Heatcraft Refrigeration Products H-IM-FL1A User Manual

FL AC Scroll Refrigeration Systems
H-IM-FL1A December, 2004 Part No. 25006901
Table of Contents
Installation and
Operation Manual
General Safety Information ...................................................... 2
Inspection ................................................................................. 2
Warranty Statement ..................................................................
Air Cooled Condensing Unit and Condenser Space and Location
Condensing Unit Rigging and Mounting ................................... 4
Ambient Fan Cycle Control ...................................................... 4
Condensing Unit Accessories ..................................................
Suction Filters, Driers, Sight Glasses ....................................... 5
Refrigerant Oils ........................................................................ 6
Phase Loss Monitor .................................................................. 7
Recommended Refrigerant Piping Practices ........................... 7
Refrigeration Pipe Supports .................................................... 7
Suction Lines ............................................................................ 8
Suction Line Risers .................................................................. 8
Liquid Lines .............................................................................. 8
Evacuation and Leak Detection ...............................................11
Refrigerant Charging Instructions ........................................... 12
Field Wiring............................................................................. 12
Check Out and Start Up ......................................................... 12
Operational Check Out ........................................................... 13
System Balancing - Compressor Superheat .......................... 13
System Troubleshooting Guide ..............................................
Preventive Maintenance Guidelines ....................................... 15
Replacement Parts ................................................................. 15
Wiring Diagrams ................................................................ 16-18
Submittal .......................................................................... 19, 20
Service Record ....................................................................... 21
2
5
14
General Safety Information
1. Installation and maintenance to be performed only by qualified personnel who are familiar with this type of equipment.
2. Some units are pressurized with dry air or inert gas. All units must be evacuated before charging the system with refrigerant.
WARNING: Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered
responsibly. Failure to follow this warning may result in personal injury or death.
Inspection
Responsibility should be assigned to a dependable individual at the job site to receive material. Each shipment should be carefully checked against the bill of lading. The shipping receipt should not be signed until all items listed on the bill of lading have been accounted. Check carefully for concealed damage. Any shortage or damages should be reported to the delivering carrier. Damaged material becomes the delivering carrierʼs responsibility, and should not be returned to the manufacturer unless prior approval is given to do so. When uncrating, care should be taken to prevent damage. Heavy equipment should be left on its shipping base until it has been moved to the final location. Check the serial tag information with invoice. Report any discrepancies to your Heatcraft Refrigeration Products Sales Representative.
Warranty Statement
Seller warrants to its direct purchasers that products, including
Service Parts, manufactured by SELLER shall be of a merchantable quality, free of defects in material or workmanship, under normal use and service for a period of one (1) year from date of original installation, or eighteen (18) months from date of shipment by SELLER, whichever first occurs. Any product covered by this order found to Sellerʼs satisfaction to be defective upon examination at Sellerʼs factory will at SELLERʼs option, be repaired or replaced and returned to Buyer via lowest common carrier, or SELLER may at its option grant Buyer a credit for the purchase price of the defective article. Upon return of a defective product to SELLERʼs plant, freight prepaid, by Buyer, correction of such defect by repair or replacement, and return freight via lowest common carrier, shall constitute full performance by SELLER of its obligations hereunder.
SELLER shall have no liability for expenses incurred for repairs made by Buyer except by prior, written authorization. Every claim on account of breach of warranty shall be made to SELLER in writing within the warranty period specified above – otherwise such claim shall be deemed waived. Seller shall have no warranty obligation whatsoever if its products have been subjected to alteration, misuse, negligence, free chemicals in system, corrosive atmosphere, accident, or if operation is contrary to SELLERʼs or manufacturerʼs recommendations, or if the serial number has been altered, defaced, or removed.
MOTOR COMPRESSORS:
Motor compressors furnished by SELLER are subject to the standard warranty terms set forth above, except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer (not at SELLERʼs factory) and no freight shall be allowed for transportation of the motor compressor to and from the wholesaler. The replacement motor compressor shall be identical to the model of the motor compressor being replaced. Additional charges which may be incurred throughout the substitution of other than identical replacements are not covered by this warranty.
2
© 2004, Heatcraft Refrigeration Products LLC
3. Make sure that all field wiring conforms to the requirements of the equipment and all applicable national and local codes.
4. Avoid contact with sharp edges and coil surfaces. They are a potential injury hazard.
5. Make sure all power sources are disconnected before any service work is done on units.
An optional, nonassignable, four (4) year extended compressor warranty may be purchased within the boundaries of the United Sates of America, its territories and possessions, and Canada. With this extended compressor warranty, replacements are administered by an authorized compressor distributor only. Replacements within the first year of the warranty area available through the distributor; the second through fifth years, the purchaser must submit a proof­of-purchase of a compressor and supply it to Heatcraft Refrigeration Products Warranty Claims for reimbursement.
