Heatcraft Refrigeration Products 4346B001 User Manual

Bulletin H-IM-71A
Part No. 4346B001
August 2002
(Replaces H-IM-71, August 1996)
Air Handler Unit
Installation & Operations Manual
TABLE OF CONTENTS
Coil Stacking ........................................................................................ 5
Condensate Drain Traps .......................................................................
Direct Expansion Coils .........................................................................
Filter Quantities ....................................................................................
Freezing Temperatures ........................................................................
Inspection ............................................................................................
Motors & Drives ...................................................................................
Section Assembly .................................................................................
Shipment of Sections ...........................................................................
Start-up ................................................................................................
Steam Coils ...........................................................................................
Water Coils ...........................................................................................
Weights ................................................................................................
4 3 8 6 2 2 4 4 2 8 5 7 4 2, 3 3 7
Inspection
Shipment should be checked against the bill of lading to verify that all items listed have been received.
All parts should be carefully inspected to determine if any damage was incurred in shipment.
Any shortage and/or claims for damage should be immediately reported to the delivering carrier followed by filling a claim for shortages and/or damages.
Shipment of Units
Depending on the unit size and accessories included, the shipment may be made in two or more sections.
Handling
Special care should be taken when handling and assembling component sections of the unit. Rough handling at the job site can result in damaged bearings, bent shaft, etc.
All units are shipped on wooden skids. It is recommended that units not be moved removed from skids until they are at a place of installation. The mounting legs/rails provided for isolators should be used when lifting units into place.
Suspended Units
Unit sizes 03 through 41 may be ceiling suspended from the mounting legs/based rails with 5/8” diameter rods (furnished by others). These rods will pass through the 11/16” diameter mounting holes provided.
Unit sizes 50, 65, and 75 cannot be ceiling suspended.
Installation
It is very important that the unit be installed in a level position to prevent distortion and to insure proper damper operation and coil drainage.
Allow sufficient space around the unit for proper maintenance. Major factors to be considered are filter removal for cleaning or replacement, access to all removal panels, removal of coils and shaft if ever necessary, lubrication access and motor belt adjustment.
Canvas duct connections should be used between the unit and both supply and return air ducts.
Units are furnished with 1 1/4” F.P.T. Drain connection on each side of the coil section. The drain line from the drain pan connection must be adequately pitched
and should have a water seal of sufficient depth to compensate for the air pressure within the units. (See Condensate Drain Traps on page 4.)
When the unit is located on the roof, it must be mounted on support beams that span load bearing walls. If this is not done, excessive vibration may occur due to the resiliency of the roof.
Fan noise is a function of the fan design, volume flow, pressure, and the efficiency of the fan. Present methods of measuring fan noise do not evaluate the pure tones generated by some fans and these tones can be objectionable when radiated into occupied spaces.
Therefore, on critical applications we recommend extra sound attention in the octave band containing the tone.
Motors & Drives
All units will normally be shipped with motor and drive installed.
When mounting a motor on the adjustable base (Installed on the unit) extreme care should be taken to insure proper alignment and belt tension.
All electrical work should be done in strict accordance with local codes and regulations.
Steam Coils
Type “J” and “NFS” coils have supply and return connections on the same end. Types “R”, “S”, and “RA” coils have supply and return connections on opposite ends.
Type “NFD” coils have supply connections one each end of the coil , with a single return connection, one end only.
All piping should be in accordance with accepted industry standards and local codes. Support all piping independent of coil and provide adequate swing joints in all piping to absorb expansion and contraction strains.
Run return piping the full size of the coil return connection from the coil to a dirt pocket. (do not use reducing fittings.)
Install drip traps in steam mains ahead of coils. Do not drip steam mains through the coils.
Install a vacuum breaker (1/2” 15º check valve) ahead of the trap on low pressure open gravity return systems and on high pressure systems. Install a 1/2” 15º swing check valve in a 1/2” vacuum equalizing line, bypassing the condensate trap, on low pressure vacuum systems.
2
When two or more steam coils are furnished in a unit, provide separate traps for each coil. Size traps with ample capacity using the maximum heating load and service factor recommended b y the trap manufacturer.
Select control valves in accordance with the recommendations of the control manufacturer using actual heating loads.
Install suitable strainer ahead of all automatic valves and traps to catch dirt and scale. Provide adequate air vents to expel air and other non-condensable.
Control valves used for Type “J”, “NFS”, “RA” and “NFD” coils must be gradual acting modulating type with veeport.
