Heatilator EC36, EC39, EC42 Installation & Operating Instructions Manual

INSTALLATION & OPERATING
INSTRUCTIONS
EC36 EC39 EC42
WOODBURNING FIREPLACE
WARNING!
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency or the gas supplier.
08/04 17339 Rev L 1
EC SERIES INSTALLATION INSTRUCTIONS
Table of Contents
Design and Installation Considerations ......................................................................................... 3
A. Listings and Code Approvals ......................................................................................................... 4
B. Description of the Fireplace System .............................................................................................. 4
C. Fireplace System Components ..................................................................................................... 5
D. Pre-Installation Preparation ......................................................................................................... 10
E. Chimney Requirements ............................................................................................................... 12
F. Installation of Fireplace ............................................................................................................... 15
G. Constructing a Chase .................................................................................................................. 22
H. Operating Instructions .................................................................................................................25
I. Maintenance Instructions ............................................................................................................ 29
Index ........................................................................................................................................... 31
Warranty ..................................................................................................................................... 32
CAUTION:
Do not expose the fireplace to the elements (i.e. rain, etc.) and keep the fireplace dry at all times. Wet insulation will produce an odor when the fireplace is used.
WARNING!
This fireplace is tested and listed for use only with the optional accessories listed in these instructions. Use of optional accessories not specifically tested for this appliance could void the warranty and/or result in a safety hazard.
Safety Precautions
1. Please read these installation instructions completely before beginning installation procedures. Failure to follow them could cause a fireplace malfunction resulting in serious injury and/or property damage.
2. Always check your local building codes prior to installation. The installation must comply with all local, regional, state and national codes and regulations.
3. An adequate supply of replacement combustion air from outside the house must be available to the fire for the fireplace to operate properly. To achieve this, the use of the optional outside air kit is highly recommended.
In the event the home is unusually tightly sealed, the optional combustion air kit may not provide all the air required to support combustion. Hearth & Home Technologies is not responsible for any smoking or related problems that may result from the lack of adequate combustion air. It is the responsibility of the builder/contractor to ensure that adequate combustion air has been provided for the fireplace.
4. The fireplace must be installed with the Hearth & Home Technologies SL Series Chimney System.
The chimney system must always terminate outside the building. Be sure to follow all chimney specifications given in these installation instructions.
5. NEVER leave children unattended when there is a fire burning in the fireplace.
6. This fireplace is built for solid fuel only. NEVER use gasoline, gasoline type lantern fuel, kerosene, charcoal light
fluid, or similar liquids in this fireplace. Keep any flammable liquids a safe distance from the fireplace.
7. DO NOT use chimney cleaners or flame colorants in your fireplace.
8. The flue damper must be open at all times when the fireplace is in use.
9. While servicing this fireplace, always shut off any electricity or gas to the fireplace. This will prevent possible electric
shock or burns. Also, make sure the fireplace is completely cooled before servicing.
10. To ensure a safe fireplace system and to prevent the build up of soot and creosote, inspect and clean the fireplace and chimney prior to use and periodically during the burning season. See “Maintenance Instructions” in this manual for cleaning instructions.
2 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
DESIGN AND INSTALLATION CONSIDERATIONS
When selecting a location for your woodburning fireplace, it is important to evaluate a number of considerations. Modern construction techniques can create conditions that may not allow your chimney to draft properly. This may result in smoke spillage from your fireplace, as well as cause other combustion appliances to operate incorrectly.
Tightly sealed construction is important for energy efficiency. Unfortunately, a great deal of effort has been directed to tightening up sidewall construction, while considerably less attention has been paid to tightening upper portions of the warm air envelope (insulated ceilings). This has increased the “Stack Effect”, a condition that increases the negative pressure generated by the structure. This negative pressure will directly affect the drafting performance of a fireplace chimney. To minimize the negative pressure generated by stack effect, make certain that all duct work installed in the attic spaces is sealed airtight. Minimize the number of recessed light fixtures installed in the insulated ceiling, and use sealed recessed light fixtures. Finally, make certain the whole house fans and attic access panels are tightly sealed. These are important design considerations that must be observed during the design and construction stage of the home.
