Heat & Glo RED40ST User Manual

Models: RED40 RED40ST
Owner’s Manual
Installation and Operation
NOTICE
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
WARNING: If the information in these instructions is not followed exactly, a fi re or explosion may result causing property damage, personal injury, or death.
DO NOT store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance.
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency, or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile Homes, CAN/CSA Z240MH, in Canada.
This appliance is only for use with the type(s) of gas indicated on the rating plate.
• Read, understand and follow these instructions for safe installation and operation.
DO NOT
DISCARD
• Leave this manual with party responsible for use and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory trained professionals, or technicians supervised by an NFI certifi ed professional.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
1
Not Not for for use use with with solid solid fuel.fuel. ((Ne Ne doit doit pas pas entre entre utilise utilise avec avec un un combustible combustible solide).solide).
This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes, codes, if if any; any; if if not, not, follow follow ANSI ANSI Z223.1Z223.1 in in the the USA USA or or CAN/CGA CAN/CG A B149 B149 installation installation codes. codes. (Installer (Installer l’appareil l’appareil selon selon les les codes codes ou ou reglementsreglements
locaux locaux ou, ou, en en l’absence l’absence de de tels tels reglements, reglements, selon selon les les codes codes d’installation d’installation CAN/CGA-B149.)CAN/CGA-B149.)
Type Type of of Gas Gas (Sorte (Sorte De De Gaz)Gaz)::
NNAATURALTURAL GASGAS
MADE MADE IN IN USAUSA
Minimum Minimum Permissible Permissible Gas Gas Supply Supply for for Purposes Purposes of of Input Input Adjustment.Adjustment. Approved Approved Minimum Minimum (De (De Gaz) Gaz) AcceptableAcceptable 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau) Maximum Maximum Pressure Pressure (Pression)(Pression) 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau) Maximum Maximum Manifold Manifold Pressure Pressure (Pression)(Pression) 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau) Minimum Minimum Manifold Manifold Pressure Pressure (Pression)(Pression) 0.00.0 in in w.c.w.c. (Po. (Po. Col. Col. d’eau)d’eau)
Model:Model:
(Modele):(Modele):
SerialSerial
(Serie):(Serie):
ANSI ANSI Z21XX-XXXX Z21XX-XXXX · · CSA CSA 2.XX-MXX 2.XX-MXX · · UL307BUL307B
XXXXXXXXXXXXXXXX
IN IN CANADACANADA ALTITUDE:ALTITUDE: 0-0000 0-0000 FT.FT. 0000-0000FT.0000-0000FT. MAX. MAX. INPUT INPUT BTUH:BTUH: 00,00000,000 00,00000,000 MIN. MIN. INPUT INPUT BTUH:BTUH: 00,00000,000 00,00000,000 ORIFICE ORIFICE SIZE:SIZE: #XXXXX#XXXXX #XXXXX#XXXXX
XXXXXXXXXXXXXXXX
Total Total Electrical Electrical Requirements: Requirements: 000Vac, 000Vac, 00Hz., 00Hz., less less than than 00 00 AmperesAmperes
Heat & Glo, a brand of Hearth & Home Technologies, Inc. 7571 215th Street West, Lakeville, MN 55044
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heat & Glo gas fi replace, an elegant and clean alternative to wood burning fi replaces. The Heat & Glo gas fi replace you have selected is designed to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new fi replace, you’ll want to read and carefully follow all of the instructions contained in this owner’s manual. Pay special attention to all cautions and warnings.
Homeowner Reference Information
This owner’s manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.
The information contained in this owner’s manual, unless noted otherwise, applies to all models and gas control systems.
Your new Heat & Glo gas fi replace will give you years of durable use and trouble-free enjoyment. Welcome to the Heat & Glo family of fi replace products!
We recommend that you record the following pertinent information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________ Serial Number: __________________________________________ Location on fi replace: _____________________ Dealership purchased from: _______________________________ Dealer Phone: __________________________ Notes: _______________________________________________________________________________________ _____________________________________________________________________________________________
Listing Label Information/Location
Type of Gas
Gas and Electric Information
The model information regarding your specifi c fi replace can be found on the rating plate usually located in the control area of the fi replace.
Model Number
Serial Number
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/122
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
A. Congratulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
B. Limited Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1 Listing and Code Approvals
A. Appliance Certifi cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
B. Glass Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
C. BTU Specifi cations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . . 7
E. Non-Combustible Materials Specifi cation. . . . . . . . . . . . . . 7
F. Combustible Materials Specifi cation . . . . . . . . . . . . . . . . . 7
G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
H. Requirements for the Commonwealth of Massachusetts . . 8
User Guide
2 Operating Instructions
A. Gas Fireplace Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
B. Your Fireplace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
C. Clear Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
D. Decorative Doors and Fronts . . . . . . . . . . . . . . . . . . . . . . 10
E. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
F. Remote Controls, Wall Controls and Wall Switches . . . . . 10
G. Before Lighting Fireplace . . . . . . . . . . . . . . . . . . . . . . . . . 10
H. Lighting Instructions (IPI) . . . . . . . . . . . . . . . . . . . . . . . . . 11
I. After Fireplace is Lit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
J. Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . 12
3 Maintenance and Service
A. Maintenance Tasks-Homeowner . . . . . . . . . . . . . . . . . . . 13
B. Maintenance Tasks-Qualifi ed Service Technician . . . . . . 14
Installer Guide
4 Getting Started
A. Typical Appliance System. . . . . . . . . . . . . . . . . . . . . . . . . 15
B. Design and Installation Considerations . . . . . . . . . . . . . . 16
C. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . 16
