Heliocol HC50, HC40, HC10.5, HC12.5, HC30 Installation Manual

...
Page 1
TOP HEADER
BOTTOM HEADER
SOLAR COLLECTOR
HEADER COUPLING
Z BARS BETWEEN COLLECTOR AND ROOF TILE
CONTINUE
BOTTOM HEADER
GATOR CLAMPS RE: NOTES #2
Z BARS BETWEEN COLLECTOR AND ROOF TILE
05
01*
*02
*02
*03
01
06
04
*10
01
DISCHARGE TO POOL
INTAKE FROM POOL
VACUUM RELIEF
01
*02
04
*11
05
*07
THERMOMETER
*03
04
05
SENSOR
BALL VALVE
06
*07
08
09
CHECK VALVE
3-WAY VALVE
WATER SENSOR
FILTER
08 09
*10
PUMP
AUXILLARY HEATER
*11
GENERAL NOTE: * COMPONENTS ARE OPTIONAL
*OPTIONAL COMPONENTS
MIRROR IMAGE PLUMBING LAYOUT ALLOWED – FEED & RETURN @ OPPOSITE DIAGONAL CORNERS
GATOR CLAMP RE: FIG 04
SOLAR COLLECTOR
ROOF TILE
FOAM ADHESIVE RE: NOTES #3
EXIST. UNDERLAYMENT (2) TAPCONS RE: NOTES #2
EXIST. SHEETING
Z BAR RE: FIG 04
EXIST. TRUSS
INSTALLATION OF A SOLAR POOL HEATING SYSTEM WITH A ROOF TOP COLLECTOR
WIND LOAD: 200 D, RISK CATEGORY II
WINDLOAD RESITANCE DETERMINED BY GATOR - HEADER CLAMPS
HELICOL SOLAR POOL HEATER COLLECTOR:
DIMENSIONS: 4'-0" X (8', 10' OR 12')
02
SCALE: 1/2" = 1'-0"
FIGURE 2
SHEET NO:
DATE: REVISION NO./DATE:
SHEET NAME:
ROOF ANGLE:
COLLECTOR INSTALLATION STANDARD FLUSH W/ ROOF
01
SCALE: N.T.S.
FIGURE 1
03
SCALE: N.T.S.
FIGURE 3
04
SCALE: NTS
USE OEM ATTACHMENT PARTS ONLY
NOTES FOR INSTALLATION OF HELIOCOL SPH (SOLAR POOL HEATER
) SYSTEM ON ROOFS USING LAGS, CONCRETE SCREWS, OR ADHESIVE FOAM:
THE DETAILS SPECIFIED ON THIS “PAPER” PLAN ARE CONSIDERED TO BE THE MINIMUM NEEDED BY AHJ (AUTHORITY HAVING JURISDICTION) AND INSTALLERS. USERS ARE ENCOURAGED TO ACCESS EV (ELECTRONIC VERSION) OF THIS PLANHTTP://GEZELMANPE.COM/GENERIC/0223S.AS_HELICOL_FL.PDF
ACTIVE HYPERLINKS ON EV PROVIDE EASY ACCESS TO INFORMATION. EV ALSO ALLOWS VIEWER TO STUDY THE PLAN AND OEM DETAILS AT A MAGNIFICATION OF HIS CHOICE UP TO 6400%. IF A CONFLICT SHOULD OCCU R BETWEEN A DRAWING AND/OR SPECIFICATION HEREON AND AN OEM DETAIL, OEM SHALL PREVAIL.
1.THESE DRAWINGS AND ENGINEERING ESTABLISH THE INSTALLATION REQUIREMENTS FOR HELIOCOL SOLAR POOL HEATING EQUIPMENT IN ROOF PRESSURE ZONES 1 & 2 (PZ1 & PZ2) ON BUILDINGS IN FLORI DA 30 FEET OR LESS IN HEIGHT AND AT ROOF ANGLES FROM FLAT UP TO 45 DEGREES. INSTALLATIONS OUTSIDE THAT PERMISSIVE “WINDOW” REQUIRE SITE SPECIFIC ENGINEERING.
2.THERE ARE METHODOLOGIES EXP LAINED ON THIS PLAN AND IN THE OEM INSTALLATION MANUAL FOR ALL TYPICAL ROOF COVERINGS.
3.THERE SHALL BE NO TILT-UP. THE SPH COLLECTO RS SHALL REST DIRECTLY UPON AND SHALL BE MOUNTED PARALLEL WITH THE ROOF SURFACE.
4.HELIOCOL SPH COLLECTORS ARE UNIQUE. UNLIKE OTHER SPH COLLECTO RS, HELIOCOL DOES NOT “FIGHT THE WIND”. HELIOCOL SPH COLLECTORS ARE COMPOSED OF NUMEROUS PARALLEL INDIVIDUAL SOLAR COLLECTION WA TER TUBES WHICH ARE OVER-MOLDED INTO AN UPPER AND LOWER HEADER. THE INDIVUAL TUBES ARE HELD IN ALIGNMENT BY SNAP-ON RIBS WHI CH ARE SPACED ABOUT 18-INCHES APART PARALLEL WITH THE HEADERS AND PROVIDE AN AIR-GAP FOR PRESSURE EQUALIZATION BETWEEN THE ROOF COVERING AND THE SOLAR COLLECTOR. AIR FLOWS AROUND THE INDIVIDUAL TUBES WITHOUT GREAT WIND RES ISTANCE. THIS PERFORMANCE CAN BE COMPARED TO THE RELATIVELY HIGHER SURVIVABILITY OF PALM TREES WHICH BEND WITH HIGH WINDS AND SURVIVE HURRICANES WHILE NEIGHBORING LIVE OAK AND OTHER MASSIVE TREES WHICH RESIST THE WIND ARE UPROOTED.
5.HELIOCOL COLLECTORS ARE CLAMPED TO THE RESPECTIVE ROOF WITH OEM “GATOR CLAMPS”. AS SHOWN IN THE DRAWING FIGURES. REFER TO OEM INSTALLATION MANUAL FOR SPECIFICATIONS AND HAVE AN OEM INSTALLATION AVAILABLE ON JOBSITE FOR AHJ INSPECTOR REFERENCE. THE UPLIFT RESISTANCE OF THE STANDARD METHOD OEM-RECOMMENDATION OF 4-GATOR CLAMPS PER HELICOL COLLECTOR TWO EACH FOR UPPER & LOWER HEADERS IS ADEQUATE FOR WIND CONDITIONS TH RU VULT 160-MPH, EXPOSURE _ D, RISK CATEGORY II.
6.GREATER WIND FORCES REQUIRE THE USE OF A THIRD GATOR CLAMP EACH ON THE UPPER AND LOWER HEADERS.
7.GATOR CLAMPS ARE LAGGED THRU THE ROOF INTO STRUCTURAL FRAMING (MINIMUM 5/16-INCH DIAMETER, MINIMUM 3-INCH THREAD EMBEDMENT) ON SHINGLE & MEMBRANE ROOFS.