Seller makes no express warranties except as noted above. All implied warranties are limited to the duration of the Express Warranty. Liability for incidental and consequential damages is excluded.
The forgoing is in lieu of all other warranties, express or implied, notwithstanding the provisions of the uniform commercial code, the Magnuson-Moss Warranty-Federal Trade Commission Improvement Act, or any other statutory or common law, federal or state.
SELLER makes no warranty, express or implied, of fitness for any particular purpose, or of any nature whatsoever, with respect to products manufactures or sold by seller hereunder, except as specifically set forth above and on the face hereof. It is expressly understood and agreed that SELLER shall not be liable to buyer, or any customer of buyer, for direct or indirect, special, incidental, consequential or penal damages, or for any expenses incurred by reason of the use or misuse by buyer or third parties of said products. To the extent said products may be considered "consumer products," As defined in Sec. 101 of the Magnuson-Moss Warranty
- Federal Trade Commission Improvement Act, SELLER makes no warranty of any kind, express or implied, to "consumers," except as specifically set forth above and on the face hereof.
The following conditions should be adhered to when installing this unit to maintain the manufacturers warranty:
(a) System piping must be in accordance with good refrigeration practices. (b) Inert gas must be charged into the piping during
brazing.
(c) The power supply to the unit must meet the
following conditions:
A. Three phase voltages must be +/­ 10% of nameplate ratings. Single phase must be within +10% or
-5% of nameplate ratings. B. Phase imbalance cannot exceed 2%. (d) All control and safety switch circuits must be
properly connected according to the wiring diagram.
(e) The factory installed wiring must not be changed
without written factory approval.
(f) All equipment is installed in accordance with
Heatcraft specified minimum clearances.
Space and Location Requirements for Air Cooled Condensing Units and Remote Condensers
The most important consideration which must be taken into account when deciding upon the location of air-cooled equipment is the provision for a supply of ambient air to the condenser, and removal of heated air from the condensing unit or remote condenser area. Where this essential requirement is not adhered to, it will result in higher head pressures, which cause poor operation and potential failure of equipment. Units must not be located in the vicinity of steam, hot air or fume exhausts. Corrosive atmospheres require custom designed condensers.
Figure 1. Space and Location Requirements for Condensing Units and Remote Condensers
Another consideration which must be taken is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building. Units should be mounted over corridors, utility areas, rest rooms and other auxiliary areas where high levels of sound are not an important factor. Sound and structural consultants should be retained for recommendations.
Walls or Obstructions
The unit should be located so that air may circulate freely and not be recirculated. For proper air flow and access all sides of the unit should be a minimum of “W” away from any wall or obstruction. It is preferred that this distance be increased whenever possible. Care should be taken to see that ample room is left for maintenance work through access doors and panels. Overhead obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for units in a pit.
Units in Pits
The top of the unit should be level with the top of the pit, and side distance increased to “2W”.
If the top of the unit is not level with the top of pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is a minimum requirement.
Multiple Units
For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end to end, the minimum distance between units is 4 feet.
Decorative Fences
Fences must have 50% free area, with 1 foot undercut, a “W” minimum clearance, and must not exceed the top of unit. If these requirements are not met, unit must be installed as indicated for “Units in pits”.
* “W” = Total width of the condensing unit or condenser.
3
Condensing Unit Rigging and Mounting
Rigging holes are provided on all units. Caution should be exercised when moving these units. To prevent damage to the unit housing during rigging, cables or chains used must be held apart by spacer bars. The mounting platform or base should be level and located so as to permit free access of supply air.
Ground Mounting
Concrete slab raised six inches above ground level provides a suitable base. Raising the base above ground level provides some protection from ground water and wind blown matter. Before tightening mounting bolts, recheck level of unit. The unit should in all cases be located with a clear space in all directions that is at a minimum, equal to the height of the unit above the mounting surface. A condensing unit mounted in a corner formed by two walls, may result in discharge air recirculation with resulting loss of capacity.
Roof Mounting
Due to the weight of the units, a structural analysis by a qualified engineer may be required before mounting. Roof mounted units should be installed level on steel channels or an I-beam frame capable of supporting the weight of the unit. Vibration absorbing pads or springs should be installed between the condensing unit legs or frame and the roof mounting assembly.
Access
Provide adequate space at the compressor end of the unit for servicing. Provide adequate space on the connection side to permit service of components.