D. Inspect Appliance and Components . . . . . . . . . . . . . . . . . 16
5 Framing and Clearances
A. Selecting Appliance Location . . . . . . . . . . . . . . . . . . . . . . 17
B. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 18
C. Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
D. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 20
6 Termination Locations
A. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 21
7 Vent Information and Diagrams
A. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
B. Vent Table Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
C. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
D. Measuring Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
E. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8 Vent Clearances and Framing
A. Pipe Clearances to Combustibles . . . . . . . . . . . . . . . . . . 30
B. Wall Penetration Framing . . . . . . . . . . . . . . . . . . . . . . . . . 30
C. Install the Ceiling Firestop . . . . . . . . . . . . . . . . . . . . . . . . 31
D. Install Attic Insulation Shield . . . . . . . . . . . . . . . . . . . . . . . 32
9 Appliance Preparation
A. Appliance Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
B. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 34
C. Active Convection Technology . . . . . . . . . . . . . . . . . . . . . 35
10 Installing Vent Pipe (DVP Pipe)
A. Assemble Vent Sections. . . . . . . . . . . . . . . . . . . . . . . . . . 36
B. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . . 37
C. Secure The Vent Sections . . . . . . . . . . . . . . . . . . . . . . . . 37
D. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . . . 38
E. Install Decorative Ceiling Components . . . . . . . . . . . . . . 38
F. Install Metal Roof Flashing . . . . . . . . . . . . . . . . . . . . . . . . 39
G. Assemble and Install Storm Collar . . . . . . . . . . . . . . . . . . 39
H. Install Vertical Termination Cap . . . . . . . . . . . . . . . . . . . . 40
I. Heat Shield Requirements for Horizontal Termination . . . 40
J. Install Horizontal Termination Cap . . . . . . . . . . . . . . . . . . 40
11 Gas Information
A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
B. Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
C. Gas Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
D. High Altitude Installations . . . . . . . . . . . . . . . . . . . . . . . . . 42
12 Electrical Information
A. Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
B. IntelliFire Ignition System Wiring . . . . . . . . . . . . . . . . . . . 43
C. Optional Accessories Requirements . . . . . . . . . . . . . . . . 43
D. Optional LED Lighting Circuit . . . . . . . . . . . . . . . . . . . . . . 45
E. Electrical Service and Repair . . . . . . . . . . . . . . . . . . . . . . 45
F. Junction Box Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 45
G. Active Convection Blower Replacement . . . . . . . . . . . . . 46
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
3
13 Finishing
A. Splatter Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
B. Framing and Finishing Instructions . . . . . . . . . . . . . . . . . 48
C. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 50
D. Facing Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
E. Mesh Fronts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
14 Appliance Setup
A. Remove Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . 55
B. Remove the Shipping Materials . . . . . . . . . . . . . . . . . . . . 55
C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
D. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
E. Rock Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
F. Porcelain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
G. Granite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
H. Sheet Metal Refractory . . . . . . . . . . . . . . . . . . . . . . . . . . 55
I. Fixed Glass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
J. Install the Mesh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
K. Air Shutter Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
15 Troubleshooting
A. IntelliFire Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . 57
16 Reference Materials
A. Appliance Dimension Diagram . . . . . . . . . . . . . . . . . . . . . 59
B. Vent Components Diagrams . . . . . . . . . . . . . . . . . . . . . . 61
C. Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
D. Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
= Contains updated information.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/124
B. Limited Lifetime Warranty
g
y
y p
p
y
y
y
y
Hearth & Home Technologies Inc.
LIMITED LIFETIME WARRANTY
Hearth & Home Technologies Inc., on behalf of its hearth brands (”HHT”), extends the following warranty for HHT gas, wood, pellet, coal and electric hearth appliances that are purchased from an HHT authorized dealer.
WARRANTY COVERAGE:
HHT warrants to the original owner of the HHT appliance at the site of installation, and to any transferee taking ownership of the appliance at the site of installation within two years following the date of original purchase, that the HHT appliance will be free from defects in materials and workmanship at the time of manufacture. After installation, if covered compo­nents manufactured by HHT are found to be defective in materials or workmanship during the applicable warranty period, HHT will, at its option, repair or replace the covered components. HHT, at its own discretion, may fully discharge all of its obligations under such warranties by replacing the product itself or refunding the verified purchase price of the product itself. The maximum amount recoverable under this warranty is limited to the purchase price of the product. This warranty is subject to conditions, exclusions and limitations as described below.
WARRANTY PERIOD:
Warranty coverage begins on the date of original purchase. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent, authorized HHT dealer/ distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from HHT, regardless of the installation or occupancy date. The warranty period for parts and labor for covered components is produced in the following table.
The term “Limited Lifetime” in the table below is defined as: 20 years from the beginning date of warranty coverage for gas appliances, and 10 years from the beginning date of warranty coverage for wood, pellet, and coal appliances. These time periods reflect the minimum expected useful lives of the designated components under normal operating conditions.