8.TILE ROOFS REQUIRE THE USE OF A CO NTINUOUS Z-BAR UNDER EACH HEADER. THE Z-BARS ARE ATTACHED BY CONCRETE SCREW TO EACH TILE CONTACTED. THE GATOR CLAMPS SCREW THRU THE Z-BARS. REFER TO OEM MANUAL. THE TILES AT EACH ANCHOR POINT SHALL BE BONDED TO ROOF COVERING WITH A SOLID FSM (FOAM SET METHOD) BED OF DOW TILE BOND HTTP://BUILDING.DOW.COM/NA/EN/PRODUCTS/ADHESIVES/TILEBOND.HTM
9.ENGINEER HAS EVALUATED THE INSTALLATION COMPONENTS AND HARDW ARE CURRENTLY PROVIDED AS HELICOL OEM INSTALLATION KITS AND FOUND THEM TO MEET THE REQUIREMENTS OF THE FLORIDA BUILDING CODE. THERE SHALL BE NO SUBSTITUTION OF OTHER VENDOR MATERIALS WITHOUT PRIOR APPROVAL OF ENGINEER THRU OEM.
10. PLUMBING SHALL BE PER FIGURE 1 (WITH OR WITHOUT THE DESIGNATED O PTIONAL ITEMS). FLORIDA PLUMBING CODE SHALL BE ADHERED TO WITH PARTICULAR ATTENTION TO PIPE SUPPORT, PER FPC TABLE 308.5, THE ABS VALUE OF 4-FT SHALL BE TAKEN AS THE MAXIMUM FOR HORIZONTAL AND 10-FT FOR VERTICAL SOLAR PIPING. CONTRACTOR SHALL INSTALL THE SYSTEM ACCORDING TO THE MANUFACTURER'S WRITTEN INSTALLATION MANUAL.
11. INSTALL TAPCONS PER MANUFACTURER INSTRUCTIONS
HTTP://WWW.CONCRETESCREWS.COM/CONCRETE-SCREW-INSTALLATION.ASPX .
12. FOAM SET METHOD AVOIDS ANY PENETRATION OF THE ROOF COVERING BENEATH T HE TILE. WATERPROOFING OF OTHER ROOFS SHALL RELY UPON A GENEROUS PUDDLE OF FLORIDA NOA/PCA APPROVED ROOFING SEALANT BETWEEN GATOR CLAMP AND ROOF COVERING. AS AN ALTERNATE, WITH APPROVAL OF AHJ, CONTRACTOR MAY SUBSTITUTE A FLASHING DETAIL OF HIS PREFERENCE FROM NRCA ROOFING & WATERPROOFING MANUAL OR OTHER RECOGNIZED PROFESSIONAL PUBLICATION.
13. CONTRACTORS, INSPECTORS, AHJS AND OTHERS HAVING QUESTIO NS MAY CONTACT ENGINEER DIRECTLY - OFFICE: 813 909 1956, E-MAIL: [email protected].
ALLEN GEZELMAN 16502 HANNA RD. LUTZ, FLORIDA 33549
PH. 813 650 7246
APPLICABLE CODE:
ASCE 7
COMPATIBLE WITH:
ASCE7-10
THIS IS A SINGLE
SHEET PLAN
COMPONENT AND CLADDING LOADING DIAGRAMS
DRAWN: SB CHECKED: AG
0223S.AS_HELICOL_FL.dwg
2010 FLORIDA BUILDING CODE
TESTING & CERTIFICATION NOTE:
SOLAR POOL HEATING COLLECTORS ARE REQUIRED TO BE TESTED, CERTIFIED AND LISTED BY THE FLORIDA SOLAR ENERGY CENTER. THE COLLECTORS LISTED ON THIS PLAN COMPLY. THEIR FSEC LISTINGS AND RATINGS MAY BE VIEWED ONLINE AT:
HTTP://WWW.FSEC.UCF.EDU/EN/INDUSTRY/TESTING/STCOLLECTORS/POOL_RATINGS/INDEX.HTM
COPYRIGHT & INTELLECTUAL PROPERTY NOTICE
• THIS PLAN SET IS COPY RIGHT PROTECTED AND CONTAINS I
NTELLECTUAL PROPERTY WHICH BELONGS TO ALLEN GEZELMAN PE.
• ACCESS IS GIVEN TO THE INFORMATION HEREON SOLELY FOR
THE PURPOSE OF COMPLETION OF THE PROJECT FOR WHICH IT IS INTENDED.
• NO OTHER USE MAY BE MADE OF THE INFORMATION, DRAWING
S, OR IDEAS HEREON WITHOUT THE EXPRESS, WRITTEN, PERMISSION OF ALLEN GEZELMAN PE
VALIDITY:
VOID WITHOUT RAISED OR ELECTRONIC SEAL, MAY NOT BE USED FOR PLANS ON FILE, EVERY PERMIT PULLED REQUIRES A SEALED ELECTRONIC PLAN OR SEALED ORIGINAL PAPER COPY OF THIS PLAN
ENLARGED VIEWING:
HTTP://WWW.GEZELMANPE.COM/GENERIC/0223S.AS_HELICOL_FL.PDF
7/15/2012 2:56 PM
PZ 1 PZ 2 PZ 3
05
SCALE: N/A
ENGINEERING NOTES
EJCDC C-700
ALL AFFIDAVITS, DESIGNS, OPINIONS, CALCULATIONS & OTHER ENGINEERING SERVICES PROVIDED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON ANY AND ALL PROJECTS ARE SUBJECT TO THE PROVISIONS OF EJCDC C-700 (ENGINEERS JOINT CONSTRUCTION DOCUMENT COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCT ION CONTRACT) CURRENT AT THE TIME. THOSE OBJECTING TO SAID EJCDC C-700 OR P ROVISIONS THEREOF ARE DIRECTED NOT TO USE THE A FFIDAVIT, DESIGN, OPINION, CALCULATION OR OTHER ENGINEERING SERVICE OFFERED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON THE PROJECT. EJCDC C-700 MAY BE VIEWED AT: HTTP://GEZELMANPE.COM/REFERENCE/AG/C-700.PDF
NO PZ3 USE IN HVHZ
SOLAR UNIT (THERMAL OR PV) WIND FORCES
OEM:
ATTACHMENT DETAIL
SCALE 1-1/2" = 1'-0"
Z BAR
HELICOL COLLECTOR ON Z BAR GATOR CLAMP
HELICOL COLLECTOR HEAD ASSEMBLY
HELICOL GATOR CLAMP ASSEMBLY
SCALE: NTS
S5 CLAMP SYSTEM
http://www.heliocol.com/
Page 2
Residential Installation Manual
Swimming Pool Solar Heating System
Heliocol 2011
Revised 09/11
Page 3
Disclaimer:
Before attempting installation, read these instructions carefully. This manual contains easy to follow step-by­step procedures to properly install a Heliocol system. A little time spent understanding the system and its parts will assure a successful, trouble-free installation. If you have any product or installation questions regarding this system, contact your Heliocol Representative. When working on or around your roof or pool, please take care to avoid hazards such as electrical wires and loose shingles or tiles. CAUTION! Safety comes rst!
It is important to recognize that this manual outlines the recommended installation methods and practices as prescribed by the factory. It is designed to aid a seasoned contractor or novice do-it-yourself individual while providing optimum protection for the products. It is not designed to override any local codes or ordinances. Also, these are the minimal requirements; additional hardware or protection may be required in hazardous environments or in areas subject to extremes of weather or microburst climate events. In those areas, the lo­cal expertise of the contractor may be relied upon in coordination with factory approval for special installation considerations.
