Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.
MODEL#
OPERATING INSTRUCTIONS
AND OWNER’S MANUAL
READ INSTRUCTIONS CAREFULLY: YOUR SAFETY IS IMPORTANT TO YOU AND TO OTHERS.
Read and follow all instructions. Place instructions in a safe place for future reference. Do not allow
anyone who has not read these instructions to assemble, light, adjust or operate the heater.
HSU200NG
HSU250NG
HSU300NG
HSU400NG
LARGE UNIT HEATER
FOR RESIDENTIAL/COMMERCIAL USE
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause
injury or property damage. Refer to this manual. For assistance or additional information
consult a qualified installer, service agency or the gas supplier.
-WHAT TO DO IF YOU SMELL GAS
Ǟ DO NOT try to light appliance.Ǟ DO NOT touch any electrical switch, do not use any phone in your buildingǞ Leave the building immediatelyǞ Immediately call your gas supplier from a phone remote from the building. Follow the gas suppliers
instructions
Ǟ If you cannot reach your gas supplier, call the Fire Department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
WWW.HEATSTARBYENERCO.COM1-(866)-447-2197
60266
SAFETY
WARNING:
YOUR SAFETY IS IMPORTANT TO YOU AND TO OTHERS,
SO PLEASE READ THESE INSTRUCTIONS BEFORE YOU
OPERATE THIS HEATER.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result
in serious injury, death or property damage. Be sure to
read and understand the installation, operation, and
service in this manual. Improper installation, adjustment,
alteration, service or maintenance can cause serious
injury, death or property damage.
WARNING: Fuels used in liquefied propane
gas appliances, and the products of combustion of such
fuel, can expose you to chemicals including benzene, which
is known to the state of California to cause cancer and
cause birth defects or other reproductive harm, for more
information go to www.P65Warnings.ca.gov
HSU200HSU250HSU300HSU400
WARNING:
FIRE, BURN, INHALATION, AND EXPLOSION HAZARD.
KEEP SOLID COMBUSTIBLES, SUCH AS BUILDING
MATERIALS, PAPER, OR CARDBOARD, A SAFE DISTANCE
AWAY FROM THE HEATER. AS RECOMMENDED BY
THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES
WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE
COMBUSTIBLES, OR PRODUCTS SUCH AS GASOLINE,
SOLVENTS, PAINT THINNER, DUST PARTICLES OR
UNKNOWN CHEMICALS.
WARNING:THIS PRODUCT CAN EXPOSE
YOU TO CHEMICALS INCLUDING LEAD AND LEAD
COMPOUNDS, WHICH ARE KNOWN TO THE STATE
OF CALIFORNIA TO CAUSE CANCER AND BIRTH
DEFECTS OR OTHER REPRODUCTIVE HARM. FOR MORE
INFORMATION VISIT WWW.P65WARNINGS.CA.GOV
FRENCH ........................................................ 57 - 84
GENERAL INFORMATION
RETAIN THIS MANUAL FOR FUTURE REFERENCE.
FOR QUESTIONS, PROBLEMS, MISSING PARTS BEFORE
RETURNING TO RETAILER PLEASE CALL WITH MODEL
NUMBER AND SERIAL NUMBER OF HEATER:
1-866-447-2194
MONDAY-FRIDAY 8-5 EASTERN TIME
OR E-MAIL USING THE HEATSTAR WEBSITE:
WWW.HEATSTARBYENERCO.COM
In order to provide the best service possible HEATSTAR is
now giving you more ways to get in touch with us. Find
informational videos at:
YouTube: youtube.com/heatstarTV
Large Unit Heater
HEATSTAR’S full line of products are now at:
WWW.HEATSTARBYENERCO.COM
Operating Instructions and Owner’s Manual
2
PRODUCT SPECIFICATIONS
This unit heater is a single input warm air heater with an average thermal efficiency of 80%. All units are to be supplied with single-phase 60 Hz
120VAC power. For specific information on each model, see Table 1.
Dimensional Data
Top View
Rear View
Length
HSU200
HSU250
HSU300
HSU400
Width
FIGURE 1
BTU input BTU outputSize
[BTU/HR][BTU/HR]WIDTHLENGTHHEIGHTWEIGHT[Lbs.]
HSU200
HSU250
HSU300
HSU400
200,000160,00041.3”28.7”24.8”175
250,000200,00041.3”28.7”24.8”180
300,000240,00041.3”28.7”30.3”227
400,000320,00041.3”28.7”38.6”280
TABLE 1: Specifications
BTU input
[BTU/HR]
200,0003,37796045.06501,50021. 7
250,0003,43597655.36501,50021. 7
300,0004,5071,04050.61,0001,56024.8
400,0005,7631,04052.71,0001,56024.8
Entering
Airflow
[CFM]
Outlet
Velocity
[FPM]
AIr Temp.
Rise [ºF]
Motor
[Watt]
Motor
[RPM]
Fan Diameter
Height
Width
[Inch.]
TABLE 2: General Performance Data
START-UP AND PERFORMANCE CHECK LIST
Job Name: ___________________________ Job No.: _____________________________ Date: _______________________________
Job Location: _________________________ City: ________________________________ State/Province: _______________________
Installer: _____________________________ City: ________________________________ State/Province: _______________________
Unit Model No.: _______________________ Serial No.: ____________________________ Service Technician: ____________________
Electrical Connections Tight? _____________________________ Flue Connections Tight? _____________________________________
Supply Voltage ________________________________________ Fan Timer Operation Checked? _______________________________
Gas Piping Connections Tight & Leak-Tested? _______________ THERMOSTAT Calibrated? ___________________________________
Motor Amps __________________________________________ Heat Anticipator Properly Set? ________________________________
Furnace BTU input _____________________________________ Level? ___________________________________________________
Line Pressure _________________________________________
Manifold Pressure W.C. _________________________________
Large Unit Heater
Operating Instructions and Owner’s Manual
3
SHIPPING
The heater is completely assembled. Installation instructions, two
mounting brackets (shipped loose), and a flue transition are included.
Check the unit for shipping damage. The receiving party should
contact the last carrier immediately if any shipping damage is found.
APPLICATIONS
This is not an explosion proof heater. This heater may not be used
in a Class 1 or Class 2 Explosive Environment. Consult your local fire
marshal, insurance carrier, and other authorities for approval if the
proposed installation is in question.
COMMERCIAL/INDUSTRIAL
The heater is designed and certified for use in industrial and
commercial buildings, such as warehouses, manufacturing plants,
aircraft hangars, and vehicle maintenance shops. For maximum safety,
the building must be evaluated for potential problems before installing
the heater system. This unit is certified for use as furnished by the
manufacturer. Do not alter the fan or operate motors at a reduced
speed.
CAUTION: Installation of restrictive devices to the inlet or
outlet of the fan motor may result in premature failure of the
exchanger pipe, overheating of the appliance, or damage to
the components. Do not attach ductwork, air filters, or polytubes to any HEATSTAR unit heater.
STANDARDS, CERTIFICATIONS, AND
GOVERNMENT REGULATIONS
Installation of this gas-fired heater must conform with all applicable
local, state, and national specifications, regulations, and building
codes. Contact the local building inspector and/or fire marshal for
guidance.
In the absence of local codes, the installation must conform to the
latest edition of:
CSA IN USA
Installation of gas unit heaters must conform with local building codes
or, in the absence of local codes, with the current National Fuel Gas
Code ANSI Z223.1.
Installation in aircraft hangars must be in accordance with the current
Standard for Aircraft Hangars ANSI/NFPA No. 409.
Installation in parking structures must be in accordance with the
current Standard for Parking Structures ANSI/NFPA No. 88A.
For installation in a residential garage these units must be installed so
that the bottom of the heater is located no less than 8 feet (2.438m)
above floor. Heater must be located or protected to avoid physical
damage by vehicles. Refer to the National Fuel Gas Code, ANSI Z223.1,
current edition.
Authorities having jurisdiction should be consulted before NFPA
installation. Air for combustion and ventilation must conform to the
methods outlined in ANSI Z223.1, section 5.3, Air for Combustion
and Ventilation, or applicable provisions of local building codes. ANSI
Z83.8 / CSA 2.6 is the standard for Gas Unit Heater Construction. The
National Fuel Gas Code is available from:
American National Standard Institute Inc.
11 West 42nd Street
New York, NY 10036
These units are CSA International design certified. These unit heaters
are certified for installation to combustible material as listed in Table 3 and on unit rating plate. Accessibility and service clearances must be
observed in addition to fire protection clearances.
All electrical wiring and ground for unit must be in accordance with
the regulations of the current National Electric Code ANSI/No. 70.
The National Electric Code is available from:
National Fire Protection Association
1 Batterymarch Park
PO Box 9101
Quincy, MA 02269-9101
CSA IN CANADA
The instructions are intended only as a general guide and do not
supersede local codes in any way. Authorities having jurisdiction
should be consulted before installation. The installation must conform
with local building codes or in the absence of local codes, with the
current CSA B149.1, Natural Gas and Propane Installation Code. All
electrical wiring and grounding for the unit must also comply with the
Canadian Electrical Code CSA C22.1, current edition.