If you desire to put a fireplace in your basement, we recommend that you consider a direct vent gas fireplace. Basements always have a significant negative air pressure that causes the fireplace system to be more susceptible to smoke spillage and cold flue back drafting. Since direct vent gas fireplaces are sealed, they are not affected by the negative pressure that exists in basements.
Finally, woodburning fireplaces perform best when their chimney (roof termination) is located on the upper half of the roof, especially when cathedral ceilings are present. Chimneys that are located on the lower half of the roof realize what is known as “lazy flue” and will not draft as well as a chimney that is located in the upper portion of the roof. The reason for this is that the stack effect generated by the overall height of the living spaces inside the house will exceed the draft generated by the chimney system. If you desire to place a woodburning fireplace in a location where the termination cap would be located on the lower half of a roof, such as on an outside wall at the base of a cathedral ceiling, we recommend that you consider using a direct vent gas fireplace. This will assure the homeowner a fireplace that operates correctly.
These properties do not affect just your woodburning factory built fireplace. They can cause any woodburning fireplace as well as any conventionally vented (B-vent) gas appliance to operate improperly. Careful planning at this stage of your project will ensure satisfaction with the operation of your fireplace once it is completed.
08/04 17339 Rev L 3
EC SERIES INSTALLATION INSTRUCTIONS
A. LISTINGS AND CODE APPROVALS
This fireplace system has been tested and listed in accordance with UL127 and ULC-S610 standards, and has been listed by Underwriters Laboratories Inc. for installation and operation in the United States and Canada as described in this manual.
This fireplace has been tested and listed for use with the optional components listed on page 5. These optional components may be purchased separately and installed at a later date. However, installation of an outside air kit will require significant reconstruction, and should be installed at the time of the initial fireplace installation.
WARNING!
This fireplace and its components are designed to be installed and operated as a system. Any alteration to or substitution for items in this system, unless allowed by these installation instructions, will void the Underwrit­ers Laboratories listing and may void the product warranty. It may also create a hazardous installation. Read through these instructions thoroughly before starting your installation and follow them carefully throughout your project.
Check with your local building code agency prior to installing this fireplace to ensure compliance with local codes, including the need for permits and follow-up inspections. If you need assistance during installation, please contact your local dealer or the Heatilator Technical Services Department, Hearth & Home Technologies Inc., 1915 W. Saunders St., Mt. Pleasant, Iowa 52641 (1-800-927-6841).
Heatilator® is a registered trademark of Hearth & Home Technologies Inc.
B. DESCRIPTION OF THE FIREPLACE SYSTEM
1. The Heatilator fireplace system consists of the following: a. Fireplace/Integral Grate b. Refractory c. Chimney Termination Cap d. Chimney System e. Hearth Extension
2. Optional Components Include: a. Glass Doors b. Chimney Air Kit c. Outside Combustion Air System d. Fan Kit
Note: Illustrations used throughout these instructions
reflect “typical installations” and are for design purposes only. Actual installation may vary slightly due to indi­vidual design preferences. However, minimum and maxi­mum clearances must be maintained at all times.
The illustrations and diagrams used throughout these installation instructions are not drawn to scale.
Figure 1 - Typical Fireplace System
4 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
C. SYSTEM COMPONENTS
1. Fireplace Components
Catalog # Description:
E36 E39 E42 Fireplace, includes integral grate and hearth protection strips
HX3 HX3 HX4 Hearth Extension
DM1036 DM1039 DM1042 Original Bifold Glass Doors - Black Finish
DM1036B DM1039B DM1042B Original Bifold Glass Doors - Polished Brass Finish
DM1036S DM1039S DM1042S Original Bifold Glass Doors - Stainless Steel Finish
DP1036 none DP1042 Perception Glass Doors - Black Finish
DP1036B none DP1042B Perception Glass Doors - Polished Brass Finish
DP1036S none DP1042S Perception Glass Doors - Stainless Steel Finish
DMA1036B none DMA1042B Arched Cabinet Style Glass Doors - Polished Brass Finish
GR4 GR5 GR6 Integral Grate (i ncluded with fireplace)
AK14 Outside Air Kit
HEARTH EXTENSION GLASS DOORS
CAT. # A B
HX3 52 in. 16 in.
HX4 66 in. 20 in.