1
Page 4
Introduction
Welcome to the Heliocol Family
Heliocol Solar Collectors are manufactured utilizing state-of-the-art solar technology and the most advanced production techniques. Heliocol collectors are sleek and simple, yet the pat­ented over-molded design makes Heliocol durable enough to last a lifetime. However, a pro­fessional installation is very important to the overall success of a system. Installed properly, a Heliocol System will be virtually maintenance free as it captures free, abundant and reliable heat from the sun year after year. Whether you are a seasoned contractor or a homeowner installing your own system, this manual will give you a great deal of valuable information.
Take time to read through this manual. It will guide you through the most efficient way to cor­rectly install a Heliocol Solar System. By following this step by step guide, your system will meet the installation standards recommended by the factory (see disclaimer on page 1). In addition, because we’ve included techniques and tips gathered from experienced Heliocol contractors throughout the country, using this installation guide will save you time and effort.
Table of Contents
Introduction Getting Started Collectors and Installation Kits Parts List Solar Collector Layout and Hydraulics Connecting the Solar Mounting the Solar Collectors on a Flat Roof Assembly of Row Spacer Kits Connecting the Solar Collectors to the Feed and Return Lines Running the Feed and Return Lines from the Roof to Ground Level How to Connect the Solar Collectors to the Existing Pool Filtration System Pressure Testing the Heliocol Solar System Operating and Check-Out Procedures Installation Troubleshooting Specications
2 3 5 6 7 12 13 14 15 16 18 20 21 22 24
2
Page 5
Getting Started
Before you begin your installation, here are a few important tips:
1. Caution – Safety Comes First
There is no substitute for safety. Always exercise ex­treme caution, care and good judgments when working on or around a roof or pool area.
• Please take care to avoid hazards such as over­head electrical wires or loose shingles or roof tiles.
• Be sure to secure ladders so they will not slip or fall.
• Do not allow extension cords to lie in the pool or in standing water.
• Wear shoes with proper tread to prevent slip­ping on the ladder or sloped roof areas.
• Disconnect all power to the pool equipment when installing an automatic control system.
2. Always consult with the proper authorities or check
with your local building department for the permit re­quirements and codes applicable before you start your job. Some installers prefer to use white pipe and ttings on the roof, then paint the pipe and ttings a color that closely matches the roof. The paint should be outdoor rated and UV resistant. Painted pipes and ttings will require additional maintenance. Most building depart­ments require permits for installing solar pool heaters, a practice strongly supported by Heliocol.
3. Before starting any work, determine the location of
your system and prepare a schematic drawing of the installation area. Include the location of the feed and return lines in this drawing. Roof areas often times look bigger than they really are, so be sure to measure the available area before making your schematic. Be sure the planned placement of the collectors will allow the collectors to drain when the pool pump shuts off.
4. To ensure a trouble-free system, don’t take short-
cuts. Whenever possible, collectors should be installed so that they are accessible without being walked on. Walking on the collectors should only take place when absolutely necessary.(Never walk on collectors when they are wet as they present a signicant slip hazard)
5. Familiarize yourself with all of the Heliocol com-
ponents and plumbing materials that you will need to complete the installation. Here is a list of materials most commonly used:
Pipe
Use pressure rated Schedule 40 PVC pipe. You may prefer to use black, as opposed to white, PVC pipe on the roof for aesthetic reasons. But because black PVC can be difficult to nd, some installers have inquired about the use of black ABS pipe instead. DO NOT USE ABS PIPE. ABS pipe does not have the UV inhibitors that PVC pipe has, causing ABS pipe to become brittle and to crack after several years of exposure.
Pipe Fittings
Use PVC Schedule 40 pressure-rated ttings to match your PVC pipe. Be sure NOT TO USE “plumbers” t­tings or DWV ttings (drain, waste and vent). Because black PVC ttings are difficult to nd, some installers use spray paint to paint them black. Should you do so, it is necessary to use a high-quality paint, preferably with UV inhibitors. Do not use inexpensive “discount store” brands as these will fade and peel very quickly.
PVC Cleaner and Cement
It is important to both CLEAN and CEMENT each PVC joint. Use a quality, brand-name product and refer to the product’s label for specic directions for use. Before applying cement, be sure to clean each tting and pipe end with the PVC Cleaner or “primer.” Soon after clean­ing each part, apply ample cement rst to the tting and then to the pipe end. Insert the pipe end into the tting with a slight twisting motion until it seats to evenly distribute the glue. Hold it in this position for 5 to 10 seconds to allow the joint to set up. Finally, wipe excess cement off of the joint and pipe. When gluing CPVC ttings to PVC pipe, such as the Heliocol 117 Pipe Connector, it is necessary to use a good quality CPVC all-purpose cement.
Note: Cold weather slows the set-up process for PVC glue. If installing in colder climates, refer to the PVC glue manufacturer’s charts for curing times.
Miscellaneous
Depending upon your specic job, you will need other
3
Page 6
plumbing items and materials such as: PVC valves, stain­less steel lag bolts, polyurethane caulk, silicone spray, pipe straps, black electrical wire ties, electrical wire nuts, 18ga-22ga sensor wire, 12ga-14ga electrical wire with ground, Teon tape, concrete anchors and screws, elec­trical conduit, etc. Be sure to us quality products that will withstand direct sunlight year after year.
Tools
Planning ahead and having the proper tools and materi­als on the job will make your installation much easier. Typical tools and materials that are useful to have are:
• Flat head and Phillips head screwdrivers
• Power drill with bits, 5/16’ and 7/16”
sockets and drivers
• Pipe cutter or hacksaw
• Hammer
• Level
• Marking pen
• Silicone Lubricant
• Safety belts
• Lanyards
• Ropes
• Hard hats (where required)
• Garden hose
• Tape measure
• Channel lock pliers
• Caulking gun
• Ladder
• Chalk line
Note: While this manual explains how to install Heliocol Solar Collectors properly in typi­cal situations, it cannot address all the unique or individual circumstances possible. If you have any installation questions, contact your Heliocol Representative for assistance. As the installing contractor, you are responsible for exercising good judgment when in­stalling Heliocol Systems to protect the long term integrity of the collectors as well as the mounting surfaces.
4
Page 7
Collectors and Installation Kits
Heliocol Components
There are three Heliocol components to each system— collectors, collector kits and row kits. For each Heliocol Collector that you install, you will need a collector kit. For each row (bank) of collectors that you install, you will need a row kit. To go around vents or pipes larger than six inches (chimneys, skylights or changes in roof elevations), you will need a row spacer kit. Refer to the kit contents table below for more information regarding these kits.
PK: Collector Kit
One of these kits is required for each collector. It contains the parts necessary to connect the collectors together and mount them on the installation surface.
RK: Row Kit
One of these kits is required for each row (bank) of col­lectors. It contains the parts necessary to connect the collectors to the feed and return lines or collector header.