Spring Mounted Compressor
Compressors are secured rigidly to make sure there is no transit damage. Before operating the unit, it is necessary to follow these steps:
Figure 2. Solid Mount for Mobile or Deep Sump Application.
Ambient Fan Cycle Control
This is an automatic winter control method which will maintain a condensing pressure within reasonable limits by cycling fan motors in response to outside air temperature. The thermostat(s) should be field adjusted to shut off the fan when the condensing temperature is reduced to approximately 90˚F. Table 2 on page 5 lists approximate settings for several system T.D.ʼs. These settings are approximate as they do not take into account variations in load.
CAUTION: Under no circumstance should all condenser motors be allowed to cycle off on one control. At least one motor shall be wired to operate at all times. Under most circumstances, the condenser motor nearest the inlet header should remain on whenever the compressor is operating.
a. Remove the upper nuts and washers. b. Discard the shipping spacers. c. Install the neoprene spacers. (Spacers located
in the electrical panel or tied to compressor.)
d. Replace the upper mounting nuts and washers. e. Allow 1/16 inch space between the mounting nut/
washer and the neoprene spacer.
Rigid Mounted Compressor
Some products use rigid mounted compressors. Check the compressor mounting bolts to insure they have not vibrated loose during shipment.
4
Condensing Unit Accessories
Suction Filters, Driers, Sight Glasses
There are two types of suction and liquid filter/driers used on Heatcraft Refrigeration Products units. Replaceable core and/or sealed units are used, dependent upon the option package ordered.
Suction filters, regardless of type, are always installed upstream of the compressor suction service valve, and any accumulators or other options that may be installed. Suction filters are equipped with “Schrader” type access valves to allow field measurement of pressure drop across the device. This allows plugged filters and elements to be identified very quickly and easily so they can be replaced when the pressure drop is excessive. Refer to the specific manufacturersʼ recommendation on servicing these units by make and model.
Liquid filter/driers, regardless of type, are always installed downstream of the receiver outlet service valve, and up-
stream of the liquid line solenoid valve (if supplied). Liquid line driers may or may not have an access valve, dependent on the size and application. The basic servicing of these units is similar to suction filters. Liquid line driers should be replaced whenever there is evidence of excessive pressure drop across the filter, or the system becomes contaminated due to system leaks, compressor burnouts, acid formation, or moisture accumulation as indicated by the liquid line sight glass.
The sight glass is installed in the main liquid line assembly, downstream from the receiver outlet service valve, and immediately after the liquid line drier. The sight glass is designed to give a visual indication of moisture content in the system. Generally, it requires no field service. However, in cases of extreme acid formation in a system after a compressor burnout, the acid may damage the sensing element or etch the glass. This would require that the sight glass be replaced, along with the liquid line drier after any compressor motor burnout.
Table 1. Recommended Low Pressure Control Settings for Outdoor Air Cooled Condensing Units
R-22 R-404A/R-507 R-134a *Minimum Cut-In Cut-Out Cut-In Cut-Out Cut-In Cut-Out Temp. ˚F PSI PSI PSI PSI PSI PSI
50 70 20 90 35 45 15 40 55 20 70 35 35 10 30 40 20 55 35 25 10 10 30 10 45 25 13 0 0 15 0 25 7 8 0
-10 15 0 20 1 --- ---
-20 10 0 12 1 --- ---
-30 6 0 8 1"Hg. --- ---
* Minimum ambient or box temperature anticipated, Hi pressure control setting: R-22, 360 PSI; R-404A, R-507, 400 PSI; R-134a, 225 PSI.
Table 2. Thermostat Settings
Design Thermostat Settings Models T.D. T1 T2 T3
30 60 2-fan units: 25 65 20 70 4-fan units: 15 75 30 60 40 3-fan units: 25 65 55 20 70 60 6-fan units: 15 75 65 30 60 50 30 8-fan units: 25 65 55 40 20 70 65 50 15 75 70 60
NOTE: Cycle pairs of fans on double wide units.
CAUTION: Fans closest to the headers should not be cycled on standard temperature or pressure controls. Dramatic temperature and pressure changes at the headers as a result of fan action can result in possible tube failure. Fan motors are designed for continuous duty operation.
Fan cycling controls should be adjusted to maintain a minimum of (5) minutes on and (5) minutes off. Short cycling of fans may result in a premature failure of motor and/or fan blade.
Compressors operating below +10°F SST must have air flowing over the compressor at all times when the compressor is running.
5
Refrigeration Oils*
With the changes that have taken place in our industry due to the CFC issue, we have reevaluated our lubricants to ensure compatibility with the new HFC refrigerants and HCFC interim blends offered by several chemical producers. As a secondary criteria, it is also desirable that any new lubricant be compatible with the traditional refrigerants such as CFC-12, HCFC-22 or R502. This “backward compatibility” has been achieved with the introduction of the Polyol ester lubricants.
