Shipment should be checked against the bill of lading to
verify that all items listed have been received.
All parts should be carefully inspected to determine if
any damage was incurred in shipment.
Any shortage and/or claims for damage should be
immediately reported to the delivering carrier followed
by filling a claim for shortages and/or damages.
Shipment of Units
Depending on the unit size and accessories included,
the shipment may be made in two or more sections.
Handling
Special care should be taken when handling and
assembling component sections of the unit. Rough
handling at the job site can result in damaged bearings,
bent shaft, etc.
All units are shipped on wooden skids. It is
recommended that units not be moved removed from
skids until they are at a place of installation. The
mounting legs/rails provided for isolators should be used
when lifting units into place.
Suspended Units
Unit sizes 03 through 41 may be ceiling suspended from
the mounting legs/based rails with 5/8” diameter rods
(furnished by others). These rods will pass through the
11/16” diameter mounting holes provided.
Unit sizes 50, 65, and 75 cannot be ceiling suspended.
Installation
It is very important that the unit be installed in a level
position to prevent distortion and to insure proper
damper operation and coil drainage.
Allow sufficient space around the unit for proper
maintenance. Major factors to be considered are
filter removal for cleaning or replacement, access
to all removal panels, removal of coils and shaft if
ever necessary, lubrication access and motor belt
adjustment.
Canvas duct connections should be used between the
unit and both supply and return air ducts.
Units are furnished with 1 1/4” F.P.T. Drain connection
on each side of the coil section. The drain line from
the drain pan connection must be adequately pitched
and should have a water seal of sufficient depth to
compensate for the air pressure within the units.
(See Condensate Drain Traps on page 4.)
When the unit is located on the roof, it must be mounted
on support beams that span load bearing walls. If this
is not done, excessive vibration may occur due to the
resiliency of the roof.
Fan noise is a function of the fan design, volume flow,
pressure, and the efficiency of the fan. Present methods
of measuring fan noise do not evaluate the pure tones
generated by some fans and these tones can be
objectionable when radiated into occupied spaces.
Therefore, on critical applications we recommend extra
sound attention in the octave band containing the tone.
Motors & Drives
All units will normally be shipped with motor and drive
installed.
When mounting a motor on the adjustable base (Installed
on the unit) extreme care should be taken to insure
proper alignment and belt tension.
All electrical work should be done in strict accordance
with local codes and regulations.
Steam Coils
Type “J” and “NFS” coils have supply and return
connections on the same end. Types “R”, “S”, and “RA”
coils have supply and return connections on opposite
ends.
Type “NFD” coils have supply connections one each end
of the coil , with a single return connection, one end only.
All piping should be in accordance with accepted
industry standards and local codes. Support all piping
independent of coil and provide adequate swing joints in
all piping to absorb expansion and contraction strains.
Run return piping the full size of the coil return connection
from the coil to a dirt pocket. (do not use reducing
fittings.)
Install drip traps in steam mains ahead of coils. Do not
drip steam mains through the coils.
Install a vacuum breaker (1/2” 15º check valve) ahead of
the trap on low pressure open gravity return systems and
on high pressure systems. Install a 1/2” 15º swing check
valve in a 1/2” vacuum equalizing line, bypassing the
condensate trap, on low pressure vacuum systems.
2
When two or more steam coils are furnished in a unit,
provide separate traps for each coil. Size traps with
ample capacity using the maximum heating load and
service factor recommended b y the trap manufacturer.
Select control valves in accordance with the
recommendations of the control manufacturer using
actual heating loads.
Install suitable strainer ahead of all automatic valves and
traps to catch dirt and scale. Provide adequate air vents
to expel air and other non-condensable.
Control valves used for Type “J”, “NFS”, “RA” and
“NFD” coils must be gradual acting modulating type with
veeport.
Where a control valve is used for Type “S” or “R” coils
and when the entering air temperature is below 35ºF.,
use a two position valve. Locate control element in the
entering air stream so that valve will remain open with
a minimum of five pounds steam pressure when the
entering air temperature is below 35ºF.