Kit Contents
RSK: Row Spacer Kit
One of these kits is required if you need to bypass a vent pipe or obstacle larger than six inches. It is also used to connect collectors that are on different roof lev­els or that are facing different directions into one row. It contains the parts necessary to connect the collectors to the PVC pipe between them.
Other Kits
PTK: Pressure Testing Kit
This kit gives you the components you need to pres­sure test the system once the installation is complete.
RTK: Repair Tool Kit
In the event a collector is damaged, this kit contains everything needed to make a repair to a riser tube.
PK RSKRK PTK RTK
106A 110 Short 110 Long 113
117 140 141 142 130 133
GATOR CLAMP GATOR CLAMP
Y
Other Installation Components Referred to in this Manual
110BTS 111 116 120 121A 124 125
1/4” x 4” STAINLESS STEEL LAG BOLT
“G” PIPE CLAMP
1/4” X 1-1/2” STAINLESS STEEL LAG BOLT
126 127 1790 3344 5210
1/4” X 2” STAINLESS STEEL LAG BOLT
5
Page 8
Parts List
106A
End Cap
Pipe Connector
100 Short
HC-0110 SHORT
ALLIGATOR CLAMP
Gator Clamp
117
113L
(Latch)
113B
(Bottom)
113T
(Top)
(Gasket)
113
Collector Clamp
100 Long
HC-0110 LONG
Gator Clamp
ALLIGATOR CLAMP
113G
142
Pressure Test “T” Assembly
133
1/4” Chisel
140
1/2” Ball Valve
141
Pressure Gauge
130
Pin Insert Tool
6
Page 9
Solar Collector Layout and Hydraulics
Shown Below are the Most Common Solar Collector Installations
Fig. 1.1 - Single Row
Fig. 1.2 - Double Row
Fig. 1.3 - Single Row Spit Feed
Fig. 1.4 - Series Feed
Note: No more than two (2) arrays are allowed in series feed
7
and no more than eight (8) collectors are allowed in each array.
Page 10
Roof Orientation
Collector Congurations
(Northern Hemisphere)
Ideally, collectors should be located on a south-facing or at roof, or on an elevated, ground-mounted rack facing south. The next best orientation is west, then east. Fi­nally, if arrangements are maid for proper draining, then low-pitched or at. A collector should never be installed on a north roof without a reverse rack in the northern hemisphere.
Choosing the Right Size Collector
The roof space available to you will determine which model collector to use. Since Heliocol manufactures col­lectors in ten different sizes, you have great exibility in what you can design. The ten collector sizes are:
Model #
8
9.5
10.5
12.5 *15.5 30 38 40 50 *62 *Special Order
Whenever possible, the 50 should be used. This will:
• Reduce your total collector cost
• Reduce labor and installation material cost
• Reduce the length of the solar array
• Reduce the number of roof penetrations
• Produce a more attractive installation
However, unique roof designs may require a combina­tion of different size collectors to best cover the roof area.
Nominal Size
1’ x 8’ 1’ x 9.5’ 1’ x 10.5’ 1’ x 12.5’ 1’ x 15.5’ 4’ x 8’ 4’ x 9.5’ 4’ x 10.5’ 4’ x 12.5’ 4’ x 15.5’
There are many ways to congure a solar array. The most common and preferred is in one continuous row as in Fig.
1.1. There are, however, recommended limits to the number of collectors that can be installed in this way to achieve even ow throughout the array. The maximums are:
Model #
30 40 50
52 There are conditions which may exist, especially on exist­ing pools, where the pump used for ltration is inadequate to generate enough ow (GPM). Because of the unique design of the Heliocol collector, arrays of collectors can be plumbed in series (Fig. 1.4). Specic rules apply for series feeding regarding the number of collectors in arrays and drain-down considerations. Please contact a factory repre­sentative for assistance with design criteria.
Maximum Per Row
12 10 8 7
Pump Horsepower
The horsepower of your swimming pool ltration pump must be adequate to supply the solar system with enough water to provide the recommended ow rate necessary for the collectors being installed. These recom­mended rates in gallons per minute (GPM) are:
Model #
10.5
12.5 30 40 50 62
For example; if you are installing ten 40 collectors, your pump must be able to deliver 40 GPM to the solar array. These ow rates may be exceeded by as much as 100% without any detrimental impact on the performance of the system. The existing pool recirculation pump is typically adequate for recirculating the water through the solar system. Generally, a 1 horsepower pump is sufficient for a standard pool solar system unless there is an unusually long pipe run a high roof or a large number of collectors. If you are not sure what your pump ow rate is, consult your Heliocol representative or pump manufacturer for the pump’s ow characteristics.
Minimum Flow
1 GPM 1 GPM 3 GPM 4 GPM 5 GPM 6 GPM
8
Page 11
Plumbing
It is important that you use the proper size PVC pipe for the size of the solar array. Using a pipe that is too small will produce too much restriction to the water ow and unnecessarily reduce the ow rate to the collectors. Use the following as a guide:
Flow Rate
0 to 45 GPM 46 to 80 GPM
For larger ow rates, consult your Heliocol representa­tive for the proper pipe size or alternative series plumb­ing techniques which will reduce the necessary ow rates on larger systems.
Plumbing runs should be as short as possible and the “hot return” pipe should have the shortest run to reduce potential heat loss in this pipe. Pipes should be sup­ported with pipe clamps or “G” pipe clamps at least every four feet to prevent sagging. (Check the plumbing code in the local jurisdiction.) The pipe clamp used on pipe returns across a roof should be ½’ larger than the pipe diameter to allow for expansion and contraction. The pipe clamp used on vertical roof piping or piping running up the sides of the building should be the same size as the pipe diameter to prevent vibration and to assure a professional-looking installation.
Since 90 degree elbow ttings produce a high restric­tion to ow, you will want to use a few as possible. Keep this in mind when planning your plumbing runs. Their use cannot be avoided, but with careful forethought, you will use the least number possible. Occasionally, the use of two 45 degree ttings will eliminate a 90, but it is not necessary to always use them as this will run up the expense of your materials.
Recommended Pipe Size
1 ½” 2”
Balanced Flow
When you have to split a solar system (Fig. 4.2 or Fig.
4.3, pg. 7) it is critical that the shown plumbing runs be followed to assure equal water ow through both rows of collectors. Since water will follow the path of least re­sistance, if one plumbing run is shorter than the other, more water will ow through it than through longer one. Keep this in mind if you design a collector layout differ-
ent than the examples. Your Heliocol representative can also assist with this and explain the use of “balancing valves” on larger systems.
If you are installing the solar collectors on a at roof or at ground rack, the top (return) header of the collec­tor should be a least 3” higher than the bottom (feed) header to assure equal ow through all of the tubes of all of the collectors. (See pg. 13) To achieve even distri­bution of water throughout the row of collectors, proper ow rates and a little back pressure should be present.