These heaters are CSA International certified for the clearances to
combustible material listed on the rating plate and Table 3. Provide
adequate clearance around air openings into the combustion
chamber, clearances from combustible material, and provisions for
accessibility and for combustion and ventilation air supply. Provision
shall be made for service accessibility to the heater. Note that fire
protection clearances may be exceeded to provide additional space for
service and accessibility. CAN/CGA B149.1-10 is the code for Natural
Gas and Propane Installation.
Copies of these Standards can be viewed or purchased at www.nfpa.
org or www.scc.ca.
GARAGE INSTALLATIONS
Installation in parking structures must be in accordance with the
current Standard for Parking Structures ANSI/NFPA No. 88A.
Installation in repair garages must be in accordance with the current
Standard for Repair Garages ANSI/NFPA No. 88B.
1. In a storage area, clearance from heaters to combustible materials
must be such that the material shall not attain a temperature above
160 �°F by continuous operation of the unit.
2. Eight foot minimum clearance from the floor to the bottom of the
heater must be maintained. Refer to the CSA B149.1, Natural Gas
and Propane Installation Code.
Canada: Refer to CAN/CGA B149.1: Installation Codes for Gas Burning
Appliances and applicable Standards for Public Garages.
Guidelines:
• Heaters must not be installed less than 8 ft. (2.4 m) above the
floor. Minimum clearances to combustibles must be maintained from
vehicles parked below the heater.
• When installed over hoists, minimum clearances to combustibles
must be maintained from the upper most point of objects on the
hoist.
AIRCRAFT HANGAR INSTALLATIONS
Installation of gas unit heaters must conform with local building codes
or, in the absence of local codes, with the current National Fuel Gas
Code ANSI Z223.1.
Large Unit Heater
Operating Instructions and Owner’s Manual
4
IN UNITED STATES: Refer to Standard for Aircraft Hangars, ANSI/
NFPA 409 (latest edition).
1. In aircraft storage and servicing areas, heaters shall be installed at
least 10 ft. (3 m) from above the upper surface of wings or of the
engine enclosures of the highest aircraft that may be housed in the
hangar. The measurement shall be made from the wing or engine
enclosure, whichever is higher from the floor, to the bottom of the
heater.
2. In areas adjoining the aircraft storage area (e.g., shops, offices) the
bottom of heaters shall be installed no less than 8 ft. (2.4 m) above
the floor.
3. Heaters should be located so as to be protected from damage
from aircraft or other appliances needed for servicing of aircraft.
Refer to requirements of the enforcing authorities. Provisions shall
be made to assure accessibility to suspended heaters for recurrent
maintenance purposes.
For installation in hangars, these units must be installed so that
burners and ignition source are located no less than 18” (457mm)
above floor. Heater must be located or protected to avoid physical
damage by vehicles. Refer to CSA B149.1, Natural Gas and Propane
Installation Code current edition.
IN CANADA: In a confined area, the heater must be installed in
accordance with the CSA B149.1, Natural Gas and Propane Installation
Code. Be sure to check with local codes and ordinances for additional
requirements.
Clearances To Combustibles
Front View
Access
Side
Side View
Vent
Connection
Rear
Top
Bottom
Top
Bottom
FIGURE 2
Non-Access
Side
Front
NON-STANDARD BTU GAS
Unless otherwise noted on the rating plate, this heater is designed and
orificed to operate on standard BTU gas. Contact the factory if utilizing
non-standard BTU gas.
INTRODUCTION
This heater is a gas-fired unit heater. This manual provides specific
information related to the Heatstar models. All persons involved with
the installation, operation, and maintenance of the heater must read
and understand the information in this manual.
The intent of this manual is to provide information regarding safety,
design guidelines, installation, operation, and maintenance of the this
gas-fired unit heater. You must read and understand the instructions
and all safety warnings before installing the gas-fired unit heater. This
manual is property of the owner and must stay with the owner or unit
after installation is complete.
CLEARANCES TO COMBUSTIBLES
Clearance to combustibles is defined as the minimum distance
that must exist between the specified feature of the heater and
any combustible items. It also pertains to the distance that must
be maintained from moving objects around the unit heater. A
recommended service clearance is defined as the minimum distance
that is needed to properly service the heater. When installing the
unit heater, clearances to combustible for the model heater must be
maintained. Refer to Table 3 to determine the required distances for
your model.
Unit SideFront Top and
Clearance to
Combustibles
Clearance to
Allow Service
Bottom
60”6”6”6”18”6”
60”18”29”18”18 ”18”
Access
Side
Non-
Access
Side
RearVent
Connection
TABLE 3: Clearances To Combustibles
HEATER COMPONENTS
Prior to installation, verify that the heater’s gas type and voltage (as
listed on the rating plate) match that of your application. The heater
is standard produced for operation with natural gas. In case of use
with LP / propane gas, see Fuel Conversion instructions. Also verify
that you have received the entire heater contents included with your
unit. Materials not included with the unit (e.g. screws, vent material,
threaded rod, etc.) are the responsibility of the installer. Notify your
product representative or the factory of any discrepancy of missing
items prior to installing the unit.
WARNING: Placement of explosive objects, flammable
objects, liquids, and vapors close to the heater may result in
explosion, fire, property damage, serious injury, or death.
Do not store or use explosive objects, liquids, or vapor in the
vicinity the heater.
Large Unit Heater
Operating Instructions and Owner’s Manual
5
Draft Inducer
Heater Subcomponents
High Limit Switch
Flame Sensor
Pressure
Switch
Control
Board
All installation and service of these units must be performed by a
qualified installation and service agency only as defined in ANSI Z223.1
(NFPA 54) - latest edition or in Canada by a licensed gas fitter.
This unit is certified with the controls furnished. For replacements
parts, please order according to the replacement parts list on rating
plate. Always know your model and serial numbers, we reserves the
right to substitute other authorized controls as replacements.
Unit is balanced for correct performance. Do not alter fan or operate
motors at speeds below what is shown in this manual.
Information on controls is supplied separately. The same burner is used
for natural and propane gas.
Manual Reset
Safety Gas
Spark Electrode
Gas Valve
Control Transformer
Switchers
FIGURE 3
INITIAL INSTALLATION CONSIDERATIONS AND
PRE-CHECKS
service, or maintenance can cause property damage, serious
injury, or death. Read and understand the installation,
operating, and maintenance instructions thoroughly before
installing or servicing this equipment.
This manual should be kept for future use for servicing or
service diagnostics. Leave manual with the owner. Do not
discard any literature shipped with this unit. Only a trained,
qualified installation or service personnel may install or
service this equipment.
Do not attach ductwork, air filters, or polytubes to any
propeller unit heater.
Placement of the heater is influenced by many factors. Aside from
safety factors, considerations for the general space and heating
requirements, availability of gas and electrical supply, and proximity of
possible vent locations are a few examples of factors that should all be
considered.
Inspect and evaluate the location of the heater to ensure that the
structural support is adequate to support the unit’s weight. The unit
must be installed in a horizontally level position to ensure proper
operation. To reduce noise attenuation along the structure caused by
vibration of the unit, the heater should be installed within 15 feet of
a primary building support. In the cases where this installation is not
practical or feasible, the use of spring vibration isolators may be used,
so long as they are rated for use of the unit’s weight.
Adequate space around the heater must also be considered in order
to maintain the published minimum clearance to combustibles and
recommended service clearances (see Table 3).
WARNING: Do not locate any gas-fired units in area where
chlorinated, halogenated, or acid vapors are present in the
atmosphere. These substances can cause premature heat
exchanger failure due to corrosion which can cause property
damage, serious injury, or death.
In the U.S., the installation of these units must comply with the
National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest edition and
other applicable local building codes. In Canada, the installation of
these units must comply with local plumbing or waste water codes
and other applicable codes and with the current code CSA-B149.1.
Large Unit Heater
INSTALLATION
NOTICE: High humidity or saltwater atmospheres will accelerate heater
corrosion and reduce useful life. Do not install the heater in locations
where water (in the form of rain, drips, or spray) could fall onto the
gas ignition components.
WARNING: Improper suspension of the unit heater may
result in collapse and being crushed.
Always suspend from a permanent part of the building
structure that can evenly support the total force and weight
of the heater.
Failure to maintain minimum clearance to combustibles may
result in fire and/ or explosion, property damage, serious
injury, or death. Always maintain minimum clearances.
The units are designed to be hung with threaded bolts via the four (4)
threaded inserts on the top panel of the heater:
Hanging Points
7.89 inch
(200.5mm)
9.16 inch
(233mm)
(562mm)
22.13 inch
9.73 inch
(247mm)
18.86 inch
(479mm)
HANGING
POINTS:
For the anchorage
of the unit heater
use 3/8”-16 bolts
or eyebolts
FIGURE 4
The suspension of the heater must conform to all applicable codes
referenced in the STANDARDS section.