DM1036/DM1036B/DM1036S DM1039/DM1039B/DM1039S DM1042/DM1042B/DM1042S
JUNCTION BOX
JK8
INTEGRAL GRATE
(supplied)
FAN KIT
DMA1036B DMA1042B
DP1036/DP1036B/DP1036S DP1042/DP1042B/DP1042S
FK18
GR4, GR5, GR6
08/04 17339 Rev L 5
BC10
Fan Speed Control
EC SERIES INSTALLATION INSTRUCTIONS
Cat . # A B C D
E/EC36 36 in. [914mm] 41 in. [1041mm] 25-1/4 in. [641mm] 12-5/8 in. [321mm]
E/EC39 39 in. [991mm] 44 in. [1118mm] 28-1/4 in. [718mm] 14-1/8 in. [359mm]
E/EC42 42 in. [1067mm] 47 in. [1194mm] 31-1/4 in. [794mm] 15- 5/8 in. [397mm]
Fireplace Dimensions
OUTSIDE AIR KIT
AK14
6 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
2. Chimney Components
The following pictures show only those chimney components which may be safely used with this fireplace.
Catalog # Description:
CAK4A Chimney Air Kit
ID 4 Insul a t e d D uct/Outsi de A i r
UD4 Uninsulated Duct/Outside Air
SL306 Chimney Section - 6 in. long
SL312 Chimney Section - 12 in. long
SL318 Chimney Section - 18 in. long
SL324 Chimney Section - 24 in. long
SL336 Chimney Section - 36 in. long
SL348 Chimney Section - 48 in. long
SL3 Chimney Stabilizer
SL315 Chimney Offset/Return - 15-degree
SL330 Chimney Offset/Return - 30-degree
FS338
FS339 Firestop - 15-degree
FS340 Firestop - 30-degree
AS8 SL300 Straight Attic Insulation Shield, 24 in.
JB877 Chimney Joint Band
CB876 Chimney Bracket
RF370 Roof Flashing - Flat to 6/12 Pitch
RF371 Roof Flashing - 6/12 to 12/12 Pitch
TR344 Round Termination Cap
TR342 Round Telescoping Termination Cap
ST375 Square Termination Cap
TS345 Square Termination Cap
TS345P Square Termination Cap - Painted
TCT375 Terra Cotta Termination Cap
CT35 Chase Top
LDS33 Decorative Shroud - 3 ft x 3 ft
LDS46 Decorative Shroud - 4 ft x 6 ft
Firestop - Straight
08/04 17339 Rev L 7
Chimney Sections
Catalog # A B
SL306 6 in. 4-3/4 in.
SL312 12 in. 10-3/4 in.
SL318 18 in. 16-3/4 in.
SL324 24 in. 22-3/4 in.
SL336 36 in. 34-3/4 in.
SL348 48 in. 46-3/4 in.
A = Actual Length B = Effective length (length of
chimney part after it has been snapped to another)
EC SERIES INSTALLATION INSTRUCTIONS
SL330 - Offset/Return
SL3 - Chimney Stabilizer
Firestop Spacer
RF370 - Roof Flashing
Flat to 6/12 Pitch
RF371 - Roof Flashing
6/12 to 12/12 Pitch
Catalog # A B
FS338 0-deg. 14-1/2 in.
FS339 15-deg. 18-3/8 in.
FS340 30-deg. 23 in.
CB876
Chimney Bracket
JB877
Joint Band
AS8
Straight Attic
Insulation Shield
8 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
LDS33 (3 ft x 3 ft) LDS46 (4 ft x 6 ft)
Decorative Shroud
ST375
Square
Termination Cap
TR344 Round
Termination Cap
TS345/TS345P
Square
Termination Cap
TR342
Round Telescoping
Termination Cap
CT35
Chase Top
CAK4A
Chimney Air Kit
08/04 17339 Rev L 9
EC SERIES INSTALLATION INSTRUCTIONS
D. PRE-INSTALLATION PREPARATION
1. Fireplace Locations and Space Requirements
Several options are available to you when choosing a location for your fireplace. This fireplace may be used as a room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 2.
Locating the fireplace in a basement, near frequently opened doors, central heat outlets or returns, or other locations of considerable air movement can affect the performance and cause intermittent smoke spillage from the front of the fireplace. Consideration should be given to these factors before deciding on a location.
CLEARANCES!
