Heatilator G141, G141L, G141E, G141LE Owner's Manual

Heatilator
WARNING!
Installation and service must be performed by a qualified installer, service agency or the gas supplier. Improper installation, adjustment, alteration, service or maintenance can cause injury or property dam­age. Refer to this manual. For assistance or additional information, consult a qualified installer, ser­vice agency or the gas supplier.
1915 W. Saunders Street
Mt. Pleasant, IA 52641
A Division of Hearth Technologies Inc.
G141 SERIES B-VENT GAS APPLIANCE
OWNERS MANUAL
AND INSTALLATION INSTRUCTIONS
WARNING: If the information in this manual
is not followed exactly, a fire or explosion may result causing property damage, personal in­jury or loss of life.
 Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
 What to do if you smell gas
 Do not try to light any appliance.  Do not touch any electrical switch; do not
use any phone in your building.
 Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers instructions.
 If you cannot reach your gas supplier, call
the fire department.
 Installation and service must be performed by
a qualified installer, service agency or the gas supplier.
CAUTION:
Do not expose the fireplace to the elements (such as rain, etc.)
10-00 1 32921 Rev A
This manual must be used for installation of the G141 Series Gas Appliance and retained by the homeowner for operation and maintenance instructions.
G141 SERIES B-VENT GAS APPLIANCE
Table of Contents
A. Preparation ..................................................................................................................... 3
B. Locations & Clearances .................................................................................................. 5
C. Framing ........................................................................................................................... 6
D. Setting the Fireplace ........................................................................................................ 6
E. Venting ............................................................................................................................ 7
F. Utilities .......................................................................................................................... 10
G. Finishing Materials. ........................................................................................................ 15
H. Firebox Preparation ....................................................................................................... 16
J. Lighting Instructions ....................................................................................................... 18
K. Seasonal Checklist ........................................................................................................ 20
L. Maintenance Instructions ................................................................................................ 21
M. Trouble Shooting ............................................................................................................ 24
N. Optional Components .................................................................................................... 26
O. Replacement Parts ........................................................................................................ 27
Safety Precautions
1. Please read these installation instructions completely before beginning installation procedures. Failure to follow them could cause a malfunction resulting in serious injury and/or property damage.
2. Always check your local building codes prior to installation. The installation must comply with all local, regional, state and national codes and regulations.
3. Installation and repair should be done by a qualified service person. This appliance should also be inspected annually by a qualified service person. More frequent inspections/cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment and burners of the appliance be kept clean.
4. The G141 is a vented gas fireplace. Do not burn wood or other material in this appliance.
5. NEVER leave children unattended when there is a fire burning in the fireplace.
6. This appliance must be vented with a minimum 5 B-Vent system and must terminate above the roof line. Venting must not be connected to a chimney flue servicing a solid fuel burning appliance.
7. Use only the fuel gas specified on the rating label of this gas appliance.
8. The appliance area shall be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
9. While servicing this appliance, always shut off all electricity and gas to the fireplace. This will prevent possible electrical shock or burns. Also, make sure the fireplace is completely cooled before servicing.
10. The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
11. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
12. Be sure to provide adequate clearances around the air openings into the combustion chamber and adequate accessibility clearances for servicing and proper operation.
13. Provisions shall be made to provide adequate combustion and ventilation air. The flow of combustion and ventilation air should not be obstructed.
32921 Rev A 2 10-00
G141 SERIES B-VENT GAS APPLIANCE
A. PREPARATION
1. CERTIFICATION.
The G141 Series Gas Fireplace has been tested in accordance with the standard ANSI Z21.50-1998­CGA 2.22-M98. The G141 has been certified by Underwriters Laboratories Inc. for installation and operation as described in these Installation Instructions. All components are AGA or UL safety certified.
2. LOCAL CODES.
Check with your local building code agency prior to installing this appliance to ensure compliance with local codes, including the need for permits and follow-up inspections. This appliance must conform with local codes, or in the absence of local codes, comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.; in Canada, the CANI-B149-latest edition.
3. OPTIONAL COMPONENTS.
This gas appliance has been tested and listed for use with the optional components listed below. Many optional components may be purchased separately and installed at a later date. However, installation of a remote control will require electrical power. To avoid costly reconstruction, a separate
course of electrical power should be supplied to the fireplace at the time of initial installation of the system for possible addition of these accessories at a later date.