Automatic Drain Down
The collectors and the PVC pipe should be installed so the water will drain out of them when the pool pump shuts off. This is especially important in areas of the country where freezing conditions occur. (The Heliocol
solar pool collectors are warranted against internal freezing when installed to allow for drain down.) To
allow for the water to drain a vacuum breaker, 121 is installed on the solar feed line above the non-positive 3-way valve as shown on page 18, Fig. 15. (Non-positive means that the valve allows for water to drain back through the valve even when in the off position. If you have a 3-way valve that is not non-positive, you can make it so by drilling a 1/8” hole in the diverter.) If, as a result of a unique roof design or adverse pool equip­ment location, it is not possible to achieve complete automatic drain down, manual drain down valves should be installed in appropriate places in the plumbing or at the end of the bottom (feed) header. Instead of installing an end cap 106A at the end of the header, you would place a pipe connector 117, a 1 ½” slip x 1/2” threaded PVC reducer bushing along with a ½” boiler drain 140. These valves should be opened when shutting down the system for the winter months or when freezing condi­tions are possible. On at roof installations, it might be necessary to open the collector connections at the end of the swimming season and manually lift the collectors to evacuate all the uid from the system. Your Heliocol representative can assist you with the parts necessary for manual drain down installations.
9
Page 12
Mounting the Solar Collectors Using Gator Clamps
The beauty of the Gator Clamp installation is its simplic­ity. It can be used on just about any type of roof or rack installation.
Collector Header (Top)
113T Collector Clamp Top
113L Latch
113G Gasket
Fig. 2 113B Collector
Clamp Bottom
110 Long Gator Clamp
HC-110 Long Alligator Clamp
110 Short Gator Clamp
HC-110 Short Alligator Clamp
For rack systems, asphalt shingle roofs or tile roofs, fol­low these simple steps:
1. Snap a chalk line across the roof or rack where you want the top edge of the collectors to be located. The collectors should slope slightly down toward the feed end of the array for proper drainage.
2. Locate the center of the rst truss/rafter you plan to start from and drill a pilot hole where the rst lag screw will penetrate the roof. After verifying the pilot hole properly penetrated the structural wood truss or rafter, measure and mark off the center-to-center truss dimen­sions for the rest of the trusses being used. This as­sumes trusses are located on 24” centers. Position the rst clamp on the chalk line six (6) inches in from the top corner of the rst collector. The rst collector will be the one that is connected to the feed line at the bottom header.
3. Subsequent clamps should be spaced out evenly along the chalk line every 24”. Each clamp can be located anywhere along the top header to match up to the spacing of the roof rafters as long as there is a 2” space between the edge of the clamp and the ribs (See “ribs” in Fig. 14, pg. 17) on the collector header that exist every one foot. This allows for horizontal expansion and contraction. For barrel tile roofs, each clamp needs to
be positioned so that it is centered on the top ridge of a tile, still as close to 24” centers as possible.
4. Since normal horizontal expansion and contraction of an array of collectors takes place every day as collec­tors heat up and cool down, it is preferable to lock the center of each array in place so that the expansion and contraction takes place evenly to the left and right of this center point. The center collector of an array may be locked in place by locating the clamps on that collector adjacent to the left and right of one of the header ribs. (Fig. 4, pg. 11) these clamps should be attached using two lag bolts as opposed to one. Do not use this proce­dure more than once on any array of collectors.
5. Apply ample sealant to the bottom of the clamp over the hole or holes where the anchor bolt will attach (be generous with sealant). (Fig. 5-A, pg. 11) Position the bottom portion of the clamp perpendicular to the chalk line with the lower hole being placed right on the chalk line. Lag the clamp to the roof through the lower hole using a 1/4” x 4” S.S. lag bolt. (Fig. 5-B, pg. 11) For bar­rel tile roofs, place four (4) 110BTS barrel tile spacers underneath each clamp by inserting the four feet of the barrel tile spacer into the four corners of the bottom of the clamp. (Fig. 6, pg. 11)
6. The bottom of the clamp is designed to grip the roof’s
10
Page 13
surface to avoid rotation back and forth; however, if the roof surface is particularly hard or slick you can use an additional lag bolt in either the top or center hole.
7. To ensure proper spacing, hang the top headers of collectors in the bottom portion of the clamps attached to the roof as you go. Once again, be sure clamps are at least 2” away from each ridge along the header. (Fig. 5-D)
8. Once all clamps are properly lagged to the rack or roof surface, and all the collectors are hung in place, connect the top headers of each collector using 113 collector clamps. Snap the top portion of each clamp over the collector header onto the bottom portion of each clamp by pushing down rmly. (Fig. 5-C)
9. Install two (2) SS screws (#6 x ¾) to secure clamp top to clamp bottom assembly.
10. Attach the bottom headers of the collectors with 113 collector clamps.
11. Locate and mount the clamps (2 each) along the bottom header, aligned with the upper header clamps. The bottom clamp should be installed allowing a large gap on the top, allowing for contraction.
12. Attach feed and return lines following Heliocol’s published guidelines.
13. The corners where the feed and return are located should be fastened down by pipe straps that are also supporting the pipe.
Note: Additional clamps are required for sur-
Pipe Strap
faces with a pitch of 10/12 or greater.
Note: To allow for vertical expansion and con­traction, any clamps installed on the bottom header must be positioned so that the header is in the middle of the cradle. (Fig. 7)
Pipe Strap
Fig. 3
Fig. 5-A
110BTS
Gator Feet
11
110BTS
Gator Feet
Fig. 4
Fig. 5-B Fig. 5-C Fig. 5-D
Fig. 6
Fig. 7
Page 14
Connecting the Solar Collectors Together
In subsequent pages of this installation manual, you will be instructed to connect Heliocol collectors together by using the 113, plastic collector clamps. It is helpful to familiarize yourself with this procedure ahead of time. To assure a proper connection, follow these steps:
1. Lay two collectors next to one another with riser tube spacer bars on the bottom. Lay an 113 plastic collector clamp top, bottom, gasket and latch at both ends where the headers meet. (Fig. 8-A)
2. Clean the groove of both headers.
3. Spray the gasket with a silicone spray only. (An easy way to do this is to put all of the gaskets in one plastic bag. Spray silicone into the plastic bag to lubricate all of the gaskets at once.)
4. Insert gasket into the groove of one of the headers. (Fig. 8-B) (Half in, half out.)
Fig. 8-A Fig. 8-B
t
5. Place the bottom half of the plastic collector clamp (113) under the header end with the larger at portion facing the roof.
6. Seat both headers together by inserting the gasket into the opposite header groove and placing the ends of both headers into the open space in the plastic collector clamp bottom. (Fig. 8-C)
7. Interlock the top half of the plastic collector clamp with the tab on the bottom half. Swing top half closed over top of headers. Caution: Be sure to align top and bottom so riser tubes pass through notch space in interlocking end of collector clamp. (Fig. 8-G) Lock both halves of the clamp together using the latch. (Note: Slide large end of latch over small end of plastic collec­tor clamp assembly. (Fig. 8-D and Fig. 8-E)
8. Use channel lock pliers to tighten the latch grip by squeezing it with reasonable force until it seats ush or even slightly farther so it cannot slide out of its position. (Fig. 8-F)
9. Repeat the procedure to connect the bottom headers of the collectors.
Fig. 8-C
Fig. 8-E Fig. 8-F
t
Notch Space
t
Fig. 8-D
Riser Tube
Note: Now using four (4) Gator clamps, neither the top or bottom header touches the roof.
