HeatLink TWH070P, TWH070XP Installation, Operation And Maintenance Manual

Heat Link
®
TWH070P, TWH070XP
Tankless Water Heater Panels Installation, Operation, and Maintenance Manual
MECHANICAL
ROOM IN A BOX
L6TWH000P
Heat Link
www.heatlinkgroup.com
Table Of Contents
Warnings ........................................................................................................................3
Tools Needed ...............................................................................................................3
Function .........................................................................................................................4
Unpacking .....................................................................................................................4
Panel Components ....................................................................................................5
Speci cations ...............................................................................................................6
Dimensions ...................................................................................................................7
Panel Component Speci cations .........................................................................7-9
Valve Adjustments .....................................................................................................9
Mounting.......................................................................................................................10
Piping Hookup ............................................................................................................11
Fill and Purge ..............................................................................................................12
Panel Wiring .................................................................................................................13
Panel Control Sequence ...........................................................................................14
DHW Priority Switch Installation ...........................................................................15
Troubleshooting .........................................................................................................16-17
Maintenance ................................................................................................................17
Schematics
Mechanical ...............................................................................................................18-25
Electrical Rough-in ................................................................................................26-27
Electrical Detail .......................................................................................................28-34
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
2
®
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Warnings
The zone control panel is for indoor use only and must be installed by a quali ed installer/service technician. This product must be installed and operated in strict accordance with the terms set out in this manual and in accordance with the relevant requirements of the Local Authority Having Jurisdiction. Failure to comply will result in a void of warranty, and may also result in property damage, serious injury, or death.
Servicing
Prior to commencing installation of this panel it is necessary to read and understand all sections of this manual. The symbols below are used throughout this document to ensure proper operation of the panel, and your safety. Please pay attention to these symbols.
Warning
Possible Hazard
In order to avoid injury or death, switch o the power to the panel prior to inspecting or making connections to the terminal strip.
Disclaimer
HeatLink Group Inc. shall not be responsible for errors in its brochures or printed materials. HeatLink Group Inc. reserves the right to alter its products at any time without notice, provided that alterations to products already on order shall not require material changes in speci cations previously agreed upon HeatLink Group Inc. and the Purchaser. All trademarks in this material are property of the respective companies. HeatLink and the HeatLink logotype are trademarks of HeatLink Group Inc. All rights reserved.
Tools For Installation
• Level
• Screwdriver or power drill
• Flat head bit
• Phillips head bit # 2
• 2 adjustable wrenches (or 2× 30mm wrenches and 2× 40mm wrenches)
Warning
Live Power
Warning
Hot Pipes
Warning
Treated Water
3
®
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Function
This panel can provide mixing, distribution, and zoning for a wide variety of hydronic heating applications.
The e ectiveness of the system is dependant on the system being designed and installed correctly. Proper consideration of factors such as BTU loads, outdoor design temperature, indoor design temperature, room set-point temperature(s), di erential  uid temperatures, head loss,  ow rates, and transfer capacities of the heat emitters is critical.
Once these factors have been considered and the system requirements determined, these can then be evaluated and compared to the zone control panel capabilities (refer to pages 5-9).
Note: This panel does not regulate or monitor the operating safety limit temperatures of the  uid leaving the heat source.
Unpacking
Step 1 Examine carton for any damage that may have occurred during shipping. If damage is visible notify your courier and
supplier immediately.
Step 2 Open the carton by removing the staples.
Step 3 Remove the cardboard spacers from the carton, then remove the panel from the carton. Lift the panel by the base,
not the enclosure.
Step 4 There are 2 screws holding the enclosure in place during shipping. They are located at the top left & right of the panel
base. Remove these 2 screws.
Step 5 Remove the enclosure from the panel by sliding it upwards until it stops, then gently pulling outwards o .