Warranty Period HHT Manufactured Appliances and Venting
Parts Labor Gas Wood Pellet
EPA
Wood
Coal Electric Venting
Components Covered
All parts and material except as
1 Year
XXXXXXX
covered by Conditions,
Exclusions, and Limitations
listed
Igniters, electronic components,
and
lass
-installed blowers
2 years
XXX
XXXXX Factor
X Molded refractor
3 years
ears 1 year X X Castings and baffles
5
7 years 3 years X X X
10
ears
Limited
Lifetime
1 year X Burners, logs and refractory
3 yearsXXXXX Firebox and heat exchanger
XFire
HHT chimne
ots and burnpots
Manifold tubes,
and termination
anels
90 Days
4021-645C 12-29-10 Page 1 of 2
XXXXXXX
See conditions, exclusions, and limitations on next page.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
All replacement parts
ond warranty period
be
5
B. Limited Lifetime Warranty (continued)
WARRANTY CONDITIONS:
 7KLVZDUUDQW\RQO\FRYHUV++7DSSOLDQFHVWKDWDUHSXUFKDVHGWKURXJKDQ++7DXWKRUL]HGGHDOHURUGLVWULEXWRU$OLVWRI
++7DXWKRUL]HGGHDOHUVLVDYDLODEOHRQWKH++7EUDQGHGZHEVLWHV  7KLVZDUUDQW\LVRQO\YDOLGZKLOHWKH++7DSSOLDQFHUHPDLQVDWWKHVLWHRIRULJLQDOLQVWDOODWLRQ  &RQWDFW\RXULQVWDOOLQJGHDOHUIRUZDUUDQW\VHUYLFH,IWKHLQVWDOOLQJGHDOHULVXQDEOHWRSURYLGHQHFHVVDU\SDUWVFRQWDFW
WKHQHDUHVW++7DXWKRUL]HGGHDOHURUVXSSOLHU$GGLWLRQDOVHUYLFHIHHVPD\DSSO\LI\RXDUHVHHNLQJZDUUDQW\VHUYLFH
IURPDGHDOHURWKHUWKDQWKHGHDOHUIURPZKRP\RXRULJLQDOO\SXUFKDVHGWKHSURGXFW  &KHFNZLWK\RXUGHDOHULQDGYDQFHIRUDQ\FRVWVWR\RXZKHQDUUDQJLQJDZDUUDQW\FDOO7UDYHODQGVKLSSLQJFKDUJHV
IRUSDUWVDUHQRWFRYHUHGE\WKLVZDUUDQW\
WARRANTY EXCLUSIONS:
7KLVZDUUDQW\GRHVQRWFRYHUWKHIROORZLQJ  &KDQJHVLQVXUIDFHILQLVKHVDVDUHVXOWRIQRUPDOXVH$VDKHDWLQJDSSOLDQFHVRPHFKDQJHVLQFRORURILQWHULRUDQG
H[WHULRUVXUIDFHILQLVKHVPD\RFFXU7KLVLVQRWDIODZDQGLVQRWFRYHUHGXQGHUZDUUDQW\
 'DPDJHWRSULQWHGSODWHGRUHQDPHOHGVXUIDFHVFDXVHGE\ILQJHUSULQWVDFFLGHQWVPLVXVHVFUDWFKHVPHOWHGLWHPV
RURWKHUH[WHUQDOVRXUFHVDQGUHVLGXHVOHIWRQWKHSODWHGVXUIDFHVIURPWKHXVHRIDEUDVLYHFOHDQHUVRUSROLVKHV
 5HSDLURUUHSODFHPHQWRISDUWVWKDWDUHVXEMHFWWRQRUPDOZHDUDQGWHDUGXULQJWKHZDUUDQW\SHULRG7KHVHSDUWV
LQFOXGHSDLQWZRRGSHOOHWDQGFRDOJDVNHWVILUHEULFNVJUDWHVIODPHJXLGHVOLJKWEXOEVEDWWHULHVDQGWKHGLVFRORU-
DWLRQRIJODVV
 0LQRUH[SDQVLRQFRQWUDFWLRQRUPRYHPHQWRIFHUWDLQSDUWVFDXVLQJQRLVH7KHVHFRQGLWLRQVDUHQRUPDODQGFRP-
SODLQWVUHODWHGWRWKLVQRLVHDUHQRWFRYHUHGE\WKLVZDUUDQW\
 'DPDJHVUHVXOWLQJIURPIDLOXUHWRLQVWDOORSHUDWHRUPDLQWDLQWKHDSSOLDQFHLQDFFRUGDQFHZLWKWKHLQVWDOODWLRQ
LQVWUXFWLRQVRSHUDWLQJLQVWUXFWLRQVDQGOLVWLQJDJHQWLGHQWLILFDWLRQODEHOIXUQLVKHGZLWKWKHDSSOLDQFHIDLOXUHWR
LQVWDOOWKHDSSOLDQFHLQDFFRUGDQFHZLWKORFDOEXLOGLQJFRGHVVKLSSLQJRULPSURSHUKDQGOLQJLPSURSHURSHUD-
WLRQDEXVHPLVXVHFRQWLQXHGRSHUDWLRQZLWKGDPDJHGFRUURGHGRUIDLOHGFRPSRQHQWVDFFLGHQWRULPSURSHUO\ LQFRUUHFWO\SHUIRUPHGUHSDLUVHQYLURQPHQWDOFRQGLWLRQVLQDGHTXDWHYHQWLODWLRQQHJDWLYHSUHVVXUHRUGUDIWLQJ FDXVHGE\WLJKWO\VHDOHGFRQVWUXFWLRQVLQVXIILFLHQWPDNHXSDLUVXSSO\RUKDQGOLQJGHYLFHVVXFKDVH[KDXVWIDQVRU IRUFHGDLUIXUQDFHVRURWKHUVXFKFDXVHVXVHRIIXHOVRWKHUWKDQWKRVHVSHFLILHGLQWKHRSHUDWLQJLQVWUXFWLRQV LQVWDOODWLRQRUXVHRIFRPSRQHQWVQRWVXSSOLHGZLWKWKHDSSOLDQFHRUDQ\RWKHUFRPSRQHQWVQRWH[SUHVVO\DXWKRUL]HG DQGDSSURYHGE\++7PRGLILFDWLRQRIWKHDSSOLDQFHQRWH[SUHVVO\DXWKRUL]HGDQGDSSURYHGE\++7LQZULWLQJ
DQGRULQWHUUXSWLRQVRUIOXFWXDWLRQVRIHOHFWULFDOSRZHUVXSSO\WRWKHDSSOLDQFH  1RQ++7YHQWLQJFRPSRQHQWVKHDUWKFRPSRQHQWVRURWKHUDFFHVVRULHVXVHGLQFRQMXQFWLRQZLWKWKHDSSOLDQFH  $Q\SDUWRIDSUHH[LVWLQJILUHSODFHV\VWHPLQZKLFKDQLQVHUWRUDGHFRUDWLYHJDVDSSOLDQFHLVLQVWDOOHG
 ++7¶VREOLJDWLRQXQGHUWKLVZDUUDQW\GRHVQRWH[WHQGWRWKHDSSOLDQFH¶VFDSDELOLW\WRKHDWWKHGHVLUHGVSDFH,QIRUPD-
WLRQLVSURYLGHGWRDVVLVWWKHFRQVXPHUDQGWKHGHDOHULQVHOHFWLQJWKHSURSHUDSSOLDQFHIRUWKHDSSOLFDWLRQ&RQVLGHU-
DWLRQPXVWEHJLYHQWRDSSOLDQFHORFDWLRQDQGFRQILJXUDWLRQHQYLURQPHQWDOFRQGLWLRQVLQVXODWLRQDQGDLUWLJKWQHVVRI
WKHVWUXFWXUH
This warranty is void if:
 7KHDSSOLDQFHKDVEHHQRYHUILUHGRURSHUDWHGLQDWPRVSKHUHVFRQWDPLQDWHGE\FKORULQHIOXRULQHRURWKHUGDPDJLQJ
FKHPLFDOV2YHUILULQJFDQEHLGHQWLILHGE\EXWQRWOLPLWHGWRZDUSHGSODWHVRUWXEHVUXVWFRORUHGFDVWLURQEXEEOLQJ
FUDFNLQJDQGGLVFRORUDWLRQRIVWHHORUHQDPHOILQLVKHV  7KHDSSOLDQFHLVVXEMHFWHGWRSURORQJHGSHULRGVRIGDPSQHVVRUFRQGHQVDWLRQ  7KHUHLVDQ\GDPDJHWRWKHDSSOLDQFHRURWKHUFRPSRQHQWVGXHWRZDWHURUZHDWKHUGDPDJHZKLFKLVWKHUHVXOWRIEXW
QRWOLPLWHGWRLPSURSHUFKLPQH\RUYHQWLQJLQVWDOODWLRQ
LIMITATIONS OF LIABILITY:
 7KHRZQHU¶VH[FOXVLYHUHPHG\DQG++7¶VVROHREOLJDWLRQXQGHUWKLVZDUUDQW\XQGHUDQ\RWKHUZDUUDQW\H[SUHVVRU
LPSOLHGRULQFRQWUDFWWRUWRURWKHUZLVHVKDOOEHOLPLWHGWRUHSODFHPHQWUHSDLURUUHIXQGDVVSHFLILHGDERYH,QQR