Fig. 8-G
12
Page 15
Mounting the Solar Collectors on a Flat Roof
Multi-Ply Flat Roof
Single-Ply Flat Roof
13
Asphalt Built Up Flat Roof
Page 16
Assembly of Row Spacer Kits
When you need to install collectors over an obstruction larger than six (6) inches wide, or if the obstruction is less than one foot from a collector header, you’ll need a row spacer kit to circumvent the obstruction.
Fig. 9
RSK
Connect the four (4) 117 pipe connectors to the head­ers of the collectors to be connected with a 113 plastic collector clamp using the same procedures outlined in the section on connecting solar collectors together on page 12.
Cut two lengths of 1-1/2” PVC pipe long enough to ce­ment the 117 pipe connectors on each collector to each other.
Cement the PVC pipe to the pipe connectors as shown in Fig. 9.
If the distance between the collectors is over 4 inches, a 2-inch pipe clamp should be used on both pipes to prevent sagging.
Note: When gluing the 117 CPVC pipe con­nectors, it is necessary to use good quality, multi-purpose cement. The spacer bar may need to be cut out of the way if it falls in the obstruction’s path.
Warning: This should not be done between the header and the rst spacer bar as it will possibly pull the riser tube out of the head­er. The Heliocol warranty does not cover leaks occurring from this type of incorrect installation. A row spacer kit could be used for this situation.
Flexible riser tubes are snapped out of the spacer bars to go around small obstructions. The spacer bar may need to be cut out of the way if it falls in the obstruc­tion’s path.(Fig. 10)
Fig. 10
14
Page 17
Connecting the Solar Collectors to the Feed and Return Lines
1. The feed line will be connected to the low end of the bottom header which should be the corner farthest from the pool pump. The return line will be connected to the top header on the opposite end of the array. This gives the heated pool water the shortest route back to the pool.
2. The 106A end caps will be located on the corners of the solar array opposite of the corners where the feed line and return lines will be. Attach the 106A end caps using the 113 plastic collector clamp as described on page 12. (See Fig. 11)
3. Attach the 117 pipe connectors to the corners of the array where the feed and return lines will be, using the 113 plastic collector clamp. (See Fig. 12)
4. The 117 pipe connector allows a 1 ½” PVC street 90 to be glued directly into the socket, or a 2” PVC 90
degree to be glued on the outside. All-purpose cement should be used when attaching PVC ttings or pipe to the pipe connectors to provide for a durable connec­tion. A 90 degree PVC tting and vertical pipe run of at least ve feet should always be attached to the return line pipe connector to allow for lateral expansion and contraction of the return line pipe run.
5. Connect the feed and return pipes using good plumbing techniques.
Note: Be sure to align the top and bottom of the clamp so that the riser tubes can pass through the notch space in the inter­locking end of the collector clamp. A clamp that is improperly aligned can cause dam­age to the riser tubes (See Fig. 13).
Fi g . 11
15
Fig. 12
t
Notch Space
Fig. 13
Page 18
Running the Feed and Return Lines from the Roof to Ground Level
Discussed here is the standard, most straightforward way of running the PVC pipe from the feed and return lines to the equipment pad. Some installations require a more creative approach due to unique roof designs or equipment pad locations. Whenever possible, how­ever, the return line should have the shortest run and all pipes should run slightly “downhill” to allow for auto­matic drain-down of the plumbing and solar array. As discussed earlier, if this is not possible, manual drain valves should be installed as needed.
If your equipment pad is against your house, you may want to complete the necessary plumbing at the equip­ment pad before completing this portion of the instal­lation. This allows you to know exactly where the pipes should come down from the roof. If you will be trenching from the equipment pad to the installation location, this is not necessary.
1. Cement the appropriate size PVC 90 degree elbow to the return line stub facing down toward the bottom header. Repeat the process for the feed line header stub and face the elbow down away from the array (see Fig. 14, page 17)
Note: Whenever cementing, lay a rag on the roof or rack under the joint to avoid dripping cement on the mounting surface. Also, it is a good idea to tape the cans of PVC cleaner and PVC cement together. They are less likely to tip over and spill this way.
2. Determine where the feed and return pipes will go over the edge of the roof. If possible, this should be per­pendicular to the exact points where they will fasten into the existing system or into pipes coming from another location. (See Fig. 15, pg. 18)
3. Measure the distance from the return elbow down to the spot that you want to go, across the roof, to the point established above. Be sure to include the depth of the socket in the elbow in your measurement. Cut a piece of PVC pipe to this length. Repeat this process for the feed line.
the elbows.
5. Measure across the roof from these pipes to the points established in step 3. Cut and de-burr pipes to these lengths and assemble corner with 90 degree elbows.
6. Continue this process around the edge of the roof and down to the existing plumbing, using a level to keep the pipes looking plumb and keeping pipes as short, straight and tight to the building as possible.
7. Once you are satised with the plumbing arrange­ment, go back and cement the joints together using the good plumbing techniques explained in the “Getting Started” section.
8. Secure long pipe runs with pipe clamps or “G” pipe clamps one size larger than the pipe diameter using (116) #14 S.S. hex head screws and polyurethane caulk. Secure vertical pipe runs on the side of buildings with pipe clamps the same size as the pipe diameter using screws and anchors as needed.
Note: All four corners of each row of collec­tors should be surely fastened to the roof. The corners should already be secured with the “G” pipe clamps or pipe straps on the plumbing lines connected to the feed and return lines. The top corner opposite the return corner should already be se­cured by the collector mounting hardware.
Note: Be sure to support all of the weight of the plumbing with “G” pipe clamps or pipe straps. The mounting hardware is not designed to support the weight of the plumbing in addition to the weight of the collectors.
4. If you are not experienced at cutting and tting pipe, it is a good idea to assemble all pipe and ttings before cementing them just in case you make an error. Clean the burrs off these cut pipe lengths and insert them into
16
Page 19
End Cap u
t Return Line
Feed Line q
17
Rib p
Fig. 14
End Cap
p
Page 20
How to Connect the Solar Collectors to The Existing Pool Filtration System
(121)
WIRE TO ROOF SENSOR
(PTK)
(5210)
Manual
(5210)
(3344)
Wire to Optional Motorized Actuator
(1790)
Optional Motorized Actuator
Fig. 15
18
Page 21
How to Connect the Solar Collectors to The Existing Pool Filtration System
Fig. 15 on page 18 shows how a typical Heliocol solar pool heating system is plumbed into existing pool plumbing. This drawing may not be just like every sys­tem you encounter. The feed and return plumbing on a solar system may be reversed, or it may have a different type of lter, or it may have additional equipment such as a chlorinator, pool cleaner, gas heater, etc. It may also have a long run of plumbing from the pool equip­ment to the solar collectors.
Whether the system is like this or not, Fig. 15 will help you understand the ow of water from the pool, through the pump, lter, solar system and back to the pool. Study the diagram and become familiar with the valves needed to connect the solar collectors to the existing plumbing.
Notice that the union check valve is plumbed in after the lter. This prevents the lter from being backwashed by the water draining down from the collectors when the pump shuts off. The three-way valve either diverts the water to the solar system or directly back to the pool. This three-way valve should be a non-positive valve. This enables the water in the solar system to drain back to the pool when the pump shuts off. (If your three-way valve is not non-positive you can make it so by drilling a 1/8” hole in the diverter.) The ball valves on the solar feed and return lines allow you to isolate (completely shut off) the solar system. A check valve can be substituted for the ball valve on the return pipe side if desired.