Side View
To p
Screws
Step 6 Verify the following items:
• (4) Mounting screws
• (4) ¾" MBSP x 1" FNPT adapters
• (6) ¾" rubber washers (2 spares)
• (2) 1" rubber washers (spares)
Bottom
4
Heat Link
www.heatlinkgroup.com
Panel Components
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
TWH070P
1
TWH070XP
4
3
5
2
7
1
3
8
4
5
2
6
Part Number
# Component
1
Primary Circulator PUMP1558 PUMP2699BR
2
Secondary Circulator PUMP1558 PUMP1558
3
Thermostatic Mixing Valve
4
Power Box with 6' Power Cord PWRB7R2 PWRB7R2
5
Thermometer 76940 76940
6
Enclosure n/a n/a
Accessory Pack ACCTWH ACCTWH
7
3⁄4" Washer WHTWSH34 WHTWSH34
1" Washer NTRWSH1 NTRWSH1
Flow Switch for DHW Priority
8
(optional, sold separately)
TWH070 TWH070XP
FLWSWTCH FLWSWTCH
5
®
3
1
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Speci cations
Listing cETLus Conforms to CAN/CSA-C22 No.14, UL508 Dimensions 18.25"H x 16.25"W x 8"D Nominal panel output 70,000 btu/hr 70,000 btu/hr Primary nominal fl ow 4.0 US gpm @ 35°F ΔT 4.0 US gpm @ 35°F ΔT Primary nominal pressure drop outside of panel 14 ft 24 ft Secondary nominal fl ow 7 US gpm @ 20°F ΔT 7 US gpm @ 20°F ΔT Secondary nominal pressure drop outside of panel 4 ft 4 ft Max ambient temperature 120°F Max water temperature 200°F Min required fl ow for correct temp control 1.3 US gpm (5 L/min) Power supply: pre-wired on system controller 110 V(ac)
Primary circulator
Secondary circulator
Auxiliary terminal Yes DHW priority Optional @ ~0.5 US gpm DHW fl ow Temperature control method 1" 3-Way thermostatic Temperature control range 100°F - 145°F Valve Cv 3.0 Piping Piping connections 1" FNPT DHW priority switch connection Backplate Galvanized steel Enclosure Powder coated steel
TWH070P TWH070XP
Non-ferrous, Grundfos
UPS15-58CIL2
Non-ferrous, Grundfos
UPS15-58CIL2
⁄4" 304 Stainless steel tubing
⁄2" FNPT (FLWSWTCH optional)
Non-ferrous, Grundfos
Non-ferrous, Grundfos
UPS26-99BFC
UPS15-58CIL2
20.0
18.0
16.0
14.0
12.0
10.0
FT HD
8.0
6.0
4.0
2.0
0.0
TWH Series FT HD Outside of Panel
12345678
US GPM
6
Heat Link
www.heatlinkgroup.com
Dimensions
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
18.250”
3.602”
1.563”
2.936”
7.998”
Panel Component Speci cations
16.250”
7.908”
1.563”
3.570”
7.533”
Power Box
This module provides the required power for all electronic components on the panel, via the ON/OFF switch. Power box may not be exactly as shown.
Speci cations:
• Requires 115V power source.
• Requires a maximum 15A circuit breaker.
7
®
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Circulators
The circulators moves the heated  uid through the hydronic system when there is a call for heat from the thermostat. Primary pump on the TWH070XP is a UPS26-99BFC.
Speci cations:
• The following pump curves apply.
UPS15-58CIL2 Pump Curve
20
18
16
14
12
10
8
Head (feet)
6
4
2
0
0246810121416
Flow (gpm)
1st Speed 2nd Speed 3rd Speed
8
UPS26-99BFC Pump Curve
35
30
25
20
15
Head (feet)
10
5
0
0 5 10 15 20 25 30 35
Flow (gpm)
1st Speed 2nd Speed 3rd Speed
Heat Link
www.heatlinkgroup.com
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Indicator
on back
3-Way Thermostatic Mixing Valve (TMV)
The TMV controls the temperature of the hydronic system via a self regulating thermostat.
MINMAX7
1
2
Setting the TMV
The indicator for the valve is located at the base of the knob on the back. The mixed (desired) temperature is a function of the TMV setting.