To ensure proper operation, the heater must be installed in a level
horizontal position depending on desired location as governed by
clearances, vent connection, air direction, gas supply, electrical supply
and service accessibility.
Be sure the means of suspension is adequate to support the
weight of the unit (see Table 1 for unit weights).
Operating Instructions and Owner’s Manual
6
1.63 inch
(41.5mm)
CAUTION: Do not install units below 7’ measured from the
bottom of the unit to the floor in commercial applications
(unless unit is properly guarded to provide user protection
from moving parts).
Be sure no obstructions block air intake and discharge of unit
heaters.
The minimum distance from combustible material is based
on the combustible material surface not exceeding 160�°F.
Clearance from the top of the unit may be required to be
greater than the minimum specified if heat damage, other
than fire, may occur to materials above the unit heater at the
temperature described.
Allow 18” clearance at rear (or 12” beyond end of motor at
rear of unit, whichever is greater) and access side to provide
ample air for proper operation of fan.
VENTING
Heatstar unit heaters must be vented as described here to properly
direct the flue gases from the unit to the outside atmosphere. The
venting can terminate vertically through the roof (up) or horizontally
through a sidewall (sideways).
WARNING: Gas-fired heaters must be vented. Do not operate
unvented. A built in power exhauster is provided. Additional
external power exhausters are not required or permitted.
Insufficient ventilation and/or improperly sealed vents may
release gas into the building which could result in health
problems, carbon monoxide poisoning, or death. Improper
venting may result in fire, explosion, injury, or death.
Determine that there is not blockage, restriction, leakage, corrosion,
or other deficiencies that can cause hazards. The vent pipe should
be corrosion-resistant galvanized steel of a thickness that meets the
National Fuel Gas Code. Minimum thickness for connectors varies
depending on the pipe diameter. Never vent this unit heater with PVC
or plastic pipe.
WARNING: If replacing an existing heater, vents may require
re-sizing. Improperly sized venting systems can result in vent
gas leakage or condensation. Refer to the National Fuel Gas
Code ANSI Z223.1 (NFPA 54) or CSA B149.1 - latest edition.
Failure to follow these instructions can result in serious injury
or death.
GENERAL VENTING REQUIREMENTS
NOTICE: The vent is a passageway, vertical or nearly so, used to
convey flue gases from an appliance, or its vent connector, to the
outside atmosphere. The vent connector is the pipe or duct that
connects a fuel-gas burning appliance to a vent or chimney.
Do not intermix different vent system parts from different
manufacturers in the same venting system.
Vent connectors serving Category I and Category II Appliances shall
not be connected into any portion of mechanical draft systems
operating under positive pressure.
All joints shall be secured with at least two corrosion resistant screws.
All joints must be checked for gas tightness after installation.
CAUTION: The heater and the venting system shall be
inspected once a year by a qualified service agency.
CAUTION: Installation must conform with local building
codes or in the absence of local codes, with Part 7, Venting
of Equipment, of the National Fuel Gas Code, ANSI Z223.1
(NFPA 54) – latest edition. In Canada installation must be in
accordance with CSA B149.1.
Heatstar heaters come with a factory-installed vent for attaching vent
pipe to the heater. Attach the venting material to the adapter with
three (3) non-corrosive sheet metal screws. If necessary, drill pilot holes
prior to attaching the vent pipe. The venting material must not be
smaller than the factory installed adapter.
WARNING: Do not vent this appliance into another heater’s
vents or through a masonry chimney.
Do not use dampers in the heater vent pipe.
The venting system must be exclusive to a single appliance
and no other appliance is allowed to be vented into it.
Precautions must be taken to prevent degradation of
building materials by flue products.
Single Wall vent pipe must not pass through any unoccupied
attic, inside wall, concealed space, or floor.
Un-insulated single wall vent pipe must not be used
outdoors for venting appliances in regions where winter
design temperature is below freezing.
REPLACING EXISTING EQUIPMENT
If the unit heater is replacing existing equipment and using an existing
vent system, inspect the venting for proper size and horizontal pitch as
directed in these instructions and the latest edition of the National Fuel
Gas Code, ANSI Z223.1 (NFPA 54) or CSA B149.1 Installation Code.
Configuration of the vent termination determines the category type.
All model heaters must be installed in accordance to the requirements
of this section, as well as the requirements of its category
determination, as described in this manual.
All Heatstar Model Requirements:
• Use vent pipe material that is corrosion-resistant galvanized steel
of a thickness that meets the National Fuel Gas Code.
• Do not exceed a maximum vent length as indicated in Table 4.
• Maintain a minimum vent length of 3 feet (914mm).
• Have all vent pipe seams or connectors fastened together with at
least three corrosion resistant sheet metal screws (supplied by the
installer).
• Maintain a 6 inch clearance around all single wall vent pipe from
any combustible materials. For double wall vent pipe (type B)
follow the vent manufacturer’s clearance to combustibles.
• The equivalent length for a 4 inch 90�°elbow is 5 feet.
• The equivalent length for a 6 inch 90�°elbow is 7 feet.
• Avoid using more than two 90�°directional changes in the venting
system.
• Suspend and secure all horizontal runs at points no greater than 3
feet (914mm) apart.
• Vent termination must maintain a minimum distance of 6 feet
from any mechanical air supply inlet.
• Vent must terminate a minimum of 4 feet below, 4 feet
horizontally from, or 1 foot above any window or door that may
be opened or gravity air inlet into the building.
Large Unit Heater
Operating Instructions and Owner’s Manual
7
• Vent must terminate a minimum of 4 feet above grade level
and must extend beyond any combustible overhang. When
condensation may be a problem, the vent system shall not
terminate over public walkways or over an area where condensate
or vapor could create a nuisance or hazard or could be
detrimental to the operation of regulators, relief openings, or
other equipment.
• The vent terminal must be installed to prevent any blockage by
snow and protect building material from degradation by flue
gases.
• The vent cap must be a minimum of 6 inches from the sidewall of
the building.
• Vent must be a minimum of 36 inches below or extend beyond
any combustible overhang.
• Consult NFPA ANSI Z223.1 Gas Vent Termination criteria for vents
that terminate on a roof pitch that exceeds 9:12.
• Canada: vents must terminate a minimum of 3 feet (914mm) from
a window or door that may be opened, and a non-mechanical air
supply inlet or combustion air inlet into the building.
ModelVent Pipe
HSU200
HSU250
HSU300
HSU400
Diameter
4”3’70’
6”3’70’
Equivalent Vent Length
MinimumMaximum
TABLE 4
Vent Pipe Diameters and Equivalent Vent Pipe
Lengths for Horizontal Venting Systems
General Venting Requirements
Listed Terminal
When possible, avoid venting through an unconditioned space. Venting
through an unconditioned space promotes condensation. When
venting through an unconditioned space is unavoidable, or if the unit
is installed in an area that is prone to condensation, insulate venting
runs greater than 5 feet to minimize the production of condensation.
Inspect for leakage prior to insulating the venting and only use
insulation that is non-combustible with a temperature rating of not less
than 500�°F. It is recommended that the venting system is installed
with a tee, drip leg, and clean-out cap as shown in Figure 5.
When venting pipe passes through a combustible interior wall or
floor, a metal thimble with a diameter 4 inches greater than the vent
pipe diameter must be used. If there is 6 feet or more of vent pipe
prior to passing through the combustible wall or floor, then the metal
thimble need only be 2 inches greater than the vent pipe diameter.
If a metal thimble is not used, all clearance to combustibles from the
vent pipe must be 6 inches. Where permitted, type B vent may be
used for the last section of vent pipe to reduce the required clearance
to combustibles when passing through a combustible wall or floor.
When using type B venting, follow the manufacturer’s recommended
clearance to combustibles. Any material used to close or insulate the
opening must be non-combustible.
How to attach a single wall vent terminal to double wall (Type B) vent
pipe:
1. Look for the “flow” arrow on the vent pipe.
2. Slide the vent terminal inside the exhaust end of the double wall
vent pipe.
3. Drill 3 holes through the pipe and the vent terminal. Using 3/4”
long sheet metal screws, attach the cap to the pipe. Do not
overtighten.
How to connect a single wall vent system to a double wall (Type B)
vent pipe:
1. Slide the single wall pipe inside the inner wall of the double wall
pipe.
2. Drill 3 holes through both walls of the single and double wall vent
pipes. Using 3/4” sheet metal screws, attach the 2 pieces of pipe.
Do not overtighten.
3. The gap between the single and double wall pipe must be sealed
but it is not necessary to fill the full volume of the annular area. To
seal, run a large bead of 500�°F silastic around the gap.
“H” Min.
Roof Flashing
Tee with drip leg and
cleanout cap (slope
1/4” per foot
downward toward
drip leg)
Use listed
thimble
through roof
and ceiling
4” Min.
Exhaust
12” Min.