HYHQWZLOO++7EHOLDEOHIRUDQ\LQFLGHQWDORUFRQVHTXHQWLDOGDPDJHVFDXVHGE\GHIHFWVLQWKHDSSOLDQFH6RPHVWDWHV
GRQRWDOORZH[FOXVLRQVRUOLPLWDWLRQRILQFLGHQWDORUFRQVHTXHQWLDOGDPDJHVVRWKHVHOLPLWDWLRQVPD\QRWDSSO\WR\RX
7KLVZDUUDQW\JLYHV\RXVSHFLILFULJKWV\RXPD\DOVRKDYHRWKHUULJKWVZKLFKYDU\IURPVWDWHWRVWDWH(;&(3772
7+((;7(173529,'('%</$:++70$.(612(;35(66:$55$17,(627+(57+$17+(:$55$17<
63(&,),('+(5(,17+('85$7,212)$1<,03/,(':$55$17<,6/,0,7('72'85$7,212)7+(
(;35(66(':$55$17<63(&,),('$%29(
4021-645C 12-29-10 Page 2 of 2
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/126
1
1
Listing and Code Approvals
A. Appliance Certifi cation
MODEL: RED40, RED40ST LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Vented Gas Fireplace Heater STANDARD: ANSI Z21.88b-2008 CSA 2.33a-2008
Vented Gas Fireplace Heaters
This product is listed to ANSI standards for “Vented Gas Fireplace Heaters” and applicable sections of “Gas Burn­ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOTICE: This installation must conform with local codes. In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
NOT INTENDED FOR USE AS A PRIMAR Y HEAT SOURCE.
This appliance is tested and approved as either supplemen­tal room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
B. Glass Specifi cations
This appliance is equipped with 5 mm ceramic glass. Re­place glass only with 5 mm ceramic glass. Please contact your dealer for replacement glass.
C. BTU Specifi cations
(U.S. or Canada)
RED40
RED40ST
(NG)
RED40
RED40ST
(LP)
Models
(2000-4500 FT)
(2000-4500 FT)
US
(0-2000 FT)
CANADA
US
(0-2000 FT)
CANADA
Maximum
Input BTU/h
34,000 24,000 #34
29,500 22,000 #36
34,000 25,000 #50
31,500 23,000 #51
Minimum
Input
BTU/h
Orifi ce
Size
(DMS)
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
Check with your local gas utility to determine proper orifi ce size.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed pa­per, plant fi bers, plastics, or other material that can ignite and burn, whether fl ame proofed or not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
7
Note: The following requirements reference various Massachuset ts and national codes not contain ed in this document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addi­tion, the installing plumber or gas fi tter shall observe that a battery operated or hard wired carbon monoxide detec­tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fu­eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob­serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro­vide the parts for venting the fl ue gases, but identifi es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu­eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB­STRUCTIONS”.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/128
• The referenced “special venting system” instructions
shall be included with the appliance or equipment in­stallation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
2
2
Operating Instructions
User Guide
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation AND cool down.
Hot glass will cause burns.
DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable materials.
• Keep clothing, furniture, draperies and other fl ammable materials away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
WARNING! Choking Hazard! Keep rock media out of reach of children.
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be present.
Contact your dealer for more information, or visit: www. hpba.org/safety-information.
T o prevent unintended operation when not using your fi re- place for an extended period of time (summer months, vacations, trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 3 volt adapter plug.
B. Your Fireplace
WARNING! DO NOT operate fi replace before read- ing and understanding operating instructions. Failure
to operate fi replace according to operating instructions could cause fi re or injury.
If you expect that small children or vulnerable adults may come into contact with this fi replace, the following precau- tions are recommended:
• Install a physical barrier such as:
- A decorative fi rescreen.
- Adjustable safety gate.
DECORATIVE DOORS
SECTION 2.D.
CLEAR SPACE
3 FT. IN FRONT
OF FIREPLACE
C. Clear Space
WARNING! DO NOT place combustible objects in front of the fi replace. High temperatures may start a fi re. See Figure 2.1.
