The zone control panel is for indoor use only and must be installed by a quali ed installer/service technician. This product
must be installed and operated in strict accordance with the terms set out in this manual and in accordance with the relevant
requirements of the Local Authority Having Jurisdiction. Failure to comply will result in a void of warranty, and may also result
in property damage, serious injury, or death.
Servicing
Prior to commencing installation of this panel it is necessary to read and understand all sections of this manual. The
symbols below are used throughout this document to ensure proper operation of the panel, and your safety. Please pay
attention to these symbols.
Warning
Possible Hazard
In order to avoid injury or death, switch o the power to the panel prior to
inspecting or making connections to the terminal strip.
Disclaimer
HeatLink Group Inc. shall not be responsible for errors in its brochures or printed materials. HeatLink Group Inc. reserves
the right to alter its products at any time without notice, provided that alterations to products already on order shall not
require material changes in speci cations previously agreed upon HeatLink Group Inc. and the Purchaser. All trademarks
in this material are property of the respective companies. HeatLink and the HeatLink logotype are trademarks of HeatLink
Group Inc. All rights reserved.
This panel can provide mixing, distribution, and zoning for a wide variety of hydronic heating applications.
The e ectiveness of the system is dependant on the system being designed and installed correctly. Proper consideration
of factors such as BTU loads, outdoor design temperature, indoor design temperature, room set-point temperature(s),
di erential uid temperatures, head loss, ow rates, and transfer capacities of the heat emitters is critical.
Once these factors have been considered and the system requirements determined, these can then be evaluated and
compared to the zone control panel capabilities (refer to pages 5-9).
Note: This panel does not regulate or monitor the operating safety limit temperatures of the uid leaving the heat source.
Unpacking
Step 1 Examine carton for any damage that may have occurred during shipping. If damage is visible notify your courier and
supplier immediately.
Step 2 Open the carton by removing the staples.
Step 3 Remove the cardboard spacers from the carton, then remove the panel from the carton. Lift the panel by the base,
not the enclosure.
Step 4 There are 2 screws holding the enclosure in place during shipping. They are located at the top left & right of the panel
base. Remove these 2 screws.
Step 5 Remove the enclosure from the panel by sliding it upwards until it stops, then gently pulling outwards o .
Side View
To p
Screws
Step 6 Verify the following items:
• (4) Mounting screws
• (4) ¾" MBSP x 1" FNPT adapters
• (6) ¾" rubber washers (2 spares)
• (2) 1" rubber washers (spares)
Bottom
4
HeatLink
www.heatlinkgroup.com
Panel Components
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
TWH070P
1
TWH070XP
4
3
5
2
7
1
3
8
4
5
2
6
Part Number
#Component
1
Primary CirculatorPUMP1558PUMP2699BR
2
Secondary CirculatorPUMP1558PUMP1558
3
Thermostatic Mixing Valve––
4
Power Box with 6' Power CordPWRB7R2PWRB7R2
5
Thermometer7694076940
6
Enclosuren/an/a
Accessory PackACCTWHACCTWH
7
3⁄4" WasherWHTWSH34WHTWSH34
1" WasherNTRWSH1NTRWSH1
Flow Switch for DHW Priority
8
(optional, sold separately)
TWH070TWH070XP
FLWSWTCHFLWSWTCH
5
®
3
1
HeatLink
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Speci cations
ListingcETLus
Conforms toCAN/CSA-C22 No.14, UL508
Dimensions18.25"H x 16.25"W x 8"D
Nominal panel output70,000 btu/hr70,000 btu/hr
Primary nominal fl ow4.0 US gpm @ 35°F ΔT4.0 US gpm @ 35°F ΔT
Primary nominal pressure drop outside of panel14 ft24 ft
Secondary nominal fl ow7 US gpm @ 20°F ΔT7 US gpm @ 20°F ΔT
Secondary nominal pressure drop outside of panel4 ft4 ft