Recommended
FIGURE 5
Large Unit Heater
VERTICAL VENTING
An appliance that operates with a positive vent static pressure
and with a vent gas temperature that avoids excessive condensate
production in the vent is said to be ‘Category III’. This unit heater is
considered a Category III appliance if the venting system meets all of
the following criteria:
• The vent system terminates vertically (up).
• The length of the horizontal portion of the vent run is less than 75%
of the vertical rise length. (e.g.- If the vertical vent height is 10 feet,
the horizontal run is less than 7-1/2 feet).
• Horizontal sections of the vent pipe must be installed with an
upward slope from the appliance at a pitch of 1/4 inch per foot and
suspended securely from overhead structures at points not greater
than 3’ apart.
• The vent terminates a minimum of 5 feet above the vent connection
on the unit.
Operating Instructions and Owner’s Manual
8
Venting Through Combustible Roof or Wall
Specied
Terminal
Roof Flashing
Listed Thimble
FIGURE 6
For vertical vent termination, the venting must comply with all the
General Venting Requirements and with the following vent locations
and clearances:
• Separate air intake duct from vent pipe by a minimum of 4 feet by
placing vent pipes higher than adjacent air intake ducts.
• Utilize a listed type B vent termination cap.
• The vent terminal must extend a minimum of 2 feet above the roof.
• Vent caps should be located a minimum of 2 feet away from
adjoining structures.
• All vertically vented heaters that are Category I must be connected
to a chimney or vent complying with a recognized Standard, or
lined masonry (or concrete) chimney with a material acceptable to
the authority having jurisdiction. Venting into an unlined masonry
chimney is not permitted. Refer to the National Fuel Gas Code.
• Use a listed vent terminal to reduce down drafts and moisture in the
vent.
• Ensure the vent connector runs as short as possible with a minimum
number of elbows. Refer to the (American) National Fuel Gas Code
ANSI Z223.1 or (Canada) CSA B149.1 Natural Gas and Propane
Installation Code for maximum vent and vent connector lengths.
Horizontal run of the vent connector from the induced draft blower
to the chimney/vent cannot exceed the values in Table 4.
• When the length of a single wall vent including elbows, exceeds 5
feet (1.5m), the vent shall be insulated along its entire length with a
minimum of 1/2” thick foil faced fiberglass 1-1/2# density insulation.
If a single wall vent is used in an unheated area it shall be insulated.
Failure to do so will result in condensation of flue gases.
• All vertical type B-1 vents, single wall vents, or listed chimney lining
system must be terminated with a listed vent cap or listed roof
assembly.
• The vent must extend at least 3’ (1m) above the highest point
where it passes through a roof of a building and at least 2’ (0.6m)
higher than any part of a building within a horizontal distance of
10’ (3.05m) unless otherwise specified by the (American) National
Fuel Gas Code, ANSI Z223.1 or (Canada) CAN/CGA-B149 Installation
Code. The vent must extend at least 5’ (1.6m) above the highest
connected equipment flue collar.
HORIZONTAL VENTING
An appliance that operates with a positive vent static pressure
and with a vent gas temperature that avoids excessive condensate
production in the vent is said to be ‘Category III’. This unit heater is
considered a Category III appliance if the venting system meets all of
the following criteria:
• The vent system terminates horizontally (sideways).
• The vent terminates vertically, but the length of the horizontal
portion of the vent run exceeds 75% of the vertical rise length.
(e.g.- If the vertical vent height is 10 feet, the horizontal run is
greater than 7-1/2 feet).
• Horizontal venting sections of the vent pipe must be installed with
a downward slope from the appliance at a pitch of 1/4 inch per
foot.
• The vent terminates below 5 feet of the vent connection on the
unit.
Due to changes to Z83-8 2009 CSA2.6-2009, the use of single wall
B-Vent is no longer permitted as an acceptable material when venting
horizontally, this change covers both residential and commercial
installations. All horizontally vented units manufactured after July of
2011 must be vented as a Category III Unit/Utility Heater in compliance
with UL 1738 & ULS636.
Seal vent pipes with high temperature sealant and three (3) #8 sheet
metal screws. Vent enclosed spaces and buildings according to the
guidelines in this manual and applicable national, state, provincial and
local codes.
You must use venting approved for Category III applications, and
manufactured by a listed vent system manufacturer. For single wall
vent systems, one continuous section of double wall vent pipe may be
used with the vent system to pass through a wall or barrier.
All horizontal Category III vents must be terminated with a listed vent
cap.
Exhaust Vent Construction Through
Combustible Walls
Fiber Glass
Insulation
Min. 2”
Metal
Sleeve
Terminal
Vent Pipe
Diameter
12” Min.
Metal Face
Plate
Vent Termination
Support Bracket
(where required)
2” Min.
2” Min.
Metal
Sleeve
FIGURE 7
Large Unit Heater
Operating Instructions and Owner’s Manual
9
Additional requirements for horizontal venting:
• Category III venting systems may NOT be common vented, and no
other gas units are allowed to be vented into it.
• Vent must terminate a minimum of 3 feet (914mm) above any
forced air inlet that is located within 10 feet.
• The bottom of the vent terminate must be located a minimum
of 12 inches above grade level and must extend beyond any
combustible overhang.
• Never join two sections of double wall vent pipe within one
horizontal vent system, as it is impossible to verify that inner pipes
are completely sealed.
• For a vent termination located under an eave, the distance of the
overhang must not exceed 20”. The clearance to combustibles
above the exterior vent must be maintained at a minimum of 12”.
Consult the National Fuel Gas Code for additional requirements
for eaves that have ventilation openings.
Horizontal Venting
GAS CONNECTIONS
WARNING: Danger of explosion and fire. Improperly
connected gas lines may result in serious injury and death,
explosion, poisonous fumes, toxic gases, or asphyxiation.
Connect gas lines in accordance to national, state, provincial,
and local codes.
This heater burns natural gas or liquefied petroleum (LP) gas
and is equipped with a regulator. The regulator is built into
the gas valve. The maximum inlet pressure to this regulator
is 20 in. W.C.. If gas line pressure exceeds 20 in. W.C., then
an additional regulator must be installed before the heater/
regulator to step down the pressure to a maximum of 20 in.
W.C..
All field gas piping must be pressure/leak tested prior to
operation. Never use an open flame. Use a soap solution or
equivalent for testing.
You must follow these instructions exactly. If over-heating
occurs or if gas supply fails to shut off, shut off the manual
gas valve to the appliance before shutting off electrical
supply.
12”
Min.
Terminal
5 ft.
Min.
Tee with Drip Leg and
Cleanout Cap at Low
Point of Vent System
The Horizontal Run
of Vent Pipe Shall
be Pitched Upward
1/ 4 IN. to the FT.
(21 MM to the M).
Power
Exhauster
Outlet
FIGURE 8
COMBUSTION AIR REQUIREMENTS
Adequate facilities for supplying air for combustion and ventilation
must be provided in accordance with the latest edition of section 5.3,
Air for Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1, in the U.S.A., CSA B149.1 Natural Gas and Propane Installation Code, the National Standards of Canada or applicable provisions
of local building codes.
All gas fired appliances require air to be used for the combustion
process. In many buildings today, there is a negative indoor air pressure
caused by exhaust fans, etc. If sufficient quantities of combustion air
are not available, the heater or another appliance will operate in an inefficient manner, resulting in incomplete combustion which can result
in the production of excessive carbon monoxide.
Follow these guidelines and all applicable codes for all models prior to
installing the combustion air duct work.
WARNING: Suf ficient combustion air must be supplied
to the appliance at all times. Lack of combustion air may
result in property damage, headaches, nausea, dizziness,
asphyxiation, serious injury, or death.
CAUTION: Gas lines should be purged of air as described
in ANSI Z223.1 (NFPA 54) or CSA-B149.1– latest version.
Installation of the piping must also conform with the local
building codes, or in the absence of local codes, with the
latest edition of the National Fuel Gas Code (NFPA 54). In
Canada, installation must be in accordance with CSA-B149.1.
When leak testing the gas supply piping system, the
appliance and its combination gas control must be isolated
during any pressure testing in excess of 14” W.C. (1/2 psi).
The unit should be isolated from the gas supply piping
system by closing its field installed manual shut-off valve.
This manual shut-off valve should be located within 6’ of the
heater.
Turn off all gas before installing appliance
NOTICE: The total input to the appliance must fall within +/- 5% of
the rated input as indicated on the rating plate. Otherwise the heat
exchanger may prematurely fail.
All piping installed must comply with local codes and ordinances or
with National Fuel Gas Code, ANSI Z223.1 (NFPA 54), whichever takes
precedence. When installing piping, the following requirements must
be taken into consideration: Canadian installations must comply with
the B149.1.2 Gas Code.
• Use new properly reamed black pipe free from chips.
• Apply a good quality pipe compound to all male threads prior
to assembly. If LP gas is the fuel, ensure that pipe compound is
resistant to LP gas. Do not use Teflon™ tape.