Typical Steam Coil Piping
Low Pressure Open Gravity Return System
Steam Main
Gate Valve
12” Minimum
High Pressure System
12” Minimum
Control Valve
Union
Vacuum Breaker
1/2”-15” Check Valve
Vent
Gate Valve
Union
Strainer
Dirt Pocket
Control Valve
Union
Vacuum Breaker
Vent
1/2”-15” Check Valve
Gate Valve
Union
Strainer
Dirt Pocket
Strainer
Combination Float
Thermostatic Trap
Strainer
Union
and
Return Main
Gate Valve
Union
Float or
Bucket Trap
Return Main
Open Vent
Steam Main
When the system is started up the damper should remain
closed for approximately ten minutes after the steam
valve is opened.
Properly locate all temperature sensing elements at a
point of true average air mixture temperature.
Refer to “Typical Steam Coil Piping Diagrams” for
controls positioning and piping configuration.
When face and bypass dampers are used, it is good
practice to install on the coil a valve which closes as
the face damper closes to prevent over heating due to
damper leakage or heat picked up by the air wiping the
exposed coil face.
Water Piping
All piping must be supported independent coils.
Swing joints or flexible fittings must be provided to absorb
expansion and contraction strains. Rigid piping may also
reduce effectiveness of vibration isolators.
The water supply should always be connected to the
bottom inlet of the coil. The coil connections are identified
with stickers.
Water coils , 3 through 10 rows, are supplied with a vent
and drain connection (1/4” MPT) which extends through
the unit casing.
For protection of coils exposed to freezing temperatures,
refer to page 6.
Coils must be adequately vented in order to prevent air
binding.
Direct Expansion
Both the liquid distributor and the suction line extend
through the casting.
The expansion valve utilized must be of the external
equalizer tube type. The expansion valve bulb must be
located on the suction line between the coil and the 1/4”
external equalizer tube. Never locate the bulb in a trap.
All refrigerant piping practices used should be in
accordance with local codes and latest ANSI Standard
B9 Safety Code. Hard drawn type “L” or “K” copper tubing
should be used. Soft tubing where bending is required
may be used provided it is protected in accordance with
local code restrictions.
Good Practice should be followed as to pulling adequate
vacuum, tubes cleaned of foreign material, etc.
3
Condensate Drain Trap
(Air Seal)
1 1/4” Pipe Drain
Start-Up
Make sure all bolts and screws are tight.
Remove tagged shipping tie-down bolts and spacers
from the fan and motor assembly before start-up.
(Internally isolated units only.)
Check the sheaves to see if they are alignment and
make suer the set screws are tight. Make sure that
the dimension across the top is equal on all grooves,
otherwise excessive belt wear will result.
Check for proper rotation of the blower pulley. Three
phase motor rotation can be reversed by exchanging
two of the three leads at the motor starter. The rotation
of single phase motors can be reversed by exchanging
leads inside the motor junction box. (See motor wiring
diagram.)
Check the amperage draw of the motor. This should not
exceed the nameplate amps shown on the motor serial
plate.
After approximately two weeks of operation, the belts
will have nearly acquired their permanent stretch. After
this interval, the belt tension should be checked again
and proper adjustment made.
Maintenance
The belt tension should be checked at three month
intervals.
The fan shaft bearings on Sizes 03, 06, 08, 10, and
12 with low pressure forward curved fans have lifetime
lubricated bearings. All other units have ball bearings
which can be relubricated. These bearings mounted
inside the fan section have extended lubrication lines
which are mounted on the outside of the fan panels.
The suggested greasing intervals indicated in a sticker
attached to the unit.
It is recommended that bearings be lubricated with a
high quality lithium grease at intervals indicated on
sticker attached to the unit.
Instructions are included on the motor nameplate for
lubricating the motor bearings.
The filter should be periodically inspected and replaced
or cleaned when necessary. Dirt filters reduce the sir
flow which reduces the capacity of the system.