Where a control valve is used for Type “S” or “R” coils and when the entering air temperature is below 35ºF., use a two position valve. Locate control element in the entering air stream so that valve will remain open with a minimum of five pounds steam pressure when the entering air temperature is below 35ºF.
Typical Steam Coil Piping
Low Pressure Open Gravity Return System
Steam Main
Gate Valve
12” Minimum
High Pressure System
12” Minimum
Control Valve
Union
Vacuum Breaker 1/2”-15” Check Valve
Vent
Gate Valve
Union
Strainer
Dirt Pocket
Control Valve
Union
Vacuum Breaker
Vent
1/2”-15” Check Valve
Gate Valve
Union
Strainer
Dirt Pocket
Strainer
Combination Float
Thermostatic Trap
Strainer
Union
and
Return Main
Gate Valve
Union
Float or
Bucket Trap
Return Main
Open Vent
Steam Main
When the system is started up the damper should remain closed for approximately ten minutes after the steam valve is opened.
Properly locate all temperature sensing elements at a point of true average air mixture temperature.
Refer to “Typical Steam Coil Piping Diagrams” for controls positioning and piping configuration.
When face and bypass dampers are used, it is good practice to install on the coil a valve which closes as the face damper closes to prevent over heating due to damper leakage or heat picked up by the air wiping the exposed coil face.
Water Piping
All piping must be supported independent coils.
Swing joints or flexible fittings must be provided to absorb expansion and contraction strains. Rigid piping may also reduce effectiveness of vibration isolators.
The water supply should always be connected to the bottom inlet of the coil. The coil connections are identified with stickers.
Water coils , 3 through 10 rows, are supplied with a vent and drain connection (1/4” MPT) which extends through the unit casing.
For protection of coils exposed to freezing temperatures, refer to page 6.
Coils must be adequately vented in order to prevent air binding.
Direct Expansion
Both the liquid distributor and the suction line extend through the casting.
The expansion valve utilized must be of the external equalizer tube type. The expansion valve bulb must be located on the suction line between the coil and the 1/4” external equalizer tube. Never locate the bulb in a trap.
All refrigerant piping practices used should be in accordance with local codes and latest ANSI Standard B9 Safety Code. Hard drawn type “L” or “K” copper tubing should be used. Soft tubing where bending is required may be used provided it is protected in accordance with local code restrictions.
Good Practice should be followed as to pulling adequate vacuum, tubes cleaned of foreign material, etc.
3
Condensate Drain Trap
(Air Seal)
1 1/4” Pipe Drain
Start-Up
Make sure all bolts and screws are tight.
Remove tagged shipping tie-down bolts and spacers from the fan and motor assembly before start-up. (Internally isolated units only.)
Check the sheaves to see if they are alignment and make suer the set screws are tight. Make sure that the dimension across the top is equal on all grooves, otherwise excessive belt wear will result.
Check for proper rotation of the blower pulley. Three phase motor rotation can be reversed by exchanging two of the three leads at the motor starter. The rotation of single phase motors can be reversed by exchanging leads inside the motor junction box. (See motor wiring diagram.)
Check the amperage draw of the motor. This should not exceed the nameplate amps shown on the motor serial plate.
After approximately two weeks of operation, the belts will have nearly acquired their permanent stretch. After this interval, the belt tension should be checked again and proper adjustment made.
Maintenance
The belt tension should be checked at three month intervals.
The fan shaft bearings on Sizes 03, 06, 08, 10, and 12 with low pressure forward curved fans have lifetime lubricated bearings. All other units have ball bearings which can be relubricated. These bearings mounted inside the fan section have extended lubrication lines which are mounted on the outside of the fan panels. The suggested greasing intervals indicated in a sticker attached to the unit.
It is recommended that bearings be lubricated with a high quality lithium grease at intervals indicated on sticker attached to the unit.
Instructions are included on the motor nameplate for lubricating the motor bearings.
The filter should be periodically inspected and replaced or cleaned when necessary. Dirt filters reduce the sir flow which reduces the capacity of the system.
Do not operate system without filters.
Condensate Drain Traps
The condensate drain trap piping must be properly designed to insure the removal of condensate. Incorrect trapping can hold water in pan causing overflow. On blow-thru units, particular, system air can escape down the drain with incorrect trapping.
(a) On draw-thru units (A) shall be equal to or greater the coils section’s negative pressure at operating conditions.