MIX
See the below chart to determine the proper setting for you system. After allowing the system to run for a short period, verify the setting and adjust if necessary.
Unit
°F 81 90 100 111 120 127 136 145 152
°C 27 32 38 44 49 53 58 63 67
Min. 1234567Max.
Mixed Fluid Temperature
Flow Switch for DHW Priority (FLWSWTCH) (optional, sold separately)
The electronic  ow indicator provides DHW priority when the DHW  ow rate reaches a factor pre-set level (approx. 0.5 US gpm). Must be piped in downstream of panel (see schematic on page 15). Mounted separately from the panel (see page 15).
Thermometer (76940)
The pipe mounted thermometer reads the supply  uid temperature.
Speci cations:
• Temperature range of 32-210°F (0-100°C).
9
Heat Link
www.heatlinkgroup.com
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Mounting
Prior to mounting the panel, ensure the wall is capable of supporting the weight of the panel. Ensure that a 115V receptacle is within reach of the 6-foot cord and plug.
Step 1 Determine the locations and distance
between the wall studs. With a level at a minimum height of 4' from the  oor draw a straight line on the wall and mark the stud locations.
If the panel cannot be secured directly to the
studs, or suitable backing boards, plywood may need to be installed behind the panel to properly secure it in place.
Step 2 Screw two of the supplied mounting screws
into the wall studs (or backing plywood) 2" from the top of desired height, and 10-½" apart, leaving ¼" of screw out from the wall.
Step 3 Lift and place the panel onto the mounting
screws.
min. 4' from fl oor
Wall Stud
1
2"
10-½"
⁄4"
Step 4 Screw the two remaining mounting screws
into the holes at the bottom of the panel and tighten the top two screws.
Step 5 Before replacing the enclosure, refer to pages
12-14 for  ll and purge, and proper wiring instructions.
10
®
Heat Link
www.heatlinkgroup.com
Piping Hookup
Step 1 Before making any connections, identify the
required connections to and from the panel.
Adapters are ¾" M BSPP x 1" FNPT, and must use
the supplied adapters and rubber washers.
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Step 2 Connect all adapters.
1. Connect MNPT adapter E to copper pipe or tubing F.
2. Screw supplied M x FNPT adapter D onto E using appropriate thread sealant.
3. Take assembly
D E F
and place rubber
washer C on  at surface of D.
4. Without disturbing rubber washer C, place assembly against  anged stainless steel pipe
B
.
5. Slide nut
A
over adapter D and  rst  nger tighten nut. Then, using two 30mm wrenches, tighten the nut taking care not to overtighten the nut, as this will damage the rubber washer.
Step 3 See page 15 for instructions on connecting
the optional Flow Switch for DHW Priority (FLWSWTCH).
A
Primary Supply
1
Primary Return
2
Secondary Supply
3
Secondary Return
4
4
312
C
D
E
F
B
Note: Use precautions when soldering or applying heat within 16" of the panel.
Do not overtighten brass nuts!
11
®
Heat Link
www.heatlinkgroup.com
Fill And Purge
The following steps are recommended in order to  ll the panel with water and purge entrained air once piping is completed, and before activation of the panel.
The discharged system  uid from the  ll and purge process is not for consumption or washing.
Note: Additional purging steps may be required for the rest of
the hydronic system.
Note: Isolation and drain valves are not included with the
panel, but are necessary to properly  ll and purge the panel, and to isolate the panel for service.
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
E F
Step 1 Ensure the panel is not plugged in.
Step 2 Adjust the thermostatic mixing valve to a position of
“Max.“ (see page 9).
Step 3 Fully close valves A, B, C, D,and F. Fully open valve E.
Step 4 Attach a purge hose (not included) to E and a  ll
hose (not included) to F. Open valve F.
Step 5 When exiting water from E is free of bubbles, close
valve E, then valve F.