• A sediment trap meeting the typical requirements of Figure 9 shall
be installed in the line to the gas valve.
• A dedicated shutoff valve for the heater must be installed in the
gas supply line.
Refer to Table 5 for natural gas and Table 6 for propane to determine
the cubic feet per hour (CFH) required for the type of gas and size of
unit to be installed. To determine the proper pipe diameter, use the
CFH value and the length of pipe necessary. In the case where several
units are serviced by the same main gas line, the total capacity (CFH)
and length of main must be adequate to service all appliances downstream of this main.
Large Unit Heater
Operating Instructions and Owner’s Manual
10
HSU200
HSU250
HSU300
HSU400
Gas supply
Connection
[“][“ W.C.][“ W.C.][“ W.C.][“][CFH]
1/28204.50.1106190.5
1/28204.90.1107238.1
1/28201.730.1389285.7
3/48202.130.13811380.9
Gas supply
Pressure min.
Gas supply
Pressure max.
Manifold
Pressure
Orifice Drill
Size
# of
Orifices
Consumption
TABLE 5: Natural Gas Consumption
*Assumes an average heating value of 1050 BTU/SCF and a Specific Gravity of 0.60.
HSU200
HSU250
HSU300
HSU400
Gas supply
Connection
[“][“ W.C.][“ W.C.][“ W.C.][“][CFH][Gal/Hr.
1/211207. 2 30.075680.02.19
1/211207. 2 30.0757100.02.74
1/211203.810.0839120.03.29
3/411204.740.08311160.04.38
Gas supply
Pressure min.
Gas supply
Pressure max.
Manifold
TABLE 6: Propane Gas Consumption
*Assumes an average heating value of 2500 BTU/SCF and a Specific Gravity of 1.53.
• All piping must be installed in accordance with the requirements
outlined in the National Fuel Gas Code ANSI/Z223.1 (latest
edition) or CSA-B149.1 and B149.2. Support all gas supply piping
with pipe hangers, metal strapping, or other suitable material. Do
not rely on the heater to support the gas pipe.
WARNING: Always use two (2) opposing wrenches to tighten
mating pipe connections to prevent excessive torque on the
gas valve and manifold pipe. Excessive torque can damage
the valve and/or misalign the orifice, resulting in fire,
explosion, serious injury, or death.
Pressure
Orifice Drill
Size
# of
Orifices
Consumption
Propane]
Gas Supply Connection
Manual
Main Shut-o Valve
(Furnished by Installer)
• When connecting gas supply lines, the length of the piping run
from the gas meter to the heater must be considered in determining the pipe size to avoid excessive pressure drop.
• A drip leg should be installed in the vertical pipe run to the unit.
In some localities, codes may require that a manual main shutoff
valve and union (furnished by installer) be installed external to the
unit. Union must be of the ground joint type. A drip leg should be
readily accessible to permit cleaning and emptying. See Figure 9.
NOTICE: Leave a min of 4’’ clearance to the electrical connections box
on the back of the heater to allow for access.
A 1/8” NPT plugged tap shall be installed immediately upstream of the
gas supply connection to the heater. The purpose of this is to be able
to check for proper gas pressure entering the heater.
Large Unit Heater
Operating Instructions and Owner’s Manual
11
Grounded Joint Union
Gas Flow
Drip Leg
Sediment Trap
FIGURE 9
LEAK TESTING
WARNING: Use a soap solution or equivalent for leak testing.
Never test for leak with an open flame such as with matches
or candles. Failure to comply could result in personal injury,
property damage, or death.
• Always leak test final gas assembly for gas leaks according to
the procedures outlined in NFPA 54 and all local codes and/or
Standards.
• After gas piping is completed, carefully check all piping connections, (field and factory), for gas leaks.
• Due to the natural heating cycles and vibration of this unit it is
recommended, as part of its annual maintenance, to check these
connections for proper tightness and leak-check with a soap solution or other preferred means prior to putting into service.
For leak testing on pressures below 20 inches W.C.:
Before leak testing, close the field installed manual shut off valve
shown on Figure 9 on the supply line to isolate the gas valve from the
pressure.
NOTICE: All factory installed gas connections have passed an approved
leak test.
For leak testing on pressures above 20 inches W.C.:
When leak testing with pressures above 20 inches W.C., the unit must
be isolated from the supply pipe. Close the field installed manual shut
off valve, disconnect the supply line to the unit, and temporarily cap
the supply line for testing purposes.
WARNING: Gas pressures to the appliance controls must
never exceed 20 inches W.C.. Supply pressures greater than
20” W.C. can damage the controls, resulting in personal
injury, property damage, or death.
NOTICE: In case emergency shutdown is required, shut down main
gas valve and disconnect main power to unit. These devices should be
properly labeled by the installer.
Explosion hazard. This heater must be converted
by a trained gas installation and service personnel only. Failure to comply could result in
personal injury, asphyxiation, death, and fire or
property damage.
This Unit heater is factory configured for altitudes from 0 – 2,000 ft
above sea level. If the heater is being installed at an elevation above
2,000 ft, the input rate will have to be de-rated to ensure proper
operation. The deration is achieved by an adjustment of manifold
pressure. Adjust pressure regulator to pressure shown in Table 6 for
natural gas and Table 7 for LP/propane gas.
Large Unit Heater
TABLE 8
Propane Gas Heating Values at Altitude
• Gas heating values are derated 4% per 1,000’ of elevation in the
U.S.A. and 10% between 2,000’ and 4,500’ elevation in Canada
in accordance with ANSI Z223.1 and CSA-B149, respectively.
• Refer to the unit rating plate or carton label to obtain the
necessary information about the unit. After obtaining this
information, refer to the gas pressure and selection charts shown
in Table 5 and Table 6. The pressure charts are differentiated by
elevation, fuel type, and country the product is being installed in.
The selection charts are differentiated by product type, altitude
and fuel type.
• Some utility companies may derate the BTU content (heating
value) of the gas provided at altitude to a value other than 1,050
BTU/ft3 for natural gas or 2,500 BTU/ft3 for propane gas to allow
certain heating appliances to be used with no manifold pressure
adjustments. For this reason it is necessary that the supplying
utility be contacted for detailed information about the gas type
and BTU content (heating value) before operating any heater.
Operating Instructions and Owner’s Manual
12
Table 7 and Table 8 show the standard derated heating values
(4% per 1,000’ of elevation in the USA and 10% between 2,001’
and 4,500’ elevation in Canada) of natural and propane gases at
various altitudes. If the utility is supplying gas with heating values
as shown in Table 5 and Table 6, the manifold pressure should
be set accordingly.
NOTICE: Only the high fire gas pressure need be adjusted, low fire gas
pressure should remain the same.
If the heating value of the gas being supplied is different than the
values shown in Table 5 and Table 6 use the following equation to
determine the appropriate manifold pressure for the altitude and gas
heating value being supplied:
MPACT=(BTUTBL/BTUACT)squared X MPSL
where:
MPACT = Manifold Pressure (in. W.C.) at Altitude –
Manifold pressure setting for the heater being installed
BTUTBL = BTU/ft3 Content of Gas –
Obtained from Tab. 7 or Tab. 8 (whichever is applicable)
BTUACT = BTU/ft3 Content of Gas –
Obtained from the local utility company
MPSL = Manifold Pressure (in. W.C.), at Sea Level (see Table 5 or
Table 6)
ELECTRICAL REQUIREMENTS
WARNING
Shock hazard. Disconnect power supply before
making wiring connections to prevent electrical
shock and equipment damage. All appliances
must be wired strictly in accordance with wiring
diagram furnished with the appliance. Any wiring
different from the wiring diagram could result in a
hazard to persons and property.
Ensure that the supply voltage to the appliance,
as indicated on the rating plate, is not 5% greater/
less than rated voltage.
Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 221ºF (105ºC).
• Installation of wiring must conform with local building codes,
or in the absence of local codes, with the National Electric Code
ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded
in conformance to this code. In Canada, wiring must comply with
CSA C22.1, Part 1, Electrical Code.
• Two copies of the unit wiring diagram are provided with each
unit. One is located in the side access control compartment and
the other is supplied in the literature packet. Refer to this diagram
for all wiring connections.
• Make sure all multi-voltage components (motors, transformers,
etc.) are wired in accordance with the power supply voltage.
• The power supply to the unit must be protected with a fused
or circuit breaker switch, so that power can be turned off for
servicing.
Power Supply
[V][A][Hz][Ph][W]
HSU200
HSU250
HSU300
HSU400
1206.3601756
1206.3601756
120106011,200
120106011,200
TABLE 9: Electrical Specifications
External electrical service connections that must be installed include:
a. Supply power connection (115, 208, 230, 460, or 575 volts).
b. Connection of thermostats, or any other accessory control devices
that may be supplied (24 volts).
All supply power electrical connections are made in the side access
control compartment of the unit. The low voltage (thermostat and
accessory control devices) can be wired to the terminals in the side
access control compartment. Refer to the wiring diagram for the
terminal location of all low voltage wiring.