(b) On blow-thru units (A) can be as small as 1” but (B) must equal or exceed the total static pressure in the coil section.
Internally Isolated Units
Sizes 03-41 which have optional internal spring isolation have four hold-down shipping braces. Remove the 1/2” bolt between each shipping brace and the motor base, then loosen the bolt to the frame and slide the brace to the end of the slot so that the brace is 5/8” from motor support base. Re-tighten the bolt so that the shipping brace acts as a snubber on fan start up.
4
Typical ‘Accessory-to-Coil-Section’
and ‘Accessory-to-Accessory’ Attaching Method
5
Water Coils Exposed to Freezing Temperature
Water coils exposed to freezing temperatures must be protected from freeze-up by either adding anti-freeze solution to coils or proper draining of the coils.
The coils are circuited so that there are no trapped circuits. However, because of the serpentine nature of the circuiting, it is almost impossible to adequately drain the coils by gravity alone. Particularly on longer coils, even a fraction of a degree deviation from a horizontal plane can lead to water being trapped within the serpentine.
Water that failed to drain from a single tube, or even part of a tube, can cause the tube to rapture upon freezing.
Draining Coils Using Supplemental Air Blower
Ideally, a blower capable of delivering 150 CFM of air at approximately 40-50 inches of water or more should be used. Some small air compressors, while delivering higher pressures, probably will not deliver sufficient volume of air and this is equally as important.
1. Drain the coils by gravity after opening the supply, return, vent and drain connection.
2. Connect the blower to large connection that is at the greatest elevation. The small vent or drain connection on the header to which the blower is connected should be closed.
Refer to Figure 1 for typical hook -up during the blow-out operation.
It is helpful to tap the coil causing along the length of the coil during the draining process. The blower should be operated until no moisture can be detected leaving the coil. Then, shut the blower off and permit the coil to stand for a few minutes. This will permit the moisture that has adhered to the walls to accumulate. Then the blowing out operation should be repeated. Ideally, the coil should be permitted to stand twenty-four (24) hours and blown out again.
3. Leave all connections open until coil is put into operation.
Installation of Anti-Freeze Solution
A second way to prevent a coil freeze-up is to add an anti-freeze to the coil, such as industry inhibited glycol. The coil should be valved off so that only the coil would
6
have anti-freeze added to it. The most positive way to assure the mixing of the anti-freeze is to make a run­around loop with a circulating pump.
1. Open all connections and drain the coil as thoroughly as possible.
2. The anti-freeze solution should be added to the coil and circulated through the coil until the solution is thoroughly mixed and all air is purged from the coil. The air vent should be opened during the filling operation and cracked during the pumping operation to accomplish this. When the solution has circulated for 15-20 minutes, the concentration of the solution should be checked with suitable hydrometer. If the concentration is low, add more glycol and operate the pump again. A typical piping diagram is shown in Figure 2.
3. The anti-freeze solution may then be left in the coils or drained and used to flush another coil. The concentration must be checked for each coil flushed.
The adding of anti-freeze to a system exposed to freezing conditions may be necessary if the system must be operation at a moment’s notice. This affects the chiller and coil performance and must be taken into consideration when selection the components.
Note: Most anti-freeze solution will be furnished with a chart of concentration at freezing point. It is also important to be certain that the anti-freeze solution used is not corrosive to the tubing.