Max ambient temperature120°F
Max water temperature200°F
Min required fl ow for correct temp control1.3 US gpm (5 L/min)
Power supply: pre-wired on system controller110 V(ac)
Primary circulator
Secondary circulator
Auxiliary terminalYes
DHW priorityOptional @ ~0.5 US gpm DHW fl ow
Temperature control method1" 3-Way thermostatic
Temperature control range100°F - 145°F
Valve Cv3.0
Piping
Piping connections1" FNPT
DHW priority switch connection
BackplateGalvanized steel
EnclosurePowder coated steel
TWH070PTWH070XP
Non-ferrous, Grundfos
UPS15-58CIL2
Non-ferrous, Grundfos
UPS15-58CIL2
⁄4" 304 Stainless steel tubing
⁄2" FNPT (FLWSWTCH optional)
Non-ferrous, Grundfos
Non-ferrous, Grundfos
UPS26-99BFC
UPS15-58CIL2
20.0
18.0
16.0
14.0
12.0
10.0
FT HD
8.0
6.0
4.0
2.0
0.0
TWH Series FT HD Outside of Panel
12345678
US GPM
6
HeatLink
www.heatlinkgroup.com
Dimensions
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
18.250”
3.602”
1.563”
2.936”
7.998”
Panel Component Speci cations
16.250”
7.908”
1.563”
3.570”
7.533”
Power Box
This module provides the required power for all electronic
components on the panel, via the ON/OFF switch. Power box may
not be exactly as shown.
Speci cations:
• Requires 115V power source.
• Requires a maximum 15A circuit breaker.
7
®
HeatLink
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Circulators
The circulators moves the heated uid through the hydronic system when there is a call for heat from the thermostat. Primary
pump on the TWH070XP is a UPS26-99BFC.
Speci cations:
• The following pump curves apply.
UPS15-58CIL2 Pump Curve
20
18
16
14
12
10
8
Head (feet)
6
4
2
0
0246810121416
Flow (gpm)
1st Speed2nd Speed3rd Speed
8
UPS26-99BFC Pump Curve
35
30
25
20
15
Head (feet)
10
5
0
05101520253035
Flow (gpm)
1st Speed2nd Speed3rd Speed
HeatLink
www.heatlinkgroup.com
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Indicator
on back
3-Way Thermostatic Mixing Valve (TMV)
The TMV controls the temperature of the hydronic system via a
self regulating thermostat.
MINMAX7
1
2
Setting the TMV
The indicator for the valve is located at the base of the knob on
the back. The mixed (desired) temperature is a function of the
TMV setting.
MIX
See the below chart to determine the proper setting for you
system. After allowing the system to run for a short period, verify
the setting and adjust if necessary.
Unit
°F8190100111120127136145152
°C273238444953586367
Min.1234567Max.
Mixed Fluid Temperature
Flow Switch for DHW Priority (FLWSWTCH)
(optional, sold separately)
The electronic ow indicator provides DHW priority when the
DHW ow rate reaches a factor pre-set level (approx. 0.5 US
gpm). Must be piped in downstream of panel (see schematic on
page 15).
Mounted separately from the panel (see page 15).
Thermometer (76940)
The pipe mounted thermometer reads the supply uid
temperature.
Speci cations:
• Temperature range of 32-210°F (0-100°C).
9
HeatLink
www.heatlinkgroup.com
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Mounting
Prior to mounting the panel, ensure the wall is capable
of supporting the weight of the panel.
Ensure that a 115V receptacle is within reach of the
6-foot cord and plug.
Step 1Determine the locations and distance
between the wall studs. With a level at a
minimum height of 4' from the oor draw a
straight line on the wall and mark the stud
locations.
If the panel cannot be secured directly to the
studs, or suitable backing boards, plywood
may need to be installed behind the panel to
properly secure it in place.
Step 2Screw two of the supplied mounting screws
into the wall studs (or backing plywood) 2"
from the top of desired height, and 10-½"
apart, leaving ¼" of screw out from the wall.
Step 3Lift and place the panel onto the mounting
screws.
min. 4'
from fl oor
Wall Stud
1
2"
10-½"
⁄4"
Step 4Screw the two remaining mounting screws
into the holes at the bottom of the panel and
tighten the top two screws.