Do not operate system without filters.
Condensate Drain Traps
The condensate drain trap piping must be properly
designed to insure the removal of condensate. Incorrect
trapping can hold water in pan causing overflow. On
blow-thru units, particular, system air can escape down
the drain with incorrect trapping.
(a) On draw-thru units (A) shall be equal to or
greater the coils section’s negative pressure at
operating conditions.
(b) On blow-thru units (A) can be as small as 1” but
(B) must equal or exceed the total static pressure
in the coil section.
Internally Isolated Units
Sizes 03-41 which have optional internal spring isolation
have four hold-down shipping braces. Remove the 1/2”
bolt between each shipping brace and the motor base,
then loosen the bolt to the frame and slide the brace to
the end of the slot so that the brace is 5/8” from motor
support base. Re-tighten the bolt so that the shipping
brace acts as a snubber on fan start up.
4
Typical ‘Accessory-to-Coil-Section’
and ‘Accessory-to-Accessory’ Attaching Method
5
Water Coils Exposed
to Freezing Temperature
Water coils exposed to freezing temperatures must be
protected from freeze-up by either adding anti-freeze
solution to coils or proper draining of the coils.
The coils are circuited so that there are no trapped
circuits. However, because of the serpentine nature of
the circuiting, it is almost impossible to adequately drain
the coils by gravity alone. Particularly on longer coils,
even a fraction of a degree deviation from a horizontal
plane can lead to water being trapped within the
serpentine.
Water that failed to drain from a single tube,
or even part of a tube, can cause the tube to
rapture upon freezing.
Draining Coils Using Supplemental
Air Blower
Ideally, a blower capable of delivering 150 CFM of air
at approximately 40-50 inches of water or more should
be used. Some small air compressors, while delivering
higher pressures, probably will not deliver sufficient
volume of air and this is equally as important.
1. Drain the coils by gravity after opening the
supply, return, vent and drain connection.
2. Connect the blower to large connection that
is at the greatest elevation. The small vent or
drain connection on the header to which the
blower is connected should be closed.
Refer to Figure 1 for typical hook -up during the
blow-out operation.
It is helpful to tap the coil causing along the
length of the coil during the draining process.
The blower should be operated until no moisture
can be detected leaving the coil. Then, shut the
blower off and permit the coil to stand for a few
minutes. This will permit the moisture that has
adhered to the walls to accumulate. Then the
blowing out operation should be repeated.
Ideally, the coil should be permitted to stand
twenty-four (24) hours and blown out again.
3. Leave all connections open until coil is put into
operation.
Installation of Anti-Freeze Solution
A second way to prevent a coil freeze-up is to add an
anti-freeze to the coil, such as industry inhibited glycol.
The coil should be valved off so that only the coil would
6
have anti-freeze added to it. The most positive way to
assure the mixing of the anti-freeze is to make a runaround loop with a circulating pump.
1. Open all connections and drain the coil as
thoroughly as possible.
2. The anti-freeze solution should be added to the
coil and circulated through the coil until the
solution is thoroughly mixed and all air is purged
from the coil. The air vent should be opened
during the filling operation and cracked during the
pumping operation to accomplish this. When
the solution has circulated for 15-20 minutes,
the concentration of the solution should be
checked with suitable hydrometer. If the
concentration is low, add more glycol and operate the pump again. A typical piping diagram
is shown in Figure 2.
3. The anti-freeze solution may then be left in
the coils or drained and used to flush another
coil. The concentration must be checked for each
coil flushed.
The adding of anti-freeze to a system exposed to
freezing conditions may be necessary if the system
must be operation at a moment’s notice. This affects
the chiller and coil performance and must be taken into
consideration when selection the components.
Note: Most anti-freeze solution will be furnished with
a chart of concentration at freezing point. It is also
important to be certain that the anti-freeze solution
used is not corrosive to the tubing.