Step 6 Remove hoses from drain valves and full open valves
A, B, C
Step 7 Check for leaks at connections. If any leaks are found,
use a back-up wrench and carefully tighten until leak stops. Do not overtighten.
Step 8 Readjust the setting of the thermostatic mixing valve
to provide a proper mixed  uid temperature to the hydronic system (see page 8).
, and D.
A B C D
12
®
Heat Link
www.heatlinkgroup.com
Installation, Operation, and Maintenance
Panel Wiring
Note: Terminal headers are removable to make wiring connections easier.
Thermostat Wiring
• 24V low voltage power may be supplied to the thermostat. Wiring of thermostat should be done by quali ed electrician and should meet local codes and jurisdictions. Wiring to the terminal strip requires 18 gauge 4 wire.
• Do not exceed 2VA per thermostat.
• Do not cross terminals C and R – this will damage the Power Box.
TWH – Tankless Water Heater Panels
Factory Jumper
24 V
Signal
Do not remove.
WRC AUX
2-Wire Thermostat
(battery only or non-electric)
Signal
WRC AUX
3-Wire Thermostat
(HeatLink thermostats)
Factory Jumper
24 V
24 V
Do not remove.
24 V
24 V
Dry Contact
Factory Jumper Do not remove.
Signal
Jumper to
WRC AUX
4-Wire Thermostat
(with dry contact signal)
Other Terminals
Auxiliary Contacts The auxiliary contact set is dry, meaning no supply of power is present at the terminal. The
maximum allowable load is 2A. The auxiliary dry contact located on the terminal is to switch another device (ie. the heat source) when there is a call for heat from any zone.
DHW Priority Contacts The wiring harness of the optional Flow Switch for DHW Priority (FLWSWITCH) plugs into these
contacts (see page 15).
13
®
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Panel Control Sequence
1. When the power cord 1 from the power module is plugged in, and the Power switch located on the front of the module is placed in the on position the red LED will be lit, indicating that the panel is powered with 110V.
2. The factory setting for the BYPASS switches 2 are to remain in the OFF position. Only switch the front 3-way switch to “Heat Source Pump Bypass“ or Radiant Pump Bypass switch to ON if the red and green LED’s on the power module do not light up during a call for heat. Please refer to the troubleshooting section of the manual for further details.
3. When a thermostat calls for heat, its internal 24V contacts close, the auxiliary terminals close, and both circulators 3 turn on.
4. As the circulators move  uid through the panel the thermostatic mixing valve adjusts the  uid temperature based on the user settings (page 8).
5. When the requirements of the thermostat are met, the internal contacts of the thermostat open, the auxiliary contacts open, and the circulators stop.
6. Both the primary and secondary circulators are activated once every 24 hours, for 15 minutes, to ensure that potable water in the piping is not stagnant.
Note: If the FLWSWTCH optional DHW priority  ow switch 4 is installed and the DHW  ow is above the factory setting for
this device, the primary pump stops. When the DHW  ow drops below the factory setting the primary pump resumes and the panel returns to normal operation.
4
2
3
14
1
®
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Flow Switch for DHW Priority (FLWSWTCH) Installation (optional, sold separately)
Installation Notes:
• Makes sure the cable to the  ow switch isn't under tension.
• Clean the pipe system in which the  ow switch is to be installed and remove any magnetic
particles, e.g. welding residue.
• The straight in- and outlet pipe (in front of and behind the  ow switch) has to be at least
2-1⁄2" (65 mm).
• The  ow switch should be installed in an “upright standing position” in horizontal pipework.
• The switch should only be installed in a vertical position, deviation max. 45°.
• Make sure that ther are no external magnetic  elds or large ferromagnetic
bodies in the immediate vicinity of the  ow switch, since these can impair device functioning.
• Screw on the union plastic nut with a maximum torque of 8 Nm.