A void placing candles and other heat-sensitive objects on mantel or hearth. Heat may damage these objects.
FIXED GLASS ASSEMBLY
SECTION 14.H.
Figure 2.1 General Operating Parts/Clear Space.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
CLEAR SPACE
SECTION 2.C.
9
D. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts approved by Hearth & Home Technologies. Unapproved doors or fronts may cause fi replace to overheat.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the fi replace with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
For more information refer to the instructions supplied with your decorative door or front.
E. Fixed Glass Assembly
See Section 14.H.
G. Before Lighting Fireplace
Before operating this replace for the rst time, have a qualifi ed service technician:
• Verify all shipping materials have been removed from inside and/or underneath the fi rebox.
• Review proper placement of media, refractory kits and/or other decorative materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position and that the integral barrier is in place.
WARNING! Risk of Fire or Asphyxiation! DO NOT op­erate fi replace with fi xed glass assembly removed.
F. Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed to operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1210
H. Lighting Instructions (IPI)
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an
intermittent pilot ignition (IPI) device which automatically lights the burn­er. DO NOT try to light the burner by hand.
B. BEFORE LIGHTING, smell all around
the appliance area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
WHA T TO DO IF YOU SMELL GAS
DO NOT try to light any appliance.
DO NOT touch any electric switch; do not use any phone in your building.
WARNING:
DO NOT CONNECT LINE VOLT­AGE (110/120 VAC OR 220/240 V AC) TO THE CONTROL VALVE.
Improper installation, adjustment, al­teration, service or maintenance can cause injury or property damage. Re­fer to the owner’s information manual provided with this appliance.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
If not installed, operated, and main­tained in accordance with the manufac­turer’s instructions, this product could expose you to substances in fuel or fuel combustion which are known to the State of California to cause cancer, birth defects, or other reproductive harm.
Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fi re department.
C. DO NOT use this appliance if any
part has been under water. Imme­diately call a qualifi ed service tech- nician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CAUTION:
Hot while in operation. DO NOT touch. Keep children, clothing, furniture, gaso­line and other liquids having fl ammable vapors away.
DO NOT operate the appliance with xed glass assembly removed, cracked or broken. Replacement of the fi xed glass assembly should be done by a licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
For use with natural gas and propane. A conversion kit, as supplied by the manufacturer, shall be used to convert this appliance to the alternate fuel.
Also Certifi ed for Installation in a Bedroom or a Bedsitting Room.
For assistance or additional informa­tion, consult a qualifi ed installer, ser- vice agency or the gas supplier.
LIGHTING
INSTRUCTIONS (IPI)
1. This appliance is equipped with an ignition
device which automatically lights the burner.
DO NOT try to light the burner by hand.
GAS
VALVE
2. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the fl oor. If you smell gas, STOP! Follow “B” in the Safety Information located on the left side of this la­bel. If you do not smell gas, go to next step.
3. To light the burner: Equipped with wall switch: Turn ON/OFF switch
to ON.
Equipped with remote or wall control: Press
ON or FLAME button.
Equipped with thermostat: Set temperature to
desired setting.
4. If the appliance does not light after three tries, call your service technician or gas supplier.
TO TURN OFF
GAS TO APPLIANCE
1. Equipped with wall switch: Turn ON/OFF switch
to OFF.
Equipped with remote or wall control: Press
OFF button.
Equipped with thermostat: Set temperature to
lowest setting.
2. Service technician should turn off electric power to the control when performing service.
593-913G
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
For additional information on operating your
Final inspection by
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
11
I. After Fireplace is Lit
Initial Break-in Procedure
• The fireplace should be run three to four hours continuously on high.
• Turn the fi replace off and allow it to completely cool.
• Remove fi xed glass assembly. See Section 14.H.
• Clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously on high an additional 12 hours.
This cures the materials used to manufacture the fi re- place.
NOTICE! Open windows for air circulation during fi re- place break-in.
• Some people may be sensitive to smoke and odors.
• Smoke detectors may activate.
J. Frequently Asked Questions
ISSUE SOLUTIONS
Condensation on the glass
Blue fl ames
Odor from fi replace
Film on the glass
Metallic noise
Rock noise
Rocks falling through basepan
This is a result of gas combustion and temperature variations. As the fi replace warms, this conden- sation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the fi replace is allowed to burn for 20 to 40 minutes.
When fi rst operated, this fi replace may release an odor for the fi rst several hours. This is caused by the curing of materials from manufacturing. Odor may also be released from fi nishing materials and adhesives used near the fi replace. These circumstances may require additional curing related to the installation environment.
This is a normal result of the curing process of the paint. Glass should be cleaned within 3 to 4 hours of initial burning. A non-abrasive cleaner such as gas appliance glass cleaner may be nec­essary. See your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to the sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of the fi replace.
There may be some “cracking” noise coming from the fi replace during the fi rst few heating and cooling cycles. This noise is associated with settling rock and some minor cracking of larger pieces of rock. This will lessen over time as the glass rock is conditioned to the heating and cool­ing temperature changes.
It is expected that a few small pieces of rock may fall through the basepan and come to rest on the replace bottom. This has no affect on fi replace performance.
Wall above appliance feels hot to the touch.
No action necessary. This appliance ships with a non-combustible material attached. Specifi ca- tions of the attached non-combustible material are listed in Section 1.E.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1212
3
3
Maintenance and Service
Any safety screen or guard removed for servicing must be replaced prior to operating the fi replace.
When properly maintained, your fi replace will give you many years of trouble-free service. We recommend an­nual service by a qualifi ed service technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed service technician only. The fi replace should be inspected before use and at least annually by a professional service person.
The following tasks may be performed annually by the homeowner. If you are uncomfortable performing any of the listed tasks, please call your dealer for a service ap­pointment.
More frequent cleaning may be required due to lint from carpeting or other factors. Control compartment, burner and circulating air passageway of the fi replace must be kept clean.
