Single Wire Loop with Return………………………………………………………………………………………………………………………11
Twisted Pair with Single Wire Loop………………………………………………………………………………………………………………13
Twisted Pair with Single Wire Loop With Return…………………………………………………………………………………………15
Example (target distance of 88 feet with LMPS-750)
Target Distance factor =
(88 – 75) (0.69 – 0.73)
+ 0.73 = 0.71
(100 – 75)
Configuration
Power supply
Feet
0
15
25
50
75
100
125
150
14 AWG
Twisted pair
extension
(figure 1)
LMPS-350
1 1 1
0.95
0.91
0.66
0.41
N/A
LMPS-DC350
1 1 0.95
0.86
0.74
0.62
0.45
N/A
LMPS-750
1
0.85
0.81
0.77
0.73
0.69
0.57
0.50
Figure 1 : Twisted pair extension
Modules are at the end of an extension.
The electrical conductor is a twisted pair type (example CL3P)
This configuration has the best transport performance signal.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 1 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 1: Distance Factor for Twisted Pair Extension
The distance refers to the distance between the power supply and the first LED module.
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 1 are usually enough to do proper distance factor calculations. If the distance between the power
supply and the first LED module falls between two columns in table 1, it is possible to calculate the distance factor using
linear interpolation.
Watts available for LEDs = 75 watts X 0.77 = 57.75 watts/power supply
Number of power supplies required = 155.25 watts total/57.75 watts/power supply = 3 LMPS-750
Therefore, to distribute the load equally, install 38 modules on each of the first 2 power supplies and install
39 modules on the third power supply for the total 115 modules.
Total system power consumption = 63 watts + 63 watts + 65 watts = 191 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting system
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installations can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
Example (target distance of 88 feet with LMPS-750)
Target Distance factor =
(88 – 75) (0.63 – 0.69)
+ 0.69 = 0.66
(100 – 75)
Configuration
Power supply
Feet
0
15
25
50
75
100
125
150
14 AWG BX
(figure 2)
LMPS-350
1 1 .95
.86
.62
.45
N/A
N/A
LMPS-DC350
1 1 .95
.82
.66
.49
.24
N/A
LMPS-750
1
.84
.79
.73
.69
.63
.52
.36
Figure 2 : BX extension
Modules are at the end of an extension.
This configuration is very practical as it enables use of easily
available armoured BX wire. It can also be used on retrofit
installations where BX wire is already installed.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 2 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 2: Distance Factor for BX Extension
The distance refers to the distance between the power supply and the first LED module.
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 2 are usually enough to do proper distance factor calculations. If the distance between the power
supply and the first LED module falls between two columns in table 2, it is possible to calculate the distance factor using
linear interpolation.
Watts available for LEDs = 75 watts X 0.73 = 54.75 watts/power supply
Number of power supplies required = 155.25 watts total/54.75 watts/power supply = 3 LMPS-750
Therefore, to distribute the load equally, install 38 modules on each of the first 2 power supplies and install
39 modules on the third power supply for the total 115 modules.
Total system power consumption = 63 watts + 63 watts + 65 watts = 191 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting project
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installations can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 3 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 3: Distance Factor for Straight Pair Extension
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 3 are usually enough to do proper distance factor calculations. If the distance between the power
supply and the first LED module falls between two columns in table 3, it is possible to calculate the distance factor using
linear interpolation.
The distance refers to the distance between the power supply and the first LED module.
Watts available for LEDs = 75 watts X 0.69 = 51.75 watts/power supply
Number of power supplies required = 155.25 watts total/51.75 watts/power supply = 3 LMPS-750
Therefore, to distribute the load equally, install 38 modules on each power supply for the total 115 modules.
Total system power consumption = 63 watts + 63 watts + 63 watts = 189 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting project
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installations can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 4 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 4: Distance Factor for Single Wire Loop
The distance refers to the distance between the power supply and the first LED module.
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 4 are usually enough to do proper distance factor calculations. If the distance between the
power supply and the first LED module falls between two columns in table 4, it is possible to calculate the distance factor
using linear interpolation.