NOTICE: These unit heaters use a direct spark ignition system. There
is no pilot necessary as the spark lights the main burner as the gas
valve is turned on. The direct spark ignition control board emits radio
noise during burner ignition. The level of energy may be enough to
disturb a logic circuit in a microprocessor controlled thermostat. It is
recommended that an isolation relay be used when connecting the
unit heater to a microprocessor controlled thermostat. Select circuit
protection and wire size according to the unit rating plate. Remove
electrical junction box cover and connect wiring through knockout
on the junction box located on the side of the heater. Refer to heater
wiring diagram for connection information. Use a wire for line power
connections with proper section size according to the electrical power
data indicated in Table 9 and its length. Make sure to connect line
power to wires located in the external electrical junction box behind
junction box cover. DO NOT CONNECT LINE POWER TO THERMOSTAT
TERMINAL STRIP ON OUTSIDE OF HEATER.
Electrically ground the unit in accordance with local codes or in the
absence of local codes, in accordance with the current National
Electrical Code (ANSI/NFPA No. 70) in the USA, and in Canada with
the current Canadian Electrical Code, Part 1 CSA C22.1.
Un-insulated ground wire must be wrapped in electrical tape to avoid
damage to the electrical system.
• Make line voltage connections as shown in Figure 10. Connect
field wiring as shown on wiring diagram on unit. Also, refer to
typical diagram in this manual.
• To use the blower for air circulation only, your thermostat must
have a “fan only” or fan selection setting. In case your thermostat
has this option, an additional wire should be run to the
“”terminal on the thermostat connection block. See wiring
schematic in Figure 11 .
Large Unit Heater
Operating Instructions and Owner’s Manual
13
Main Components
FIGURE 10
M1
S1
S4
VG
MC
Line Voltage
Thermostat
Wiring Connector
on Heater
S2
SE
FS
S2
S3
RFC
CFC
CB
T1
Large Unit Heater
Operating Instructions and Owner’s Manual
14
Internal Wiring Diagram
FIGURE 11
Large Unit Heater
Operating Instructions and Owner’s Manual
15
Line Voltage Field Wiring
FIGURE 12
• Connect wires together with UL approved wire connectors.
NOTICE: A UL Listed switch may be installed in the 2x4 junction box
for use as a service disconnect.
CAUTION: Route the field supplied power wires so that
they do not come in contact with the flue wrapper or
venter housing. These hot surfaces may damage the wire’s
insulation, resulting in damage to the unit.
THERMOSTAT LOCATION
The location of the thermostat should be determined by the desired
heating requirements and be mounted on an inside wall five (5) feet
above the finished floor. Locate the thermostat in a conspicuous
location, away from where it could be influenced by heat from the unit
or other sources, as this may cause the unit to short cycle. Care should
be given to locate the thermostat away from drafts or frequently
opened doors. To prevent drafts inside the wall from affecting the
thermostat’s performance, plug hole for the wire with insulation
or suitable caulk. For further information, see the accompanying
instructions with the thermostat.
WARNING: Electric shock hazard. Can cause injury or death.
Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect the
furnace and to replace any part of the control system and
any gas control which has been under water.
Before attempting to perform any service or maintenance,
turn the electrical power to unit OFF at disconnect
switch(es). Unit may have multiple power supplies.
FIELD WIRING SUPPLY VOLTAGE
Before proceeding with electrical connections, ensure that the supply
voltage, frequency, phase, and current capacity meet the requirements
specified on the rating plate. A dedicated line voltage supply with
properly sized wire should run directly from the main electrical panel to
the heater.
CAUTION: The power supply to the heater must be within
+/- 5% of the voltage rating as indicated on the rating
plate of the appliance. If input power does not meet these
specifications, contact your utility company.
• An electrical service disconnect must be provided at the furnace
location. A 2 x 4 junction box can be mounted directly to the unit
panel utilizing the provided 1/2” knock-out. If conditions do not
allow for this, locate the service disconnect not more than 5 feet
away from the service access panel.
• The main electrical supply enters at the rear of the heater utilizing
1/2” electrical knock-out. When routing the electrical supply
conduit to the unit, ensure that it does not interfere or obstruct
the heater’s service access panel.
• Unit comes with three wire leads to connect the main power
supply. Connect the hot, neutral, and ground wires as shown
in the field wiring diagram. When routing wires through the
knockout, use a UL Listed bushing or chase nipple to prevent
damage to the wire insulation. When operating this unit as a
sealed combustion appliance, the cabinet opening to the junction
box must be sealed air tight using either a UL approved bushing
or a non-reactive UL approved sealant to bushing.
WARNING: Edges of sheet metal holes may be sharp. Use
service, or maintenance can cause property damage, serious
injury, or death. This heater must be installed and serviced
by a trained gas installation and service personnel only.
During heater startup ensure that building is well ventilated.
CAUTION: Shock Hazard. Before attempting to perform any
service or maintenance, turn electrical power to unit OFF at
disconnect switch.
During the first unit startup, an odor and, perhaps,
some vapor will come from the heater. This is the gasket
binding material emitting this odor and/ or vapor. After
approximately 20 minutes, this odor will disappear and not
occur again.
During these 20 minutes it is recommended to ventilate the
room as much as possible (open doors, windows, turn on
any fans).
Pre-Start Up Checks
Verify that the installation conforms to all of the specifications of the
manual, as well as with local, state, national, and provincial codes. In
absence of local codes, the unit heater must be installed according to
the current National Fuel Gas Code ANSI Z223.1 (NFPA 54). In Canada,
the installation must conform to the current National Standard of
Canada CSA-B149 Sections 1 & 2.
Prior to starting up the unit, verify that:
• The gas type listed on the rating label matches that of your
application.
• The gas connections have been purged of air and properly leak
tested.
• The voltage type and frequency listed on the rating label matches
that of your application.
• The unit is properly grounded as per the National Electrical Code,
ANSI/NFPA 70 or Canadian Electrical code CSA C22.1 Part 1.
• The unit is properly mounted to a permanent structure able to
bear the weight of the unit.
Operating Instructions and Owner’s Manual
16
• The proper mounting height is observed for the application.
• All clearance to combustible distances or service clearances are
maintained.
• The unit is properly isolated or installed to prevent excessive
vibration.
• The unit is level horizontally.
• Venting is properly installed in accordance with this manual and
any applicable codes.
• Combustion air supply is sufficient to support proper operation at
all times.
See Annex 1 for a start up and performance check list to fill for each
unit.
Verify Proper Inlet Pressure
WARNING: Before starting up the unit, smell all around
the unit heater for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the
floor.
When turning the gas shut off valve, only use your hand. Never use
tools to turn the knobs, as it may damage the valve resulting in a fire
or explosion. If the knob is stuck, do not try to repair it.
Contact a qualified service technician or your local gas company.
To verify the proper inlet pressures, follow the following steps:
1. Turn off the gas supply at the manual gas shut off valve.
2. Unscrew the screw inside the inlet pressure hose connector. See
Figure 13.
3. Turn on the gas supply at the manual gas shut off valve.
4. Turn on the electrical power to the unit heater.
5. To light the main burners, set the room thermostat to a point
above room temperature.
Gas Valve
Inlet Pressure:
Unscrew this screw to
read the pressure.
Manifold Pressure Regulation:
• Remove the cap with a at blade screw
driver:
• Act on the plastic regulator:
Decrease pressure
Counter-clockwise
FIGURE 13
Increase pressure
Clockwise
Manifold Pressure:
Unscrew this
screw to read the
pressure.
FIGURE 13
NOTICE: This unit heater is equipped with an ignition device, which
automatically lights the burner. This unit heater cannot be lit manually.
Do not try to light the burner by hand.
Large Unit Heater
The minimum and maximum inlet gas supply pressure are
indicated in Table 5 and in Table 6.
Verify minimum inlet gas supply pressure:
6. Turn on all other gas appliances that are on the same supply
line. If the other gas appliances have multiple inputs, set it to the
maximum rating.
7. Observe the pressure rating on the pressure gauge.
Verify maximum inlet gas supply pressure:
8. Turn off all other gas appliances on the same supply line.
9. Observe the pressure reading on the pressure gauge.
IMPORTANT: If the inlet gas supply pressure is not within the
minimum and maximum range as shown on the rating plate, contact
your gas supplier.
Removing pressure gauge from inlet port on gas valve:
10. Set thermostat or other control device to the lowest set point.
11. After heater has completed the post-purge cycle, turn off the
electrical power to the unit heater.
12. Turn off the gas supply at the manual gas shut off valve.
13. Remove the pressure gauge tube.
14. Close the screw inside the inlet pressure hose connector.
15. Leak check using a soap solution or equivalent method as
described in ANSI Z223.1 (NFPA 54).
Verify Manifold Pressure
Before starting up the unit, smell all around the unit heater for gas.
Be sure to smell next to the floor because some gas is heavier than air
and will settle on the floor.