Step 5Before replacing the enclosure, refer to pages
12-14 for ll and purge, and proper wiring
instructions.
10
®
HeatLink
www.heatlinkgroup.com
Piping Hookup
Step 1 Before making any connections, identify the
required connections to and from the panel.
Adapters are ¾" M BSPP x 1" FNPT, and must use
the supplied adapters and rubber washers.
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Step 2 Connect all adapters.
1. Connect MNPT adapter E to copper pipe or
tubing F.
2. Screw supplied M x FNPT adapter D onto E
using appropriate thread sealant.
3. Take assembly
D E F
and place rubber
washer C on at surface of D.
4. Without disturbing rubber washer C, place
assembly against anged stainless steel pipe
B
.
5. Slide nut
A
over adapter D and rst nger
tighten nut. Then, using two 30mm wrenches,
tighten the nut taking care not to overtighten the nut, as this will damage the rubber washer.
Step 3See page 15 for instructions on connecting
the optional Flow Switch for DHW Priority
(FLWSWTCH).
A
Primary Supply
1
Primary Return
2
Secondary Supply
3
Secondary Return
4
4
312
C
D
E
F
B
Note: Use precautions when soldering or applying heat within 16" of the panel.
Do not overtighten brass nuts!
11
®
HeatLink
www.heatlinkgroup.com
Fill And Purge
The following steps are recommended in order to ll the panel
with water and purge entrained air once piping is completed,
and before activation of the panel.
The discharged system uid from the ll and purge
process is not for consumption or washing.
Note:Additional purging steps may be required for the rest of
the hydronic system.
Note:Isolation and drain valves are not included with the
panel, but are necessary to properly ll and purge the
panel, and to isolate the panel for service.
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
EF
Step 1 Ensure the panel is not plugged in.
Step 2 Adjust the thermostatic mixing valve to a position of
“Max.“ (see page 9).
Step 3Fully close valves A, B, C, D,and F. Fully open valve E.
Step 4Attach a purge hose (not included) to E and a ll
hose (not included) to F. Open valve F.
Step 5When exiting water from E is free of bubbles, close
valve E, then valve F.
Step 6Remove hoses from drain valves and full open valves
A, B, C
Step 7Check for leaks at connections. If any leaks are found,
use a back-up wrench and carefully tighten until leak
stops. Do not overtighten.
Step 8Readjust the setting of the thermostatic mixing valve
to provide a proper mixed uid temperature to the
hydronic system (see page 8).
, and D.
ABCD
12
®
HeatLink
www.heatlinkgroup.com
Installation, Operation, and Maintenance
Panel Wiring
Note: Terminal headers are removable to make wiring connections easier.
Thermostat Wiring
• 24V low voltage power may be supplied to the thermostat. Wiring of thermostat
should be done by quali ed electrician and should meet local codes and
jurisdictions. Wiring to the terminal strip requires 18 gauge 4 wire.
• Do not exceed 2VA per thermostat.
• Do not cross terminals C and R – this will damage the Power Box.
TWH – Tankless Water Heater Panels
Factory Jumper
24 V
Signal
Do not remove.
WRCAUX
2-Wire Thermostat
(battery only or non-electric)
Signal
WRCAUX
3-Wire Thermostat
(HeatLink thermostats)
Factory Jumper
24 V
24 V
Do not remove.
24 V
24 V
Dry Contact
Factory Jumper
Do not remove.
Signal
Jumper to
WRCAUX
4-Wire Thermostat
(with dry contact signal)
Other Terminals
Auxiliary Contacts The auxiliary contact set is dry, meaning no supply of power is present at the terminal. The
maximum allowable load is 2A. The auxiliary dry contact located on the terminal is to switch
another device (ie. the heat source) when there is a call for heat from any zone.
DHW Priority Contacts The wiring harness of the optional Flow Switch for DHW Priority (FLWSWITCH) plugs into these
contacts (see page 15).
13
®
HeatLink
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Panel Control Sequence
1. When the power cord 1 from the power module is plugged in, and the Power switch located on the front of the module
is placed in the on position the red LED will be lit, indicating that the panel is powered with 110V.