Watts available for LEDs = 75 watts X 1 = 75 watts/power supply
Number of power supplies required = 155.25 watts total/75 watts/power supply = 3 LMPS-750
Therefore, to distribute the load equally, install 38 modules on each of the first 2 power supplies and install
39 modules on the third power supply for the total 115 modules.
Total system power consumption = 63 watts + 63 watts + 65 watts = 191 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting project
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installation can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 5 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 5: Distance Factor for Single Wire Loop With Return
The distance refers to the distance between the power supply and the first LED module.
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 5 are usually enough to do proper distance factor calculations. If the distance between the
power supply and the first LED module falls between two columns in table 5, it is possible to calculate the distance factor
using linear interpolation.
Watts available for LEDs = 75 watts X 0.77 = 57.75 watts/power supply
Number of power supplies required = 155.25 watts total/57.75 watts/power supply = 3 LMPS-750
Therefore, to distribute the load equally, install 38 modules on each of the first 2 power supplies and install
39 modules on the third power supply for the total 115 modules.
Total system power consumption = 63 watts + 63 watts + 65 watts = 191 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting project
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installations can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 6 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 6: Distance Factor for Twisted Pair With Single Wire Loop
The distance refers to the distance between the power supply and the first LED module.
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 6 are usually enough to do proper distance factor calculations. If the distance between the
power supply and the first LED module falls between two columns in table 6, it is possible to calculate the distance factor
using linear interpolation.
Twisted pair extension : 50 ft ; Single wire loop: 50 ft
Distance factor : 0.50
Wattage 1 =
95 PolyoptikTM 20˚X20˚ 3000K X 1.35 watts
= 128.25 watts
Wattage 2 =
20 PolyoptikTM 180˚X180˚ 3500K X 1.35 watts
= 27 watts
Total wattage =
128.25 watts + 27 watts
= 155.25 watts
Watts available for LEDs = 75 watts X 0.50 = 37.5 watts/power supply
Number of power supplies required = 155.25 watts total/37.5 watts/power supply = 5 LMPS-750
Therefore, to distribute the load equally, install 23 modules on each power supply for the total 115 modules.
Total system power consumption = 40 watts + 40 watts + 40 watts + 40 watts + 40 watts = 200 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting project
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installations can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
Calculating the wattageof the LEDs to be installed
The following method can also be used to calculate the load on only one power supply or individual sections of the
architectural lighting project. Please note that the “watts per module" value must be taken from the specification sheet of
the appropriate product.
wattage = number of modules X watts per module
total wattage = wattage of module type 1 + wattage of module type 2 + (…)
Applying the distance factor if applicable
If the power supply is installed away from the LEDs, use table 7 below to apply the appropriate distance factor to the
wattage of the power supply.
Table 7: Distance Factor for Twisted Pair Extension
The distance refers to the distance between the power supply and the first module.
Watts available for LEDs = wattage of the power supply X distance factor
The values given in table 7 are usually enough to do proper distance factor calculations. If the distance between the power
supply and the first LED module falls between two columns in table 7, it is possible to calculate the distance factor using
linear interpolation.
Watts available for LEDs = 75 watts X 0.65 = 48.75 watts/power supply
Number of power supplies required = 155.25 watts total/48.75 watts/power supply = 4 LMPS-750
Therefore, to distribute the load equally, install 29 modules on each of the first 3 power supplies and install
28 modules on the fourth power supply for the total 115 modules.
Total system power consumption = 50 watts + 50 watts + 50 watts + 48 watts = 198 watts
Calculating the number of power supplies your project requires
When using a distance factor use the “watts available for the LEDs” instead of the “wattage of the power supply”. Round
the result up to the next integer.
Number of power supplies = total wattage / wattage of the power supply
Please note that HEICO lightingTM’s LMPS-350 and LMPS-DC350 have a wattage of 35 watts and the LMPS-750 has a wattage of 75 watts.
