Hengstler RA 58-P, RA 59-P Installation Instructions Manual

Page 1
Safety and Operating Instructions
• The absolute shaft encoders of the type RA 58-P/RA 59-P model series are quality products manufactured in accordance with established electrical engineering standards. The units have been delivered from the factory in perfect conformance to safety regulations. To maintain this condition and to ensure trouble-free operation, please ob­serve the technical specifications of this document.
• Installation and mounting may only be performed by an electrotechnical expert!
• The units may only be operated within the limits specified by the technical data.
Maximum operating voltages must not be exceeded! The units are designed complying with DIN EN 61010-part 1, protection class III. To prevent dangerous structure-borne currents, the equipment has to be run on safety extra-low voltage (SELV) and must be in an area of equipotential bonding. Please use an external fuse for protection (see Electrical Data).
• Fields of application: industrial processes and controls. Overvoltage at the connecting terminals must be limited to overvoltage­class-II values.
• Please avoid shocks to the housing – especially to the encoder shaft – and axial or radial overload to the encoder shaft.
• Maximum accuracy and durability of our shaft encoders are only granted when using suitable couplings.
• The high-quality EMC-specifications are only valid together with standard­type cables and plugs. When using screened cables, the screen must broadly be connected with ground on both ends. Likewise, the voltage-supply cables should entirely be screened. If this is not possible you will have to take appropriate filtering measures.
• Installation environment and wiring are influential on the encoder's EMC: Thus the installer must secure EMC of the whole facility (device).
• In electrostaticly threatened areas please take care for neat ESD-protection of plug and connecting cable during installation work.
• Specified maximum shaft loads are only given under restrictions: – Full bearing life of 1 x 10
10
revolutions (typ.) will be reached at 35% of
full rated shaft load
– a bearing life of 1 x 108revolutions (typ.) will be reached at 100% of full
rated shaft load.
Installation instructions
Absolute Shaft Encoders RA 58-P/RA 59-P, Interbus (K3)
Item No. 2 543 043 Edition: 25.02.99
Hengstler GmbH Postfach 11 51 Tel. 07424 – 890 D-78550 Aldingen Fax 07424 – 89370
Introduction
These installation instructions are provided for the connection and starting procedure of your shaft encoder.
For further informations see user guide:
RA 58-P/RA 59-P with Interbus (K3): Item No. 2 543 003
General aspects
The shaft encoder of the type RA 58-P/RA 59-P can be programmed via the Interbus. Due to this function the encoder may be used universally; thus the range of variants as well as the storage will be reduced for the customer. A lot of calculating time and expense on the host system will be saved by data processing within the encoder.
The RA 58-P/RA 59-P is equipped with an EEPROM for remanent storage of the parameters. When the device is turned on the parameters are transferred automatically to the memory.
This sign marks paragraphs particularly to be observed to assure proper use and to avoid risks.
Mechanical data
Shaft diameter 6 mm (synchro flange) / 10 mm (clamping flange) Max. shaft load 6 mm: axial 60 N (13 lbs), radial 110 N (24 lbs)
10 mm: axial 107 N (24 lbs), radial 160 N (35 lbs)
Speed 10000 RPM (short term), 6000 RPM(continuous duty) Torque 0.5 Ncm Moment of inertia synchro flange approx. 14 gcm2,
clamping flange approx. 20 gcm
2
Protection class (EN 60529) housing IP 65*, bearing IP64* Operating temperature –10 … +60 °C Storage temperature –25 … +85 °C Vibration performance (IEC 68-2-6) 100 m/s2(10 … 500 Hz) Shock resistance (IEC 68-2-27) 1000 m/s2(6 ms) Types of connection cable axial/radial, connector axial/radial,
connector 2-fold radial, bus terminal box Housing aluminium Flange S = synchro flange**, K = clamping flange*** Weight 350 g approx. Bearing life 1 x 1010revolutions (typ.) at 35 % of full rated shaft load
1 x 109revolutions (typ.) at 75 % of full rated shaft load 1 x 108revolutions (typ.) at 100 % of full rated shaft load
* IP 67 for singleturn versions on request ** Mounting with screws M4 *** Mounting with screws M3 or M4
General design as per EN 61010-part 1, protection class III,
contamination level 2, overvoltage class II
Supply voltage
1)
10 ... 30 VDC (SELV) with pole protection
Power consumption max. 0.2 A Recommended external fuse T 0.25 A Max. current for througoing max. 4.5 A (connector 2-fold), voltage supply; max. 2 A (bus terminal box); recommended external fuse T 4.5 A (connector 2-fold), T 2 A (bus terminal box) EMC Noise emission as per EN 50081-2,
noise immunity as per EN 50082-2
Linearity ± ½ LSB Type of code Binary Interface RS 485 for installation remote bus Protocol Interbus with ENCOM profile K3 (can be parameterised) Signal lines 5 V difference signals, with potential-free
power supply
Baud rate 500 KB Update every 600 µs Physical resolution
2)
1024 increments (10 Bit)
4096 increments (12 Bit)
1024 increments/4096 revolutions (22 Bit)
4096 increments/4096 revolutions (24 Bit)
Programmable functions Code sequence, scaling factor, preset, offset Max. cable length 50 m
1)
Real code-disc resolution; in addition, the desired resolution can be reduced by programming of the encoder parameters
2)
Power unit within encoder: potential-free DC/DC converter, 500 V AC withstand voltage between mains input and electronics
Electrical data
Function (programming directly Preset values Customer-specific by bus, using configuration- (manufacturer’s parameters parameter transfer) standard settings) Code sequence for clockwise rotation ascending Offset (CP-No. 05) 0 Preset value (CP-No. 04) 0 Scaling factor (CP-No. 08) 1*
* maximal resolution
Programmable functions
Item No. 2 543 043, Edition: 25.02.99
Subject to technical modifications and improvements serving the progress of our devices.