• To prevent overheating when soldering near the  ow switch, the  ow switch
(body with paddle system) and the o-ring must be removed from the pipe section.
max. 45°
Step 1 DHW connectors are 1⁄2” FNPT. Using appropriate thread sealant and
 ttings, connect the water heater output to the input on the  ow switch; and house hot water system to output on  ow switch. The straight in- and outlet pipe (in front of and behind the  ow
switch) has to be at least 2-1⁄2" (65 mm). Observe  ow direction when making connections. Be sure to connect the DHW priority downstream from the panel
(see schematic below).
Heat
Source
FS
FLWSWTCH
DHW Priority Switch
DHW Supply
to House
Thermostat
Heating Load
Min. 2-1⁄2" (65 mm)Min. 2-1⁄2" (65 mm)
Step 2 Turn the panel o . Plug the terminal header of the wiring
harness into the DHW priority contacts of the power box.
Terminal Header
of Wiring Harness
15
®
Heat Link
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
www.heatlinkgroup.com
Troubleshooting
Problem Check / Verify Possible Cause
Low Temperature Within Room
High Temperature Within Room
Misplacement of thermostat location within room.
Low temperature setting of the thermostat. Adjust the temperature setting on thermostat.
The system fails to turn on if the thermostat is set to high setting
The electronic actuator fails to open during a call for heat
Low supply mixed fl uid temperature. Adjust the thermostatic mixing valve to the
Wiring from heat source to panel. Check that the wiring is done properly. Consult
Output of heat source is unable to meet demand of heating system.
The red and green LED’s on the power module do not light up during a call for heat.
Circulator is not on during a call for heat. (Use a stethoscope or similar device to verify)
When zone valves are installed outside the panel a qualifi ed electrician should verify 24V power is supplied to the thermostats and actuator.
Check current setting of the thermostat. Adjust the temperature setting on thermostat
High supply mixed fl uid temperature. Adjust the Thermostatic Mixing Valve to the
Installed electronic actuators remain open after the thermostat is satisfi ed.
Bypass switch(es) may be on. Check that the front three-way switch on the
Make sure thermostat is not being infl uenced by an additional heat source, such as lighting or air duct.
Thermostat may be out of calibration or defective. Replace thermostat.
The electronic actuator may be improperly seated or may be defective. Replace if necessary.
appropriate setting.
qualifi ed electrician prior to alteration of wiring between heat source and panel.
Compare output of heat source to the requirements of the heating system.
The zone valve controller may be defective or there is no power being supplied to the panel or the power module is not on. If this is so, switch the power module to by-pass mode. When the front three-way switch is placed in the “Heat Source Pump Bypass” position, the green LED will be lit, indicating that the panel is powered with 110V, and the Primary pump will run. When the side “Bypass Radiant Pump” switch is placed in the “ON” position, the yellow LED will be lit, indicating that the panel is powered with 110V, and the Secondary pump will run. This will provide constant circulation so long as there is still 110V power to the panel.
The power box or circulator may be defective.
The 24V transformer may have failed. If this so, switch the power module to Bypass mode. This will provide constant circulation so long as there is still 110V power to the panel. Prior to Bypass mode selection, any zone valves must be opened manually to avoid dead­heading of the circulator.
to a lower setting.
appropriate settings.
An obstruction inside the zone valve is not allowing the actuator to fully close or the thermostat is still calling for heat.
power box is in the “ON” position and the side “Bypass Radiant Pump” switch is in the “OFF” position.
16
®
Heat Link
www.heatlinkgroup.com
Troubleshooting (continued)
Temporarily create a “permanent” heat demand:
With switch in ‘ON’ position, red ‘POWER’ light will be on.
With jumper between W & R, green and yellow lights will be on and pumps will run.
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
Install Jumper between W & R
(closed when pump running)
Maintenance
Yearly maintenance should be done on the panel prior to each heating season to ensure the e cient and accurate operation of the panel. Complete the following check list:
• Raise all thermostats to cause a call for heat within the system. Verify that the circulator starts, via a stethoscope or
similar device.
Con rm that the Auxiliary Contacts close.
• If applicable, verify that each zone valve opens during the call for heat – the actuator should be warm to the touch, the
LED will light up (on 5620x models) and the white indicator should rise from the top of the actuator.