When turning the gas shut off valve, only use your hand. Never use
tools to turn the knobs, as it may damage the valve resulting in a fire
or explosion. If the knob is stuck, do not try to repair it, contact a
qualified service technician or your local gas company.
To verify the proper manifold pressure, follow the following
steps:
1. Turn off the electrical power to the unit heater.
2. Unscrew the screw inside the manifold pressure hose connector
(see Figure 13).
3. Connect the pressure gauge tube and manometer.
4. Turn on the electrical power to the unit heater.
5. To light the main burners, set the room thermostat to a point
above room temperature.
NOTICE: This unit heater is equipped with an ignition device, which
automatically lights the burner. This unit heater cannot be lit manually.
Do not try to light the burner by hand.
6. After the unit has successfully ignited, wait five minutes prior to
taking any readings. The unit heater must be in a steady state of
operation prior to taking a manifold pressure reading.
7. While waiting for the unit to stabilize, observe the characteristics
of the flame. The flame should be stable and should not lift form
any burner. The burner color should be light blue, and not create
excessive noise.
8. After five minutes, observe the pressure rating on the pressure
gauge.
Operating Instructions and Owner’s Manual
17
The target manifold gas supply pressure is indicated in Table 5
and Table 6 :
NOTICE: Manifold pressure of the heater is pre-set at the factory. No
adjustment should be necessary.
During the verification process, a tolerance of +/- 5% of the full scale is
acceptable due to varying atmospheric conditions.
If manifold pressure is outside of this tolerance, then an adjustment
may be necessary.
9. Set the adjustment screw until reach the pressure indicated in the
rating plate.
Removing pressure gauge from manifold port on gas valve:
10. Set thermostat or other control device to the lowest set point.
11. After heater has completed the post-purge cycle, turn off the
electrical power to the unit heater.
12. Turn off the shut-off gas valve.
13. Remove the pressure gauge tube and the manometer.
14. Close the screw inside the manifold pressure hose connector (see
Figure 13).
15. Turn on the shut-off gas valve.
16. Set thermostat or other control device to the highest set point.
17. Wait until the unit starts.
18. Leak check the manifold pressure hose connector using a soap
solution or equivalent method as described in ANSI Z223.1 (NFPA
54).
Prior to Leaving Job Site
Prior to leaving the job site, verify that:
• Service access door is properly secured to the unit.
• The heater is clear of any objects that would interfere with
the proper air circulation or that violate the listed clearance to
combustibles.
• Air directional louvers are adjusted for desired air flow and are
not shut or adjusted beyond 60º°from perpendicular to the face of
the unit.
• Manual gas shut off is ON.
• Electrical power is ON.
• Thermostat is set to desired temperature.
• Properly dispose of all packaging materials.
• Check to be sure you have all of your tools.
• Leave the Installation, Operation, Maintenance and Parts Manual
to the owner or end user.
UNIT WORKING SEQUENCE
WARNING: FOR YOUR SAFETY READ BEFORE LIGHTING
BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
WARNING: This appliance does not have a pilot ignition. It is
equipped with an ignition device which automatically lights
the burner. Do not attempt to light the system by hand.
1. STOP! Make sure you have read and understand all of the safety
information regarding the operation of this gas appliance. Any and
all service should be performed by a licensed installer
2. Set the thermostat to lowest setting.
3. Turn off all electrical power to appliance.
4. This appliance is equipped with an ignition device which
automatically lights burner. DO NOT attempt to light the burners
manually.
5. There is a main shut-off valve upstream of the unit. Open it. (See
Figure 9 on Page 11)
6. Wait five minutes to clear out any gas. If you then smell gas, STOP!
Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions. If you do not smell gas go to next
step.
Large Unit Heater
7. Turn on electrical power to unit.
8. Set the thermostat to desired setting.
WARNING: Should overheating occur, or the gas supply
control system fail to shut off the flow of gas, shut off the
manual gas valve to the utility heater before shutting off the
electrical supply
SHUTDOWN PROCEDURES
1. Set thermostat to lowest level.
2. Turn off all electrical power to unit if service is to be performed.
3. Turn manual shut off knob upstream the unit. Do not force.
Operating Instructions and Owner’s Manual
19
MAINTENANCE
CAUTION: Turn off gas and electrical power to unit before
performing any maintenance or service operations on this
unit. Remember to follow lighting instructions when putting
unit back into operation after service or maintenance.
If any of the original wire as supplied with the appliance
must be replaced, it must be replaced with wiring material
having a temperature rating of at least 105°C.
Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and replace any gas control which has been under
water.
• Check gas tightness of the safety shut off valves on at least an
annual basis.
• To check gas tightness of the safety shut off valves, turn off the
manual valve upstream of the appliance combination control.
Remove the hex head plug on the inlet side of the combination
control and connect a manometer to that tapping.
• Turn the manual valve ON to apply pressure to the combination
control. Note the pressure reading on the manometer, then turn
the valve off. Any loss of pressure indicates a leak. If a leak is
detected, use a soap solution to check all threaded connections.
If no leak is found, combination control is faulty and must be
replaced before putting appliance back in service.
Should maintenance be required, perform the following inspection and
service routine:
BURNERS
• Periodically examine burner flames for proper appearance during the
heating season.
• Before each heating season examine the burners for any deposits or
blockage that may have occurred.
Clean burners as follows:
1. Turn off both electrical and gas supplies to unit.
2. Disconnect gas supply piping, high tension and sensor leads.
Remove gas manifold. Remove burner tray.
3. Clean burners as necessary. Make sure that burner heads line up
properly to ensure flame crossover. Check spark gap on electrode
and adjust if required. The gap should be between 0.110 inch and
0.140 inch (2.79mm to 3.56mm). The gap may be checked with
appropriately sized twist drills or feeler gauges.
4. Reinstall burner tray, gas manifold, high tension and sensor leads.
Reconnect gas supply piping.
5. Restore electrical power and gas supply. Follow lighting instructions
to light unit. Check burner flame.
FLUE PASSAGEWAY AND FLUE BOX
The flue passages and flue box should be inspected and cleaned
prior to each heating season. The sequence of operation should be as
follows:
1. Turn off both electrical and gas supply to unit.
2. Disconnect combustion air blower wiring.
3. Remove screws securing flue box to unit. Remove flue box. If
necessary, remove blower assembly from flue box. Clean flue box
with wire brush.
4. Remove turbulator retention bracket and turbulators. Clean
turbulators with wire brush.
5. Remove burners as described in section “BURNERS” section.
6. Clean tubes with a wire brush.
7. Reassemble unit. The combustion air and flue box gaskets should
also be replaced during reassembly.
8. Restore electrical power and gas supply. Follow lighting instructions
to light unit. Check operation of unit.
COMBUSTION AIR BLOWER
Under normal operating conditions, the combustion air blower should
be checked and cleaned prior to the heating season with the power
supply disconnected. Use a small brush to clean blower wheel.
ELECTRICAL
1. Check all wiring for loose connections.
2. Check for correct voltage at unit (unit operating).
3. Check amperage draw.
FLUE AND CHIMNEY
Check all vent and vent connector joints for tightness. Ensure that
connections are sealed and that there are no blockages.
OTHER CHECKS
1. Inspect the area near the unit to be sure that there is no
combustible material located within the minimum clearance
requirements listed in this manual. Under no circumstances should
combustible material be located within the clearances specified
in this manual. Failure to provide proper clearance could result in
personal injury or equipment damage from fire.
2. Complete the appropriate unit startup procedure as given in the
Operation section of this Manual (see lighting instructions on the
unit rating plate.)
• Check the burner adjustment.
• Also check all gas control valves and pipe connections for leaks.
3. Check the operation of the automatic gas valve by lowering the
setting of the thermostat, stopping the operation of the gas unit
heater. The gas valve should close tightly, completely extinguishing
the flame on the burner.
4. If combustion air is room supplied, ensure that a 12 inch clearance is
maintained all around the inlet openings.
5. Check and test functions of all safety devices supplied with the
heater (see UNIT START-UP and UNIT WORKING SEQUENCE
sections).
Large Unit Heater
Operating Instructions and Owner’s Manual
20
THIS PAGE INTENTIONALLY LEFT BLANK
ESTA PÁGINA INTENCIONALMENTE SE DEJA EN BLANCO
CETTE PAGE A ÉTÉ INTENTIONNELLEMENT LAISSÉE VIERGE
Large Unit Heater
Operating Instructions and Owner’s Manual
21
Position of the Manifold Screws
FUEL CONVERSION INSTRUCTIONS
The heater is standard manufactured for operation with natural gas. In case of use with LP /propane gas, use the conversion orifices supplied
with the unit. Follow the instructions below.
4 Screws
FIGURE 14
Rotation of the Valve/Manifold Assembly
ROTATE valve/manifold
assembly
Large Unit Heater
FIGURE 15
Operating Instructions and Owner’s Manual
22
WARNING: Explosion Hazard
TURN OFF THE GAS SUPPLY TO THE HEATER
BEFORE PERFORMING ANY SERVICE OR MAINTENANCE.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL
RESULT IN DEATH, INJURY OR PROPERTY DAMAGE.