CAUTION! Risk of Burns! The fi replace should be turned off and cooled before servicing.
Glass Cleaning
Frequency: Seasonally By: Homeowner Tools Needed: Protective gloves, glass cleaner, drop
cloth and a stable work surface.
CAUTION! Handle fi xed glass assembly with care.
Glass is breakable.
• Avoid striking, scratching or slamming glass
• Avoid abrasive cleaners
DO NOT clean glass while it is hot
• Prepare a work area large enough to accommodate fi xed glass assembly and door frame by placing a drop cloth on a fl at, stable surface.
Note: Fixed glass assembly and gasketing may have res­idue that can stain carpeting or fl oor surfaces.
• Remove door or decorative front from fi replace and set aside on work surface.
• See Section 14.H for instructions to remove fi xed glass assembly.
• Clean glass with a non-abrasive commercially available cleaner.
- Light deposits: Use a soft cloth with soap and water
- Heavy deposits: Use commercial fireplace glass
cleaner (consult with your dealer)
• Refer to Section 14.H for glass removal and replacement instructions.
• Reinstall door or decorative front.
Doors, Surrounds, Fronts
Frequency: Annually By: Homeowner Tools needed: Protective gloves, stable work surface
• Assess condition of screen and replace as necessary.
• Inspect for scratches, dents or other damage and repair as necessary.
• Check that louvers are not blocked.
• Vacuum and dust surfaces.
Remote Control
Frequency: Seasonally By: Homeowner Tools needed: Replacement batteries and remote con-
trol instructions.
• Locate remote control transmitter and receiver.
• Verify operation of remote. Refer to remote control operation instructions for proper calibration and setup procedure.
• Place batteries as needed in remote transmitters and battery-powered receivers.
• Place remote control out of reach of children.
If not using your fi replace for an extended period of time (summer months, vacations/trips, etc), to prevent unin­tended operation:
• Remove batteries from remote controls.
• Unplug 3 volt adapter plug on IPI models.
• Verify that the sensor rod does not contact the burner.
Venting
Frequency: Seasonally By: Homeowner Tools needed: Protective gloves and safety glasses.
• Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow, debris, etc.
• Verify termination cap clearance to subsequent construc­tion (building additions, decks, fences, or sheds). See Section 6.
• Inspect for corrosion or separation.
• Verify weather stripping, sealing and fl ashing remains intact.
• Inspect draft shield to verify it is not damaged or missing.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
13
B. Maintenance Tasks-Qualifi ed Service
Technician
The following tasks must be performed by a qualifi ed ser- vice technician.
Gasket Seal and Glass Assembly Inspection
Frequency: Annually By: Quali ed Service T echnician T ools needed: Protective gloves, drop cloth and a stable
work surface.
• Inspect gasket seal and its condition.
• Inspect fi xed glass assembly for scratches and nicks that can lead to breakage when exposed to heat.
• Confi rm there is no damage to glass or glass frame. Replace as necessary.
• Verify that fi xed glass assembly is properly retained and attachment components are intact and not damaged. Replace as necessary.
Firebox
Frequency: Annually By: Quali ed Service T echnician Tools needed: Protective gloves, sandpaper, steel wool,
cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion or perforation. Sand and repaint as necessary.
• Replace fi replace if fi rebox has been perforated.
• Inspect for lifting or other fl ame problems.
• Verify air shutter setting is correct. See Section 14.J for required air shutter setting. Verify air shutter is clear of dust and debris.
• Inspect orifi ce for soot, dirt and corrosion. Verify orifi ce size is correct. See Service Parts List for proper orifi ce sizing.
• Verify manifold and inlet pressures. Adjust regulator as required.
• Inspect pilot fl ame pattern and strength. See Figure 3.1 for proper pilot fl ame pattern. Clean or replace orifi ce spud as necessary.
• Inspect IPI fl ame-sensing rod for soot, corrosion and deterioration. Polish with fi ne steel wool or replace as required.
• Verify IPI millivolt output. Replace as necessary.
• Verify that there is not a short in fl ame sense circuit by checking continuity between pilot hood and fl ame- sensing rod. Replace pilot as necessary.
Control Compartment and Firebox Top
Frequency: Annually By: Quali ed Service T echnician Tools needed: Protective gloves, vacuum cleaner, dust
cloths
• V acuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.
• Remove all foreign objects.
• Verify unobstructed air circulation.
Burner Ignition and Operation
Frequency: Annually By: Quali ed Service T echnician T ools needed: Protective gloves, vacuum cleaner, whisk
broom, fl ashlight, voltmeter, indexed drill bit set, and a manometer.
• Verify burner is properly secured and aligned with pilot or igniter.
• Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.
• Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.
Figure 3.1 IPI Pilot
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1214
4
4
A. Typical Appliance System
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only . Illustrations/diagrams are not drawn to scale. Actual product may vary from pictures in manual
Getting Started
HORIZONTAL
TERMINATION CAP
(SECTION 7)
WALL PENETRATION
FRAMING
(SECTION 8B)
VERTICAL TERMINATION CAP
(SECTION 10.I)
CONVECTION
DUCTING
NON-COMBUSTIBLE ROOF FLASHING
MAINTAINS MINIMUM CLEARANCE
AROUND PIPE
(SECTION 10)
STORM COLLAR
(SECTION 10.G)
VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS (SECTION 8.C)
(SECTION 9.C)
Installer Guide
VENT PIPE
(SECTIONS 7&8)
CEILING FIRESTOP ON FLOOR OF ATTIC (SECTION 8.C)
FRAMING/HEADER (SECTION 5)
GAS LINE (SECTION 11)
ATTIC INSULATION SHIELD (NOT SHOWN) MUST BE USED HERE TO KEEP INSULA­TION AWAY FROM VENT PIPE IF ATTIC IS INSULATED. (SECTION 8.D)
FRAMING HEADED OFF IN CEILING JOISTS (SECTION 8.C)
WALL SWITCHES
REQUIRED ACTIVE
CONVECTION AND
CONVECTION
DUCTING
(SECTION 9.C)
Figure 4.1 Typical System
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
15
B. Design and Installation Considerations
Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fi re offi cials or authorities having jurisdiction over restrictions, installation inspection and permits.