Air Handler Component Unit Size
Section
Model ID Description Fan S Short FC
S Short AF L Long FC L Long AF V Vertical FC HD Heating Duty FC HD Heating Duty AF FO Fan Only FC FO Fan Only AF Flat -TA & Pleated 2” Flat -Permanent 2” Flat -Pleated 4” High Capacity -TA & Pleated High Capacity -Permanent High Efficiency- 21” Section High Efficiency- 28” Section High Efficiency- 44” Section Economizer
Combination Filter & Economizer Internal Face and Bypass External Face and Bypass
S Auxiliary Coil Module L Auxiliary Coil Module
Electric Heater
Large Other Filter Fan and Coil
Coils Accessories Section Section
5/8” Tube
(Type 5)
10 FPI
1 Row 2 Row 3 Row 4 Row 6 Row 8 Row 10 Row
03 06 08 10 12 14 18 20 26 34 41 50 65 75 290 430 500 550 650 790 816 836 968 1188 1386 –
946 1177 1518 1782 2700 3300 4496 318 450 553 600 732 988 1033 1067 1221 1474 1672 – – 1177 1430 1793 2057 2850 3480 4690 296 387 482 535 615 860 1004 1111 1254 1628 1881 – – 170 280 312 360 450 510 564 605 693 902 1078 – – – 715 891 1221 1474 2600 3200 3359 162 266 296 342 428 485 536 575 658 857 1024 – – – 679 846 1160 1400 2470 3040 3191 60 73 83 95 99 104 106 108 115 160 185 255 315 384 66 79 89 101 106 114 126 135 165 240 275 390 460 560 75 88 98 110 119 124 126 127 130 185 210 298 351 428 149 168 187 206 215 224 230 234 244 260 290 360 440 535 155 176 196 216 225 234 240 244 254 365 450 520 650 790 82 95 112 133 133 153 175 180 194 235 248 269 330 359 103 121 143 170 170 196 225 224 246 296 318 345 425 463 127 150 173 201 201 230 264 274 299 358 380 412 516 552 174 195 216 224 236 247 254 260 300 430 550 680 800 975 323 363 403 430 451 471 484 494 544 690 840 1040 1240 1510 52 68 79 100 115 138 148 155 180 260 350 420 520 634 57 75 87 110 128 155 166 175 200 286 385 462 650 793 129 164 204 208 223 306 280 261 310 331 362 515 640 1305 157 184 257 258 305 504 497 492 563 617 648 665 820 1499 223 356 454 550 670 774 954 1104 1434 1760 2118 2481 3143 3599 36 56 70 80 94 106 110 112 144 195 239 339 406 538 50 80 101 120 143 164 169 173 228 318 396 562 673 891 64 106 134 161 195 223 231 236 314 444 557 737 936 1168 78 132 168 202 246 282 292 299 398 569 718 913 1199 1445 109 187 240 290 353 408 422 432 578 830 1052 1278 1677 2017 141 242 311 379 461 534 552 565 760 1092 1385 1638 2154 2589 172 297 383 467 569 659 682 699 942 1355 1718 2194 2893 3478
(Coil weight include the weight of water when filled)
To Estimate Weights for Other Coils
TA = Throw away type filters For 1/2” Tube (Type A): Multiply Type 5 Coil Weight by- 0.800 AF = Airfoil Fan For Small Coil: Multiply Large Coil Weight by- 0.823 FC = Forward Curved Fan For 14 FPI: Multiply 10 FPI Coil weight by- 1.121 For 12 FPI: Multiply 10 FPI Coil weight by- 1.065 For 8 FPI: Multiply 10 FPI Coil weight by- 0.935 For 6 FPI: Multiply 10 FPI Coil weight by- 0.915
Air Handler Motor and Drive Motor Horsepower, 1800 RPM
Weight in pounds Motor
and Totally Enclosed Fan Cooled (TEFC) Drive High Efficiency Open Single Speed Weight Open 2 Speed, 2 Winding T – Frame Size
Open Single Speed Motor
1 1.5-2 3 5 7.5 10 15 20 25 30 40 50 60 75
55 65 86 105 172 193 253 286 348 400 529 600 720 828 56 71 88 104 178 194 275 336 411 461 624 670 – 67 74 114 127 209 216 341 384 396 427 621 623 – 71 97 115 160 291 267 368 356 366 – 143 145 182 184 213 215 254 256 284 286 324 326 364 365
Central Station Air Handler, Shipment of Assemblies - Basic Unit
Horizontal Style Units, fan, coil, flat filter section Vertical Style Units, fan, coil, flat filter section
S, L, FO,
HD Sizes
03 – 18
S, L, FO,
HD Sizes
20 – 75
FS
FS
CS
CS
These diagram show typical shipments.
FF
Some set-ups may vary with certain units. Consult the factory if you require a specific
FF
assembly shipped in a special way.
V Sizes
03 – 18
V Sizes
20 – 41
FS
CS
FS
CS
We ship high capacity and high efficiency filter sections, economizers,
FF
dampers, and electric heat sections separately.
