Heatilator CD4236-MOD, CD4842-MOD Installation Manual

Installation Manual
Installation and Appliance Setup
INSTALLER: Leave this manual with party responsible for use and operation. OWNER: Retain this manual for future reference.
NOTICE: DO NOT discard this manual!
Models:
CD4236-MOD CD4842-MOD
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
DO NOT store or use gasoline or other fl am-
mable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO NOT use any phone in your building.
- Leave the building immediately.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas sup­plier’s instructions.
- If you cannot reach your gas supplier, call the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency, or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280 in the United States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada.
This appliance is only for use with the type(s) of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk individuals.
1
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
Installation Standard Work Checklist . . . . . . . . . . . . . . . . . . . . 3
1 Product Specifi c and Important Safety Information
A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B. Glass Specifi cations (Tempered) . . . . . . . . . . . . . . . . . . . . 4
C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 4
E. Non-Combustible Materials Specifi cation. . . . . . . . . . . . . . 5
F. Combustible Materials Specifi cation . . . . . . . . . . . . . . . . . 5
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
H. Requirements for the Commonwealth of Massachusetts . . 5
2 Getting Started
A. Design and Installation Considerations . . . . . . . . . . . . . . . 7
B. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . . 7
C. Inspect Appliance and Components . . . . . . . . . . . . . . . . . . 7
3 Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams . . . . . . . 8
B. Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . 11
C. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 12
4 Termination Location and Vent Information
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 13
B. Chimney Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
C. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
D. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
E. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
F. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 23
B. Wall Penetration Framing/Firestops . . . . . . . . . . . . . . . . . 23
C. Ceiling Firestop/Floor Penetration Framing . . . . . . . . . . . 24
D. Install Attic Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . 24
6 Appliance Preparation
A. Vent Collar Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . 25
B. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 26
C. Non-Combustible Material Installation . . . . . . . . . . . . . . . 26
7 Venting and Chimneys
A. Assemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . . 27
B. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 28
C. Secure the Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . . 29
D. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 29
E. Vertical Termination Requirements . . . . . . . . . . . . . . . . . . 30
F. Horizontal Termination Requirements . . . . . . . . . . . . . . . 31
8 Electrical Information
A. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
B. Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
9 Gas Information
A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
B. Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . 35
E. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10 Finishing
A. Facing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
B. Finish and Sealing Joints . . . . . . . . . . . . . . . . . . . . . . . . . 37
C. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 38
D. Door Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
11 Appliance Setup
A. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
B. Remove the Shipping Materials . . . . . . . . . . . . . . . . . . . . 40
C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
D. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
E. Optional Glass Panel Installation . . . . . . . . . . . . . . . . . . . 40
F. Media Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
G. Install Trim and/or Surround . . . . . . . . . . . . . . . . . . . . . . . 42
12 Reference Materials
A. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 43
B. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 2
= Contains updated information.
Installation Standard Work Checklist
ATTENTION INSTALLER:
Follow this Standard Work Checklist
7KLVVWDQGDUGZRUNFKHFNOLVW LV WREHXVHGE\WKH LQVWDOOHU LQFRQMXQFWLRQZLWKQRW LQVWHDG RI WKHLQVWUXFWLRQVFRQWDLQHGLQ WKLV LQVWDOODWLRQPDQXDO
Customer: Lot/Address:
Model (circle one): CD4236-MOD, CD4842-MOD
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions could
OHDGWRD¿UHRUH[SORVLRQ
Appliance Install Sections 3 and 6 YES IF NO, WHY?