A minimum 1/2 in. air clearance must be maintained at the back and sides of the fireplace assembly.
Chimney sections at any level require a 2 in. minimum air space clearance between the
Figure 2 - Fireplace Locations
Figures 3 and 4 show two typical installations assuming an outside air kit is being used. Therefore, an allowance must be made for 90-deg bends. Less space is required when ducting goes directly outside without forming elbows.
framing and chimney section.
Cat . # A B
E/EC36 42 in. [1067mm] 45 in. [1143mm]
E/EC39 45 in. [1143mm] 48 in. [1219mm]
E/EC42 48 in. [1219mm] 51 in. [1295mm]
Figure 3
Installation Along a Wall or an Exterior Chase
These are rough framing
dimensions only.
Cat . # A B C D E
Figure 4 - Corner Installation
E/ EC36
E/ EC39
E/ EC42
42 in.
[1067mm]
45 in.
[1143mm]
48 in.
[1219mm]
72-3/4 in.
[1848mm]
75-3/4 in.
[1924mm]
78-3/4 in.
[2000mm]
36-3/8 in.
[924mm]
37-3/8 in.
[962mm]
39-3/8 in.
[1000mm]
15-5/8 in.
[ 39 7 mm]
16-5/8 in.
[ 42 2 mm]
17-5/8 in.
[ 44 8 mm]
51-3/8 in.
[1305mm]
53-1/2 in.
[1359mm]
55-3/8 in.
[1407mm]
WARNING!
Do not draw outside air from garage spaces. Exhaust products of gasoline engines are hazardous.
Do not install outside air ducts such that the air may be drawn from attic spaces, basements or above the roofing where other heating appliances or fans and chimneys exhaust or utilize air. These precautions will reduce the possibility of fireplace smoking or air flow reversal.
WARNING!
To prevent contact with sagging or loose insulation, the fireplace must not be installed against vapor barriers or exposed insulation. Localized overheating could occur and a fire could result.
10 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
2. Frame the Fireplace
The EC Series fireplaces will fit a framed opening with the width shown in the Table below x 40-1/4 in. tall. The finished cavity depth must be no less than 23-1/2 in.
Figure 5 shows a typical framing (using 2 x 4 lumber) of the fireplace, assuming combustible materials are used. All required clearances to combustibles around the fireplace must be adhered to. Any framing across the top of the fireplace must be above the level of the top standoffs. Chimney sections at any level require a 2 in. minimum air
space clearance between the framing and chimney section.
Ca t. # A
E/EC36 42 in. [1067mm]
E/EC39 45 in. [1143mm]
E/EC42 48 in. [1219mm]
Figure 5
Framing the Fireplace
CLEARANCES!
A minimum 1/2 in. air clearance must be maintained at the back and sides of the fireplace assembly.
Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney section.
WARNING!
Do not apply combustible finishing materials over any part of the black face of this fireplace or a structure fire may result. The black metal fireplace front may only be covered with noncombustible materials such as ce­ramic tile, brick, or stone. Do not cover or block any cooling air slots. Do not cover any portion of the opening to the fireplace that would prevent the installation of an authorized glass door.
08/04 17339 Rev L 11
EC SERIES INSTALLATION INSTRUCTIONS
3. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 12 in. from the fireplace opening. See Figure 6. If you are using a decorative surround constructed of combustible material, it must be located within the shaded area defined in Figure 6. Short stub walls are also acceptable if they are contained within the shaded area.
Cat . # A B
E/EC36 36 in. [914mm] 41 in. [1041mm]
E/EC39 39 in. [991mm] 44 in. [1118mm]
E/EC42 42 in. [1067mm] 47 in. [1194mm]
Figure 6 - Sidewalls and Surrounds
E. CHIMNEY REQUIREMENTS
When planning your fireplace location, the chimney construction and necessary clearances must be considered. The fireplace system and chimney components have been tested to provide flexibility in construction. The following figures are the minimum distances from the base of the fireplace.
1. Minimum overall straight height 13 ft
2. Minimum height with offset/return 14.5 ft
3. Maximum height 90 ft
4. Maximum chimney length between an offset and return 20 ft
5. Maximum distance between chimney stabilizers 35 ft
6. Double offset/return minimum height 24 ft
7. Maximum unsupported chimney length between the offset and return 6 ft
8. Maximum straight unsupported chimney height above the fireplace 35 ft
12 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
1. Using Offsets and Returns
a. To bypass any overhead obstructions, the chimney may be offset using a 15-deg or 30-deg offset/return.