2. The factory setting for the BYPASS switches 2 are to remain in the OFF position. Only switch the front 3-way switch to
“Heat Source Pump Bypass“ or Radiant Pump Bypass switch to ON if the red and green LED’s on the power module do not
light up during a call for heat. Please refer to the troubleshooting section of the manual for further details.
3. When a thermostat calls for heat, its internal 24V contacts close, the auxiliary terminals close, and both circulators 3
turn on.
4. As the circulators move uid through the panel the thermostatic mixing valve adjusts the uid temperature based on the
user settings (page 8).
5. When the requirements of the thermostat are met, the internal contacts of the thermostat open, the auxiliary contacts
open, and the circulators stop.
6. Both the primary and secondary circulators are activated once every 24 hours, for 15 minutes, to ensure that potable
water in the piping is not stagnant.
Note: If the FLWSWTCH optional DHW priority ow switch 4 is installed and the DHW ow is above the factory setting for
this device, the primary pump stops. When the DHW ow drops below the factory setting the primary pump resumes
and the panel returns to normal operation.
4
2
3
14
1
®
HeatLink
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Flow Switch for DHW Priority (FLWSWTCH) Installation (optional, sold separately)
Installation Notes:
• Makes sure the cable to the ow switch isn't under tension.
• Clean the pipe system in which the ow switch is to be installed and remove any magnetic
particles, e.g. welding residue.
• The straight in- and outlet pipe (in front of and behind the ow switch) has to be at least
2-1⁄2" (65 mm).
• The ow switch should be installed in an “upright standing position” in horizontal pipework.
• The switch should only be installed in a vertical position, deviation max. 45°.
• Make sure that ther are no external magnetic elds or large ferromagnetic
bodies in the immediate vicinity of the ow switch, since these can impair
device functioning.
• Screw on the union plastic nut with a maximum torque of 8 Nm.
• To prevent overheating when soldering near the ow switch, the ow switch
(body with paddle system) and the o-ring must be removed from the pipe
section.
max. 45°
Step 1DHW connectors are 1⁄2” FNPT. Using appropriate thread sealant and
ttings, connect the water heater output to the input on the ow
switch; and house hot water system to output on ow switch.
The straight in- and outlet pipe (in front of and behind the ow
switch) has to be at least 2-1⁄2" (65 mm).
Observe ow direction when making connections.
Be sure to connect the DHW priority downstream from the panel
(see schematic below).
Heat
Source
FS
FLWSWTCH
DHW Priority Switch
DHW Supply
to House
Thermostat
Heating Load
Min. 2-1⁄2" (65 mm)Min. 2-1⁄2" (65 mm)
Step 2Turn the panel o . Plug the terminal header of the wiring
harness into the DHW priority contacts of the power box.
Terminal Header
of Wiring Harness
15
®
HeatLink
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Troubleshooting
ProblemCheck / VerifyPossible Cause
Low Temperature Within Room
High Temperature Within Room
Misplacement of thermostat location within
room.
Low temperature setting of the thermostat.Adjust the temperature setting on thermostat.
The system fails to turn on if the thermostat is
set to high setting
The electronic actuator fails to open during a
call for heat
Low supply mixed fl uid temperature.Adjust the thermostatic mixing valve to the
Wiring from heat source to panel.Check that the wiring is done properly. Consult
Output of heat source is unable to meet
demand of heating system.
The red and green LED’s on the power module
do not light up during a call for heat.
Circulator is not on during a call for heat. (Use
a stethoscope or similar device to verify)
When zone valves are installed outside the
panel a qualifi ed electrician should verify 24V
power is supplied to the thermostats and
actuator.
Check current setting of the thermostat.Adjust the temperature setting on thermostat
High supply mixed fl uid temperature.Adjust the Thermostatic Mixing Valve to the
Installed electronic actuators remain open
after the thermostat is satisfi ed.
Bypass switch(es) may be on.Check that the front three-way switch on the
Make sure thermostat is not being infl uenced
by an additional heat source, such as lighting
or air duct.
Thermostat may be out of calibration or
defective. Replace thermostat.