9HUL¿HGWKDWWKHFKDVHLVLQVXODWHGDQGVHDOHG3J BBBBBBBBBBBBBBBBBBBBBBBBBBB 5HTXLUHGQRQFRPEXVWLEOHERDUGLVLQVWDOOHG BBBBBBBBBBBBBBBBBBBBBBBBBBB 9HUL¿HGFOHDUDQFHVWRFRPEXVWLEOHV3J BBBBBBBBBBBBBBBBBBBBBBBBBBB )LUHSODFHLVOHYHOHGDQGVHFXUHG3J BBBBBBBBBBBBBBBBBBBBBBBBBBB
Venting/Chimney Section 4,5 and 7
9HQWLQJFRQ¿JXUDWLRQFRPSOLHVWRYHQWGLDJUDPV3J BBBBBBBBBBBBBBBBBBBBBBBBBBB 9HQWLQJLQVWDOOHGORFNHGDQGVHFXUHGLQSODFHZLWKSURSHUFOHDUDQFH BBBBBBBBBBBBBBBBBBBBBBBBBBB )LUHVWRSVLQVWDOOHG6HFWLRQ BBBBBBBBBBBBBBBBBBBBBBBBBBB $WWLFLQVXODWLRQVKLHOGLQVWDOOHG3J BBBBBBBBBBBBBBBBBBBBBBBBBBB ([WHULRUZDOO5RRIÀDVKLQJLQVWDOOHGDQGVHDOHG6HFWLRQ BBBBBBBBBBBBBBBBBBBBBBBBBBB 7HUPLQDWLRQVLQVWDOOHGDQGVHDOHG6HFWLRQ BBBBBBBBBBBBBBBBBBBBBBBBBBB
Date Installed: Location of Fireplace: Installer: Dealer/Distributor Phone #
Serial #:
Electrical Section 8 (Pg. 33-34)
8QVZLWFKHGSRZHU9$&SURYLGHGWRWKHDSSOLDQFH BBBBBBBBBBBBBBBBBBBBBBBBBBB 6ZLWFKZLUHVSURSHUO\LQVWDOOHG BBBBBBBBBBBBBBBBBBBBBBBBBBB
Gas Section 9 (Pg. 35-36)
3URSHUDSSOLDQFHIRUIXHOW\SH BBBBBBBBBBBBBBBBBBBBBBBBBBB :DVDFRQYHUVLRQSHUIRUPHG" BBBBBBBBBBBBBBBBBBBBBBBBBBB /HDNFKHFNSHUIRUPHGDQGLQOHWSUHVVXUHYHUL¿HG BBBBBBBBBBBBBBBBBBBBBBBBBBB 9HUL¿HGSURSHUDLUVKXWWHUVHWWLQJIRULQVWDOODWLRQW\SH BBBBBBBBBBBBBBBBBBBBBBBBBBB
Finishing Section 10 (Pg. 37-39)
&RPEXVWLEOHPDWHULDOVQRW LQVWDOOHGLQQRQFRPEXVWLEOHDUHDV BBBBBBBBBBBBBBBBBBBBBBBBBBB 9HUL¿HGDOOFOHDUDQFHVPHHWLQVWDOODWLRQPDQXDOUHTXLUHPHQWV BBBBBBBBBBBBBBBBBBBBBBBBBBB 0DQWHOVDQGZDOOSURMHFWLRQVFRPSO\ZLWKLQVWDOODWLRQPDQXDOUHTXLUHPHQWV BBBBBBBBBBBBBBBBBBBBBBBBBBB
Appliance Setup Section 11 (Pg. 40-42)
$OOSDFNDJLQJDQGSURWHFWLYHPDWHULDOVUHPRYHGLQVLGHRXWVLGHRIDSSOLDQFH BBBBBBBBBBBBBBBBBBBBBBBBBBB 5HIUDFWRULHVORJVPHGLDDQGHPEHUVLQVWDOOHGFRUUHFWO\ BBBBBBBBBBBBBBBBBBBBBBBBBBB *ODVVDVVHPEO\LQVWDOOHGDQGVHFXUHG BBBBBBBBBBBBBBBBBBBBBBBBBBB $FFHVVRULHVLQVWDOOHGSURSHUO\ BBBBBBBBBBBBBBBBBBBBBBBBBBB 0HVKGRRUVRUGHFRUDWLYHIURQWSURSHUO\LQVWDOOHG BBBBBBBBBBBBBBBBBBBBBBBBBBB 0DQXDOEDJDQGDOORILWVFRQWHQWVDUHUHPRYHGIURPLQVLGHXQGHU WKHDSSOLDQFHDQGJLYHQWRSDUW\UHVSRQVLEOHIRUXVHDQGRSHUDWLRQ  BBBBBBBBBBBBBBBBBBBBBBBBBBB 6WDUWHGDSSOLDQFHDQGYHUL¿HGQR JDVOHDNVH[LVW BBBBBBBBBBBBBBBBBBBBBBBBBBB
Hearth & Home Technologies recommends the following:
3KRWRJUDSKLQJWKHLQVWDOODWLRQDQGFRS\LQJWKLVFKHFNOLVWIRU\RXU¿OH 7KDWWKLVFKHFNOLVWUHPDLQYLVLEOHDWDOOWLPHVRQWKHDSSOLDQFHXQWLOWKHLQVWDOODWLRQLVFRPSOHWH
Comments:)XUWKHUGHVFULSWLRQRIWKHLVVXHVZKRLVUHVSRQVLEOH,QVWDOOHU%XLOGHU2WKHU7UDGHVHWFDQGFRUUHFWLYH DFWLRQQHHGHGBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB &RPPHQWV&RPPXQLFDWHGWRSDUW\UHVSRQVLEOHBBBBBBBBBBBBBBBBBBBBE\BBBBBBBBBBBBBBBBBBBBBBRQBBBBBBBBBBB    %XLOGHU*HQ&RQWUDFWRU,QVWDOOHU 'DWH
Î &RQWDLQVXSGDWHGLQIRUPDWLRQ
3DUW
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
3
1
1
Product Specifi c and Important Safety Information
C. BTU Specifi cationsA. Appliance Certifi cation
MODELS: CD4236-MOD, CD4842-MOD LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Direct Vented Gas Fireplace
STANDARD:
ANSI Z21.50-2014 • CSA 2.22-2014
This product is listed to ANSI standards for “Vented Gas Fireplace Heaters” and applicable sections of “Gas Burn­ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOTICE: This installation must conform with local codes. In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemen­tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional (www.nfi certifi ed.org).
