has been closed:
0 - deactivated
1 – activated
Default: 1
Realisation: a separate parameter for each port *)
For ASC-W1 mode the following additional parameters are public:
*): With TCP / IP transmission in the standard ASC-I1 protocol, the checksum bytes are not
transmitted.In ASC-W1 mode, however, they are also transmitted!
For readers with I / O modules, depending on the Factoryparameterset, the outputs of the
respective antenna port are switched accordingly when reading.
10.8.1 ASC-W1 Mode: Reader in operation mode and sensor triggered reading
Picture 1: Successful reading with instant host confirmation
The SECS I standard defines a communication interface that is suitable for exchanging
messages between the semiconductor processing systems and a host. A host is a computer or
computer network that exchanges the information with the systems to carry out the production.
The standard does not define the data contained in the message. The meaning of the
messages must be defined by a standard that defines the message content – e.g. by the SEMI
Equipment Communications Standard E5 (SECS-II).
This message record describes the communication between a reading device with SECS-I and
a host. The host and the RFID reading device can communicate via a RS232 interface (SECS-I)
or an Ethernet interface (10/100BaseT) with HSMS protocol. The meaning of the messages is
provided in the message details section in which the message content is defined.
Serial communication (SECS-I):
The data is transmitted or received as a serial bit stream with 10 bits per character in a
supported data rate. A standard character has a start bit, 8 data bits and a stop bit. No parity
bits or other controls are used for transmitting the individual bytes.
Default setting: 19200 / 8N1
Details about the data definition and the data transmission are provide in the SEMI Standard
E4. (SEMI Equipment Communication Standard 1 Message Transfer SECS-I)
Ethernet communication (HSMS):
The reading device functions as a HSMS server. This means that it waits for a connection
request from a HOST PC (client).
TCP/IP: IP-Adress xxx.xxx.xxx.xxx Port 3241
If there is a connection request from a HOST, a HSMS connection is set up and the SECS II
messages defined in the message record are transmitted from the reading device to the
respective HOST and vice versa. The HSMS connection remains intact until it is specifically
terminated by the host or the reading device.
All reading devices available in the network (LAN) can be operated from any HOST PC. A
HSMS reading device, however, can no longer be connected to more than one HOST
simultaneously.
The network settings can be changed using a configuration tool provided by HERMOS. Each
change to the network settings causes the unit to reboot and thus disconnects existing
communication connections.
11.1 Structure of a message
The communication structure and process is defined by the SEMI Equipment Communications
Standards E4, E5 and E37 (SECS-I, SECS-II, HSMS).
SECS message blocks always have a specified structure that consists of 1-4 length bytes, 10
bytes of message headers and message data.
The length contains all the bytes transmitted after the length byte with the exception of the two
checksum bytes. The maximum block length allowed by the SECS-I is 254 bytes and the
minimum is 10 bytes.
The reverse bit (R bit) indicates the direction of the message. The R bit (MSB) is set to „0“ for
messages to the reading device and „1“ for messages to the host.
The device ID is a unique number to establish the connection with the reading device. It
consists of an 8-bit gateway ID (bit 0-7) and a 7-bit reader ID (bit 8-14). The gateway ID in the
delivery state corresponds to the last two hexadecimal characters of the serial number of the
reader. The reader ID has the value 0x01 in the delivery state. Of course, the device ID can be
changed via the corresponding parameters Gateway ID and Reader ID within the validity range.
See example with Reader ID 0x01 and Gateway ID 0x00:
Direction reading device to host 0x8000
Direction host to system (reading device) 0x0000
The W bit indicates whether the transmitter of the primary message wait for a reply. If the W bit
contains the value 1, it means that a reply is expected.
The message ID determines the format and the content of the transmitted message. It consists
of a stream and a function. The stream defines the message group and the function, the exact
meaning and the syntax of the message. A primary message (request) is defined as an
uneven message. A secondary message is defined as an even message (reply).
The end bit indicates whether a block is the last block of the message. A value of 1 means
that the block is the last block. Since all messages can be transmitted in a block, the block
number always has the value 1.
The system bytes in the header of each message are used to distinguish primary messages.
The system bytes of the reply message must correspond to the system bytes of the
corresponding primary message. The system bytes are incremented for each primary
message.
The checksum is calculated as the numerical sum of the unsigned binary values of all bytes –
after the length byte and before the checksum as well as in an individual block.
For more detailed information about the structure and transmission procedure, see SEMI E4,
E5, E37, E99.
(SEMI Equipment Communication Standard Message Transfer SECS)
This section defines the data elements used in the standard SECS-II messages described
in the message details section.
Syntax:
Name A unique name for this data item. This name is used in the message definitions
.
Format A unique name for this data item. This name is used in the message
definitions. The allowed element format code that can be used for this
default data element. Element format codes are displayed in
hexadecimal and octal, as described in chapter Data element.
The notification „3 ()“ indicates a signed integer format (30, 31, 32, 34).
Description A description of the data element with the meaning of each value. Where used
standard messages in which the data element occurs.