Table 3 below summarizes which oils/lubricants are approved for use in Copeland compressors:
Polyol Ester Lubricants
Color
As received, the POE lubricant will be clear or straw colored. After use, it may acquire a darker color. This does not indicate a problem as the darker color merely reflects the activity of the lubricantʼ s protective additive.
Oil Level
During Copelandʼ s testing of Polyol ester oil, it was found that this lubricant exhibits a greater tendency to introduce oil into the cylinder during flooded start conditions. If allowed to continue, this condition will cause mechanical failure of the compressor.
A crankcase heater is required with condensing units and it must be turned on several hours before start-up.
Hygroscopicity
Ester lubricants (POE) have the characteristic of quickly absorbing moisture from the ambient surroundings. This is shown graphically in Figure 3 where it can be seen that such lubricants absorb moisture faster and in greater quantity than conventional mineral oils. Since moisture levels greater than 100 ppm will results in system corrosion and ultimate failure, it is imperative that compressors, components, containers and the entire system be kept sealed as much as possible. Lubricants will be packaged in specially designed, sealed containers. After opening, all the lubricant in a container should be used at once since it will readily absorb moisture if left exposed to the ambient. Any unused lubricant should be properly disposed of. Similarly, work on systems and compressors must be carried out with the open time as short as possible. Leaving the system or compressor open during breaks or overnight MUST BE
AVOIDED!
Oil level must not exceed 1/4 sight glass.
Figure 3.
Mineral Oil
Table 3. Refrigeration Oils
Interims HFCʼs Traditional Refrigerants R401A, R401B, R402A HFC-134a, Refrigeration Oils HCFC-22 (MP-39, MP-66, HP-80) R404A, R507 POEʼs Mobil EAL ARCTIC 22 CC A A P
ICI (Virginia KMP) EMKARATE RL 32CF A A P Suniso 3GS P PM Mineral Texaco WF32 P PM NOT Oils Calumet RO15 (Witco) P PM ACCEPTABLE Sontex 200-LT (White Oil) (BR & Scroll Only) Witco LP-200 P
A/B Zerol 200TD AM PM NOT Soltex Type AB-200 PM ACCEPTABLE
P = Preferred Lubricant Choice A = Acceptable Alternative M = Mixture of Mineral Oil and Alkyl Benzene (AB) with minimum 50% AB. * (Reprinted with permission from Copeland)
Mineral Oils
The BR and Scroll compressors use Sontex 200, a “white oil”. This oil is not suitable for low temperature applications nor is it available through the normal refrigeration wholesalers. For field “top-off” the use of 3GS or equivalent, or Zerol 200TD is permissible, as long as at least 50% of the total oil charge remains Sontex 200.
Suniso 3GS, Texaco WF32 and Calumet R015 (yellow oils) are available through normal refrigeration wholesalers. These oils are compatible if mixed and can be used on both high and low temperature systems.
Polyol Ester Lubricants
The Mobil EAL ARCTIC 22 CC is the preferred Polyol ester due to unique additives included in this lubricant. ICI Emkarate RL 32S is an acceptable Polyol ester lubricant approved for use when Mobil is not available. These POEʼs used in the system. They are also acceptable for use with any
must be used if HFC refrigerants are
6
of the traditional refrigerants or interim blends and are compatible with mineral oils. They can therefore be mixed with mineral oils when used in systems with CFC or HCFC refrigerants. These lubricants are compatible with one another and can be mixed.
Alkyl Benzenes
Zerol 200TD is an alkyl benzene (AB) lubricant. Copeland recommends this lubricant for use as a mixture with mineral oil (MO) when using the interim blends such as R-401A, R-401B and R-402A (MP39, MP66 and HP80). A minimum of 50% AB is required in these mixtures to assure proper oil return.
Shell MS 2212 is a 70/30 mixture of AB/MO. If this lubricant is used in a retrofit situation virtually all of the existing MO must be drained prior to refilling with the MS 2212 to assure a minimum 50% AB content.
Phase Loss Monitor
The combination phase sequence and loss monitor relay protects the system against phase loss (single phasing), phase reversal (improper sequence) and low voltage (brownout). When phase sequence is correct and full line voltage is present on all three phases, the relay is energized as the normal condition indicator light glows.