NOTICE: The blower motor present in this appliance will generate sound during operation. The effects of the increased sound level can be minimized with careful planning during installation of the system. Locating the convection intake grill in an area remote of immediate living space will reduce the effects of the added sound generated during operation.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a wall switch or remote control—are desired.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualifi ed service technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Tape measure Framing material Pliers Non-corrosive leak check solution Hammer Phillips screwdriver (magnetic) Gloves Framing square Voltmeter Electric drill and bits (1/4 in. magnetic) Plumb line Safety glasses Level Reciprocating saw Manometer Flat blade screwdriver 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws Caulking material (300ºF minimum continuous exposure
rating) One 1/4 in. female connection (for optional fan).
D. Inspect Appliance and Components
• Carefully remove the appliance and components from the packaging.
• The vent system components and decorative doors and fronts may be shipped in separate packages.
• If packaged separately, the media and/or refractory kits must be installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, in- complete or substitute components. Keep appliance dry.
Hearth & Home T echnologies disclaims any responsibility for , and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance if any part has been under
water. Call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and/or gas control which has been under water.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1216
5
5
Framing and Clearances
A. Selecting Appliance Location
When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 5.1).
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access.
Due to high temperatures, the appliance should be locat­ed out of traffi c and away from furniture and draperies.
A
E
1 IN.
1 IN.
A
45°
B
C
ONE 90° ELBOW
TOP VENT
NOTICE: Illustrations refl ect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.
It is important to follow the framing and fi nishing instruc- tions step by step to ensure proper placement of fi replace in the surrounding framing/fi nishing materials. For addi- tional information and considerations for the active con­vection technology in regards to appliance location and framing, see Section 9.
B
ALCOVE
INSTALLATION
D
Inches 60-3/8 50 85-3/8
Millimeters 1533 1270 2168 613 476
Figure 5.1 Appliance Locations RED40
Note: Consider installation of the active con-
vection blower when determining appliance location. See Section 9.C for more detailed information.
TOP VENT
ONE 90° ELBOW
B
F
ABC D E F
See Section D.
Figure 5.6 & 5.7
24-1/8 18-3/4
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
17
1/2 IN.
NAILING TABS BOTH SIDES
Note: Consider installation of the active con­vection blower when determining appliance location. See Section 9.C for more detailed information.
C
A
Inches 48 17-1/4 36
B
Millimeters 1218 438 914
ABC
1/2 IN.
Figure 5.2 Appliance Locations RED40ST
C
B. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should enclosed inside the chase.
NOTICE: Treatment of ceiling fi restops and wall shield restops and construction of the chase may vary with the
type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.
Chases should be constructed in the manner of all out­side walls of the home to prevent cold air drafting prob­lems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase should be insulated. Vapor and air infi ltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infi ltration may be an issue, the inside surfaces may be sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re- stops should be caulked with caulk with a minimum of 300ºF continuous exposure rating to seal gaps. Gas line holes and other openings should be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement surface, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.
WARNING! Risk of Fire! Maintain specifi ed air space clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent accidental contact.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and re.
Figure 5.3 Nailing Tab Locations
Note: Figure 5.3, Figure 5.4, and Figure 5.5 show the replace
installed on the fl oor. However, this fi replace can be elevated off the fl oor provided that the fi replace is properly supported by framing materials and the ceiling clearances are maintained.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1218
Inches
A
F
B
J
C
D
G
MEASURE FROM TOP OF FIREPLACE OPENING
I
E
H
MINIMUM FRAMING DIMENSIONS*
ABCDE F GHIJ
Rough
Opening
(Vent Pipe)
10 46-3/4 18-1/4 50-1/4 31 0 0 1 1 36
Rough
Opening
(Height)
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
Combustible
Flooring
Behind
Appliance
Sides of
Appliance
Front of
Appliance
Millimeters
254 1187 464 1276 787 0 0 25 25 914
Figure 5.4. Clearances to Combustibles-RED40
A
C
D
B
MEASURE FROM TOP OF FIREPLACE OPENING
E
F
I
G
H
ABCDE F GHI
Rough
Opening
(Vent Pipe)
Inches
Millimeters
10 46-3/4 17-1/4 50-1/4 31 0 0 1 36
254 1187 438 1276 787 0 0 25 914
Figure 5.5. Clearances to Combustibles-RED40ST
Rough
Opening
(Height)
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
MINIMUM FRAMING DIMENSIONS*
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
Combustible
Flooring
Sides of
Appliance
Front or
Rear of
Appliance
19
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear­ances to combustibles as specifi ed. Framing or fi nishing material closer than the minimums listed must be construct­ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantels
Note: All
measurements in inches.
TO CEILING
18
12
11
10
9
8
7
6
7
11
10
9
8
31
25
13
12
Combustible Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace
2 IN. MIN.
UNLIMITED
FIREPLACE
OPENING
4 IN.
MAX.
6 IN. MIN.
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Figure 5.6 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles
Note: For non-combustible replace nish material (marble,
stone, etc) specifi cations refer to Section 13.
Non-Combustible Mantels
TO CEILING
MAX.
16
10
9
8
7
6
1/2
5
4
MEASUREMENTS FROM TOP EDGE OF THE
3
2
1
FIRESCREEN DOOR ASSEMBLY
12
6
5
4
Note: All measurements in inches.
31
MIN.
= ACCEPT ABLE
NON-COMBUSTIBLE
MANTEL LEG
ZONE
Figure 5.8 Mantel Leg or Wall Projections (Acceptable on both sides of opening)
Figure 5.7 Minimum Vertical and Maximum Horizontal Dimensions of Non-Combustibles
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1220
6
6
Termination Locations
A. Vent Termination Minimum Clearances
WARNING
Fire Risk. Maintain vent clearance to combustibles as
specifi ed.