Air Handler Component Unit Size
Section
Model ID Description Fan
SShort FC
SShort AF
LLong FC
LLong AF
VVertical FC
HDHeating Duty FC
HDHeating Duty AF
FOFan Only FC
FOFan Only AF
Flat -TA & Pleated 2”
Flat -Permanent 2”
Flat -Pleated 4”
High Capacity -TA & Pleated
High Capacity -Permanent
High Efficiency- 21” Section
High Efficiency- 28” Section
High Efficiency- 44” Section
Economizer
Combination Filter & Economizer
Internal Face and Bypass
External Face and Bypass
Replacement Parts- Note: Confirm the shaft Diameter, when Ordering Parts.
03-12, Forward Curved Shaft Bearing Bearing Shaft Blower
Unit Size, Fan Diameter, Type Diameter Part No. Type Part No. Assembly
03 FC 9” Low Pressure 3/4” 4215V Cartridge 4317Z 4317M
03 FC 9” Med Pressure 1” 4352N Pillow Block 4343N 4322M
06 FC 12” Low Pressure 1” 4350N Cartridge 4318Z 4318M
06 FC 12” Med Pressure 1 3/16” 4353N Pillow Block 4344N 4323M
08 FC 15” Low Pressure 1” 4350N Cartridge 4319Z 4319M
08 FC 15” Med Pressure 1 3/16” 4353N Pillow Block 4345N 4324M
10 FC 18” Low Pressure 1” 4350N Cartridge 4320Z 4320M
10 FC 18” Med Pressure 1 3/16” 4353N Pillow Block 4346N 4325M
12 FC 18” Low Pressure 1” 4350N Cartridge 4320Z 4320M
12 FC 18” Med Pressure 1 3/16” 4353N Pillow Block 4346N 4325M
Note: For sizes 03-12, it is less expensive to replace the blower assembly than to replace the blower wheel. Blower assembly also includes bearings and shaft
14-41, Forward Curved Shaft Pillow Block Shaft Blower Blower
Unit size, Fan Diameter, Type Diameter Bearing Wheel Wheel Cut-Off
14 FC 20” Low Pressure 1 3/16” 4353N 4342N 5154E Part of Housing
14 FC 20” Med Pressure 1 3/16” 4353N 4342N 5154E Part of Housing
18 FC 20” Low Pressure 1 3/16” 4353N 4342N 5154E Part of Housing
18 FC 20” Med Pressure 1 3/16” 4353N 4342N 5154E Part of Housing
20FC 22” Med Pressure 1 7/16” 5562N 4522R 5153E 4418T
26 FC 22” Med Pressure 1 7/16” 5562N 4522R 5153E 4418T
34 FC 25” Med Pressure 1 11/16” 5563N 4525R 5179D 4419T
41 FC 30” Med Pressure 1 15/16” 5564N 4500S 5178D 4421T
Note: For sizes 14-41 Forward Curved Fans, it is less expensive to replace the blower wheel than to replace the blower assembly.
26-75, Air Foils Shaft Pillow Block
Unit size, Fan Diameter, Type Diameter Bearing
20 AF 18 1/4” Med Pressure 1 7/16” 5562N
26 AF 18 1/4” Med Pressure 1 7/16” 5562N
34 AF 24 1/2” Med Pressure 1 15/16” 5564N
41 AF 30” Med Pressure 2 3/16” 5521T
50 AF 32 3/8” Med Pressure 2 7/16” 5597T
65 AF 39 3/8” Med Pressure 2 11/16” 5875E
75 AF 39 3/8” Med Pressure 2 11/16” 5875E
For sizes 41-75 Air Foils, for parts other than
bearing replacement, Contact the Factory.
with air handler model number, and discharge
arrangement. Heatcraft Refrigeration Products
can then advise the correct blower assembly
Air Foil Note:
Call the parts department, 800-686-7278,
description for you.
Visit our website at www.heatcraftrpd.com for technical literature online.
Since product improvement is a continuing effort, we reserve the right to make changes
in specifications without notice.
Heatcraft Refrigeration Products LLC
2175 West Park Place Blvd. • Stone Mountain, GA 30087