1. Study the plumbing after the lter and decide where you are going to install the union check valve and the PVC tee tting (See Fig. 15). If you have auxiliary equipment, you may need to re-plumb a portion of your existing plumbing so this equipment is located after the solar system as indicated in Fig. 15.
2. Cut the pipe after the lter where you have decided to locate the union check valve and where your solar return pipe will attach to your existing pool return line. If your pool plumbing is 1-1/2” and you are running 2” plumbing to your solar system, you should be using 2” valves and piping for all of your new plumbing, so you will need two (2) 2”x1-1/2” reducer bushings to adapt your new 2” ttings to the existing 1-1/2” pipe.
3. As discussed earlier in this manual, it is a good idea to assemble all pipe and ttings before cementing them just in case you make an error. Install a union check valve on the pipe coming out of the lter. Be sure that the arrow showing ow direction is pointed away from the lter.
4. The three-way valve will be installed next. It may come right next to the check valve, or you may have to use some pipe and ttings to locate it off of the main line. As stated earlier, use as few 90 degree elbows as possible.
5. Install the ball valve to the solar feed coming out of the three-way valve.
6. Install the 121A vacuum breaker about 4 feet verti­cally above the lter, up the feed line, using a PVC tee and red reducer bushing. Face the tee to the outside as shown in Fig. 12.1. Wrap the threads of the vacuum breaker with Teon tape and screw it into the ¾” threaded reducer bushing.
7. Install the second ball valve or check valve to the solar return line.
8. Now determine where to locate the PVC tee tting. The tee may be located right next to the three-way valve, or elsewhere, depending on your system. Con­nect the tee tting rst to the solar return line, then to the three-way valve, and then to the pool return line.
9. Once you are satised with the plumbing arrange­ment, go back and cement together all joints that you have not already cemented. Use good plumbing tech­niques and use caution not to drip glue or cleaner on existing pool equipment, or inside any valves.
Note: Use pipe-clamps the same size as the outside diameter of your plumbing t­tings to secure the pipe and ttings tightly to the wall.
For a truly professional-looking installation, take time to clean the white PVC pipe. Use a clean rag and pour PVC cleaner on it and then wipe the dirt and identica­tion marks off the pipe. Do this on all exposed pipe. This is also a good preparation if you plan on painting the pipe to match the house color.
19
Page 22
If you are Installing an Automatic System
The basic difference between the manual system just outlined and an automatic system is the use of a motor­ized three-way valve. This three-way valve is operated by a differential control which uses sensors to determine if the solar system is warmer or cooler than the pool water. In this way it can shut the solar system off when cloudy conditions exist and thereby generate the opti-
mum performance from your solar investment. It also allows you to select a maximum pool water temperature so the solar system doesn’t overheat the pool. It ac­complishes this by the use of a sensor on the roof and a sensor installed into the pool plumbing. The directions included with the automatic system components will direct you in the installation of the control and sensors. The three-way valve will be installed as described on the previous page and observing the note above.
Pressure Testing the Heliocol Solar System
Pressure testing the entire solar system provides for a trouble-free installation and takes only about fteen min­utes. Any weak PVC glue joints, ttings or pipe, any im­proper collector clamp connections, will be evident while the system is put under 40 to 50 pounds of pressure.
1. Allow ample time for all glue joints to dry completely. Use this time to wrap up things and to clean up the job site.
2. Wrap the threads of the 142 pressure test “T” Assem­bly, 140 ½” ball valve and 141 pressure gauge with Tef­lon tape. Temporarily replace the 121A vacuum breaker with the 142 pressure test “T” assembly. Thread the 140 ½” ball valve and pressure gauge into the pressure test “T” assembly.
3. Attach a garden hose to the ½” ball valve. Make sure
the ½” ball valve is in the off position.
4. Turn the solar system on to allow the pool pump to completely ll the solar system. (If the pool pump is not operational, shut off the ball valve on the feed line and use the garden hose to ll the system.)
5. Once the solar system is completely full of water, turn off the pool pump or turn the three-way valve to by-pass the solar system. Quickly turn off the ball valves on both the feed and return lines.
6. Turn on the city water to the garden hose and open the ½” ball valve on the pressure test “T” assembly until the pressure gauge reads 40 to 50 PSI and then turn off the ½” ball valve. Turn off the city water.
system for any leaks. A drop in pressure on the pressure gauge indicates a leak in the system.
8. If there are leaks, open the ball valve on the return line to relieve the pressure. Repair any leaks. Repeat the pressure testing procedures as needed.
9. Return the system to normal when through with pressure testing. Be sure to open both ball valves
and replace the pressure test “T” assembly with the vacuum breaker.
(142)
(141)
(140)
7. With the system under pressure, check the whole
20
Page 23
Operating and Check-Out Procedures
Congratulations: If you carefully followed the steps in
this manual, you now have an efficient, professional­looking Heliocol solar pool heating system installation.
Final Visual Inspection:
Since you passed your pressure test at this point, lets visually walk down the entire system and check the fol­lowing items:
1. Verify that the check valves, control valves and vacuum breakers are installed properly.
2. Verify that all plastic collector clamp clips are tight.
3. Verify that all lag bolts are secure and that adequate sealant was used to prevent any roof leaks.
4. Be sure all collector riser tubes are snapped into the spacer bars (except where they go around obstruc­tions).
5. Be sure that collector riser tubes are NOT rubbing on the roof surface between spacer bars. If they are, adjust spacer bars as needed to prevent this or a hole may develop in the riser tube.
6. Be certain that the system will automatically drain down when the pump is shut off or that enough manual drain valves have been included.
7. Verify that all pipe runs are properly supported with pipe clamps.
6. When the solar system is running, you should notice:
• A slightly higher pressure reading on the pressure gauge.
• At midday, if the sun is out, warmer water should be coming into the pool. This water should be 3 to 5 degrees warmer than the pool temperature. Use the back of your hand to better feel the difference in water temperature.
• All the collectors should feel cool to the touch when the sun is on them. (If they are not, see the trouble­shooting section.)
7. During the cooler months of the year, it is essential
that the pool surface be covered at night with a “pool blanket” to maintain a comfortable water temperature. Low nighttime temperatures can lower the water tem­perature more than the solar can recover during the day.
Turning the System Off
1. Turn the pool pump off.
2. Turn the three-way valve so the “closed” indicator
points toward the solar side of the valve.
3. If isolating the collectors, close the ball valves on the
feed and return lines after you are sure all the water has drained out of the collectors and plumbing.
4. Turn the pool pump on to lter the pool as needed.
Turning the System On
1. Turn off the pool pump.
2. Turn the three-way valve so that the “closed” indica­tor points toward the pool side of the valve.
3. Be sure that the ball valves on the feed and return lines are open.
4. Turn the pool pump on.
5. Set the pool pump timer, if used, so that the pump will run when sun is shining on the solar collectors. Usually 10:00 AM to 4:00 PM, but this will vary with geographic location, time of year and the compass location of the system.