4. FUEL.
Any additions, changes or conversions required in order for the appliance to satisfactorily meet the application needs, must be made by a qualified service technician using factory specified and approved parts.
This product is manufactured to use natural gas or propane gas, depending on model purchased. A natural gas fireplace can be converted to use propane gas later, but only if done by a qualified service technician and only if the CKP Natural Gas to Propane Gas Conversion Kit is used. In the event your appliance must be converted to natural gas from propane, you must use a CKN Propane Gas to Natural Gas Conversion Kit.
If any assistance is required during installation, please contact your local dealer or contact Heatilator, Technical Services Department, 1915 W. Saunders Street, Mt. Pleasant, Iowa 52641.
HEATILATOR® is a registered trademark of Heatilator, a Division of Hearth Technologies Inc.
The G141 Series is a vented gas fireplace. While a significant amount of heat is created by the G141, it is not intended to be and, therefore, should not be used as a heater.
The G141 B-Vent Gas Appliance must consist of the following:
1. Fireplace
2. B-Vent System
3. Termination
Tools and building supplies normally required for installation:
Saw Wall-finishing materials Pliers Framing material Hammer Fireplace surround Phillips screwdriver Caulking material Tape measure Plumb line Level Electric drill/bits Square
Note: Illustrations throughout these instructions reflect typical installations and are for design purposes only. Actual installation may vary slightly due to individual design preferences. However, minimum and maximum clearances must be maintained at all times.
Optional components include:
1. Remote Control
2. Outside Air Kit
3. Glass Doors
4. Refractory Upgrade
5. Quick Tile Trim
6. ID4
7. UD4
10-00 3 32921 Rev A
Vertical Termination Cap
Storm Collar
Roof Flashing
Firestop Spacer
5 Gas B-Vent Pipe Section(s)
G141 SERIES B-VENT GAS APPLIANCE
The table below is a list of only those components which may be safely used with this decorative gas appliance. Only trim kits supplied by the manufacturer shall be used in the installation of this appliance.
#golataCnoitpircseD
141Gecnailppatnaidar,tolipgnidnats,saglarutan"63
L141Gecnailppatnaidar,tolipgnidnats,sagenaporp"63 E141Gecnailppatnaidar,noitingicinortcele,saglarutan"63
EL141Gecnailppatnaidar,noitingicinortcele,sagenaporp"63
RyrotcarfeR
63GRtiKyrotcarfeR PKCtiknoisrevnocsagenaporpotsaglarutaN NKCtiknoisrevnocsaglarutanotsagenaporP 4CR)tolipgnidnats(lortnocetomeR 5CR)noitingicinortcele(lortnocetomeR 6CRlortnocetomeR
41KAtiKriA
6301MD)kcalB(sroodssalgdlof-iB
A6301MD)ssarBeuqitnA(sroodssalgdlof-iB B6301MD)ssarBdehsiloP(sroodssalgdlof-iB
B2EKQdnuorruSeliT
A163FD)ssarBeuqitnA(rooDdexiF B163FD)ssarBdehsiloP(rooDdexiF
32921 Rev A 4 10-00
G141 SERIES B-VENT GAS APPLIANCE
B. LOCATIONS & CLEARANCES
31
1
/
2
3
/
15
4
5
/
36
8
21
3
36 38
FRONT LEFT SIDE TOPRIGHT SIDE
Junction Box
FIREBOX DIMENSIONS
3
/
2
4
3
/
36
4
Air Kit
Gas Line
19
38
1. LOCATION AND SPACE REQUIREMENTS.
This appliance may be installed along a wall, across a corner or in an exterior chase. DO NOT install B-Vent Gas Appliances in strong negative air locations, such as a basement or a public facility. This fireplace uses room air for normal operation and could have problems establishing a positive draft in negative air locations. In lieu, we recommend a direct vent appliance.The G141 Series may be installed at a
height level with the floor, or it can be raised up from the floor to enhance its visual impact. Figure 1 illustrates a variety of ways the fireplace may be located in a room. These fireplaces are also certified for installation in a bedroom or bed/sitting room in the U.S. and Canada. (Bedroom installations in Canada require the addition of non-operable doors.)