DO NOT pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause overheating and fi re.
HORIZONTAL
OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
X
12
ROOF PITCH
IS X/ 12
VERTICAL
WALL
6 in. (minimum) up to 20 in.
AB
152 mm/508 mm
20 in. and over 0 in. minimum
18 in. minimum
457 mm
Gas, Wood or Fuel Oil
Termination Cap
B
A *
Gas
Termination
Cap **
If using decorative cap cover(s), this distance may need to be
*
increased. Refer to the installation instructions supplied with the decorative cap cover.
In a staggered installation with both gas and wood or fuel oil
**
terminations, the wood or fuel oil termination cap must be higher than the gas termination cap.
Roof Pitch H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
* 3 foot minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening
Figure 6.2 Staggered Termination Caps
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
21
O
N
P
C
V
B
J
V
V
= VENT TERMINAL
X
= AIR SUPPLY INLET
B
D
V
V
V
F
B
A
G
M
V
H or i
V
X
H
V
H
E
V
V
A
= AREA WHERE TERMINAL IS NOT PERMITTED
R
Q
V
L
K
Electrical
V
Service
C
V
K
V
A = 12 inches.................clearances above grade, veranda,
porch, deck or balcony
12 inches.................clearance to window or door that may
B =
be opened, or to permanently closed
window
C = 18 inches.................clearance below unventilated soffi t
18 inches.................clearance below ventilated soffi t
30
inches .................clearance below vinyl soffits and
electrical service
D = 6 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas me-
ter/regulator assembly within 3 feet
horizontally from the center-line of the
regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet H = 9 inches (U.S.A)
12 inches (Canada). clearance to non-mechanical (unpow-
ered) air supply inlet, combustion air
inlet or direct-vent termination i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (powered)
air supply inlet All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below termination.
J = 7 ft. ......................... On public property: clearance above
paved sidewalk or a paved driveway. A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings.
K = 6 inches................. clearance from sides of electrical
service
L = 12 inches................ clearance above electrical service
Location of the vent termination must not interfere with access to the electrical service.
M = 18 inches ....................clearance under veranda, porch, deck,
balcony or overhang 42
inches ................vinyl or composite overhang
Permitted when veranda, porch, deck or balcony is fully open
on a minimum of 2 sides beneath the fl oor.
Figure 6.3 Minimum Clearances for Termination
Covered Alcove Applications
(Spaces open only on one side and with an overhang)
N = 6 inches ........... non-vinyl sidewalls
12 inches ......... vinyl sidewalls
O = 18 inches ......... non-vinyl soffi t and overhang
42 inches ......... vinyl soffi t and overhang
P = 8 ft.
Q
MIN
1 cap 3 feet 2 x Q 2 caps 6 feet 1 x Q 3 caps 9 feet 2/3 x Q 4 caps 12 feet 1/2 x Q
Q
= # termination caps x 3 R
MIN
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffi c areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer.
• Local codes or regulations may require different clearances.
• Vent system termination is NOT permitted in screened porches.
• Vent system termination is permitted in porch areas with two or more sides open.
• Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
• Vinyl protection kits are suggested for use with vinyl siding.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1222
7
7
Vent Information and Diagrams
A. Approved Pipe
This appliance is approved for use with Hearth & Home Technologies DVP venting systems. Refer to Section 16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ- ent manufacturers.
The pipe is tested to be run inside an enclosed wall. There is no requirement for inspection openings at each joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli­ance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.
B. Vent Table Key
The abbreviations listed in this vent table key are used in the vent diagrams.
Symbol Description
V V H
First section (closest to appliance) of vertical length
1
Second section of vertical length
2
First section (closest to appliance) of horizontal length
1
D. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.
• Pipe measurements are shown using the effective length of pipe (see Figure 7.2).
• Measurements are made from the appliance outer wrap, not from the standoffs.
• Horizontal terminations are measured to the outside mounting surface (fl ange of termination cap).
• Vertical terminations are measured to bottom of termination cap.
• Horizontal pipe installed level with no rise.
A
B
H
Subsequent sections of horizontal length
2
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent as­pects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).
Vertical
12 in.
8-1/2 in.
Horizontal
Figure 7.1
8-1/2 in.
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/12
1-1/4 in. (32 mm)
OVERLAP
Figure 7.2 Chimney Offset/Return
Effective Length
Inches Millimeters
Effective
Height/ Length
Figure 7.3 Pipe Effective Length
Pipe
DVP4 4 102
DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219 DVP6A 3 to 6 76 to 152
DVP12A 3 to 12 76 to 305 DVP12MI 3 to 12 76 to 305 DVP24MI 3 to 24 76 to 610
E. Vent Diagrams
General Rules:
• When penetrating a combustible wall, a wall shield restop must be installed.
• When penetrating a combustible ceiling, a ceiling fi restop must be installed.
• Horizontal runs of vent do not require vertical rise; horizontal runs may be level.
23
Fire Risk. Explosion Risk. Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed. Failure to keep insulation or other material away from vent pipe may cause fi re.
Top Vent - Horizontal Termination
Venting with 1 elbow
WARNING
V1 Minimum H1 Maximum
1 ft. 305 mm 2 ft. 610 mm 2 ft. 610 mm 6 ft. 1829 3 ft. 914 mm 9 ft. 2743 4 ft. 1219 mm 12 ft. 3658 5 ft. 1524 mm 15 ft. 4572 6 ft. 1829 mm 18 ft. 5486 7 ft. 2134 mm 21 ft. 6401 8 ft. 2438 mm 24 ft. 7315
+ H1 = 63 ft. (19.2 m) Maximum
V
1
Note: 12 inches minimum vertical is required prior to attaching any elbow to the appliance.
H
1
Note: Use DVP Series components only.
V
1
Figure 7.4
Heat & Glo • RED40, RED40ST • 2155-900 Rev. P • 10/1224