Verification code
Verification code
The value of the alarm state refers to the last read. If a read or write error occurs, the alarm state
is activated. A successful read or write deactivates the alarm state. When leaving the
maintenance mode, the alarm state is also deactivated.
Alarm-Codebyte
Only the occurrence of an error is reported. Errors are usually not reset.
Bit 8 = 1 Alarm activated
Alarm Identifier
Only the occurrence of an error is reported. Errors are usually not reset.
0 No error
1 Automatic reading failed, the reader is busy
2 External read failed, the reader is busy
3 External write failed, the reader is busy
4 No transponder could be detected when the
sensor was covered, or the carrier was removed
too soon (sensor uncovered)
5 Invalid command or parameter detected
6 Unknown error
7 Reserved
8 parity error or checksum error detected
9 An unexpected confirmation has been sent
10 Locked page could not be described
11 Reserved
12 Wrong transponder type
13 External read or write failed because the sensor is not covered
14 Reserved
15 Reserved
16 Reserved
More about error codes and the corresponding corrective measures can be found in
the chapter Error Codes.
Where used S5F1
Alarm text
The length of the alarm text is between 0 and 40 characters. Depending on the version of the
reader, information about the condition of the sensor or the sensors is also transmitted in the
event of an error message from the reader
The information should be interpreted as follows:
ALTX[0] Initiator of an error message
„Configuration“ Number of heads
„AlarmStatus“ Current CIDRW sub-state of the alarm state
„OperationalStatus“ Current CIDRW sub-state in normal operation
“SoftwareRevisionLevel“ Change (version) of the software - maximum 8 bytes
„CarrierIDOffset“ Offset of the CID in the CID field (MID area)
„CarrierIDLength“ Length of the CID in the CID field (MID area)
„SERIALNUM“ Series number string
„HARDWARE“ String of the Hardware-Release
„SELF_TEST_RESULT“ Supply the result of the last self-test
„MANUFACTURER“ String of the manufacturer
The number of LEDs per antenna input depends on the design of the
hardware.
CPVAL Format: A[]
„SELF_TEST_RESULT“Returns the result of the last self-test. A self-test can
be triggered by message S18F13 using SSCMD.
„MANUFACTURER“ String from the manufacturer „HERMOS“
„ECID_00“ bis „ECID_99“ see data element ECV parameters 0 - 99
Head attribute definitions:
„HeadStatus“ Current state
„IDLE“ Reader in REST mode
„BUSY“ reader is busy
„NOOP“ Not in operation
„HeadID“ corresponds to the 2-digit target ID of the first antenna port
„01“ or „00“
Where used S18F2, S18F3
State request value
OpStatus Operating status, maintenance or rest mode
„OP“ ... operating status
„MT“ ... maintenance status
LEDStatus LED-status
„Off“ ... switch off the LED
„On“ ... switch on the LED
„Flash“ ... switch the LED to flashing mode with 1Hz
LedNo LED-number, 1 Byte
„1“ first LED of the Reader Heads (if available)
„2“ second LED of the Reader Heads (if available)
„3“ red status LED of the reader
„4“ green status LED of the reader
Timeout Timeout duration, Units seconds
„00“: permanently
„01“ bis „FF“: Timeout from 1 to 255 s. After the timeout, the LED goes off.
The data element is a vector or string of unformatted data.
The DATA area depends on the MID area of the transponder and can be between page 1 and
page 17. Read-write transponder DATA corresponds to 8 byte MID
Read-only transponder DATA corresponds to 8 byte MID
Where used S18F6, S18F7
The DATA LENGTH corresponds to the number of bytes to be read or written. The
scope depends on the length of the MID range (parameter 37).
Where used S18F5, S18F7
Used to identify the requested data.
The DATASEG corresponds to the page number (PAGEID) of the transponder.„00“ First page of each transponder or first page of the DATA area.
Multipage transponders (pages 1 to 17):
Read-Only-Transponder „F0“ Read only one page
Read-Write-Transponder „F1“ Read or write only one page
Where used S18F5, S18F7
Confirmation code for new reader attribute
0 ... parameter successfully set
1 ... parameter could not be set
Where used S2F16
Parameter number of the reader.
The values are displayed as decimal values.
Value of the reader parameter.
The values are displayed as decimal values, see parameters.
Plant model number (Hardware version)
Where used S2F14, S2F15
Material Format Code
20: The material port number corresponds to the sensor number and the sensor status.
Where used S1F2
Where used S3F5, S3F7
The data element MHED consists of the head of the SECS message block associated with the defective
message block.
Material ID, predefined area on the transponder in which the unique identifier of the cassette / box is
stored. Depending on the type of transponder, the length of the MID can be changed.
Multipage-Transponder: The MID length can be set from „0“ (no MID) to „10“ (MID occupies the first 10 pages).
Read-Write-Transponder: The MID corresponds to the DATA (writable) Read-OnlyTransponder: The MID corresponds to the DATA (fixed)
0 Material ID confirmed; the presence sensor was the initiator
1 Not specified
2 Material ID confirmed - reaction to externally triggered process; the message can not be assigned
to a sensor
>2 Material ID not confirmed
The initiator can be taken from the data element PTN.