Perform the following steps to determine the correct chimney component combination for your particular installation.
b. An offset and return may be attached together or a chimney section(s) may be used between an offset and
return.
1) Measure how far the chimney needs to be shifted to enable it to avoid the overhead obstacle. See Figure 7, dimension “A” to determine chimney sections required to achieve the needed shift.
2) After determining the offset dimension, refer to Table 1 and find the “A” dimension closest to but not less than the distance of shift needed for your installation.
3) The “B” dimension that coincides with the “A” dimension represents the required vertical clearance that is
needed to complete the offset and return.
4) Read across the chart and find the number of chimney sections required and the model number of those particular chimney parts.
5) Whenever the chimney penetrates a floor/ceiling, a firestop spacer must be installed.
6) The effective height of the fireplace assembly is measured from the base of fireplace to top of starter
collar. See Figure 6.
WARNING!
Do not combine offsets to create an offset greater than 30 deg from verti­cal. This may create a fire hazard since the natural draft may be restricted.
Table 1 Offset Chart*
15-degree 30-degree
ABAB
1-5/8 in.13-3/8 in.3-7/8 in.14-1/2 in.------
2-7/8 in.17-3/4 in.6-1/4 in.18-5/8 in.1-----
4-1/8 in.22-3/8 in.8-5/8 in.22-3/4 in.2-----
4-1/2 in. 23-5/8 in. 9-1/4 in. 23- 3/4 in. - 1 - - - -
5-3/4 in. 28-1/4 in. 11 -5/8 in. 27-7/8 in. 1 1 - - - -
6 in. 29-3/8 in. 12-1/4 in. 29 in. - - 1 - - -
7-1/4 in. 34 in. 14-5/8 in. 33 in. - 2 - - - -
7-3/4 in. 36-1/8 in. 15 -1/4 in. 34-1/8 in. - - - 1 - -
8-3/4 in. 39-3/4 in. 17 -5/8 in. 38-1/4 in. 1 - - 1 - -
10-3/8 in. 45-5/8 in. 20-5/8 in. 43-1/2 in. - - 2 - - -
10-5/8 in.46-3/4 in.21-1/4 in.44-5/8 in.----1-
11-7/8 in. 51-3/8 in. 23-5/8 in. 48-3/8 in. 1 - - - 1 -
13-1/2 in. 57-1/4 in. 26-5/8 in. 53-7/8 in. - - - 2 - -
13-3/4 in.58-3/8 in.27-1/4 in.55-3/4 in.-----1
15 in.63 in.29-5/8 in.59 in.1----1
16-1/2 in. 68-3/4 in. 32-5/8 in. 64-1/4 in. - 1 - - - 1
18 in. 74-5/ 8 in. 35-5/8 in. 69-1/2 in. - - 1 - - 1
19-5/8 in. 80-3/8 in. 38-5/8 in. 74-5/8 in. - - - 1 - 1
20-5/8 in. 84-1/8 in. 41 in. 78-3/4 in. 1 - - 1 - 1
22-3/4 in.91-7/8 in.44-5/8 in.85 in.----11
24 in. 96-1/ 2 in. 47 in. 89- 1/8 in. 1 - - - 1 1
25-7/8 in. 103 -1/2 in. 50 -5/8 in. 95-1/2 in.
SL306 SL312
-----
SL318 SL324 SL336 SL348
* Proper assembly of air cooled chimney parts result in an overlap at chimney
joints of 1¼”. Effective length is built into this chart.
Figure 7 - Chimney Offset/
Return
Example: Your “A”
dimension from Figure 7 is 14-1/2 in. Using Table 1 the dimension closest to, but not less than 14-1/2 in. is 14-5/8 in. using a 30-deg offset/return. It is then determined from the table that you would need 33 in. (Dimension “B”) between the offset and return. The chimney components that best fit your application are two SL312s.