2. CLEARANCES.
The following clearances to combustibles must be maintained: Minimum clearances to the top standoffs of the fireplace - 0, floor - 0, back - 1, sides - 1, face of the fireplace to ceiling - 30. Minimum clearances to venting are as follows: Horizontal run sections require a 3 minimum air space on the top and a 1 minimum air space on the sides and bottom of the vent section. Venting that is vertical requires a 1 minimum air space completely around the vent section.
32
1
/
2
46
16
10
1
Min.
Figure 1 - Fireplace Locations and Clearances
Before moving to the following pages, do the following:
1. Wear gloves and safety glasses for protection.
2. Keep hand tools in good condition. Sharpen cutting edges and make sure tool handles are secure.
3. Always maintain the minimum air space required to the enclosure to prevent fire.
10-00 5 32921 Rev A
65
40
17
171
WARNING!
G141 SERIES B-VENT GAS APPLIANCE
C. FRAMING
1. FRAMING THE FIREPLACE.
The G141 Series Gas Appliance will fit a framed opening of 17 deep x 40-1/4 wide x 36-3/4 tall. Figure 2 shows a typical framing of this appliance assuming combustible materials are used. All required
clearances to combustibles around the fireplace must be adhered to. A 1 air space clearance must be maintained at the back and sides of the firebox assembly. Any framing on top of the fireplace must be above the top standoffs. Vent sections for a horizontal run require a 3 minimum air space clearance on top and a 1 minimum air space clearance on the sides and bottom. Vertical vent sections require a 1 minimum air space clearance completely around the vent section.
Note: If a hand held Remote Control (RC4 or RC5) is to be used, wiring must be done prior to finish­ing to avoid reconstruction.
Minimum vent clearances are per vent manufacturers specifications
3
36
1
/
40
17
Figure 2 - Framing Requirements
4
Note: The Wall Switch must be wired prior to apply­ing the finishing material to the wall in order to avoid reconstruction.
9 to 12 Mantel Projection: 41 height 0 to 9 Mantel Projection: 38 height
/
4
Figure 3 - Mantle Heights
Minimum allowable mantel heights are shown in Figure 3. All required clearances must be adhered to.
This fireplace may be placed on either a combustible or noncombustible continuous, flat surface. If the fireplace is installed on combustible flooring other than wood, a metal or wood panel needs to be installed underneath the appliance extending its full width and depth. Slide the fireplace into position and level the fireplace from side-to-side and front-to-back. Shim with noncombustible material, such as sheet metal, as necessary.
Secure the fireplace by bending out the nailing flanges located on each side of the fireplace and nailing the fireplace to the framing. See Figure 4.
32921 Rev A 6 10-00
D. SETTING THE FIREPLACE
Figure 4 - Nailing Flanges
G141 SERIES B-VENT GAS APPLIANCE
E. VENTING
1. TERMINATION.
Common venting of this gas appliance with other gas appliances is not allowed.
This fireplace requires the use of a 5 B-vent pipe for operation and must be terminated above the roof line. Never downsize pipe. Follow all B-vent requirements and installation instructions.
The minimum height of vent installation must be 9 from the top or 12 from the base of the appliance. Horizontal run must never exceed 20% of the height of the vent system as shown in Figure 5.
The Figures 5 and 6 show the maximum distances from the base of the fireplace, as well as the minimum air space clearances that must be maintained during termination of this appliance. Maximum straight unsupported rise - 25 feet; maximum horizontal unsupported run - 3 feet; air space clearances around vertical rise - 1 on all sides; air space clearances around the horizontal run - 3 on top and 1 on sides and bottom; maximum height - 40 from the base of the fireplace.
Figure 5 - Venting Off The Top of Appliance
Note: The horizontal run of vent must have a
1/4 rise for every 1 ft. of run towards the termi­nation. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.
Minimum clearances are per vent
manufacturers specifications
9 Min.
40
Max.