Where used S3F14
Material ID verification code
2 confirmation, MID will be sent later in S3F13
Where used S3F12
Confirmation code for OFFLINE request.
0 ONLINE accepted (reader is online)
Confirmation code for ONLINE request.
0 ONLINE accepted (reader is online)
Where used S1F16
The data element corresponds to the transponder data. It contains the transponder page and the data
content of the page.
PAGEDATA [0] Correspond to the page number. The value of the page number is displayed in
PAGEDATA [1-8] The 8 bytes (one page) of the transponder ID follow.
Result information about the status of the request for the service request.„NO“Normal Operation
Indicates the success of the requested operation.„EE“Execution error
Transponder data cannot be read. MID sequence cannot be read, as valid ASCII characters were not
found exclusively in the defined MID area. However, the condition of the facilities is normal.„CE“Communication error
Syntax error in message, message format, or value.„HE“Hardware error
Error in the head of the ID reader / writer, head of the ID reader / writer is deactivated.
„TE“ Transponder error, reading / writing unsuccessful (Tag Error)
„NT“ No transponder detected in the antenna area. (No Tag)
Where used S18F2, S18F4, S18F8, S18F10, S18F12, S18F14
Specifies an operation to be performed by the subsystem. Used to distinguish between the various
subsystem commands displayed.
„ChangeState“ … change status
„GetStatus“ … query staus
„Reset“ … reset CIDRW
„PerformDiagnostics“ … A diagnosis is made.
„ADJUST“ … triggers an automatic alignment of the antenna.
„HERMOSDefParams“ … Basic setting of the readers parameters.
„SetLED „ … Set one of the device LEDs.
The status list provides information about the system status.
Consists of „PM Information“ and the current values of the CIDRW attributes „AlarmStatus“, „Operating Status“ and „HeadStatus“.
Where used S18F2, S18F4, S18F8, S18F10, S18F12, S18F14
The TargetID is defined with 2 decimal ASCII characters and corresponds to the antenna connections. The
2-digit target ID (Head-ID) is used to set the antenna port 1 to 4 for which the action is to be carried out.
(see Adressing the antenna ports). The use of the 4-digit TARGETID is currently not supported.
Where used S18F1, S18F3, S18F4, S18F7, S18F9, S18F11, S18F13
The message record describes the communication data between a reading device with and a
host. The following functions can be used via commands by the host in the reading device or
automatically transmitted from the reading device to the host:
This message is used instead of an expected reply to cancel an action. The function 0 is defined
in each stream and has the same meaning in each stream.
S1F0 (header only, no additional elements)
S1F1: ARE YOU THERE REQUEST (reading device <-> host, reply)
Determines whether the reading device or the host is online. S1F1 W (header only, no additional
elements)
The reading device contains a request to change the communication state to „offline“.
The reading device can only be set to „online“ again using the message S1F17 (or reset S2F19);
all other messages are cancelled by message SxF0.
S2F15: NEW EQUIPMENT CONSTANT SENT (host -> reading device, reply)
The host changes a reading device attribute (parameter).
S2F15 W
<L[1]
<L[2]
<U1[1] ECID>
<U1[1] ECV>
S2F16: NEW EQUIPMENT CONSTANT ACKNOWLEDGE (reading device ->host)
The reading device acknowledges the reading device parameter).
S2F16
<B[1] EAC>
S2F19: RESET SENT (host -> reading device, reply)
The host transmits a request to the reading device to reset the hardware and software.
If a heartbeat time (parameter 9) is set, the reading device transmits a S1F1 message once the
reset operation is complete.
A power-up reset takes a few seconds.
S2F19 W
<B[1] RIC>
S2F20: RESET ACKNOWLEDGE (reading device -> host)
The reading device acknowledges the reset.
This message is only displayed if a software reset (RIC=2) has been triggered.
11.3.3 Stream 3 (Material-state)
S3F5: Material found (MID FOUND) (reading device-> host, reply)
The reader sends the information that material has been detected on the input sensor. This
message is sent only when a sensor is connected and activated.
(see par. 26 Sensor Activity and par. 27 Watchport)
S3F5 W
<L[2]
<B[1] MF >
<B[1] PTN >
>
S3F6: Material found confirmation (MID FOUND, ACK) (host -> reading device)
The host confirms the message material found.
S3F6
<B[1] ACKC3 >
S3F7: Material lost (MID LOST) (reading device -> host, reply)
The reader sends the information that material has been removed from the input sensor. This
message is sent only when a sensor is connected and activated.
(see par. 26 Sensor Activity and par. 27 Watchport)
The PAGEDATA are only indicated if the last reading was successful.
S3F7 W
<L[2]
<B[1] MF >
<B[1] PTN >
<B[9] PAGEDATA >
>
S3F8: Material lost confirmation (MID LOST, ACK) (host -> reading device)
This message indicates a timeout of a transmission timer and the cancellation of the
corresponding transaction. Only the most recently transmitted message (that must be
acknowledged by the host) is saved and its acknowledgement is monitored by time.
S9F9
< B[10] SHEAD >
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.