• Return all thermostats to a desirable setting.
You are now ready for another heating season with HeatLink.
17
SCH-MRIB-R001
SCH-TWH-M002
SCH-TWH-E001
Schematic #:
Thermostat
Panel
TWH070P/
TWH070XP
T
Manifold
Radiant Heating
to House
DHW Supply
FS
Optional
T
DHW Priority Switch
Tankless Water Heater
Heat Source:
Rough-in wiring see:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
Wiring detail see:
2013-03-18
Date:
Pump
Check
Primary
Valve in
180
18
Supply
Cold Water
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
Thermostat
Manifold
Radiant Heating
DHW Supply
FS
to House
Optional
SCH-MRIB-R001
SCH-TWH-M003
SCH-TWH-E003
Schematic #:
Wiring detail see:
Rough-in wiring see:
Check
Panel
TWH070P/
TWH070XP
T
Pump
Primary
Valve in
T
DHW Priority Switch
Tankless Water Heater with Storage Tank
TWH Series
Radiant Heating – Single Zone
2013-03-18
Panel(s):
Heat Source:
Heat Load(s):
Date:
Storage Tank
180
Check Valve
R1
in Pump
P3
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Local codes, regulations, and authorities have final jurisdiction.
Cold Water
Notes:
Supply
1-866-661-5332
www.heatlinkgroup.com
19
SCH-MRIB-R001
SCH-TWH-M004
SCH-TWH-E004
Schematic #:
Thermostat
Panel
TWH070P/
TWH070XP
T
Manifold
Radiant Heating
to House
DHW Supply
FS
Optional
T
DHW Priority Switch
Tankless Water Heater with High Flow Resistance
Heat Source:
Rough-in wiring see:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
Wiring detail see:
2013-03-18
Date:
Pump
Check
Primary
Valve in
180
20
R1
P3
In Series Pump
Supply
Cold Water
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
SCH-MRIB-R001
SCH-TWH-M005
SCH-TWH-E005
Schematic #:
Rough-in wiring see:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
Wiring detail see:
2013-03-18
Date:
P3
by heater or timer.
Non-ferrous pump controlled
Manifold
Radiant Heating
Farthest
Fixture
DHW Supply
T
FS
to House
Optional
DHW Priority Switch
Tankless Water Heater
Heat Source:
Thermostat
Panel
TWH070P/
TWH070XP
T
Pump
Check
Primary
Valve in
180
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Local codes, regulations, and authorities have final jurisdiction.
Supply
Cold Water
Notes:
1-866-661-5332
www.heatlinkgroup.com
21
SCH-TWH-M006
SCH-MRIB-R001
SCH-TWH-E006
Schematic #:
Wiring detail see:
Thermostat
Manifold
Rough-in wiring see:
Radiant Heating
Recommended
Panel
TWH070P/
TWH070XP
T
Sidestream Filter
Boiler
Heat Source:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
2013-03-18
Date:
Check
Primary
Valve in
Pump
Supply
Cold Water
Boiler
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
22
SCH-TWH-M007
SCH-MRIB-R002
SCH-TWH-E002
Thermostats
T
Thermostat
Manifold
Radiant Heating
Schematic #:
Wiring detail see:
Manifold
Rough-in wiring see:
Radiant Heating
Recommended
Panel
TWH070P/
TWH070XP
Pressure
Bypass Valve
Recommended
Sidestream Filter
Boiler
Heat Source:
TWH Series
Radiant Floor Heating – Multiple Zones
Panel(s):
Heat Load(s):
2013-04-30
Date:
Check
Primary
Valve in
Pump
Supply
Cold Water
Boiler
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
23
SCH-MRIB-R001
SCH-TWH-M008
SCH-TWH-E001
Schematic #:
Wiring detail see:
Rough-in wiring see:
Check
Thermostat
Panel
TWH070P/
TWH070XP
T
Pump
Primary
Valve in
Manifold
Radiant Heating
Recommended
Sidestream Filter
Tankless Water Heater
Heat Source:
TWH Series
Radiant Floor Heating – Single Zone
Panel(s):
Heat Load(s):
2013-04-30
Date:
Supply
Cold Water
24
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
180
Notes:
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
SCH-TWH-M009
SCH-MRIB-R002
SCH-TWH-E007
Thermostats
Thermostat
Manifold
Radiant Heating
Schematic #:
Wiring detail see:
Rough-in wiring see:
Manifold
Radiant Heating
Recommended
Panel
TWH070P/
TWH070XP
Pressure
T
Bypass Valve
Recommended
Sidestream Filter
Tankless Water Heater
TWH Series
Radiant Floor Heating – Single Zone
2013-04-30
Panel(s):
Heat Source:
Heat Load(s):
Date:
Supply
Cold Water
Check
Pump
Primary
Valve in
Drawings are for HeatLink suggested system layout only! User must determine
if system layout will work for their particular application.