NOTE: If compressor fails to operate and the normal condition indicator light on the phase monitor does not glow, then the supplied electrical current is not in phase with the monitor. This problem is easily corrected by the following steps:
1. Turn power off at disconnect switch.
2. Swap any two of the three power input wires.
3. Turn power on. Indicator light should glow and compressor should start.
4. Observe motors for correct rotation.
Recommended Refrigerant Piping Practices
The system as supplied by Heatcraft Refrigeration Products, was thoroughly cleaned and dehydrated at the factory. Foreign matter may enter the system by way of the evaporator to condensing unit piping. Therefore, care must be used during installation of the piping to prevent entrance of foreign matter.
Install all refrigeration system components in accordance with applicable local and national codes and in conformance with good practice required for the proper operation of the system.
Refrigerant Pipe Support
1. Normally, any straight run of tubing must be supported in at least two locations near each end of the run. Long runs require additional supports. The refrigerant lines should be supported and fastened properly. As a guide, 3/8 to 7/8 should be supported every 5 feet; 1-1/8 and 1-3/8 every 7 feet; and 1-5/8 and 2-1/8 every 9 to 10 feet.
2. When changing directions in a run of tubing, no corner should be left unsupported. Supports should be placed a maximum of 2 feet in each direction from the corner.
3. Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in such a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the copper tubing.
4. Do not use short radius ells. Short radius elbows have points of excessive stress concentration and are subject to breakage at these points.
5. Thoroughly inspect all piping after the equipment is in operation and add supports wherever line vibration is significantly greater than most of the other piping. Extra supports are relatively inexpensive as compared to refrigerant loss.
The interconnecting pipe size is not necessarily the same size as the stub-out on the condensing unit or the evaporator.
The following procedures should be followed:
(a) Do not leave dehydrated compressors or filter-driers on condensing units open to the atmosphere any longer than is absolutely necessary.
(b) Use only refrigeration grade copper tubing, properly sealed against contamination.
(c) Suction lines should slope 1/4" per 10 feet towards the compressor.
(d) Suitable P-type oil traps should be located at the base of each suction riser of four (4) feet or more to enhance oil return to the compressor.
(e) For desired method of superheat measurement, a pressure tap should be installed in each evaporator suction line in the proximity of the expansion valve bulb.
(f) When brazing refrigerant lines, an inert gas should
be passed through the line at low pressure to prevent scaling and oxidation inside the tubing. Dry nitrogen is preferred.
(g) Use only a suitable silver solder alloy on suction and liquid lines.
Figure 4. Example of Pipe Support
Figure 5. Condensing Unit / Compressor to Wall Support.
(h) Limit the soldering paste or flux to the minimum required to prevent contamination of the solder joint internally. Flux only the male portion of the connection, never the female. After brazing, remove excess flux.
(i) If isolation valves are installed at the evaporator, full port ball valves should be used.
7
Suction Lines
Suction Line Risers
NOTE: If the suction line must rise to a point
higher than the suction connection on the evaporator, a suction line trap at the outlet of the evaporator must be provided.
Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1/4 inch per 10 feet for good oil return. When multiple evaporators are connected in series using a common suction line, the branch suction lines must enter the top of the common suction line.
For dual or multiple evaporator systems, the branch lines to each evaporator should be sized for the evaporator capacity. The main common line should be sized for the total system capacity.
Suction lines that are outside of refrigerated space must be insulated. See the Line Insulation section on page 11 for more information.
Figure 6. Suction P-Traps.
Prefabricated wrought copper traps are available, or a trap can be made by using two street ells and one regular ell. The suction trap must be the same size as the suction line. For long vertical risers, additional traps may be necessary. Generally, one trap is recommended for each length of pipe (approximately 20 feet) to insure proper oil movement. See Figure 6 below for methods of constructing proper suction line P-traps.
Slope 1/4" per 10 ft. toward compressor
Liquid Lines
Liquid lines should be sized for a minimum pressure drop to prevent “flashing”. Flashing in the liquid lines would create additional pressure drop and poor expansion valve operation. If a system requires long liquid lines from the receiver to the evaporator or if the liquid has to rise vertically upward any distance, the losses should be calculated to determine whether or not a heat exchanger is required. The use of a suction to liquid heat exchanger may be used to subcool the liquid to prevent flashing. This method of subcooling will normally provide no more than 20˚F subcooling on high pressure
systems. The amount of subcooling will depend on the design and size of the heat exchanger and on the operating suction and discharge pressures. An additional benefit from the use of the suction to liquid type heat exchanger is that it can help raise the superheat in the suction line to prevent liquid return to the compressor via the suction line. Generally, heat exchangers are not recommended on R-22 low temperature systems. However, they have proved necessary on short, well insulated suction line runs to provide superheat at the compressor.
8
Loading...
+ 16 hidden pages