The electronic actuator may be improperly
seated or may be defective. Replace if
necessary.
appropriate setting.
qualifi ed electrician prior to alteration of wiring
between heat source and panel.
Compare output of heat source to the
requirements of the heating system.
The zone valve controller may be defective
or there is no power being supplied to the
panel or the power module is not on. If this
is so, switch the power module to by-pass
mode. When the front three-way switch is
placed in the “Heat Source Pump Bypass”
position, the green LED will be lit, indicating
that the panel is powered with 110V, and the
Primary pump will run. When the side “Bypass
Radiant Pump” switch is placed in the “ON”
position, the yellow LED will be lit, indicating
that the panel is powered with 110V, and the
Secondary pump will run. This will provide
constant circulation so long as there is still
110V power to the panel.
The power box or circulator may be defective.
The 24V transformer may have failed. If this
so, switch the power module to Bypass mode.
This will provide constant circulation so long
as there is still 110V power to the panel. Prior
to Bypass mode selection, any zone valves
must be opened manually to avoid deadheading of the circulator.
to a lower setting.
appropriate settings.
An obstruction inside the zone valve is not
allowing the actuator to fully close or the
thermostat is still calling for heat.
power box is in the “ON” position and the side
“Bypass Radiant Pump” switch is in the “OFF”
position.
16
®
HeatLink
www.heatlinkgroup.com
Troubleshooting (continued)
Temporarily create a “permanent” heat demand:
With switch in ‘ON’
position, red ‘POWER’
light will be on.
With jumper between
W & R, green and yellow
lights will be on and
pumps will run.
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Install Jumper
between W & R
(closed when
pump running)
Maintenance
Yearly maintenance should be done on the panel prior to each heating season to ensure the e cient and accurate operation
of the panel.
Complete the following check list:
• Raise all thermostats to cause a call for heat within the system. Verify that the circulator starts, via a stethoscope or
similar device.
• Con rm that the Auxiliary Contacts close.
• If applicable, verify that each zone valve opens during the call for heat – the actuator should be warm to the touch, the
LED will light up (on 5620x models) and the white indicator should rise from the top of the actuator.
• Return all thermostats to a desirable setting.
You are now ready for another heating season with HeatLink.
17
SCH-MRIB-R001
SCH-TWH-M002
SCH-TWH-E001
Schematic #:
Thermostat
Panel
TWH070P/
TWH070XP
T
Manifold
Radiant Heating
to House
DHW Supply
FS
Optional
T
DHW Priority Switch
Tankless Water Heater
Heat Source:
Rough-in wiring see:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
Wiring detail see:
2013-03-18
Date:
Pump
Check
Primary
Valve in
180
18
Supply
Cold Water
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
Thermostat
Manifold
Radiant Heating
DHW Supply
FS
to House
Optional
SCH-MRIB-R001
SCH-TWH-M003
SCH-TWH-E003
Schematic #:
Wiring detail see:
Rough-in wiring see:
Check
Panel
TWH070P/
TWH070XP
T
Pump
Primary
Valve in
T
DHW Priority Switch
Tankless Water Heater with Storage Tank
TWH Series
Radiant Heating – Single Zone
2013-03-18
Panel(s):
Heat Source:
Heat Load(s):
Date:
Storage Tank
180
Check Valve
R1
in Pump
P3
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Local codes, regulations, and authorities have final jurisdiction.
Cold Water
Notes:
Supply
1-866-661-5332
www.heatlinkgroup.com
19
SCH-MRIB-R001
SCH-TWH-M004
SCH-TWH-E004
Schematic #:
Thermostat
Panel
TWH070P/
TWH070XP
T
Manifold
Radiant Heating
to House
DHW Supply
FS
Optional
T
DHW Priority Switch
Tankless Water Heater with High Flow Resistance
Heat Source:
Rough-in wiring see:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
Wiring detail see:
2013-03-18
Date:
Pump
Check
Primary
Valve in
180
20
R1
P3
In Series Pump
Supply
Cold Water
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
SCH-MRIB-R001
SCH-TWH-M005
SCH-TWH-E005
Schematic #:
Rough-in wiring see:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
Wiring detail see:
2013-03-18
Date:
P3
by heater or timer.