08/04 17339 Rev L 13
2. Chimney Height Requirements (above
roof line)
a. Major building codes specify a minimum chimney
height above the roof top. These specifications are summarized in what is known as the Ten Foot Rule. This rule states:
“If the horizontal distance from the side of the chimney to the peak of the roof is 10 ft or less, the top of the chimney must be at least 2 ft above the peak of the roof, but never less than 3 ft in overall height above the highest point where it passes through the roof.
“If the horizontal distance from the side of the chimney to the peak of the roof is more than 10 ft, a chimney height reference point is established on the surface of the roof a distance of 10 ft from the side of the chimney in a horizontal plane. The top of the chimney must be at least 2 ft above this reference point, but never less than 3 ft in height above the highest point where it passes through the roof.” See Figure 8.
b. These chimney heights are necessary in the
interest of safety but do not ensure smoke-free operation. Trees, buildings, adjoining roof lines, adverse wind conditions, etc. may create a need for a taller chimney should smoking occur.
EC SERIES INSTALLATION INSTRUCTIONS
3. Number of Sections Required
To determine the chimney components needed to complete your particular installation, follow the steps below:
a. Determine the total vertical height of the fireplace
installation. This dimension is measured from the base of the fireplace assembly to the point where the smoke exits the termination cap.
b. Subtract the effective height of the fireplace
assembly from the overall height of the fireplace installation (measured from the base of the fireplace to the bottom of the termination cap).
c. Refer to Table 2 to determine what components
must be selected to complete the fireplace installation.
d. Determine the number of firestop spacers,
stabilizers, roof flashing, etc. required to complete the fireplace installation.
Figure 8 - Chimney Height
Table 2
HEIGHT OF CHIMNEY COMPONENTS
Chimney Stabilizer
SL3 4-3/4 in.
Firestop Spacers
FS33 8 0 in.
FS33 9 0 in.
FS34 0 0 in.
Offsets/Returns
SL315 13-3/8 in.
SL330 14-1/2 in.
Roof Flashing
RF3 70 0 in .
RF3 71 0 in .
Chimney Sections*
SL306 4-3/4 in.
SL312 10-3/4 in.
SL318 16-3/4 in.
SL324 22-3/4 in.
SL336 34-3/4 in.
SL348 46-3/4 in.
* Dimensions reflect effective height
14 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
F. INSTALLATION OF FIREPLACE
WARNING!
Before starting, do the following:
1. Wear gloves and safety glasses for protection.
2. Keep hand tools in good condition. Sharpen cutting edges and make sure tool handles are secure.
3. Always maintain the minimum air space required to the enclosure to prevent fire.
1. Position the Fireplace
This fireplace may be placed on either a combustible or noncombustible continuous flat surface. Follow the instructions for framing on pages 10-12. Slide the fireplace into position. Be sure to provide the
minimum air clearance at the sides and back of the fireplace assembly.
2. Place the Protective Metal Hearth Strips
Included with your fireplace you will find two metal hearth strips measuring approximately 26 in. x 4 in. These strips are used to provide added protection where the fireplace and the hearth extension meet.
Slide each metal strip 2 in. under the front edge of the fireplace. The individual pieces must overlap each other by 1 in. minimum in the middle of the fireplace to provide continuous coverage of the floor. See Figure 9. These metal strips should extend from the front and sides of the fireplace opening by 2 in.
Figure 9 - Positioning the Metal Strips
3. Level the Fireplace
Level the fireplace side-to-side and front-to-back. Shim with noncombustible material, such as sheet metal, as necessary. Secure the fireplace (using the nailing flanges located on either side of the fireplace) to the vertical framing.
Important: To ensure proper fit of the glass doors, check the fireplace opening for square. Measure diagonal distances of the opening to make sure they are equal. If they are not equal, continue to shim the fireplace until those diagonals are equal.
08/04 17339 Rev L 15
4. Assemble Chimney Sections
Attach either a straight chimney section or an offset to the top of the fireplace (depending on your installation requirement). Chimney sections are locked together by pushing downward until the top section meets the stop bead on the lower section.
The inner flue is placed to the inside of the flue section below it. The outer casing is placed outside the outer casing of the chimney section below it. See Figure 10.
WARNING!
Carefully follow the instructions for assembly of the pipe and other parts needed to install this fireplace system. Failure to do so may result in a fire, especially if combustibles are too close to the fireplace or chimney and air spaces are blocked, preventing the free movement of cooling air.