Figure 6 - Framing Requirements
Metal plumbers strap
secured to framing
Vent supports are per
vent manufacturers
specifications
10-00 7 32921 Rev A
G141 SERIES B-VENT GAS APPLIANCE
2. ASSEMBLY.
a. Assembling Vent Sections. Attach a straight
vent section to the top of the fireplace. Elbows
directly off the top of the fireplace are not allowed. This may cause the fireplace to
operate ineffectively. Secure the attached vent section to the appliance with the three screws supplied. Use only B-vent sections.
b. Using Elbows. Elbows 45 degrees and greater
from the vertical shall be considered horizontal and therefore adopt horizontal run limitations. See Figure 7.
c. Penetrating the Ceiling. Mark and cut out
an opening in the ceiling for the firestop spacer. Frame the opening with the same size lumber used in the ceiling joists.
d. Installing the Firestop Spacers. Firestop
spacers must be used whenever the venting penetrates a ceiling/floor area.
In all situations, firestop spacers are to be nailed to the ceiling joists from the bottom or appliance side, EXCEPT when the space above is an insulated ceiling or attic space. In this situation, the firestop spacer must be nailed from the top side to prevent loose insulation from falling into the required one inch air space around the vent system.
Install the firestop spacer by positioning and nailing the four sides of the firestop spacer to the joists using a minimum of three nails per side.
Note: Be sure to provide intermediate support for the vent during construction and check to be sure inadvertent loading has not dislodged the vent from the appliance or any vent joint.
Figure 7 - Using Elbows
WARNING!
When vent sections exceeding 3 feet in length are installed between an off­set and return, structural support must be provided to reduce off-center load­ing and prevent vent sections from separating at the vent joints. Follow all B-vent manufacturer guidelines.
e. Securing Vent System. Continue assembling
the vent sections up through the firestop spacers as needed. Vent sections must be locked into position. Elbows and chimney stabilizers have straps for securing these parts to joists or rafters.
f. Marking the Exit Point in the Roof. Locate
the point where the venting will exit the roof by plumbing down to the center of the vent system. Drive a nail up through the roof to mark the center. See Figure 8.
g. Cutting Out the Hole in the Roof. Measure
to either side of the nail and mark that 7 x 7 opening required (must meet minimum clearances per venting requirements). This is measured on the horizontal; actual length may
32921 Rev A 8 10-00
Figure 8 - Exiting Through the Roof
G141 SERIES B-VENT GAS APPLIANCE
be larger depending on the pitch of the roof. Cut out and frame the opening. See the Uniform Building Code for Roof Framing details. A one inch minimum air space clearance must be maintained between the vent section and the roof.
h. Install Roof Flashing or Site-Produced
Chase Top. Position a roof flashing or a site-
produced chase to and secure into place.
i. Assembling Vent Sections. Continue to add
vent sections through the roof opening, maintaining a minimum of one inch air space clearance.
j. Termination Cap. Major building codes
specify a minimum termination height above the roof top depending on the roof pitch. See Figures 9 and 10.
These termination heights are necessary in the interest of safety and do not guarantee proper operation. Trees, buildings, adjoining roof lines, adverse wind conditions, etc. may create a need for a taller roof termination should down drafting occur.
To install the termination cap, slide the cap vent sections into the vent pipe. Secure the cap using the screws provided.
k. Checking the Vent System. Periodically the
venting system should be tested to assure proper operation. This can be done with a match while the fireplace is operating.
Hold a lighted match at the top edge of the firebox opening. If the flames and smoke remain upright, ventilation is acceptable. If the flames and smoke are drawn into the firebox, this means ventilation is good. If the flames and smoke are forced away from the firebox, this may indicate a ventilation blockage or down draft resulting in gas spillage into your home. If this occurs, turn off the fireplace and do not burn it until it has been inspected by a qualified service person.
If you have installed optional doors, close the doors and conduct the test following the same instructions above. See Figure 11.
Listed Cap
Listed Gas Vent
Storm Collar
Roof Flashing Secured with Nails
Figure 9
Vent Height for Vertical Termination
hctiPfooRteef).niM(H
21/6ottalF0.1
21/7ot21/652.1
21/8ot21/7revO5.1 21/9ot21/8revO0.2
21/01ot21/9revO5.2
21/11ot21/01revO52.3 21/21ot21/11revO0.4 21/41ot21/21revO0.5 21/61ot21/41revO0.6 21/81ot21/61revO0.7 21/02ot21/81revO5.7 21/12ot21/02revO0.8
Figure 10
Minimum Termination Height
10-00 9 32921 Rev A
Loading...
+ 19 hidden pages