Non-ferrous pump controlled
Manifold
Radiant Heating
Farthest
Fixture
DHW Supply
T
FS
to House
Optional
DHW Priority Switch
Tankless Water Heater
Heat Source:
Thermostat
Panel
TWH070P/
TWH070XP
T
Pump
Check
Primary
Valve in
180
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Local codes, regulations, and authorities have final jurisdiction.
Supply
Cold Water
Notes:
1-866-661-5332
www.heatlinkgroup.com
21
SCH-TWH-M006
SCH-MRIB-R001
SCH-TWH-E006
Schematic #:
Wiring detail see:
Thermostat
Manifold
Rough-in wiring see:
Radiant Heating
Recommended
Panel
TWH070P/
TWH070XP
T
Sidestream Filter
Boiler
Heat Source:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
2013-03-18
Date:
Check
Primary
Valve in
Pump
Supply
Cold Water
Boiler
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
22
SCH-TWH-M007
SCH-MRIB-R002
SCH-TWH-E002
Thermostats
T
Thermostat
Manifold
Radiant Heating
Schematic #:
Wiring detail see:
Manifold
Rough-in wiring see:
Radiant Heating
Recommended
Panel
TWH070P/
TWH070XP
Pressure
Bypass Valve
Recommended
Sidestream Filter
Boiler
Heat Source:
TWH Series
Radiant Floor Heating – Multiple Zones
Panel(s):
Heat Load(s):
2013-04-30
Date:
Check
Primary
Valve in
Pump
Supply
Cold Water
Boiler
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
23
SCH-MRIB-R001
SCH-TWH-M008
SCH-TWH-E001
Schematic #:
Wiring detail see:
Rough-in wiring see:
Check
Thermostat
Panel
TWH070P/
TWH070XP
T
Pump
Primary
Valve in
Manifold
Radiant Heating
Recommended
Sidestream Filter
Tankless Water Heater
Heat Source:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
2013-04-30
Date:
Supply
Cold Water
24
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
180
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
SCH-TWH-M009
SCH-MRIB-R002
SCH-TWH-E007
Thermostats
Thermostat
Manifold
Radiant Heating
Schematic #:
Wiring detail see:
Rough-in wiring see:
Manifold
Radiant Heating
Recommended
Panel
TWH070P/
TWH070XP
Pressure
T
Bypass Valve
Recommended
Sidestream Filter
Tankless Water Heater
TWH Series
Radiant Floor Heating – Single Zone
2013-04-30
Panel(s):
Heat Source:
Heat Load(s):
Date:
Supply
Cold Water
Check
Pump
Primary
Valve in
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
180
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
25
1
SCH-MRIB-R001
2
2
Heating Load
4
Rough-in Wiring for One Zone Heating
2012-10-19
Heat
Source
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
Notes:
Room Thermostat
Standard 4-wire to be run from thermostat to mechanical room.
Floor Sensor (optional)
Standard 2-wire to be run from thermostat to floor sensor.
1
2
Date:
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
26
1-866-661-5332
www.heatlinkgroup.com
SCH-MRIB-R002
22
44444
2
Manifold #2 Location
4
11
55
3
2
6
Optional
Allow for 110V power source to a 24V transformer at each manifold location instead
of supplying 24V power from the mechanical room.
Floor Sensor (optional)
Standard 2-wire to be run from thermostat to floor sensor.
4
222
Manifold #1 Location
4
6
5
Rough-in Wiring for Multiple Zone Heating with
StatLink
2012-10-19
Application:Schematic #:
Date:
Mechanical Room
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Notes:
Room Thermostats
Standard 4-wire to be run from each zone back to the corresponding manifold location.
6-wire Jumper
6-wire to be run between each manifold location. This allows for the transfer of the
clock signal, heat demand information, and power from module to module.
6-wire Jumper
6-wire to be run from the last manifold location to the mechanical room. This allows
Heat
Source
1
2
for the transfer of the clock signal, heat demand information, and power.