WARNING: Electrical Shock Hazard
UNPLUG THE ELECTRICAL CORD FROM THE OUTLET BEFORE PERFORMING ANY SERVICE MAINTENANCE.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL
RESULT IN DEATH, INJURY OR PROPERTY DAMAGE.
Step 5
Rotate the valve/ manifold assembly back up into the burner box,
making sure that all the orifices are indexed into the burners and are
not caught on the locating ring on the back of each burner. Secure the
manifold to the burner box with the four screws removed in step 2.
Step 6
Following the instructions Electrical Requirements and Gas Connections
Sections (making sure to leak check all connections with soapy water)
to reinstall the heater.
Step 7
Take the rate tag from the kit and stick it over the existing portion of
the rate label. This tag is preprinted with all the correct information for
the converted heater. See Figure 16.
The electrode and sensor are not adjustable. DO
NOT change location or position as part of this
conversion kit.
WARNING
THIS CONVERSION KIT SHALL BE INSTALLED BY A
QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE
MANUFACTURER’S INSTRUCTIONS AND ALL APPLICABLE
CODES AND REQUIREMENTS OF THE AUTHORITY
HAVING JURISDICTION. IF THE INFORMATION IN THESE
INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE,
EXPLOSION OR PRODUCTION OF CARBON MONOXIDE
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE. THE QUALIFIED SERVICE AGENCY
PERFORMING THIS WORK ASSUMES RESPONSIBILITY FOR
THE PROPER CONVERSION OF THIS APPLIANCE WITH THIS
KIT.
Step 1
CAUTION: THE UNIT MUST NOT BE CONNECTED TO EITHER
THE GAS SUPPLY OR THE ELECTRICAL POWER SUPPLY,
BEFORE PROCEEDING WITH CONVERSION.
Step 2
Remove and retain the four screws holding the manifold on to the
burner box (Figure 14). Rotate the valve/ manifold assembly, away from
the burners (Figure 15). The valve/manifold assembly holds the orifices.
This will allow access to the orifices on the manifold.
Step 3
Remove and discard the adjustment spring cap from gas valve/
regulator with a flat blade screw driver by turning the screw counterclockwise.
Position Of The Rate Tag
FIGURE 16
Step 8
Remove the converted information tag from the kit and fill in the
information. Then place this tag below the updated rating tag on the
unit.
Step 9
Replace any panels and operate heater following all warnings/cautions
and instructions in the operator’s manual and labels.
Step 4
Remove and discard the orifices from the manifold with using a ½ “
open end wrench. Turn them counter-clockwise to remove. Take the
new orifices from the conversion kit and before installing, confirm that
the number stamped on the side of the orifice matches as indicated
in Table 1. If it does not, immediately contact Heatstar, Inc. for the
correct kit. If they are the correct orifices, install them in the manifold
using caution not to cross thread.
Large Unit Heater
Operating Instructions and Owner’s Manual
23
TROUBLESHOOTING GUIDE
NOTICE: Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed during normal operation or the heater’s built-
in safety mechanisms will be compromised.
SymptomPossible CauseCorrective Action
The draft inducer motor
does not turn on
1. The air circulating fan does not turn on immediately.
1. Limit switch is open or pressure switch is
stuck closed. Find faulty switch and repair.
2. The heater does not have 120 VAC at the main power
connection.
3. There isn’t 24 VAC across the ‘R’ and ‘C’ terminals
4. There isn’t 24 VAC across the ‘W’ and ‘C’ terminals.
5. The control board is not sending 120 VAC to the draft
inducer motor.
6. The draft inducer impeller is obstructed or locked up.
7. After checking the above, the draft inducer impeller is not
obstructed or locked up.
8. The pressure switch is stuck in the closed position.
9. The two flame roll out switches and the tube temperature
limit switch are closed.
10. The two flame roll out switches and the tube temperature
limit switch are not closed.
The pressure switch indicator light does not turn on
The control board does
not send spark to the
electrode
The gas valve does not
open
The burners do not ignite1. The gas supply valve mainstream to the unit heater is not
1. The inlet or outlet of the heater is obstructed or the vent
exceeds the recommended lengths.
2. Loose wiring or restrictions in the hose connection to the
pressure switch.
3. Replace pressure switch after verifying:
• Heater, blower, and venting are clean and free of
obstructions.
• The allowable vent length is not exceeded.
• There is not a negative pressure experienced at the area
of intake (e.g., high winds, attic space, tightly sealed
building).
1. The electrode appears to be physically damaged.
2. There is no continuity by temporarily disconnecting the
igniter wire from the control board.
3. There is continuity by temporarily disconnecting the
igniter wire from the control board.
1. The inlet pressure to the heater is not within the minimum
and maximum allowable range as per the rating plate.
2. The wires to and from the gas valve are not properly
connected.
3. The voltage on V1 and V2 terminals on control board
during trial for ignition is not 24 VAC during the spark
sequence.
4. The voltage on V1 and V2 terminals on control board
during trial for ignition is 24 VAC during the spark
sequence.
open.
2. The inlet pressure to the heater is not within the minimum
and maximum allowable range as per the rating plate.
2. Find source of electrical problem.
3. Check internal transformer.
4. Repair thermostat or thermostat wiring.
5. Check power supply, and if there is power,
replace control board.
6. Remove obstruction.
7. The draft inducer motor is faulty and must
be replaced.
8. Pressure switch is faulty.
9. Replace control board.
10. Reset or replace faulty limit switch.
1. Remove obstruction or correct vent lengths.
2. Replace wiring or hose connections.
3. Replace pressure switch.
1. Replace electrode.
2. Replace electrode.
3. Replace control board.
1. Adjust inlet pressure.
2. Correct wiring.
3. Check for flash codes on the control board.
Replace the control board.
4. Gas valve is faulty. Replace the gas valve.
1. Turn on gas supply line.
2. Adjust inlet pressure.
3. The gas lines are not purged of all air.
4. The heater’s gas type does not match the gas supplied.
5. The manifold pressure doesn’t match with the specified
pressures per the rating plate.
6. Check control board for flash codes.
Large Unit Heater
Operating Instructions and Owner’s Manual
24
3. Purge gas lines.
4. Contact local representative or factory.
5. Adjust pressure or replace gas valve.
6. Consult factory.
SymptomPossible CauseCorrective Action
The burners do not stay lit 1. The burners light and then shut off immediately (within
1-2 seconds).
2. The burner does not stay on for approximately 8-10
seconds, and then shut off.
3. The heater is not properly grounded. The heater’s polarity
is not correct.
4. Reading the micro-Amp of flame sensor circuit with a
micro ammeter, it is greater than 0.5 micro-Amps. NOTE:
Meter must be able to set and be connected properly to
read the very low current value.
5. Reading the micro-Amp of flame sensor circuit with a
micro ammeter, it is not greater than 0.5 micro-Amps.
The air motor fan does
not turn on approx. 30
seconds after ignition
The heater does not stay
on until the call for heat
ends
1. The control board does not send 120 VAC to the air
movement fan after approx. 30 seconds after ignition and
if contact relay fan control is closed.
2. The control board does not send 120 VAC to the air
movement fan after approx. 30 seconds after ignition and
if contact relay fan control is open and there isn’t 24VAC
on relay fan control.
3. The control board does not send 120 VAC to the air
movement fan after approx. 30 seconds after ignition and
if contact relay fan control is open and there is 24VAC on
relay fan control.
4. The motor is dirty, obstructed, or damaged, inhibiting
rotation.
5. Motor starter capacitor damaged.
1. The heater can shut down or stay on due to:
• Limit switch opening.
• Pressure switch opening.
• Improper grounding.
• Faulty control device.
• High winds.
• Taking combustion air from the attic.
• Dirty environment.
• Fluctuating gas pressure.
1. Check inlet pressure and limit switches.
2. Check control board for flash codes.
Consult factory.
3. Correct grounding or fix polarity.
4. Check control board flash codes. Replace
ignition module.
5. Replace control board.
1. Verify wires are not damaged.
2. Check if switch start circulation is closed.
3. Replace relay.
4. Clean fan, remove obstruction, or replace
damaged parts.
5. Replace or repair.
# OF FLASHESLED DIAGNOSTIC CODES
AT ON every 3 secNormal Operation
1 FLASHSelf Test
1 FLASH every 3 secAirflow fault
2 FLASHES every 3 secFlame - No call for heat
3 FLASHES every 3 secIgnition lockout
4 FLASHES every 3 secControl Fault
TABLE 10: Led Diagnostic Codes
If no leak is found, combination control is faulty and must be replaced before putting appliance back in service.
Large Unit Heater
Operating Instructions and Owner’s Manual
25
PARTS LIST
When ordering parts include the complete unit model number listed on the unit rating plate.
Heatstar • Large Unit Heater • Model # HSU200NG / HSU250NG / HSU300NG/ HSU400NG