Air vents, expansion tanks, pressure relief valves, etc. for heat source as per
local codes.
Use isolation ball valves for all circuits and components.
Notes:
180
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
25
1
SCH-MRIB-R001
2
2
Heating Load
4
Rough-in Wiring for One Zone Heating
2012-10-19
Heat
Source
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
Notes:
Room Thermostat
Standard 4-wire to be run from thermostat to mechanical room.
Floor Sensor (optional)
Standard 2-wire to be run from thermostat to floor sensor.
1
2
Date:
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
26
1-866-661-5332
www.heatlinkgroup.com
SCH-MRIB-R002
22
444 4 4
2
Manifold #2 Location
4
1 1
5 5
3
2
6
Optional
Allow for 110V power source to a 24V transformer at each manifold location instead
of supplying 24V power from the mechanical room.
Floor Sensor (optional)
Standard 2-wire to be run from thermostat to floor sensor.
4
2 2 2
Manifold #1 Location
4
6
5
Rough-in Wiring for Multiple Zone Heating with
StatLink
2012-10-19
Application: Schematic #:
Date:
Mechanical Room
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Notes:
Room Thermostats
Standard 4-wire to be run from each zone back to the corresponding manifold location.
6-wire Jumper
6-wire to be run between each manifold location. This allows for the transfer of the
clock signal, heat demand information, and power from module to module.
6-wire Jumper
6-wire to be run from the last manifold location to the mechanical room. This allows
Heat
Source
1
2
for the transfer of the clock signal, heat demand information, and power.
3
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
27
SCH-MRIB-R001
SCH-TWH-E001
Rough-in wiring see:
46443
C C R W NTC
Optional
TWHP Panel
RC AUX W
24 Vac
FS
Switch
FLWSWTCH
DHW Priority
L
Pump
Secondary
Pump
Primary
N
Single Zone Heating
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
28
1-866-661-5332
www.heatlinkgroup.com
46443
SCH-MRIB-R002
SCH-TWH-E002
Rough-in wiring see:
1
21122
R
C
W
CR
C
C C R W NTC
R
24 V
Module 40226
StatLink Base
L
or
110V
220V
N
Multiple Zone Heating with StatLink
2013-03-18
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
Notes:
Date:
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
Transformer
24 Vac Class II
(Floating Neutral)
Boiler
Contacts
TWHP Panel
RC AUX W
24 Vac
FS
Switch
Optional
FLWSWTCH
DHW Priority
L
Pump
Secondary
Pump
Primary
N
1-866-661-5332
www.heatlinkgroup.com
29
SCH-MRIB-R001
SCH-TWH-E003
R1
24 Vac
SPDT
Relay
P3
Rough-in wiring see:
Aquastat
End Switch
C
R
24 V
46443
Transformer
24 Vac Class II
(Floating Neutral)
C C R W NTC
FS
Switch
Optional
FLWSWTCH
DHW Priority
RC AUX W
24 Vac
L
or
110V
220V
N
L
TWHP Panel
Pump
Secondary
Pump
Primary
N
One Zone Heating with Storage Tank
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
30
1-866-661-5332
www.heatlinkgroup.com
SCH-MRIB-R001
SCH-TWH-E004
R1
24 Vac
SPDT
Relay
Rough-in wiring see:
P3
Pump
C
R
24 V
46443
Transformer
24 Vac Class II
(Floating Neutral)
C C R W NTC
FS
Switch
Optional
FLWSWTCH
DHW Priority
RC AUX W
24 Vac
L
or
110V
220V
N
L
TWHP Panel
Pump
Secondary
Pump
Primary
N
One Zone Heating with Fixed Speed Pump
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
31
SCH-MRIB-R001
SCH-TWH-E005
Rough-in wiring see:
See Tankless
Water Heater
Instructions
Heater
Tankless Water
P3
Pump
Recirculation
46443
C C R W NTC
Optional
TWHP Panel
RC AUX W
24 Vac
FS
Switch
FLWSWTCH
DHW Priority
L
Pump
Secondary
Pump
Primary
N
Single Zone Heating
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
Notes:
2013-03-18
Date:
HeatLink electrical schemat ics.