3
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
27
SCH-MRIB-R001
SCH-TWH-E001
Rough-in wiring see:
46443
C C R WNTC
Optional
TWHP Panel
RCAUX
W
24 Vac
FS
Switch
FLWSWTCH
DHW Priority
L
Pump
Secondary
Pump
Primary
N
Single Zone Heating
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
28
1-866-661-5332
www.heatlinkgroup.com
46443
SCH-MRIB-R002
SCH-TWH-E002
Rough-in wiring see:
1
21122
R
C
W
CR
C
C C R WNTC
R
24 V
Module 40226
StatLink Base
L
or
110V
220V
N
Multiple Zone Heating with StatLink
2013-03-18
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
Notes:
Date:
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
Transformer
24 Vac Class II
(Floating Neutral)
Boiler
Contacts
TWHP Panel
RCAUX
W
24 Vac
FS
Switch
Optional
FLWSWTCH
DHW Priority
L
Pump
Secondary
Pump
Primary
N
1-866-661-5332
www.heatlinkgroup.com
29
SCH-MRIB-R001
SCH-TWH-E003
R1
24 Vac
SPDT
Relay
P3
Rough-in wiring see:
Aquastat
End Switch
C
R
24 V
46443
Transformer
24 Vac Class II
(Floating Neutral)
C C R WNTC
FS
Switch
Optional
FLWSWTCH
DHW Priority
RCAUX
W
24 Vac
L
or
110V
220V
N
L
TWHP Panel
Pump
Secondary
Pump
Primary
N
One Zone Heating with Storage Tank
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
30
1-866-661-5332
www.heatlinkgroup.com
SCH-MRIB-R001
SCH-TWH-E004
R1
24 Vac
SPDT
Relay
Rough-in wiring see:
P3
Pump
C
R
24 V
46443
Transformer
24 Vac Class II
(Floating Neutral)
C C R WNTC
FS
Switch
Optional
FLWSWTCH
DHW Priority
RCAUX
W
24 Vac
L
or
110V
220V
N
L
TWHP Panel
Pump
Secondary
Pump
Primary
N
One Zone Heating with Fixed Speed Pump
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
31
SCH-MRIB-R001
SCH-TWH-E005
Rough-in wiring see:
See Tankless
Water Heater
Instructions
Heater
Tankless Water
P3
Pump
Recirculation
46443
C C R WNTC
Optional
TWHP Panel
RCAUX
W
24 Vac
FS
Switch
FLWSWTCH
DHW Priority
L
Pump
Secondary
Pump
Primary
N
Single Zone Heating
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, an d authorities have final jurisdiction.
32
1-866-661-5332
www.heatlinkgroup.com
46443
SCH-MRIB-R001
SCH-TWH-E006
Rough-in wiring see:
Boiler
Contacts
TWHP Panel
C C R WNTC
RCAUX
W
24 Vac
L
Pump
Secondary
Pump
Primary
N
Single Zone Heating
2013-04-22
Application:Schematic #:
Date:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
Notes:
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
33
46443
SCH-MRIB-R002
SCH-TWH-E007
Rough-in wiring see:
1
21122
R
C
W
CR
C
C C R WNTC
R
24 V
Module 40226
StatLink Base
RCAUX
W
(Floating Neutral)
L
or
110V
220V
N
Multiple Zone Heating with StatLink
2013-04-22
Application:Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
Notes:
Date:
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
Transformer
24 Vac Class II
TWHP Panel
24 Vac
L
Pump
Secondary
Pump
Primary
N
34
1-866-661-5332
www.heatlinkgroup.com
HeatLink
www.heatlinkgroup.com
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
35
Canada
Manufactured & distributed by HeatLink Group Inc.
Head Office:
4603E - 13th Street N.E.
Calgary, Alberta, T2E 6M3
Eastern Canada Distribution Center:
2810 Argentia Road, Units 5-7
Mississauga, Ontario, L5N 8L2
Toll Free: 1-800-661-5332
Fax: 1-866-450-1155
China
Distributed by Cathay-Links International
Phone: 852-25693213
Fax: 852-25359271