EC SERIES INSTALLATION INSTRUCTIONS
Figure 10
Assembling Chimney
Sections
5. Install Firestop Spacers
Mark and cut out an opening in the ceiling for the firestop spacer being utilized (14-1/2 in. x 14-1/2 in. for an FS338, 14-1/2 in. x 18-3/8 in. for an FS339 and 14-1/2 in. x 23 in. for an FS340). Frame the opening with the same dimension lumber used in the ceiling joists. Install the firestop spacer. These firestop spacers are designed to provide the minimum 2 in. air space required around the chimney. In all situations, the firestop spacers are to be nailed to the ceiling joists from the bottom or fireplace side, EXCEPT when the space above is an insulated ceiling or attic space. In this situation, the firestop spacer must be nailed from the top side to prevent loose insulation from falling into the required 2 in. air space around the chimney. See Figure 11.
CAUTION:
Firestop spacers must be used whenever the chimney penetrates a ceiling/floor area.
Figure 11
Installing the Firestop Spacer
16 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
6. Attic Insulation Shield
An insulation shield should be installed when there is a possibility of insulation coming into contact with the factory built chimney system.
a. Bend the tabs at the top of the attic insulation
shield inward. This will help keep the chimney section centered in the shield.
b. Position the shield over the vertical chimney
section where it penetrates a firestop spacer.
c. Slide the shield down until it rests on the firestop
spacer. The firestop spacer will support the insulation shield. See Figure 12.
8. Secure Chimney System
When offsets and returns are joined to straight pipe sections, they must be locked into position with the screws provided (outer only), using the predrilled holes. To prevent gravity from pulling the chimney sections apart, the returns and the chimney stabilizers have straps for securing these parts to joists or rafters. See Figure 13.
Note: You must provide support for the pipe during
construction and check to be sure inadvertent load­ing has not dislodged the chimney section from the fireplace or at any chimney joint.
Figure 12 - Installing an Attic Insulation Shield
WARNING! RISK OF FIRE.
Do not fill the space between the chimney section and the insulation shield with insulation.
7. Double-check the Chimney Assembly
Continue assembling the chimney sections up through the firestop spacers as needed. While doing so, be aware of the height and unsupported chimney length limitations that are given on page 12 under “Chimney Requirements”.
Check each section by pulling up slightly from the top to ensure proper engagement before installing the succeeding sections. If they have been connected correctly, they will not disengage when tested.
CAUTION:
Inner flue and outer liner sections cannot be dis­assembled once locked together. Plan ahead to ensure the proper installation height is achieved with the selected chimney compo­nents.
Figure 13 - Offset/Return with Stabilizer
WARNING!
When chimney sections exceeding 6 ft in length are installed between an offset and return, structural support must be provided to reduce off-center loading and prevent chimney sections from separating at the chimney joints.
WARNING!
Maintain a minimum of 2 in. air clearance to all parts of the chimney system at all times! Fail-
ure to maintain this 2 in. air clearance will cause a structure fire.
08/04 17339 Rev L 17
9. Mark the Exit Point of the Roof
Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney. Drive a nail up through the roof to mark the center. See Figure 14.
10. Cut out the Hole in the Roof
Measure to either side of the nail and mark the 14-1/2 in. x 14-1/2 in. opening required. This is measured on the horizontal; actual length may be larger depending on the pitch of the roof. Cut out and frame the opening. See Chapter 25 of the Uniform
Building Code for roof framing details.
Be sure to maintain a 2 in. minimum air space between the chimney section and the roof.
11. Assemble the Chimney Sections
Through the Roof
Continue to add chimney sections through the roof opening, maintaining at least a 2 in. air space.
EC SERIES INSTALLATION INSTRUCTIONS
12. Install the Roof Flashing
If a roof flashing is to be used, install the roof flashing appropriate to the roof pitch and install a round termination cap following the instructions shipped with the cap.
For chase installations you can use a round termination cap (TR344), a round telescoping termination cap (TR342) or a square termination cap (ST375/TS345/ TS345P). A chase installation must use a chase top. Chase tops are available from your Heatilator distributor. See page 22 for building a chase.