B. Glass Specifi cations (Tempered)
Hearth & Home Technologies appliances manufactured with tempered glass may be installed in hazardous lo­cations such as bathtub enclosures as defi ned by the Consumer Product Safety Commission (CPSC). The tempered glass has been tested and certifi ed to the re- quirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certifi cation Council SGCC# 1595 and
1597. Architectural Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Sec- tion 1201.5 “Certifi cation and labeling requirements” which refers to 15 U.S. Code (USC) 2063 stating “…Such certifi cate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered.”
Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order.
Models
(U.S. or Canada)
CD4236-MOD
(NG)
CD4236-MOD
(LP)
CD4842-MOD
(NG)
CD4842-MOD
(LP)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
Maximum
Input
BTU/h
28,000 19,000 40
25,200 17,100 41
20,000 14,000 55
18,000 12,000 56
32,000 22,000 35
28,800 19,800 36
22,000 15,000 54
20,000 14,000 55
Minimum
Input
BTU/h
Orifi ce
Size
(DMS)
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
Check with your local gas utility to determine proper orifi ce size.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 4
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered
non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed pa­per, plant fi bers, plastics, or other material that can ignite and burn, whether fl ame proofed or not, or plastered or unplastered shall be considered combustible materials.
In the event that the side wall horizontally vented gas fu­eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 VAC circuit for this product must be pro-
tected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
Note: The following requirements reference various Massachusetts and national codes not contained in this document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addi­tion, the installing plumber or gas fi tter shall observe that a battery operated or hard wired carbon monoxide detec­tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
Signage
A metal or plastic identifi cation plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu­eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB­STRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob­serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2) (a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu­eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
5
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro­vide the parts for venting the fl ue gases, but identifi es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment in­stallation instructions; and
• The “special venting systems” shall be Product Ap­proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 6
2
2
Getting Started
A. Design and Installation Considerations
Heatilator direct vent gas appliances are designed to op­erate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fi re offi cials or authorities having jurisdiction over restrictions, installation inspection and permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping requirements.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan, wall switch, or remote control—are desired.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional (www.nfi certifi ed.org).
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualifi ed service technician, service agency or your dealer.
B. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Tape measure Framing material Pliers Hammer Phillips screwdriver Manometer Gloves Framing square Voltmeter Electric drill and bits (1/4 in.) Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non-corrosive leak check solution 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws Caulking material (300 ºF minimum continuous exposure
rating) One 1/4 in. female connection (for optional fan).
C. Inspect Appliance and Components
• Carefully remove the appliance and components from the packaging.
• The vent system components and decorative doors and fronts may be shipped in separate packages.
• Media must be installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, in- complete or substitute components. Keep appliance dry.
Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the media or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance if any part has been under
water. Call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
7
3
3
A
B
C
D
E
FRONT VIEW
TOP VIEW
LEFT SIDE RIGHT SIDE
F
G
H
I
J
K
L
O
P
GAS LINE
ACCESS
Q
R
N
Framing and Clearances
A. Appliance/Decorative Front Dimension Diagrams
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5.