FF
7
Quantity and Dimensions of Filters for:
Flat Filter Section
Filter Air Handler Unit Size Filter Dimensions Dimensions
2” x 16” x 20” 2” x 20” x 20” 2” x 16” x 25” 2” x 20” x 25”
03 06 08 10 12 14 18 20 26 34 41 50 65 75 1 2 3 1 2 6 4 6 7 8 4
1 3 1 2 4 8 12 20 10 – 2 4 2 2 4 14 4 – 2 2 2 8 10
2” x 16” x 20” 2” x 20” x 20” 2” x 16” x 25” 2” x 20” x 25”
High Capacity Filter Sections
2” x 16” x 20” 2” x 20” x 20” 2” x 16” x 25” 2” x 20” x 25”
2 4 – 2 20 – – 6 2 8 4 6 4 2 4 12 14 – 4 4 4 4 6 10 20 30 30 35
2” x 16” x 20” 2” x 20” x 20” 2” x 16” x 25” 2” x 20” x 25”
High Efficiency Filter Sections
24” x 24” 12” x 24”
1 2 2 2 2 3 6 4 5 10 10 15 15 20 1 2 3 3 3 4 5 5 3 4
24” x 24” 12” x 24”
Replacement Parts- Note: Confirm the shaft Diameter, when Ordering Parts.
03-12, Forward Curved Shaft Bearing Bearing Shaft Blower Unit Size, Fan Diameter, Type Diameter Part No. Type Part No. Assembly
03 FC 9” Low Pressure 3/4” 4215V Cartridge 4317Z 4317M 03 FC 9” Med Pressure 1” 4352N Pillow Block 4343N 4322M 06 FC 12” Low Pressure 1” 4350N Cartridge 4318Z 4318M 06 FC 12” Med Pressure 1 3/16” 4353N Pillow Block 4344N 4323M 08 FC 15” Low Pressure 1” 4350N Cartridge 4319Z 4319M 08 FC 15” Med Pressure 1 3/16” 4353N Pillow Block 4345N 4324M 10 FC 18” Low Pressure 1” 4350N Cartridge 4320Z 4320M 10 FC 18” Med Pressure 1 3/16” 4353N Pillow Block 4346N 4325M 12 FC 18” Low Pressure 1” 4350N Cartridge 4320Z 4320M 12 FC 18” Med Pressure 1 3/16” 4353N Pillow Block 4346N 4325M
Note: For sizes 03-12, it is less expensive to replace the blower assembly than to replace the blower wheel. Blower assembly also includes bearings and shaft
14-41, Forward Curved Shaft Pillow Block Shaft Blower Blower Unit size, Fan Diameter, Type Diameter Bearing Wheel Wheel Cut-Off
14 FC 20” Low Pressure 1 3/16” 4353N 4342N 5154E Part of Housing 14 FC 20” Med Pressure 1 3/16” 4353N 4342N 5154E Part of Housing 18 FC 20” Low Pressure 1 3/16” 4353N 4342N 5154E Part of Housing 18 FC 20” Med Pressure 1 3/16” 4353N 4342N 5154E Part of Housing 20FC 22” Med Pressure 1 7/16” 5562N 4522R 5153E 4418T 26 FC 22” Med Pressure 1 7/16” 5562N 4522R 5153E 4418T 34 FC 25” Med Pressure 1 11/16” 5563N 4525R 5179D 4419T 41 FC 30” Med Pressure 1 15/16” 5564N 4500S 5178D 4421T
Note: For sizes 14-41 Forward Curved Fans, it is less expensive to replace the blower wheel than to replace the blower assembly.
26-75, Air Foils Shaft Pillow Block Unit size, Fan Diameter, Type Diameter Bearing
20 AF 18 1/4” Med Pressure 1 7/16” 5562N 26 AF 18 1/4” Med Pressure 1 7/16” 5562N 34 AF 24 1/2” Med Pressure 1 15/16” 5564N 41 AF 30” Med Pressure 2 3/16” 5521T 50 AF 32 3/8” Med Pressure 2 7/16” 5597T 65 AF 39 3/8” Med Pressure 2 11/16” 5875E 75 AF 39 3/8” Med Pressure 2 11/16” 5875E
For sizes 41-75 Air Foils, for parts other than
bearing replacement, Contact the Factory.
with air handler model number, and discharge
arrangement. Heatcraft Refrigeration Products
can then advise the correct blower assembly
Air Foil Note:
Call the parts department, 800-686-7278,
description for you.
Visit our website at www.heatcraftrpd.com for technical literature online.
Since product improvement is a continuing effort, we reserve the right to make changes
in specifications without notice.
Heatcraft Refrigeration Products LLC
2175 West Park Place Blvd. • Stone Mountain, GA 30087
770.465.5600 • Fax: 770.465.5990 • www.heatcraftrpd.com
Loading...