Page 2
Installation instructions
Absolute Shaft Encoders RA 58-P/RA 59-P, Interbus (K3)
Page 2 of 2
Connection diagram
INTERBUS interface (Standard assignment according to ENCOM)
Cable with plug Connector 2-fold (internal T-manifold)
Pin (12 poles) IN (9 poles, pins) OUT (9 poles, socket)
1 D02 D01 D02 2 D02 D01 D02 3 DI 2 DI 1 DI 2 4 DI 2 DI 1 DI 2 5 D01 GND signal output1)GND signal output
1)
6 D01 PE
2)
PE
2)
7 DI 1 10 … 30 VDC 10 … 30 VDC 8 DI 1 0 V (supply voltage) 0 V (supply voltage) 9 RBST N.C. RBST 10 0 V (supply voltage) 11 GND signal output
1)
12 10 … 30 VDC
1)
Signal output; due to potential separation not identical with 0 V (supply voltage); used to set the RBST input to logically "0".
2)
Functional earthing; connected to the encoder housing
INTERBUS/K3 (installation remote bus)
Concerning function and transmission procedure, the absolute shaft encoder RA 58-P/RA 59-P complies with the Class 3-profile (K3) — defined by the ENCOM User group — with programmable parameters. The interface is encoder-integrated and includes a potential-free power supply. The Master (e.g. PLC-attachment assembly) is responsible for cyclic data transfer to RA 58-P/RA 59-P. In each cycle two words are sent from the Master to the encoder and transferred from the encoder to the Master.
Starting procedure
With connection type cable:
• Connect the encoder to an external T-manifold. By this T-manifold the encoder is connected to the bus system and to the power supply.
• If further devices follow in the same bus line, a bridge between RBST and GND signal output must be made, in the connecting plug for the continuing bus, on the external T-manifold.
With connection type connector 2-fold:
• Connect the incoming bus to the encoder input (IN) (see connection dia­gram).
• If further devices follow in the same bus line: Connect continuing bus to the encoder output (OUT) (see connection dia­gram). A bridge between RBST and GND signal output must be made in the mating connector for the encoder output!
Maximum current: 4.5 A via pin 7 and 8! Recommended external fuse for the complete bus supply voltage: T 4.5 A
With connection type bus terminal:
• Release screws and pull bus terminal box off the encoder.
• Insert incoming bus cable through the middle screwed conduit entry and connect to the input terminals (index 1), according to marking.
• If no further devices follow in the same bus line: In the bus terminal box, plug jumper ST2.
• If further devices follow in the same bus line: Facing the opened bus terminal box, insert outgoing bus cable through the right-hand screwed conduit entry and connect to the output terminals (index
2), according to marking.
Maximum current: 2 A via UBand 0 V! Recommended external fuse for the complete bus supply voltage:
T 2 A
• Only if external power supply (not via bus) desired: Facing the opened bus terminal box, insert external encoder supply voltage through the left-hand screwed conduit entry and connect to UBand 0 V.
• Put bus terminal box on encoder and tighten screws.
Protection class
4 IP 65 7 IP 67
Ordering code (see identification plate)
Output
T RS 485
Connection
A Cable, axial B Cable, radial
I Connector 2-fold, 9 poles, radial, clockwise
(internal T-manifold)
Z Bus terminal box (3-fold PG), radial
(internal T-manifold)
Interface
I INTERBUS
Code
B Binary
Resolution
1)
0010 10 Bit (S) 0012 12 Bit (S) 1210 22 Bit (M) 1212 24 Bit (M)
Cable length
1. Letter Length code for meters (A=0, B=1, C=2 etc.)
2. Digit: Decimeters
PE TI
/
·
*
Plug
C CONIN 12 poles, clockwise
Type
RA 58 Standard RA 59 Stainless steel
Version
P Programmable
Supply voltage
E 10 … 30 VDC
Mounting
K Clamping flange
(10 mm shaft)
S Synchro flange
(6 mm shaft)
Q Square flange 63.5 x 63.5
(Shaft diameter A or B)
Shaft diameter
1 6 mm (S) 2 10 mm (K) A 10 x 25 (Q) B 9.52 x 25 (Q)
5 V difference signals (RS 485) ENCOM-profile K3, 32 Bit
Binary process data, right-aligned DT format Sµpi-address 0 1 2 3 (as per Phoenix) Byte-Nr. 3 2 1 0 ID-Code 37H (= 55 decimal)
Host to RA 58-P
31 30 29 28 27 26 25 24 23 - 16 15 - 8 7 - 0
*)
Data CP-number Control bits
RA 58-P to Host
31 30 29 28 27 26 25 24 23 - 16 15 - 8 7 - 0
*)
Data CP-number Status bits
*) Bit 24 not used
INTERBUS data input/output format
1)
S=Single-turn, M=Multi-turn with 4096 (12 Bit) revolutions
3)
1.5 m cable with 12-poles plug included, clockwise
BC
Item No. 2 543 043, Edition: 25.02.99
Subject to technical modifications and improvements serving the progress of our devices.
* Special types are additionally marked by an
ordering-code -S. In this case customer specifications are to be applied. If you don’t know these, please call us for the speci­fications, indicating the encoder’s item number.