Calculating the system wattage
Take the number of watts of LEDs at the output of each power supply and use the appropriate power curve on figure 8 (p.17)
to determine each power supply’s consumption. The average output power can also be used if the load is distributed evenly
throughout the power supplies.
Calculating the total system power consumption
The total system power consumption equals the sum of the power consumption of each power supply.
Calculating the cost of electricity for a year for the complete architectural lighting project
Please note that “Price of electricity per kW/h” is according to your local electricity rate.
Determining the system efficiency
Due to the high frequency nature of the output of the LMPS power supplies, the input power factor must be used to determine
the system efficiency. Take the input watts of each power supply and use the appropriate power factor curve on figure 9
(p.18) to determine the system efficiency.
Additional Considerations
Distribute the load equally between multiple power supplies. This ensures a uniform level of light across the power
supplies.
Contact HEICO lighting
All calculations are theoretical. Measurements made on the real life installations can differ from the calculations.
TM
for more details about power consumption calculations when using a distance factor.
“A location not normally subject to dampness, but may include a location subject to temporary dampness, as in the case of
a building under construction, provided ventilation is adequate to prevent an accumulation of moisture.” (UL Standard 1598,
publication of 2008)
DAMP LOCATION
“An exterior or interior location that is normally or periodically subject to condensation of moisture in, on, or adjacent to,
electrical equipment, and includes partially protected locations.” (UL Standard 1598, publication of 2008)
It includes exterior locations such as under canopies, marquees, roofed open porches and similar locations. This also includes
interior locations subject to moderate degrees of moisture, such as some basements, some barns and some cold-storage
warehouses. Locations sheltered from the weather are considered damp locations.
WET LOCATION
“A location in which water or other liquid can drip, splash, or flow on or against electrical equipment.” (UL Standard 1598,
publication of 2008)
This also includes outdoor locations, which are any location exposed to the weather. Locations sheltered from the weather
are not considered outdoor locations. Conductors exposed to direct sunlight shall bear the mark “SUN RESISTANT”, “SR”, or similar or be listed as being sun resistant if they don’t bear such marking.
Specifications are subject to change without notice. (Technical bulletin #34)
Factors such as wire construction and the layout and length of the electrical circuit can affect the loading of the power supply. As
those factors are beyond the control of HEICO lightingTM it is the responsibility of the installer to ensure that maximum loading will
not be exceeded.
In wire loop with return configurations the return wire needs to be routed as close as possible from one another and they need to be
tied together at least each foot.
The user is responsible for proper selection of the electrical conductor type that will be used for the specific application; see the
requirements in technical bulletin #27 “Wiring for architectural applications”.
Contact HEICO lighting
TM
for other wire types and distances usage.
IMPORTANT: The user is responsible for the safe electrical and mechanical installation of the power supply and of the suitability
of the wiring system, mounting surfaces and any mounting hardware used. Failure to do so can lead to electrical and mechanical
failure of the system and serious personal injury.
All equipment shall be installed in a neat and workmanlike manner. See NECA 1-2010 standard “Good Workmanship in Electrical
Construction”.
The user is responsible for proper selection of the electrical conductor type that will be used for the specific application; see the
requirements in technical bulletin #27 “Wiring for architectural applications”.
The Class 2 circuit shall be physically separated from other circuit types.
All technical data in this technical bulletin is based on test results and is believed to be correct. However since the end use of HEICO
lightingTM products, usage application and installation, is beyond our control, HEICO lightingTM makes no warranty expressed or implied
as to the fitness of use. Their use shall be solely by the judgment and at the risk of the user notwithstanding any statement in this
technical bulletin.
All equipment shall be installed in a neat and workmanlike manner. See NECA 1-2010 standard “Good Workmanship in Electrical
Construction”.
The user is responsible for proper selection of the electrical conductor type that will be used for the specific application; see the
requirements in technical bulletin #27 “Wiring for architectural applications”.
The modules installed in the same area should have the same bin letter.
For other LED colors, configurations and general information about layouts please contact HEICO lighting
TM
Refer to the product sheet for more information about the
LMPS-350, LMPS-DC350, LMPS-750 power supplies and the VirgoliteTM modules.