Location Inches Millimeters
A 41 1041
B 36-1/8 918
C 33-1/2 851
D 34-5/8 879
E 2-1/4 57
Figure 3.1 Appliance Dimensions - CD4236-MOD
F 9-11/16 246
G 26-7/8 683
H 6 dia 152
I 39-7/8 1013
Location Inches Millimeters
J 21 533
K 11-11/16 297
L 28-1/2 724
M 14-1/4 362
N 8-1/2 216
O 2-7/8 73
P 8-1/2 216
Q1 25
R 40-7/8 1038
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 8
GAS LINE
ACCESS
L
M
J
N
TOP VIEW
R
K
H
D
C
I
G
LEFT SIDE
O
P
Location Inches Millimeters
Q
FRONT VIEW
A 48 1219
B 43-1/8 1096
C 35-1/2 902
D 36-5/8 930
E 2-3/8 60
F 9-15/16 252
G 28-7/8 734
H 6 152
I 41-7/8 1064
B
A
Location Inches Millimeters
J 21 533
K 11-11/16 297
L 35-1/2 901
M 17-3/4 451
N 8-1/2 216
O 2-7/8 73
P 8-1/2 216
Q1 25
R 42-7/8 1089
E
F
RIGHT VIEW
Figure 3.2 Appliance Dimensions - CD4842-MOD
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
9
Decorative Front Dimension
SIMON DECORATIVE FRONTS
32 1/32 in.
SIM-36
Figure 3.3 SIM-36 Simon Decorative Front Dimensions
33 15/16 in.
35 25/32 in.
SIM-42
Figure 3.4 SIM-42 Simon Decorative Front Dimensions
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 10
42 13/16 in.
B. Clearances to Combustibles
When selecting a location for the appliance it is important
to consider the required clearances to walls (see Figure
3.5).
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access. Due to high temperatures, the appliance should be lo­cated out of traffi c and away from furniture and draperies.
NOTE: THE REAR STANDOFF MAY NEED
TO BE REMOVED WHEN VENTING AT 45º
A
1/2 IN.
F
A
B
C
TOP VENT
ONE 90º ELBOW
NOTICE: Illustrations refl ect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.
B
ALCOVE
INSTALLATION
D
CD4236-MOD
CD4842-MOD
Figure 3.5 Appliance Locations
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
in. 51 42 72
mm 1295 1067 1829 559 451
in. 55-7/8 49 79
mm 1419 1245 2007 559 502
B
E
ABC D E F
See Section 10.C.
Mantel Projections
See Section 10.C.
Mantel Projections
22 17-3/4
22 19-3/4
11
C. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling restops and wall shield restops and construction of the chase may vary with the
type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.
Chases should be constructed in the manner of all out­side walls of the home to prevent cold air drafting prob­lems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase should be insulated. Vapor and air infi ltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infi ltration may be an issue, the inside surfaces may be sheetrocked and taped (or an equivalent method may be used) to achieve maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re- stops should be caulked with caulk with a minimum of 300 ºF continuous exposure rating to seal gaps. Gas line holes and other openings should be caulked with caulk with a minimum of 300 ºF continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement surface, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.
WARNING! Risk of Fire! Maintain specifi ed air space clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent accidental contact.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and a fi re.
A
B
F
C
D
* MINIMUM FRAMING DIMENSIONS
AB C DE F G H I J
Models
CD4236-MOD
CD4842-MOD
Rough
Opening
(Width)
in. 10 40-1/8 22 42 25 0 0 1/2 1/2 36
mm 254 1019 559 1067 635 0 0 13 13 914
in. 10 42-1/8 22 49 25 0 0 1/2 1/2 36
mm 254 1070 559 1245 635 0 0 13 13 914
* Adjust framing dimensions for interior sheathing (such as sheetrock)
Rough
Opening
(Height)
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
J
G
Combustible
Flooring
I
Behind
Appliance
Sides of
Appliance
E
H
Front of
Appliance
Figure 3.6 Clearances to Combustibles
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 12
4
4
Termination Location and Vent Information
A. Vent Termination Minimum Clearances
WARNING
Fire Risk.
Maintain vent clearance to combustibles as specifi ed.
DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away from vent pipe could cause overheating and fi re.
6 in. (minimum) up to 20 in.
AB
152 mm/508 mm
20 in. and over 0 in. minimum
Gas, Wood or Fuel Oil
Termination Cap
B
A *
18 in. minimum
457 mm
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
* 3 foot minimum in snow regions
Figure 4.1 Minimum Height From Roof to Lowest Discharge Opening
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
VERTICAL
WALL
IS X/ 12
Gas
Termination
Cap **
If using decorative cap cover(s), this distance may need to be
*
increased. Refer to the installation instructions supplied with the decorative cap cover.
In a staggered installation with both gas and wood or fuel oil
**
terminations, the wood or fuel oil termination cap must be higher than the gas termination cap.