21
That’s all there is to it. You have installed a Heliocol solar pool heating system that has been tested and proven worldwide for quality and reliability. If you run into any problems with your installation, or have any future problems, call your Heliocol representative or our corporate office at 800-79-SOLAR.
Page 24
Installation Troubleshooting
Trouble spots may arise during the initial installation of your Heliocol solar pool heater. Generally the primary cause of problems, depending on its age, is the existing pool/pump ltration system. Prob­lems can also arise from installer error or oversight. We are condent that your system will work effectively and efficiently when properly installed and matched to your existing pool/pump lter system. This troubleshooting guide is designed to help your installation go smoothly and work properly the rst day and every day there­after.
There are Air Bubbles in the Pool when the Solar
Heater is Operating
Diagnosis:
There may be air coming into the pump through an air leak on the suction side of the pump due to the pump working harder to move the water through the solar system.
Pump Answers:
Be sure pump trap lid is on tight.
Check the “O” ring on the pump trap lid. Clean, lubri­cate or replace as needed.
If you have a suction type pool cleaner, remove it. If this eliminates the air bubbles, use it only when the solar system is off.
If you have a clear lid on the pump and can see air bub­bles in the trap, use a garden hose to run water over the lid and each joint individually to see if the air bubbles will clear up. If there is not a clear lid, listen to pump noise for a smoother operation. Repair any air leaks.
Diagnosis:
If the vacuum breaker is installed on the roof, there is not enough water pressure in the solar system to keep the vacuum relief valve closed so it is allowing air to be drawn into the water as it ows by the valve.
Install Answers:
Be sure lter is clean. Backwash to reduce pressure.
Locate vacuum breaker on the feed line as shown on page 18, Fig. 15, and put a solid end cap at the end of the top header where the vacuum relief was located.
Using the (5210) ball valve on the return line, throttle back the ow to produce more back pressure on the system.
Some of the Solar Collectors are Warm to the
Touch while Others are Cool
Diagnosis:
There is not equal ow through all of the collectors. Warm collectors indicate low water ow.
Pump Answers:
Be sure the lter is clean. Backwash to reduce pressure.
The pump may not be providing enough water to the solar system. Check water ow using a ow meter. Increase pump horsepower to maintain recommended ow. If there is a suction type cleaner in the pool, re­move it. If this eliminates the problem, use it only when the solar system is off.
Install Answers:
If the system is a single row array and there is adequate ow, using the (5210) ball valve on the return line to throttle the ow back to produce more back pressure on the system. This will even out the ow through the collectors. If the array contains more collectors than the maximum recommended on page 8 of this manual, change the array to a double row or single row split feed as shown in Fig. 1.2 and Fig. 1.3 on pg 7.
If the system is a double row or single row split feed ar­ray and there is adequate ow, install a ball valve on the return side of the set of collectors that are coolest to throttle back the ow through these collectors and force more water through the warmer collectors. If any section of the array contains more collectors than the maximum recommended on page 8 of this manual, make changes as needed to correct this.
22
Page 25
Installation Troubleshooting Continued
Water Coming from the Solar System is not as Warm as it Should Be
Diagnosis:
The water is owing too fast through the collectors.
Install Answers:
Test water ow rate. Refer to the Collector Data for rec­ommended ow on page 24. Adjust the three-way valve to by-pass some of the water.
Diagnosis:
Seasonal normal operation
Answer:
In the cooler months of the year, or on cool, windy or partly cloudy days, the temperature rise through the collectors may only be 2 or 3 degrees. Use the back of your hand to feel the water temperature difference at the pool return inlet.
23
Page 26
Performance Rating
BTUs PER DAY
Certifying Organization 50 40 30 Performance Equations
Int’l Standard ORTECH 47,400 39,400 28,440
National Standard SRCC 47,400 39,400 28,440
Florida Standard 956 BTU’s/ft
Performance Note: Solar scientists agree that there are many variables to consider when properly sizing a system. Wind condition, micro climates, ow rates, orientation and shading of the pool and/or collectors all affect the performance of your system. A BTU rating is just one of the many factors to consider.
2
956 BTU’s/ft
2
956 BTU’s/ft
2
.872 - 3.729 (Ti-TA) / I
X = 1.00-.0316(S) - .0104(S)
K
A
.872 - 3.729 (Ti-TA) / I
KAX = 1.00-.0316(S) - .0104(S)
.828 - 3.26 (Ti-TA) / I
KAX = 1.00 - .11(S)
2
2
Head Loss Per Flow Rate
Heliocol 50
Collector Rating Number
Thousands of BTU’s per day per collector
Category T(°F)
Water Temp.
Minus Air Temp
2,000 BTU/ft
A (-9) 98.74 78.07 57.49
B (+9) 64.13 44.01 23.96
C (+36) 22.91 7.64 0
D (+90) 0 0 0
E (+144) 0 0 0
Solar Insolation
2
1,500 BTU/ft21,000 BTU/ft
Collector Data
Collector Model 50 40 30 12.5 10
Size, Nominal 4’ x 12.5’ 4’ x 10.5’ 4’ x 8’ 1’ x 12.5’ 1’ x 10.5’
Width 47” (120 cm) 47” (120 cm) 47” (120 cm) 11.75” 11.75”
Length 152.1” (380 cm) 127” (323 cm) 91” (231cm) 151.5” 127”
2
Area (sq. ft) 50.0 (4.65 m
Manifold Diameter 2” (5.08 cm) 2” (5.08 cm) 2” (5.08 cm) 2” 2”
Weight (dry) 22 lbs (10 kg) 19 lbs (8.5 kg) 15 lbs (6.8 kg) 5.5 lbs 4.75 lbs
Volume Capacity 3.7 gal (14 L) 3.1 gal (12 L) 2.4 gal (9 L) .93 gal .78 gal
Workin gPressure 90 psi 90 psi 90 psi 90 psi 90 psi
Burst Pressure 270 psi 270 psi 270 psi 270 psi 270 psi
Recommended Flow 5 gpm 4 gpm 3 gpm 1.25 gpm 1 gpm
) 41.6 (3.88 m2) 30.0 (2.77 m2) 12.2 10.2
2
OG-100 Collector Approved OG-300 System Approved
24
Page 27
Notes
25
Page 28
Notes
26
Page 29
Installation Manual
Heliocol is the rst and only solar pool collector in the world to achieve the elite status of ISO 9001:2008 certication. Relatively few manufacturers have the priviledge of placing the ISO 9001:2008 emblem on their products. Only those companies performing at the highest levels in their industries can meet the stringent requirements specied by this demanding international stan­dard. The technical and engineering expertise of Heliocol and their relentless pursuit of continuous product improvement have earned them the world­renowned ISO 9001:2008 certication. Over the two-year process necessary to gain certication, their customer service record, product failure rate and engineering processes were all carefully scrutinized and found deserving of ISO 9001:2008 certication.
The solar energy system described in this manual, when properly installed and maintained, meets or exceeds the minimum standards established by the Solar Rating and Certication Corporation (SRCC). This certication does not imply endorsement or warranty of this product by the SRCC.
Heliocol solar pool collectors are NSF-50 certied. This certication ensures that the water passing through the collectors will be free from unacceptable levels of contaminates and will continue to perform effectively under the intended use conditions.
Loading...