13. Install the Outside Air Kit
The outside air kit is an optional feature with this fireplace and its use is highly recommended to minimize the effects of negative pressure within the structure. It is recommended to utilize the shortest duct run to optimize the performance of the outside air kit. The outside air kit inlet thimble should be positioned at least 4 ft above the ground level, in a manner that will not allow snow, leaves, etc. to block the inlet.
The outside air kit is installed on the left hand side of the fireplace. Remove the cover plate from the side of the fireplace assembly where the air kit is to be installed. See Figure 15 for handle location/operation.
Figure 14 - Ceiling/Attic Construction
Figure 15 - Air Kit Handle Location
CAUTION:
The air kit handle may get hot while burning the fireplace. Use care when operating the handle.
14. Install the Chimney Air Kit (Required in
Canada)
When installing the chimney air kit, follow the instructions provided with this accessory.
18 17339 Rev L 08/04
EC SERIES INSTALLATION INSTRUCTIONS
15. Complete the Enclosure
Complete the fireplace enclosure, allowing space for outside air ducts and gas piping if desired. Electrical wiring should not come in contact with the fireplace. A
minimum clearance of 1/2 in. must be maintained between the fireplace sides and the enclosure as well as the fireplace back and the enclosure. See
pages 10-12 for framing details.
Note: Use only a noncombustible material to finish
the face of the fireplace below the level of the front standoffs. A noncombustible material such as USG MICORE CV230 Mineral Fiber Board, or USG DUROCK Cement Board is recommended for this purpose.
CAUTION:
When using a gas log set, the fireplace damper must be set in the fully open position. This en­sures proper venting of combustion products.
16. Gas Log/Lighter Provisions
Knockouts are provided on both sides of the fireplace to allow for connection of a certified gas log lighter or a decorative gas appliance with a maximum input of 100,000 BTU/hour, incorporating an automatic gas shut-off device and complying with the Standard for
Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60. The decorative gas
appliance should be installed in accordance with the National Fuel Gas Code, ANSI Z223.1-1980. The side refractories are designed to allow 1/2 in. iron pipe to pass through. Use a noncombustible sealant to seal any opening between the gas pipe and refractory on the inside. Repack the insulation removed to seal around the gas pipe where it exits the side of the fireplace. A minimum 1-1/2 in. air clearance must be provided around the 1/2 in. iron pipe for a minimum of 4 in. beyond the fireplace. See Figure 16.
WARNING!
This fireplace was not tested by the fireplace manufacturer for use with an unvented gas log heater. To reduce risk of injury, do not install an unvented gas log heater in this fireplace unless it has been specifically tested and listed by Underwriter’s Laboratories Inc. for use in this specific model fireplace. Unless the unvented gas log heater is tested and listed for use in this factory built fireplace, a fire hazard may be created that can result in a structure fire.
Figure 16 - Air Clearance Around Gas Line
CLEARANCES!
A minimum 1/2 in. air clearance must be maintained at the back and sides of the fireplace assembly.
Chimney sections at any level require a 2 in. minimum air space clearance between the framing and chimney section.
08/04 17339 Rev L 19
EC SERIES INSTALLATION INSTRUCTIONS
17. Hearth Extension
A hearth extension must be installed with all fireplaces to protect the combustible floor in front of the fireplace from both radiant heat and sparks.
The construction of, and materials used for a hearth extension are shown in Figures 17 and 18. A hearth extension of this construction may be covered with any noncombustible decorative material and may have a maximum thickness as per the illustration. Seal gaps between the hearth extension and the front of the fireplace with a bead of noncombustible sealant.
Figure 17 - Factory Built Hearth Extension
Field constructed hearth extensions should be constructed in accordance with the instructions in Figure 18. The field constructed hearth extension must be constructed from 1/2 in. MICORE CV230, or a material with an equivalent insulation value.
Cat . # A B
E/EC36 52 in. [1321mm] 16 in. [406mm]
E/EC39 52 in. [1321mm] 16 in. [406mm]
E/EC42 66 in. [1676mm] 20 in. [508mm]
Figure 18 - Field Constructed Hearth Extension
WARNING!
Hearth extensions are to be installed only as illustrated to prevent high temperatures from occurring on con­cealed combustible materials. Hearth sealing strips prevent burning or hot particles from inadvertently falling directly on combustible surfaces in the event the building should settle and disturb the original construction.
20 17339 Rev L 08/04
Loading...
+ 44 hidden pages