Figure 4.2 Staggered Termination Caps
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
13
B. Chimney Diagram
C
V
B
J
V
V
= VENT TERMINAL
X
= AIR SUPPLY INLET
B
D
V
V
V
A
= AREA WHERE TERMINAL IS NOT PERMITTED
A = 12 inches.................clearances above grade, veranda,
porch, deck or balcony
12 inches.................clearance to window or door that may
B =
be opened, or to permanently closed window
C = 18 inches.................clearance below unventilated soffi t
18 inches.................clearance below ventilated soffi t
30
inches .................clearance below vinyl soffits and
electrical service
D = 9 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas me-
ter/regulator assembly within 3 feet horizontally from the center-line of the regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet
H = 9 inches (U.S.A)
12 inches (Canada). clearance to non-mechanical (unpow-
ered) air supply inlet, combustion air
inlet or direct-vent termination i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (powered)
air supply inlet All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below termination.
J = 7 ft. ......................... On public property: clearance above
paved sidewalk or a paved driveway. A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings.
K = 6 inches................. clearance from sides of electrical
service
L = 12 inches................ clearance above electrical service
Location of the vent termination must not interfere with access to the electrical service.
M = 18 inches ................... clearance under veranda, porch, deck,
balcony or overhang
42 inches ................vinyl or composite overhang
Permitted when veranda, porch, deck or balcony is fully open
on a minimum of 2 sides beneath the fl oor.
Figure 4.3 Minimum Clearances for Termination
F
B
G
M
O
N
P
R
Q
H or i
V
X
H
V
V
H
E
V
V
A
V
K
V
L
Electrical
Service
C
V
K
V
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl soffi t and overhang
42 inches ......... vinyl soffi t and overhang
P = 8 ft.
Q
MIN
1 cap 3 feet 2 x Q
2 caps 6 feet 1 x Q
3 caps 9 feet 2/3 x Q
4 caps 12 feet 1/2 x Q
Q
= # termination caps x 3 R
MIN
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffi c areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer.
• Local codes or regulations may require different clearances.
• Vent system termination is NOT permitted in screened porches.
• Vent system termination is permitted in porch areas with two or more sides open.
• Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
• Vinyl protection kits are suggested for use with vinyl siding.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 14
C. Approved Pipe
This appliance is approved for use with Hearth & Home Technologies DVP or SLP venting systems. Refer to Sec­tion 12.A for vent component information and dimensions.
DO NOT mix pipe, fi ttings or joining methods from differ- ent manufacturers.
The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli­ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15
15
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent as­pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect. See Figure 4.4.
Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows. See Figure 4.4.
Figure 4.5 shows the vertical and horizontal offsets for DVP or SLP elbows.
Y
X
VERTICAL
EFFECTIVE
LENGTH
RUN
HORIZONTAL
SLP
Pipe
SLP4 4 102 2-3/4 70
SLP6 6 152 4-1/4 108
SLP12 12 305 8-1/2 216
SLP24 24 610 17 432
SLP36 36 914 25-1/2 648
SLP48 48 1219 34 864
SLP6A 3 to 6 76 to 152
SLP12A 3 to 12 76 to 305
DVP Pipe
DVP4 4 102 2-3/4 70
DVP6 6 152 4-1/4 108
DVP12 12 305 8-1/2 216
DVP24 24 610 17 432
DVP36 36 914 25-1/2 648
DVP48 48 1219 34 864
DVP6A 3 to 6 76 to 152
DVP12A 3 to 12 76 to 305
Figure 4.4
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
2-1/8-4-1/4 54-108
2-1/8-8-1/2 54-216
Effective Length Rise/Run
Inches Millimeters Inches Millimeters
2-1/8-4-1/4 54-108
2-1/8-8-1/2 54-216
RISE
Vent Type
DVP 4-1/2 114 17 432
SLP 5 127 11-3/4 298
Inches Millimeters Inches Millimeters
XY
X
X
Vent Type
DVP 16-1/4 413
SLP 11-1/4 286
Figure 4.5 Vertical and Horizontal Offset for DVP and SLP Elbows
Inches Millimeters
X
E. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards:
• Pipe measurements are shown using the effective length of pipe. See Section 12.A (Figure 12.1 for DVP, Figure
12.6 for SLP) for information on effective length of pipe components.
• Horizontal terminations are measured to the outside mounting surface (fl ange of termination cap) (see Figure
4.3).
• Vertical terminations are measured to bottom of termination cap.
• Horizontal pipe installed level with no rise.
Heatilator • CD4236-MOD, CD4842-MOD Installation Manual • 2241-901 Rev. C • 6/15 16