Local codes, regulations, an d authorities have final jurisdiction.
32
1-866-661-5332
www.heatlinkgroup.com
46443
SCH-MRIB-R001
SCH-TWH-E006
Rough-in wiring see:
Boiler
Contacts
TWHP Panel
C C R W NTC
RC AUX W
24 Vac
L
Pump
Secondary
Pump
Primary
N
Single Zone Heating
2013-04-22
Application: Schematic #:
Date:
Drawings are for HeatLink suggested electrical schematics only! User must
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
Notes:
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
1-866-661-5332
www.heatlinkgroup.com
33
46443
SCH-MRIB-R002
SCH-TWH-E007
Rough-in wiring see:
1
21122
R
C
W
CR
C
C C R W NTC
R
24 V
Module 40226
StatLink Base
RC AUX W
(Floating Neutral)
L
or
110V
220V
N
Multiple Zone Heating with StatLink
2013-04-22
Application: Schematic #:
Drawings are for HeatLink suggested electrical schematics only! User must
Notes:
Date:
determine if electrical schematic will work for their particular application . User
must also confirm all HeatLink schematics with manufacturer schematics of each
particular control chosen.
In all cases manufacturer equipment schematics will take precedence over
HeatLink electrical schemat ics.
Local codes, regulations, and authorities have final jurisdiction.
Transformer
24 Vac Class II
TWHP Panel
24 Vac
L
Pump
Secondary
Pump
Primary
N
34
1-866-661-5332
www.heatlinkgroup.com
Heat Link
www.heatlinkgroup.com
®
Installation, Operation, and Maintenance
TWH – Tankless Water Heater Panels
35
Canada
Manufactured & distributed by HeatLink Group Inc.
Head Office:
4603E - 13th Street N.E. Calgary, Alberta, T2E 6M3
Eastern Canada Distribution Center:
2810 Argentia Road, Units 5-7 Mississauga, Ontario, L5N 8L2
Toll Free: 1-800-661-5332 Fax: 1-866-450-1155
China
Distributed by Cathay-Links International Phone: 852-25693213 Fax: 852-25359271
Ireland
Distributed by Jamoni Ltd. Phone: 057 - 932 4062 Fax: 057 - 932 4063 Freephone: 1800-311338
México
Distributed by Distribuidora Caisa S.A. de C.V. Phone: (52-55) 3300-4400 Fax: (52-55) 3300-4406
HeatLink, the HeatLink logo, and “Mechanical Room in a Box” logo are either registered
April 30, 2013
United States
Distributed by HeatLink Group Inc.
USA Distribution Center:
1000 - 100th Street SW, Suite B Byron Center, MI, 49315 Toll Free: 1-800-661-5332 Fax: 1-800-869-6098
www.heatlinkgroup.com
trademarks or trademarks of HeatLink Group Inc.
Printed in Canada
© HeatLink Group Inc.
Loading...